_ _ _ _ _ _ - _ _ _ _
,-.. N Commonwealth Edison
/
l
- / One First National Plaza Cheago, lilites k
~
/ Address Reply to: Post Office Box 767
'L/ Chicago, Illinois 60690 0767 January 21, 1987 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, D.C.
20555
Subject:
LaSalle county Station Units 1 and 2 SOR Differential Pressure Switch Calibration Data NRC Docket Nos. 50-373 and 50-374
Dear Sir:
Attached are the most recent calibration data from the Static "O"
Ring differential pressure switches installed at LaSalle county Station.
This data is current as of January 20, 1987.
Information provided was requested in a telecon January 16, 1987 with members of your staff.
If you have any additional questions regarding this matter, please contact this office.
Very truly yours, I
C. M. Allen Nuclear Licensing Administrator 1m cc:
Dr. A. Bournia - NHH Regional Administrator - RIII NRC Resident Inspector - I.SCS 2628K 0702020165 070121 PDR ADOCK 05000373 IkI P
)
Page
.1 i
i fUNIT 1 CALIBRATION DATA
- ======================a ECUIPMENT' PIECE NUMBER
1Bdi-N024A APPLICATION:
REACTOR VESSEL : LOW LEVEL SCPAM h, NOMINAL SETPOINT:
63.15" WC
/ 58.90" WC
' CALIBRATION TOLERANCE:
63.78-62.51" NC / 59.40-58.40" WC ACTION t,IM'TS:
/ - 56.10-61.70" WC 1
REJECTICN LIMITS:
/ ' 56.00-61.80" WC TECH SPEC AL.LGWABLE:
64.84" WC
/ 64.84" WC i
t i
Calibration Date "As,Tound" "As Found" "As Left" "9s Left" Trip
.Resst Trip Reset I
9/ 9/86 58.70 53.60 9/24/06 58.50 SC.' 8 0 58.70 53.60 1 10/ 6/86 59,20 53.IO 59.10 53.40.
]10/20/86 60.00 54.10 58.90 53.60 11/17/86 59.OS 53.25 58.4 53.4 m
101/12/07 59.2 5G. 0 59.2 52.2 i-,
l I
i 1
t p
i J.3 r
l 1
a J
e i
3 l
E E
t
.a.
._m._,
.. - ~.
x
~
,-=
page 1
] UNIT 1 CALIBRATION DATA
===-e=======
EQUIPMENT PIECE NtiMBER:
IB21-Ne24D
' APPLICATION:
REACTOR VESSEL LOW LEVEL GCRAM
\\
NOMINAL GETPOINT:
G3.15" WC
/ 58.90" WC i CALIBRATION TOLERANCE:
63.78-62.51" WC / 59.40-59.40" WC 1
ACTION LIMITS:
/ BG.10-61.70" WC REJECTION LIMITE:
/ 56.00-61.80" WC j TECH SPEC ALLOWABLE; 64.84" WC
/ G4.84" WC i
Calibration I,at e "As Found" "As.Found" "As'Left" "As Left" Trip Reset Trip Renet 9/ 9/86 59.00 54.30 1
9/24/8G 59.00 53.70 59.00 54.80 10/ 6/86 E0.30 55.20 59.10 54.40 10/00/86 59.40 55.00 58.90 54.40 i 11/17/86 58.9 54.6 58.75 5 4. 6 ~
01/12/G7 59.2 54.0 59.0
-53.5 J
l i
4 1
l r
1 t
I l
4 I
4 4
1 i
.i 1
l i
1 l
J
(
i l
l
- ~. -.
i Page l'
?
3 a
' ' UNIT 1 CALIBRATION DATA
- i ma==.==========..e-=.=====
, EQUIPMENT PIECC NUMBER:
1921-N024C
! APPLICATION:
PEACTOR VESSEL. LOW LEVEL SCRAM t
i
! NGMINAL SETPOINT:
63.15" WC
/ 58.90" WC
.1 CALIERATIGN TOLERANCE:
63.78-62.51" WC / 59.40-58.40" WC
]. ACTION LIMIT 5:
/ 56.10-61.70" WC REJECTION LIMITS:
/ 56.00-61.80" WC l
i iTECH SPEC ALLOWABLE:
64.84" WC
/ 64.84" WC c
1
! Calibration Date "As Found" "As Found" "As Left"
" As Le f t "
Trip' Reset Trip Reset l
t l
l 9/ 9/86 58.80 52.00 9/24/66 56.70 52.20 58.65 52.60
' 10/ 6/86 59.70 52.30 59.20 52.00 10/20/86 60.20 52.80 58.80 31.00 11/17/GG 58.7 50.4 58.5 51.4
}01/12/87 59.9
- 51. 3 59.1 51.1 i
l 1
4
?
i l
3 t
t i
i i
i r
i l
i
(
}
i 1
I I
1 f
3 b
i
~
l i
t l
l
[
..-,,-m,-..
..~,,,.m..,,,,,
...m.--,,
..--...__--_....,..m.,____.,.~,,....._,,._..,.___,_,,,...,,,.,_m_.._-
Pdge 1
I i
UNIT 1 CALIBRATION D'iTA
==============:
r EQUIPMENT PIECE NUMBER:
1921-N024D
{ APPLICATION:
REACTOR VESSEL ~ LOW LEVEL SCRAM l NOMINAL SETPOINT:
63.15" WC
/ 58.90" WC
!CALIBPATION TOLERANCE:
'53.78-62.51" WC / 59.40-58.40" WC i
l ACTION LIMITS:
-/ 56.10-61.70" WC
- REJECTION LIMITS
/ ~ 56.00-61.80" WC.
i i TECH SPEC ALLOWABLE:
64.84" WC
/ 64.84" WC L
i 4-Calibration Date "As Found" "As Found" "As Left"'
"As Left" j
Trip Reset Trip Reset 4
1 9/ 9/86 58.80 52.80 i
}
9/24/86 58.65 53.50 58.90 54.30 10/ G/86 61.00 55.00 59.20 53.40 1 10/20/86 58.90 53.30 58.90 53.60 i 11/17/86 58.95 52.8 59.0 53.4 I
- t 01/12/87 59.5 52.5 58.8 52.1-t i
i.
i
)
i 1
a f
I t
4 I
'l 4
n i
t d
i 4
1 6
3
}
P I
i i
l i
1 l
)
)
4 _. _ _. -. _ ~ _ _. - - _......, _.. - - -... _ - - - _.
Page.
1 i
f I
i i
- ' UNIT 1 CALIBRATION DATA 1
l=======================
l 1
i
~
- EQUIDMENT PIECE NUMBER
iAPPLICATION:
REACTOR _ LOW LEVEL CONFIRMED ADS PERMISSIVE NOMINAL GETPOINT:
58.9" WC
! CALIBRATION TOLERANCE:
58.4-59.4" WC j
i
} ACTION LIMITS:
56.1-61.7" WC i
- REJECTION LIMITS
56.0-61.8" WC l
TECH SPEC ALLOWABLE:
64.84" WC l
' Calibrat ion Dat<.
As Found" "As Found" "As Left" "As Left"
~
Trip Reset Trip Reset 4
i 9/ 9/86 58.85 52.4-4 g
9/24/86 58.1 52.1 58.9 53.2 4
I 10/ 9/86 59.45 53.4 58.75 52.9
!11/06/86 59.2 53.1.
59.2 53.2 l' 01/02/87 58.7 52.2 58.6 52.4
}.
i i
l' f
^
t i
i 8
F
+
i f
5 4
l i
I-
' m-ver re w,e e.*
- -F-m m w wws -
e~m-m'-'
+ws e. 'r>+.*v er em w a --"weu-*
e-m-
-s',-*'
w am -e-r -w w w-w e = m we --- - -.
. ew NNw eer'e v
Page 1
UNIT 1 CALIBRATION DATA
==========
EQUIPMENT PIECE NUMBER:
1821-N038B APPLICATION:
REACTOR LOW LEVEL CONFIRMED ADS PERMISSIVE NCMINAL GETPOINT:
58.9" WC CALIBRATIGN TOLERANCE:
58.4-59.4" WC ACTION LIMITS:
56.1-61.7" WC REJECTION LIMITO:
56.0-61.8" WC TECH SPEC ALLOWADLE:
64.84" WC Cal:brstion Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset 9/ 9/86 59.1 53.0 9/25/0G 58.7 5C. 8 58.7 52.9 10/ 9/86 58.8 52.8 58.8 52.0 11/06/86 59.4
- 32. G 59.3 52.8 01/02/87 59.4 52.0 59.2 52.4
~.
O 5
t i
s u
5 1
)
l l
i
I-Page' 1
l'
.t J
fUNIT 1 CALIDRATION DATA
_t
===========
1 EQUIPMENT PIECE NUMBER:
IB21-NO31A
) APPLICATION:
REACTOR LOW LOW LEVEL HPCS INITIATE
}
'l 1 NOMINAL SETPOINT:
134.00" WC CALIBRATION 'OLERANCE:
133.00-135.00" WC ACTION LIMITS:
128.60-139.40" NC
- REJECTION LIMIT 5
125.40-142.60" WC
! TECH SPEC ALLOWABLE:
150.64" WC
(-57.0" ACT. RX. LEVEL) 1
)
fCalibration Date "As Found" "As Found" "At Left" "As Left" l
Trip Reset Trip Reset l_______________________________________________
t 1
9/11/86 134.0 126.25 4
134.0 126.5 134.0 126.5 i
9/30/8C t
12/31/86 134.5 126.0 134.5 126.O f
l
'1 i
a i
I l
i i
I I
I i
I l
3
)
i 1
i 1
I I
i a
i l
i J
I l
t i
i I
i i
I 1
'l
Page i
I 3
I l UNIT 1 CALIBRATION DATA
,=======================
' EQUIPMENT PIECE NUMBER:
1B21-N031B fAPPLICATIONi REACTOR LOW. LOW LEVEL HPCS INITIATE i
{ NOMINAL SETPOINT:
134.00" WC j CALIBRATION TCLERANCE:
133.00-135.00" WC
,l'! ACTION LIMITS:
128.60-139.40" WC I REJECT 73N LIMITS:
125.40-142.60" WC
.I TECH SPEC-ALLOWABLE:
150,64" WC
(-57.0" ACT. RX. LEVEL) i i
!l Calibration Date "As Found" "As Found" "As Left" "As Left"
{
Trip Reset Trip Reset i
i 9/11/66 134.0 125.O l
9/30/86 134.0 126.0 134.0 126.0 l
4 4
12/31/86 134. 5 125.5 134.5 125,5
=
1 i
i i
i r
I f
s 1
1 l
l i
i i
i I
1 1
1 1
1 4
__%.e mwe e *eur,,rne w y,ww.=rwi
_ _ _ _. - _.___ _._.._._..___...._ _____._._.__ _ _____.._._ ___.__._ ____ _ _ _ _ _ _ _., _ _ _. ~.. _ _ _ _ _ _
Page
'll 1
i-1 UNIT.-1 CALIBRATION DATA
===========
2 EQUIPMENT PIECE NUMBER:
1B21-NO31C I APPLICATION:
REACTOR LOW LOW LEVEL HPCS INITIATE T
l NOMINAL SETPOINT:
134.00" WC 3 CALIBRATION TOLERANCE:
133.00-135.00" WC ACTION LIMITS:
128.60-139.40" WC-REJECTION LIMITS:
125.40-142.50" WC TECH SPEC AL'OWABLE:
150.64" WC.(-57.0" ACT. RX. LEVEL)
L 1'
j Calibration Date "As Found".
"As Found" "As Left" "As Left" l
~
j.
Trip Reset Trip Reset 9/11/85 134.0 126.ca
{
9/30/86 134.2 126.'d 134.2 125.5
~
! 12/31/86 135.0 126.G 134.5 127.0 i
I L
I f
i b
l 1
l l
r f
I l
1 t
l i
)
l 1
-l
Page i
UNIT 1 CAl IDRATION 2ATO
.:===.-==
=
. - = -.=:_
EC!J I PMDJT NIECE M' J'% E P :
~
I D21 --N0 310 p< rs r.,< > _. r_ eq y e n a,4.,
Fjg ges7, q n
_C.,, s,
, 7,,,
t_ T' \\v E' 8 64F."e a 1 nit T..t ArTt
..r.c a
e m
i r
v F
n,
u f d C M i fv'a l-CC] CO { f jY.
1 _~2 2. I? s.i (v tfP
-u u
l 2
t s
1 - A t
C T' L I F:Ti A T I CN TGLERANCE-17" 0 0 -- 1 3'a. 0 0 " WC c, r,i. t "4
t _ I '1 T. T ';. -
1."_ u. e.*u
- 1_m; m. t ('i "
!.,' r
-T n, i
3,
o w
OEJECr1ON L1MIT~'
125.40-142.60" WC r - c u.
- a, c r +, m L nJ,..' rt.r _ r.-
i r t,, r /, " t u' -.
- r.. t, -'. 'v "
hr_ T.
ta'. y. L c t. 'E. i._ )
m? a s
. r L
_r u
C;.1;
'M Found"
" A :: F co m d "
" A.= Left" "As Left"
';co
+
Trip Peset
- Trip, Reset 4
(fr
- A y ' t. ('-
A L' _ 4'.f b
k s / 1 rs M
7 h.
1+.g 1 c.. L).
j g
iu.
1 r**
I av o,a 4 O 94
^
c i u,/ v i /;2 f
} a-4 1
_7, '<?
3 c-:
a i v.e..
3 3. ~,7, t,
u
-~Y g
i Page-1 l
l iiUNIT 1 CALIBRATION D7TA j
======================-
fl'ECUIPMENT PIECE NUMBER:
1821-N026AB l APPLICATION:
REACTOR LOW / LOW LEVEL MSIV_ISOLAVION i
i
' NOMINAL SETPOINT:
134.0" WC
! CALIBRATION TOLERANCE:
133.0-135.0" WC l-4 ACTION LIMITS:
128.6-139.4" WC 4
! REJECTION LIMITS:
125.4-142.6" WC j TECH SPEC ALLOWADLE:
150.64".WC i
1 l Calibration Date "As Found" "As Found" "As Left" "As Left" i
i Trip Reset Trip Roset l
{ -
- l 09/12/86 134,i 123, e 10/29/86 135.0 122,5 134.8 122.5 i 12/29/86 135.5 122.0 134.3-122.0 i
i.
i i
1 l
t i
e t
a
+
I 1
k
_. -- - -.. _.. -.~. - -... -.
PaDe 1
s 1
1 f
?
.i l' UNIT.1 CALIBRATION DATA'
'l
'I i=======================
EQUIPMENT PIECE' NUMBER:
1D21-N026BB 1iAPPLICATION:
REACTOR LOW / LOW LEVEL MSIV ISOLATION i-t NOMINAL. SETPOINT:
134.0" WC l
' CALIBRATION TOLERANCE:
133.0-135.0" WC
}
4 ACTION LIMIT 5:
1 2 8. 6 - 1 3 's. 4 " WC lLREJECTION LIMITS:
125.4-142.6" WC TECH SPEC ALLOWABLE:
150.64" WC 3
'i j Ca l i t: rat i on Date "As Found" "As Found" "As Left" "As Left" i
Trip Reset Trip Reset t
1
)
i j 09/12/GG 134.0 123.5 l
j 10/30/06 137.5 123.5 134.0 115.0 j
1 12/29/G6 137.5 119.O^
133.5 108.0 l
l l
t i
I t
1 e
i i
I 4
t
\\
(
I i
i l
i i
1 1
i l
1 I
4 i
k~
i l
l i
c I
1 l
[
l
.. - ~.,.. _.. _,,,.... _. _ _., _.. _. _... _... _, _ _ _ - _. _.... _ _ _ _.., _ _. _. _, _.. __
Page
' 1.
i 3.-
t t
j UNIT 1 CA'_IBRATION DATA
============_
EQUIPMENT PIECE NUMBER:
,' APPLICATION:
REACTOR LOW / LOW LEVEL MSIV ISOLATION NOMINAL SETPOINT:
134.0" WC
! CALIBRATION TOLERANCE:
133.0-135.0" WC i
' ACTION LIMITS:
128.6-139.4" WC REJECTION LIMITS:
z
.125.4-142.G" WC TECH SPEC ALLOWABLE:
150.64" WC i Calibration Date "As Found" As Found" "As Left" As Left" Trip Reset Trip
' Reset r
i
) 03/12/G6 133.75
'125.0 j10/30/86 134.2 123.0 134.2 123.0 12/29/86 135.0 120.5 134.4 123.0
.)
I i
l t
i t
J k
1 t
l l
4 4
3
-3
-r,y er-.
,-4 3-e-,w-m,~
u - - - - p
-ee
---s.-y
.-.--3
-,--i--,-
.--vw
,-v-
+,--ev..-
r-,--
Page 1
UNIT 1 CALIDPATION DPTA
,== -
- :..- - =. :== -
E_ v, U.r p,. r r, r m-r r3 ' rA
-~-
r ". + M. r. r_ ".n.
a n s l Ms t t n <o..
r 2
.a c
1-u m
. -. 4 O P P L I C i'.T I G J:
D:GCTCR L O*!' L C'.J L E ' ' E L '" : '.' IFOLATION N";MINAL EETPOINT-134. O'-
WC CALIPPATION f CL r r
-ce-.
17, g _ ; ;c3, g o gc et, I t i.s i 4 L.1 i ;i s
m n'.t, L., n.. '+
,,-,n.,
1,.r--,
4
,,, i,r vd u t?I. T T,. f ' 'I 'tr>'
! v..8p
? k.'. T. *tC' 1 --F. /v._ <,1i.'.. f* 'I s
. +
4 1
.tm 6
I1, T L' I'.' t '
C.i ' -r' i _* i- ' '.- l. D. 'c.! (1 L, I'f tt {.
1619
(..**
f 9 v'
?f
! l 6
4. -
5 f' q g y, t j
' ' [] _.
f,)13 y 3(j "
O :
[. ( y f (
Q' 0, O f (
C,'j'&
< f.
1
[.;b+2 Trip r? >
t Trip Rc wt
{,
l L &
a__**.
J
'm.-.J s',
4 fi f '
L'.
T 9 '
11 r.
l u u'*'e.
A '
.-s; a 6_.**
t ".
)
4 *=
Va
.- p3y m jf. ky
<A-/
i( -
g - -,
r 4.t.,.
l.
t A.
i 1 _'!
. c~J t
L s
k-3 4
i
.Page 1
i h
UNIT 1 CALIBRATION DATA
======================_,
EQUIPMENT PIECE-NUMBER:
1B21-NO37AA APPL ICATIOff r RX LO LO-RCIC; LO LO LO LPCS/RHR; ADS PERM NOMINAL SETPOINT:
189.0" WC CALIBRATION TOLERANCE:
187.0-191.0" WC j
ACTION LIMITS:
181.2-196.8" WC l REJECTION LIMITS:
178.8-199.2" WC TECH SPEC ALLOWABLE:
207.17" WC i
Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset j
9/1e./ac 189.s 17s.6 i
10/14/DC 190.3 175.0 189.9 176.0 01/14/87 190.3 175.0 190.5 175.0 I
i i
h I
i f
i l
L r
.I l
i i
I 1
I
)
w
[
Page 1
!~
i i
!!. UNIT 1 CALIDRATION DATA i
========u==
I EQUIPMENT PIECE NUMBER:
IB21-N037BA jAPPLICATION:
RX LO LO RCIC; LO LO LO LOCS/RHR; ADS PERM.
lNOMINALSETPOINT:
189.0" WC 1 CALIERATION TOLERPNCE:
187.0-191.0" WC i
1 ACTION LIMITS:
181.2-196.0" WC l REJECTICN LIMIT 5:
178.8-199.2" WC i TECH SPEC ALLOWABLE:
207.17" WC i
1 i
l Caliber, tion Date As Found" "As Found" "An Left" "An Left" i
l Trip Reset Trip Reset f
I.
l 9/15/86 189.2 179.6 10/14/06 189.8 179.5 189.7 180.0 l
l 01/14/87 191.0 181.0 187.0 176.0 i
i 4
a i
i F
I t
i a
k
.i i
a i
e j
i
)
?
4
~.
h 1
4 s
}
t i
4 4
.,,-------_.,-----,n_n--.-
--n e,.~,na__,,.-n,--_-.<w-~,,,..,.nen,,-n-,,~
, n-w,-,,,,---,v, emm e-e n -
Page 1
i.
it.
1 I
j UNIT 1 CALIBRATION DATR l=======================
\\
' EOUIPMENT PIECE NUMBER:
[ APPLICATION:
RX LO LO RCICl'LO LO LO LPCS/RNR; ADS PERM l
l NOMINAL SETPOINT:
189.0" WC CALIBRATION TCLERANCE:
187.0-191.0" WC i
- j. ACTION LIMITS:
181.2-196.8" WC l
J REJECTION LIMITS:
178.8-199.2" WC r
l TECH SPEC ALLOWABLE:
207.17" WC
} Calibration'Date "As Found" "As Found" "As Left" "As Left" a
Trip Reset Trip Reset l
g_______
4 l
I 9/14/86 187.9 169.1
_j 10/14/86 189.3 169.5 189.0 170.1 j 01/14/87 188.5 171.0 188.0 171.5 i
h R
i i
1 i
1 1
i f
}
l l
i l
l i
L l
\\
l
'Page '
I l UNIl 1 CALIBRATION DATA i.=======================
J l EQUIPMENT PIECE NUMBER:
1B21-NO37DA LAPPLICATION:
RX LO LO RCIC; LO LO LO LPCS/RHR; ADS PERN NOMINAL SETPOINT:
199.0" WC CALIBRATION TOLERANCE:
187.0-191.0" WC l ACTION LIMITS:
181.2-195.8" WC l REJECTION LIMITS:
178.8-199.C" WC
! TECH SPEC ALLOWABLE:
207.17" WC 4
I t
l Calibration Date "As Found" "As Found"
" As Lef t "
" As Left "
(
Trip Reset Trip Reset j----.--.----.----------------_-.------.-..--------..
1 1
9/15/86 188.6 178.5 i 10/14/8G 189.1 178.5 189.3 178.8 I 01/14/87 190.5 179.0 190.0 179.0
}
t
[
T l
1 I
i I
j t
t I
I I
i l
t i
i i
r i
i 3
I e
t f
i t
t t
- m. - ~
s Page 1
l j
1 l UNIT 1 CALIDRATION DATA l=m===a EQUIPMENT PIECE NUMBER:
1921-NO37AB l
-APPLICATIONi RX LO LO RCIC; LO LO LO LPCS/RHR;. ADS PERM.
l NOMINAL SETPOINT:
134.0" WC l
CALIBRATION TOLERANCE:
133.0-135.0" WC t
i
, ACTICN LI$ITS:
128.6-139.4" WC l REJECTION LIMITS:
125.4-142.6" WC l
' TECH SPEC ALLOWABLE:
150.64" WC j
I Calibration Date "As Found" "As Found"
" As Lef t "
"As Left" i
Trip Reset Trip Reset l
j I
9/14/86 134.2 126.9 l
10/14/86 134.4 127.4 134.G 127.6 1
01/14/87 133.5 127.0 133.5 127.O l
i l
I I
a l
l l
I r
i I
r 1
a f
b i
t
=
l Page 1
i jUNIT 1. CALIBRATION DATA
,:.u=====-=======~=====_==
EQUIPMENT PIECE NUMBER:
1821-N037BB APPLICATION:
RX LC'LO RCIC; LO LO LO LPCS/RHR; ADS ~ PERM 4
LNOMINAL SETPOINT:
134.0" WC 1 CALIBRATIOri TOLERANCE:
133.0-135.0" WC j
! ACTION LIMITS:
- 128,6-139.4" WC
- REJECTION LIMITS
125.4-142.6" WC
- . TECH SPEC ALLOWABLE
- ,
150.64" WC Il Calibration Date As Found" As Found" "As Left" "As Left" Trip Reset Trip Reset i
9/15/86 133.9 125.7
- 10/14/86 135.0 125.8 134.3 125.7 i 01/14/87 13% 0 125.0 134.5 125.0 i
I t
l i
i i
e 1
4 1
I 1
l l
1-J
't l-
)
i 1
1,.,---..,.me,...m
.+-e,%.%-4..,,,.,.y,
,.w
-__.,w-.-,
,y,.my,,,,.7.,,w,,,w,
,,,,,-.,,_..y.+w,,,,,,.,_c._yy-,--,,,,,,,y,o.-wn_w.-.,,,.e
.t '
Page 1
l l
UNIT 1 CALIBRATION DATA i
====2======
a j' EQUIPMENT PIECE NUMBER:
IB21-NO37CD
{ APPLICATION:
RX'LO'LD RCIC;=LO LO LO LPCS/RHR;. ADS PERM' i NOMINAL SETPOINT:
134,0" WC CALIBRATION TOLERANCE:
133.0-135.0" WC-ACTION LIMITS:
128.6-139.4" WC REJECTION LIMITS:
125.4-142.G" WC-
.i TECH SPEC ALLOWABLE:
150.64" WC fCalibrationDate "As Found"
" A s Fo u nd '.'
"As Left" "As Left" Trip Reset; Trip Reset 9/15/86 133.5 126.7 10/14/86 134.1 126.8 133.9 126.9 4
01/14/87 134. +)
127.0 133.5 127.0 e
t i
4 i
4 i
s J
I f
4 e
t i
j
?
- r A
e
-.n-.
,r.
.--m--
,-.-w,
...~,,,
.-.,-...n,.---n-.. - -, -..,., - - - -,
,nn.ee-,---..,,.,--,er,-.-<
_. ~. _.. _
1 Page 1
4 l UNIT 1 CALIBRATION DATA
:=================
l EQUIPNENT PIECE NUMBERr 1B21-NO37DD AP.7LICATION:
RX LO'LO RCIC; LO LO LO LPCS/RHR; ADS PERM.
4 j NOMINAL SETPOINT:
134.0" WC
- CALIBRATION TCLERANCE
133.0-135.0" WC i-ACTION LIMITS:
128.6-139.4" WC d
! REJECTION LIMITS:
125.4-142.G" WC
! TECH SPEC ALLOWABLE:
150.64" WC
) Calibration Date "As Found" "As Found" "As Left" "As.Left" Trip Reset Trip Reset 9/15/86
.134.0-126.3 10/14/06 134.7 126.2-134.5 126.4 01/14/87 134.5 126.0 134.5 126.0 4
f i
I i
i i
i i
?
)
4 i
a 6
~
I
. -. _ -.... -.... _,. - _ -. _.,,.. ~.. - - _
-.. _ - - ~ _ _
Page 1
i e UNIT 1 CALIBRATION DATA
e============
l EQUIPMENT PIECE NUMBER:
1E21-N004 i APPLICATION:
'LPCS MIN FLOW DYPASS NOMINAL SETPOINT:
23.0" WC j CALIBRATION TOLERANCE:
23.6-22,4" WC
' ACTION LIMITS:
24.7-21.3" WC
- REJECTION LIMITS
25.4-20.6" WC TECH SPEC ALLOWABLE:
3,187" WC
. Calibration Date "As Fcund" "As Found" "As Left" "Ac Left"
{
Trip Reset Trip Reset
- 09/07/86 22.8 29.2 12/1O/86 23.3 31.0 23.6 30.3 f
r
/
L 1
l i
~
1 i
i l
r 9
i I
a 1
1
,_.._,_,--~.--_.~--.._,,.m..
_--._.,,...-,.-....-,.-r.-
t
?
Page
~1 f
l
- UNIT i CALIBRATION DATA
- a = = = =
- .= n e : n = = =.= = = =
2IEQUIPMENT PIECE NUMBER:
1E22-N006 t APPLICATION:
HPCS MIN FLOW DYPASS
!NOMINALSETPOINT:
23.00 "WC jCALIBRATIONTOLERANCE:
22.40-23.60 "WC
{
I ACTION LIMITS:
21.30-24.70 "WC i
} REJECTION LIMITS:
20.00~26.00 "WC i TECH SPEC ALLOWADLE:
7.85 "WC I
i
{ Calibration Date
'"An Found" "As Found"
" As Le f t " -
"As Left"
-l Trip Reset Trip Reset
)
)
i a
l 9/15/86 23.10 31.10 4
f10/10/86 23.30 31.00 23.20 31.00 1 01/09/87 22.8 32.3 22.8 29.4
}
J l
i 1
4 i
4 f
L I
i 1
1 5
i l
t i
k i
}
i
!i
- =
-g+ws-
- _ nwg m 4: mm am m mkom e e4 Page
-I 4
1
! UNIT 1 CALIBRATION DATA l======== nun============
j-4 EQUIPMENT PIECE NUMBER:
, APPLICATION:
RHR PUMP MIN FLOW DYPASS (LPCI MODE) l 4
ii NOMINAL SETPOINT:
23.0" WC CALIBRATION TOLERANCE:
22.4-23.6" WC l
t ACTION LIMITS:
21.3-24.7" WC j
REJECTION LIMITS:
17.7-28.3" WC l
TECH SPEC ALLOWABLE:
1.78" WC l
(
' Calibration Date As Found" As Found" "As Left" "As Left" 1
]
Trip Reset Trip Reset 1
......----.--- ~.... -- ------.----.--- --.
j 1
l 1
09/10/86 23.0 27,2 l
10/22,'86 C2. 8 29.6-23.0 27.8 l
I i
i
?
f.
i 9
I o
i i
i
- I I
i t
i I
i I
I l
- ~
Page 1-1 l-i i
i! UNIT 1 CALIBRATION DATA 5
==amn=e
===n
- EGtJIPMENT PIECE NUMDER
! APPLICATION:
RHR PUMP MIN FLOW BYPASS (LPCI' MODE) i NOMINAL SETPOINT:
23.0" WC
. CALIBRATION TCLEPANCE:
22.4-23.G" WC
{
l
.i ll ACTION LIMITS:
21.3-24.7" WC e
l REJECTION LIMITS:
17.7-28.3" WC
, TECH SPEC ALLOWABLE:
1.78" WC l
i i
i 1
{ Calibt'ation Dato
" As Fo md "
"As Found" "As Left" "As Left" Ttip Roset Trip Reset l
l 09/10/86 22.8 28.4~
10/22/06 22.4 29.2 22.8 28.2 i
i i
t l
+
s 1
l w --~ --.
- L
4-L d.p-A.a.
_r-h K
5+
J4
>m2=
JJ....
..o+
p, n.
4g a
i A h. fa p Page 1
l i'
I fUNIT 1 CALIBRATION DATA.
:========r.==
4 EQUIPMENT PIECE NUMDER:
1E12-N010CA JAPPLICATION:
RHR PUMP MIN FLOW DYPASS (LPCI MODE) 1 NOMINAL SETPOINT:
23,0" WC
- CALIBRATIGN TOLERANCE
22.4-23.6" WC
- ACTION LIMITS
21.3-24,7" WC REJFCTION LIMITS:
17.7-28.3" WC
, TECH SPEC ALLOWABLE:
1.78" WC 4
l i
1' Calibration Date As Found" As Found" "An Left" "As Left" a
Trip Reset Trip Reset j
09/11/86 23.4
- 29. 'd 8
- 10/22/86 23.8 29.6 23.2
- 28. le s
s i
}
D D
N 4
j e
j w
~
n s
.,A h
{
s
, ~ ~.
s
)
i 1
t 1
i e-h 1
-s 3
-s
'N t
l
@ )
I '
,g, l '
s 1
A s
4 3
.g y
s 1 - +> f $. \\
l
)
' s -
i i
x b
w.
z.y
.n,-
I
~
}'
Page-1[
j l
I'
., UNIT 1 CALIBRATION DATA
- =======
===u======n
EQUIPMENT PIECE NUMBER:
1E12-N010AB fAPPLICATION:
RHR DUMP MIN FLOW BYPASS (LPCI MODE) 4 NOMINAL SETPOINT:
25.0" WC CALIBRATION TOLERANCE:
24.0-26.0" WC 1
j ACTION LIMITS:
N/A l REJECTION LIMITS:
N/A l TECH SPEC ALLOWABLE:
N/A 1
i ij Calibration Date "As Found" "As Found"
" As' L ef t "
"As Left" l
Trip Reset Trip Reset J____.._________________.__.._____._____________.-______________.._.
i i
i 1 09/10/85 24.4 17.O
- 10/22/86 24.2 18.0 24.8.
20.4.
1 f
i s
1 i
I
}
}
(
i i
i i.
i i
i
.i i
l
+
r i
(
i I
L 6
^4
... -. -.. ~... - - -..
I i!~
l Paga 1
}! UNIT 1 CALIBRATION' DATA i
s' EQUIPMENT PIECE' NUMBER:
1E12-N010DB-i f APPLICATION:
RHR PUMP MIN FLOW BYPASS (LPCI' MODE) l l
_t l NOMINAL SETPOINT:
25.0" WC s
! CALIBRATION TOLERGNCE:
- 24.0-26.0" WC i
ri t
j ACTION LIMITS:
N/A
[
! REJECTION LIMITS:
N/A i
! TECH SPEC ALLOWABLE:
N/A I
i
?
! Cali.bration Date
-"As Fodnd"
^"As Found" "As Left" "As Left" l
Trip,_
-Reset Trip Reset 1
.__-_____..s.______.__._.__________________________
I 1 09/10/86 25.8 20.4 l10/22/06 25.6 20.6 25.4
.20.8 i
4 f
e b
}
i i
's I
l b
i i
l 1
i
+>
0 li i
i I
l a
k 1
I
.L
.}
3 l
v-t j
l i
i i
i k
i j \\1 y
b p.
R P
j l
s' 4
r
/
j i
i i
t..-.-
.~...-
Page.
1-UNIT 1 CALIBRATION DATA
===========
l EQUIPMENT PIECE-NUMBER:
' APPLICATION:
RHR PUMP MIN FLOW BYPASG-(LPCI MODE) 4 NOMINAL SETPOINT:
25.0" WC L CALIBRATION TOLERANCE:
24.0--26.0" WC i.
ACTION LIMITS:
N/A REJECTION LIMITS:
N/A
- TECH SPEC ALLOWABLE
N/A i Calibration Date "As Found" "As Found" "As Left"
- " As Left" Trip Reset Trip Roset 09/10/86 24.6 19.4 10/22/85 24.8 19.4 24.6 19.6 s
'i i
I 1
a i
I
)
I 4
I i
I i
f l
l
-c.
,-.r
,r
...7
~~
-PaDe 1
0 1
I l
UNIT 1 CALIBRATION DATA i
]
===========
I EQUIPMENT PIECE NUMBER:
I APPLICATION:
MAIN STEAM LINE HIGH FLOW MSIV ISOLATION-NOMINAL SETPOINT:
97.6 PSID a
CALIBRATION TOLERANCE:
96.6-98.6 PSID ACTION LIMITS:
8?.5-105.7 PSID h
REJECTION LIMITS:
87.2-108.0 PSID TECH SPEC ALLOWABLE:
116.O PSID
.]
I' Calibration Date "As Found" As Found" "As Left"'
"As Left" Trip Roset Trip Reset I
J 9/12/86
.97.4 73.9 10/15/86 98.4 73.2 98.3 75.7 12/15/86 99.8 72.0 97.0 62.4 4
t 1
t
?
l t
1 i
3 e
f i
l i
l t
i
.--.._-_...--.,._,.,..--.-i-_~-.
-n---.--
w-1
~
~.
Page l'
1 l UNIT 1 CALIBRATION DATA
===========
! EQUIPMENT PIECE NUMBER:
1E31-N008B APPLICATION:
MAIN STEAM LINE HIGH FLOW MSIV ISOLATION
~
4
' NOMINAL SETPOINT:
97.6 PSID CALIDRATION TOLERANCE:
96.6-98.6 PSID ACTION LIMITS:
89.5-105.7 PSID REJECTION LIMITS:
87.2-108.0 PSID TECH-SPEC ALLOWABLE:
116.0 PSID e' Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Recet Trip Reset 2
9/14/86 97.2 69.7
- 10/15/86 97.9-70.2 97.1 69.3
- 12/15/86 100.0 67.0 97.6 63.0 j
i l
l i
a I
J r
1-i
\\
i
[
l l
l
'Page l'
1
.i i UNIT 1 CALIBRATION DATA
- = = = =
i EQUIPMENT PIECE NUMDER:
. APPLICATION:
MAIN STEAM LINE HIGH FLOW MSIV ISOLATION
! NOMINAL SETPOINT:
97.6 PSID j CALIBRATION TOLERANCE:
96.6-98.6 PSID i
4
] ACTION LIMITS:
89.5-105.7 PSID I REJECTIGN LIMITS:
87.2-108.O PSID
! TECH SPEC ALLOWABLE:
116.0 PSID l
i i Calibration Date "An Found" As Found" "As Left" As Left" i
Trip Reset Trip Reset j__..____,_________.________._____.____________________________,._____.-__.______
I i
9/13/86 97.6 72.7 l
. 10/15/86 98.6 74.9 97.85 74.1 j12/15/86 101.2 69.4 97.0 65.2 f
g i
i i
k i
I.
i i
i I
1 b
J s
l i
l i
+.m..<-wa.,.--=%=.-,_--r-i--.m-r++=w--mv w-cr-
,-m,-
er-+-.*wv-e
-w w w o -e-
,mw.-=v-6--=ww w e w-w w ww w w v"1Wm w-rw f av' vW ree rw' er d-Uw-
-v =w ow-v ua-w ww- " v'*"M e y
- V 9 v n *= w *= -**
- Page-1 Y
4 E
- UNIT 1.CALIDRATION DATA i, =
=
EQUIPMENT PIECE NUMBER:
$ APPLICATION:
MAIN STEAM LINE-HIGH FLOW MSIV ISOLATION e
.; NOMINAL SETPOINT:
97.6 PSID i' CALIBRATION TOLERANCE:
96'6-90.6 PSID
$j ACTION LIMITS:
89.5-105.7 PRID l REJECTION LIMITS:
- 87. 2-108. 0- PSID l TECH. SPEC ALLOWADLE:
116.0 PSID i
[CalibrationDate "As Found" "As Found" "As Left" "As Left" l
Trip Reset-Trip Reset
-t.9/14/86 97.1 7 '1. 0 j
- 10/15/86 101.3 69.0
~97.35 72.3
.]12/15/8G 107.6 *) ACTION 62.0 97.8 61.2 d
i i
j I
f l
(
I l
I I
l 4
1 f
4 4
4 j
i
., _,.., _ _......... _. -, _., _....,... -,,...,...,.,.. _ -,. _..,, -,,,,, ~., -. _...
--~
Page-1 UNIT 1 CALIBRATION D'TA A
===========
EQUIPMENT PIECE NUMBER:
1E31-N009A APPLICATION:
MAIN STEAM LINE'HIGH FLOW MSIV ISOLATION NOMINAL SETPOINT:
97.6 PSID j CALIDRATION TOLERANCE:
96.6-98.6.PSID l ACTION LIMITS:
89.5-105.7 PSID REJECTION-LIMITS:
87.2-108.0 PSID TECH SPEC ALLOWABLE:
116.0 PSID l
! Calibration Date "As Found" "Os Found" "As Left" "As Left" Trip Reset Trip Reset 9/13/86 97.5 72.5.
11/07/86 98.9 68.0 97.8 71.2 01/05/87 90.1 70.3 97.6 71.3 i
4 1
s t
i I
l 1
I i
i e
4 i
j i
i i
{.
4
^
I Page
-i J-i i
i t
j I
. UNIT 1 CALICRATION DATA ~
,i
n==================
)EQUIPMENTPIECENUMBER:
jAPPLICATION:
MAIN STEAM LINE HIGH FLOW MSIV ISOLATION 1
?i NOMINAL SETPOINT:
97.6 PSID
-CALIBRATION TOLERANCE:
96.6-98.6 PSID ACTION LIMITS:
89.5-105.7 PSID REJECTION LIMITS:
87.2-108.0 PSID TECH SPEC ALLOWAELE:
.116.0 PSID-e i
i Calibration Date "As Found" "As Found" "As Left"
A s Le f t "
Trip-Reset Trip Reset t
9/14/86 97.4 74.9 11/07/86 99.0 72.0 97.G 73.0
! 01/05/87 99.8 73.~G 97.1 73.8 1
i i
i i
1 i).
i t
1 i
E t
h i
i i
4
,I i
I 1
i
k r
Page 1
i i
1 1
i~ -
'. UNIT.1~ CALIBRATION DATA
+
r EQUIPMENT PIECE NUMBER:
{ APPLICATION:
MAIN STEAM LINE HIGH FLOW MSIV ISOLATION 4
s
.. NOMINAL SETPOINT:
97.6 PSID 1; CALIBRATION TOLERANCE:
96.6-98.6 PSID i
j
' ACTION LIMITS:
89.5-105.7 PSID 1 REJECTION. LIMITS: _
87.2-108.0 PSID
116.O PSID J
l 1; Calibration Date "As Found" "As Found" "As Left" "As Left" i
Trip Reset Trip Reset 1
i t
i 9/13/8G 97.9 75.1
'-11/07/8E 100.5 71.5 97.5 72.0 01/05/87 98.9 72.0 97.4 73.3 j
)
e b
i 1
4 I
i l
i r
l i
i v
t J
4 i
?
I i
i R
i
r Page 1
\\
5 i
4
.. CALIDRATION DATA (UNIT 1 j.==========e============
i ECUIPMENT. PIECE NUMEER:
.! APPLICATION:
MAIN _ STEAM LINE HIGH FLOW MSIV ISOLATION t
'; NOMINAL SETPOINT:
97.6 PSID CALIDRATION TCLERANCE:
96.E-98.G PSID.
j ACTION LIMITS:
89.G-105.7 PSID
{-REJECTION LIMITS:
87.2-108.0 PSID TECH SPEC-ALLOWABLE:
116.0 PSID I
j Ceilibration Date "As Found" "As Found" "As Left"
" As Le f t"
}
Trip Reset Trip Reset I
3/14/86
'37.9
- 74. G 4.11/OS/0G 102.0 72.0 97.7 G9. 0
'; 01/05/87 9G.1 69.3 97.0 69.9 i-i 1
i
}
l i
j
-i j
5 t
L f
I i
i t
i
)
.I ii l,
l i
L i
I i
l t
i l
1
Page
. 1 J.
i
. UNIT i CALIBRAlION DATA l=======================
EQUIPMENT PIECE NUMBER:
1E31-N010A APPLICATION:
MAIN STEAM LINE HIGH FLOW MSIV ISOLATION NOMINAL SETPOINT:
97.6 PSID.
CALIDRATION TOLERANCE:
96.G-98.6 PSID ACTION LIMITS:
89.5-105.7 PSID I REJECTION LIMITS:
- 87. i? -108. 0 PSI D
' TECH SPEC ALLOWABLE:
116.0 PSID A
Calibratien Date "As Found" "As Found" "As Left" "As Left" Trip Roset Trip Reset 1
i 9/13/86 97.4 75.7
..12/04/06 99.7 71.4 97.3 7E.6 1
4 i
I I.
l 4
i
(
+
4 l
I i
l 1
i 1
l 4
5 L.. -..
i.
Page 1
I-
\\
i 4
, UNIT 1 CALIDRATION DATA i
a======n=======
i ECUIPMENT PIECE NUMBER:
' APPLICATION:
MAIN STEAM LINE HIGH FLOW MSIV ISOLATION i
] NOMINAL OETPOINT:
97.6 PSID j CALIBRATION TOLERANCE:
96.5-98.G PSID 1 ACTION LIMITS:
89.5-105.7 PSID-I PEJECTION LIMITS:
27.2-108.0 PSID I TECH SPEC ALLOWADLE:
116.0 PSID 4
Calibration Date As Found" "As Found" "As Left" "As Left" j
i Trip
.Penet Trip Resnt j -..____.__._
4 9/14/06 97.2 70.5
- 12/05/86 99.1 68.3 98.0 69.7 i
b I
i i
l 1
l J
1 i
2 l
l 1
i 1
e i
d l
l 1
1 1
-r.
..r-
,--n--n w w, -s w-r--w,x-+-,,,w-
,-r
~.
.... - =
Page
.1 W
i
' UNIT 1-CALIDRATION DATA
,========~=
=u=========.
j
' EQUIPMENT PIECE NUMBER:
1E31-N010C APPLICATION:
MAIN STEAM LINE HIGH FLOW MSIV ISOLATION i
$ NOMINAL SETPOINT:
97.6 PSID CALIDRATION TOLERANCE:
96.6-98.6 PSID i
i r
ACTION LIMIT 5:
89.5-105.7 PSID REJECTION LIMIT 5:
87.C-108.0 PSID TECH SPEC ALLOWABLE:
116.0 PSID i
! Calibration Date
" A n Fo'md "
"An Found" "As Left"
" As Le f t "
j Trip Reset Trip Reset 9/13/0C 97.9 71.3
.1 :' /,15 / 8 6 99.9 C9. 3 97.2 68.0
-i a
l i
4 9
a
.i 4
1 t
i i
i i
l 6
4 I
e r
l i
i i
1 I
t I
1
m.
1 Page 1
L UNIT
- 1. CALIBRATION DATA u==ux=========e========
1
', Ef2UIPMENT PIECE -NUMDER:
1E31-N010D l APPLICATION:
MAIN GTEAM LINE HIGH FLOW MSIV ISOLATION i
[ NOMINAL GETPOINT:
97.6 PSID
- CALIPRATION TOLERANCE
96.6--90.6 PSID i ACTION LIMITS:
09.5-105.7 PSID fREJECTION LIMITS:
87.2--108.O PSID i TECH SPEC ALLOWABLE:
116.0 PSID.
i j Calibration Date "As Found" "An Found" "As Left" "At Left"
/
Teip Reset Trip Resut; I
a I
9/14/86 97.6 74.0 y
1 12/05/06 9G. O G7.4 9G. 9 72.6 1
'S l
4 B
i J
i 1
4 I
i e
l 4
I r
1 i
e I
f r
t L
4 I
E i
i k
1 i
i l
i 1
6 t
1 3
J
.-.-. -._ -_ ~.. --..-. -.-.-,-,,. -,.... -. -. - -,._. - -..
Page 1
i
- UNIT 1 CALIBRATION DATA j
n = = = = u = = n = = = = : - = = = = = n :-
i EC' IPMENT PIECE NiJMGER:
4i APPLICATION:
MAIN GTEAM LINE HIGH FLOW MSIV ISOLATION a
1 3 NOMINAL SETPOINT:
97.G PGID l CALIBRATION TOLERANCE:
9G.G-98.6 PSID
- { ACTICN LIMITS:
89.5-105.7 PSID
} REJECTION' LIMITS:
87.2-108.O PSID
} TECH SPEC ALLGWABLE:
116.0 PEID i
4 j Calibration Date "As F o ei n d "
"As Found' "As Left" "As Left"
+
Tri Reset Trip Resel 1,___.._.--______.~___._____p _ _ _. _. _ _ _ - _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _. _
4 3
9/13/05 97.5
- 71. G I12/04/8G 101,9 73.4 90.0 71.8 3
i
)
I 4
\\
l J
5 0
i f
4
)
2 i
i i
i i
,i i
i l
1 f
t I
i I
f i
i l
3 Page 1
+
t i
i f' UNIT-1CALIBRATIONDATA
n====m==u==========
i s
]
! EQUIPMENT PIECE NUMFtER:
j APPLICATIOrl:
MAIN STEAM LINE HIGH FLOW MSIV ISOLATION NOMINAL SETPOINT:
97.6 PSID l
CALIDRATION TOLERANCE:
96.6-98.6 PSID l
I ACTION LIMITG:
89.5-105.7 PSID REJECTICN. LIMITS:
87.2-108.0 PSID l
J TECH SPEC ALLOWABLE:
116.0 PSID l
1 J
t
! Calibration Date "As Founcf" "As Found"
" As Le f t "
"As Left"
{
Trip Reset Trip Reset
~ _ _ _ _ _ - _ _ _
I 9/14/8C c'7. 3 70.6 S
12/05/86 9G. G G8. 0 98.0 72.2 l;
i
}
i 1
I 6
1 6
l i
i 4
i t
e i
t I
f i
}
4 l
i
-. ~..
Pago i
i UNIT 1 CALIBPATIO*1 DATA
============ : -
EOUIPMENT PIECE NUMBER:
1E31-N011C APPLICATIOT.
MAIN RTEAM LINE IIIGH FLOW MSIV IGOLATION NOMINAL OETPOINT:
97.G 0010 CALIERATION TOLEUANCE:
OG. C--98. 6 PSID ACTION L I r1 I T C -
99.5-105.7 P'3 I D PEJECTION LIMITO:
R', 2 -- 108. O PSID T E C'r i SIT.C A.LOWADLE:
116.0 PSID rali:., t i m Date
'A3 round" "A=
Found" "As Le f t "
"Ac Left"
->' i p Penet Trip Reset.
n-
,. < e,.,
,.y<..n
< t. e.
i >.
a 1 m....... y. _, n.. L.
n-. 9
-.,. ft u.
s
's
.cu.u i
Page 1
UNIT 1 CALIBRATION DATA u=============-======:=
EGUIPMENT PIECE NUMBER:
1E31-N011D APPLICATION:
MAIN STEAM LINE HIGH FLOW MSIV ISOLATION NOMINAL SETPOINT:
97.6 PSID CALIDRATION TOLERANCE:
9 G. G - 9 6. 6.. P S I D ACTION LIMITS:
89.5-105.7 PSID REJECTION LIMITS:
37.2-108.0 PSID TECH SPEC ALLOWABLE:
116 O PSID Calibration Date "As Found" "As Found"
" As Le f t "
"A3 Le f t "
Trip Ro wb Tr1p Reset a
9/14/86 97.6 76.0 12/05/8C 100.5 74.9 97.7 75.5 1
i PaDe 11 o
i i
UNIT 1 CALIBRATION DATA
!==========.-============
- EQUIPMENT PIECE NUMBER
1E31-N007AA APPLICATION:
STEAM LINE HIGH FLOW RCIC ISOLATION J
NOMINAL SETPOINT:
111.4" WC 4
CALIBRATION TOLERANCE:
110.4-112.4" WC t
. ACTION' LIMITS:
106.0--116.8" WC
! REJECTION LIMITS:
102.8-120.0" WC i TECH SPEC ALLOWABLE:
128.0" WC J
j 2
i Calibration Date "As Found" "As Found" As Left" "As Left" d
Trip.
Peset Trip Reset I
jSERIAL NUMBER
! 06-6-E517
}09/09/85 REVISED SETPOINT 111.0 104.3 i 09/13/06 114.0 102.0 111.0 105.0
!11/19/GE 113.5 105.0 111.2 105.2 1
1 5
i 1
l i
i I
i i
j I
I i
l n,
I i
\\
4 l
Ii.,__,,.-....._--._..... _ - -. - -. _. ~..,,... ~ - ~. -. _. _. - _.. _ _ _ _ _ _ _.,. _. _. _
i 4
o4i ym.4.a:
4
+
ae w
m-,5 4
+
w 4 m
,-2M E
.a w
._w Page 1
i.
i 1
' UNIT 1 CALIBRATION DATA
= = = = a = = =. = = - a = u n a n = = = = = n a
l EQUIPMENT PIECE NUMBER:
.. APPLICATION:
STEAM LINE HIGH FLOW RCIC ISOLATION NOMINAL SETPOINT:
lit.4" WC
{ CALIDRATION TOLERANCE:
110.4-112.4" WC
- ACTIGN LIMITS
106.0-116.8" WC i REJECTION LIMITS:
102.0-120.0" WC l TECH SPEC ALLOWABLE:
128.0" WC tj Calibration Date As f'ound" As Found" "As Left" As Left" Teip-Reset Tr*1p Reset t
! SERIAL NUMEER j 85-4-2C1 l09/10/86 REVISED SETPOINT 111._1 105.0
- 09/13/8G 112.0 106.0 111.5 106.0 i11/19/86 111.8 105.6 111.6 10G.0 5'
l 1
4 i
t a
f i
I Jj.
.s j
i t
'I I,
i, 6
Y
}i J
r l
}
i
. ~. -
Page.
1 i
I l UNIT 1 CALIBRATION DATA l=====================u=
j EQUIPMENT PIECE NUMBER:
- i. APPLICATION:
STEAM LINE-HIGH FLOW RCIC ISOLATION
.' NOMINAL SETPOINT:
75.4" WC 1; CALIBRATION TOLERANCE:
74.4-76.4" WC f
i
! ACTION LIMITS:
70.0-80.8" WC j
i REJECTION LIMITS:
66 s-84.0" WC i TECH SPEC ALLOWABLE:
1ES.0" WC i
i 11 Calibration Date "As Four.d" "As Found"
" As Le f t "
"As Left" a
j Trip Reset Trip-
' Reset.
1 l
.i J SERIAL NUMBER l85-4-262 09/10/06 REVISED SETPOINT 75.7 69.5 4
I09/13/86 76.0 69.0 76.O 69.0 l11/19/86 77.2 71.0 75.0 68.5 1
i A
i a
f I
+
i i
i l
n
}
}
i l
i l
1 1
i il i
i i
i l
e f
1 I
t
... ~..._...., -.. _...,.-.- ~._-. _,.-...,..-_.. _. - - -, _, _ _... _.. ~.. _
Page 1
UNIT 1 CD.IDPGTICN DATG
._r===
-- :=.
--.cu==
E Q! j I m'E N T PIEE NUMEER:
1 E 3 1 - N C 0 7 E'P Ft P PL I ff AT I ON :
9 TEOS1 L1NE HISH FLGW RCIC ISCLATION NOMINAL GETPOINT:
7F.4" (K
cal.IERATICN T O L E P '" !C L 74.4-75.4" WC ACTION LIMITS:
70.0-00.O' WC p r: J Fu" ", I C ' '.._ T " ' 7 " -
1 r. u% N. 0 "
'rJ r t
.< ' i. 2 m..
v t
T i_..
b-c r, r. r Ii. L.ts'.m r!_ r..
->.ni i ~
r O. (3. +
W' L
, r -
L
- e v
&1 C i l "a l 11 - " 1 r 0 /. '
'D-F a i.i rd "
" A :, F.a u rid "
" f4 _ Left" "Pc Left"
- 'c i p Re - it Irip Fe se t; Ee.
Ap, M 4 w ee m*
- , ),.s
- . k,' r /
r1 'b.
' ' e) r.. 4
~
e-r '- ~r " b7
-Fr
'[' 'd 3 I
I*
k (I
$/g %l k
4-
'l O '.' ' l 3 / s 7/,- ',.
EE. 0 7C. C 69.0 4
.k
_ /. y'
- C- (o, a -
v, ).
k
(? ' y
,)
,n e
_f
(
g r' ('
g J
l l
5
\\
~. -.
j.
PdDe 1
i
- UNIT 1 CALIDRATION DATA l=uwu============
==e==n i
j EQUIPMENT PIECE NUMBER:
1E31-N013AA l APPLICATION:
STEAM LINE HIGH FLOW RCIC-ISOLATICN i
} NOMINAL SETPOINT:
166.4" WC
} CALIBRATION TOLERANCE:
165.4-167.4" WC 1
l ACTION LIMITS:
161.0-171.8" WC j REJECTION LIMITS:
155.3-177.0"WC j TECH SPEC ALLOWA9LE:
185.0" WC i Calibration Date "As Found" "As Found"-
"As Left" "As Left" Trip Reset Trip Re' set j
i
, SERIAL P!JMBER l-BS-4-264 l09/10/86 REVISED SETPOINT 166. G 158.5 i
j09/13/86 167.0 150.0 167.0 159.0 1 11/19/65 168.6 160.9 165.7 158.0 i
k 4
i I
I t
i i
1 l
j 1
a a
i J
1 2
- l l
1 i
4 I
)
1 1
1
)
Page 1
1 2
1 l
UNIT'l CALIDRATION DATA
- =======================
EQUIPMENT PIECE NUMBER:
1E31-N012AB APPLICATION:
STEAM LINE HIGH FLOW RCIC ISOLATION 1
NOMINAL SETPOINT:
166.4" WC
- CALIBRATION TOLERANCE
165.4-167.4" WC i
i ACTION LIMITS:
161.0--171.8" WC j REJECTION LIMITS:
155.8-177.0"WC TECH EPEC ALLOWAOLE:
185.0".W]
I j Cali twat ion Date "At Founri" "As Found" "As Left" "As'Left" Reset Trip Reset Trip jSERIALNUMDER 85--5-2C5
- 09/10/GG REVISED SETPOINT 166.t 15G. 5 i 09/13/86 167.5 157.0 166.0 157.0
' 11/19/06 167.0 158.8 166.7 159.0 1
l
-4 1
1 1
1 5,
i 1
i 4
)
I
'e 4
?
1 j
)
+
i 2
i I
l l
L,_..-..._-.,_-._--_..---._-.
. - _...... -. _ _ - _ _. _ _ _. _ _..., _. = _ _ _. -,.. _. _. ~ -. _ _..
\\-
1 j
Page 1
j 4
I i
i
. UNIT 1 CALIBRATION DATA
.n=================
==
i EQUIPMENT PIECE NUMBER:
APPLICATION:
GTEAM LINE HIGH FLOW RCIC ISOLATION l
1 j NOMINAL SETPOINT:
166.4" WC i CALIBRATION TOLERANCE:
165.4-167.4" WC 1
j ACTION LIMITS:
161.0-171.0" WC j REJECTION LIMITS:
IDS.8-177.0"WC jTECHSPECALLOWABLE:
185.0" WC Calibration Date
" As Foimd" "As Found" "As Left"'
"As Left" 1
Trip Revet Trip-
. Reset
- - - - ~ ~ ~ - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -. - - - - - - - - - - -.. - - - - - -
I SERIAL NUMDER i
85-1-24C5 09/10/86 REVISED SETPOINT 166.5 158.2
- 09/13/GG 1G6. 5 1 G 1. 0 166.5 161.0 l 11/19/OG 168.5 1G1.5 165.5 157.5 f
4 i
f i
l i
e I
3 f
I
+
P l
f l
I i
~
Page 1
UNIT 1 CALIBRATION DATA
= = n = = e = = = = = = = = = u = a = = = u _-
EQUIPMENT-PIECE NUMBER:
1E31-N013BD l APPLICATION:
STEAM LINE HIGH FLOW RCIC ISOLATION j NOMINAL SETPOINT:
166.4" WC CALIBRATION TOLERANCE:
165.4-1G7.4" WC ACTION LIMITG:
161.0-171.8" WC l REJECTION LIMITS:
155.8-177.0"WC i TECH SPEC ALLOWADLE:
185.0" WC y
i
' Calibration Date "As Found" "As Found"
" As Lef t "
"As Left" Trip Reset Trip Reset
_________.__________rc__2__________________________a____________________
1
- SERIAL NUMBER
] 66-6-2515
] 09/10/86 PEVISED GETPOINT 166.0 157.5
- 09/13/06 166.5 159.0 166.5 159.0 i 11/19/86 167.4 I S'/. 0 166.2 157.O i
1 M
i
)
i i
t l
1 I
)
1 d
e*
g l
f
.i i
l
}
l l
1 i
f d
I I
...,6t 4'
Page 1
1 t
t
~
3.
's UNIT 1 CALIDPATION DATA s
,s c=.=m
_-=r.===:.
N EQUIPMENT PIECE NUMOER:
APPLICATICN:
RHR WHUTDOWN COOLING) llI SUCTION FLOW ISO NOMINAL SETPOINT:
1FA.4" WC..
CALIDRATICN TCLEPANCE:
167. 4 -- 1 G9. '4 " WC.
ACTION LIMITO:
162.0-173.0" WC' REJECT 1CN LIMITS:
150.8-178.0" WC' TECH CPEC ALLOWADLE:
186.C" WC
['
z.
s
\\
s
.f t '3 ' t "
"An Left" ~'
C a l i b r n t 1.'r, F'a t e "A:a Found" "Am F o u n d
" A ;--
Trip R
,et Trip F+wt
..__._._._____m_..
__..__._____.__.__u_
.._-____.____-_e___.s.________..s_____.______
1 09/11/e6 1GG 0 145.0 11/05 'OG 107,5 153.0 1 G7. L 153.0 01/10 / E-'
t r,7. 5 154.O i GG. 5 156.S t
A h
t w s 4
)*
[
4 6 '
)
..~
. _ _ _ _ _ ~. _.. _. _ _. _ _ -
~.. _...,
?
Page'.
.1-i-
1 4
1 -
1 I
4
}. UNIT 1 CALIBRATION DATA
!, c u m n :s = = = = e n c = = = = n = d = n = =
4 i
l EQUIPMENT PIECE NUMBER:
1E31-N012AB I APPLIC(1 TION:
RHR (SHUTDOWN COOLING).HI'5UCTION FLOW 150 t
1' i NOMINAL SETPOINT:.
168.4" WC
.t CALIBRATION TOLERANCE:
-167.4-169.4" WC i
i i ACTION LIMITS:
163.0-173.8" WC l REJECTION LIMITS:
158.8-170.0" WC j TECH SPEC ALLOWABLE:
186.0" WC i
jCalibration Date "As Found" "As Found" "As Left"'
"As Left" i
4 1
Tt-ip Roset Tt 1p Reset f,. _ _ _.-
09/11/86 168.0
-158.0
)
j11/05/86 170.0 150.0 169.0-152.0 i
i 01/10/87 158.5 155.0 160,7 155.0
}
l I
I l
i 1
1 I
.l i;
4
?
\\
/
t j
i i
1 i
f 4
\\
f i
I f
{.-__._.._._.-_.._.____._._,,_..__._._._._..__
. - ~. _... _ _,.. _,.. _ - _. _....
Page 1
UtJIT 1 CALIBRATION DATA
==================.
' EQUIPMENT PIECE NUMBER:
1E31-N012BA APPLICATION:
RHR (SHUTDOWN COOLING > HI SUCTION FLOW ISO NOMINAL SETPOINT:
.168.4" WC CALIBRATION TOLERANCE:
2C7.4-169.4" WC ACTION LIi1ITS:
1E3.0-173.8" WC REJECTION LIMITSt 158.8-178.0" WC 1
TECH SPEC ALLOWADLE.:
185.0" WC I
Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset 09/11/86 168.2 157.5 11/05/86 169.0 150.0 1 GB. 0 150.5 01/10/87 168.3 153.2 1'68.5 153.0 w
4
1 l
Page 1
1 I
i l
2 l
l UNIT 1 CALIBRATION DATA
$===cu==================
1
' EGUIPMENT PIECE NUMBER:
' APPLICATION:
RHR (SHUTDOWN COOLING) HI SUCTION FLOW ISO l
t j NOMINAL SETPOINT:
168.4" WC l
- CALIBRATION TOLERANCE
167.4-169.4" -WC
(
l 4
i 1 ACTION LIMITS:
163.0-173.8" WC
! REJECTION LIMITS:
158.8-178.0" WC i TECH SPEC ALLOWABLE:
185.0" WC i
1 i
j t
l j Calibration Date "As Found" "As Found" "As Left" "As Left" l
Trip Reset Trip Reset j
- 09/11/86 169.2 153.5 y
i 11/05/66 170.5 149.0 169.0 152.0 Aj 01/10/87 169.0 153.0 168.2 132.O i
.t.
i i
i 4
I i
1 l
4 F
i 7
i t
1 i
i T
4 l
1 1
1 4
l J
l i
?
Ii
}
l i
i J_____._____.._______.___.-..._.___.,-.___,_,.__-.
page 1
l l-UNIT 2 CALIBRATION DATA j=========r-e============
l 4
{ EQUIPMENT PIECE NUMDER:
2B21-N024A APPLICATION:
LEVEL 3 SCRAM AND ISOLATION 3
NOMINAL SETPOINT:
58.90" WC l
l CALIBRATIGN TOLERANCE:
58.40-59.40" WC i
i ACTlON LIMITS:
36.10-61.70" WC
- REJECTION LIMITS:
56.00-61.80" WC l TECH SPEC ALLOWABLE:
64.84" WC 1,
i I
- Calibration Date "As Found" "As Found" "As Left" "An Left" Trip Reset Trip Reset i
i i 07/30/86 58.90 53.60
- 08/18/86 58.30 52.40 59.10 54.40 09/01/86 59.30 54.00 58.80 53.60 9/30/06 59.00 53.60 58.90 54.10 i
11/21/06 61.4 53.0 58.9 52.9 I
l f
s e
I k
1 i
i 1
Il 4
5 A
i l
i
,,,,..-.-n-..,-
.~,,,---,,n--
-n..--
,.~~---,,,----,....-.,.,7,.-.._,..,.
-n..
.. _.... _ _. _ _ _ _ _..__..-~._
9 l
~Page
'l l
l J
i i
) UNIT 2 CALIBRATION DATA I
f-l = = = = r.
l
!! EQUIPMENT PIECE NUMBER:
2821-N024B
(
APPLICATICN:
LEVEL 3 SCRAM AND ISOLATION t
NOMINAL SETPOINT:
58.90" WC l
ICALIBRATION TOLERANCE:
58.40-59.40" WC 1
I b
i ACTION LIMITS:
56.10-61.70" WC-l REJECTION LIMITS:
56.00-61.80" WC I TECH SPEC ALLOWABLE:
64.04" WC i
i l
r a
l Calibration Date "As Found" "As Foured" "As Left" "As Left" Trip Reset Trip Reset.
l I
i 07/30/06 58.90 54.00 f
j08/18/8G 59.15 54.05 59.00 54,40 i 09/01/85 3G. 90 53.80 98.90 54.10
}
9/30/86 59.05 54.30 59.05 54.60 i
! 11/21/86 60.4 52.5 58.G 52.2 1
t 1
I t
i i
t 1
l t
I i
t I
l 1
I s
I I
}
I i
I
._ ~
}
Page 1
j i
4 r
l UNIT 2 CALIBRATION DATA j
=_====~u======n l
l EQUIPMENT PIECE NUMDER:
CB21-N024C jAPPLICATION:
LEVEL 3 SCRAM AND ISOLATION i
l NOMINAL SETPOINT:
58.'30" WC f
! CALIBRATION TOLERANCE:
58.40-59.40" WC f
- i. ACTION LIMITS:
56.10-61.70" WC i
I REJECTION LIMITS:
56.00-E1.80".WC
(
- TECH SPEC ALLOWAELE
64.84" WC i
i f
~ Calibration Date "As Found" "As Found" "As Left"
" As L eft "
Trip Roset Trip Reset i
53.30 i
07/30/05
'58,90
'08/18/06 58.85 52.70 58.80 53.10
,09/01/8G 58.50 52.60 58.50 52.70 9/30/86 58.75 53,1G 58.70 53.20
] 11/21/86 60.4 52.2 58.6 50.5 l
i i
i 4
)
t i
4 F
l i
L i
f
'i
\\
i 4
P i.
1 i
i i
i E
L.. -.
=
i i
Page'
.1 4-i I
i t
b
'I l
l UNIT 2 CALIBRATION DATA j
i _ _ _. _ _... _ _ _ _ _.... _ _ _ _ _ _ _. _ _ _ _
i EQUIPMENT PIECE NUMBER:
l APPLICATION:
. LEVEL 2 SCRAM AND ISOLATION 1
- NOMINAL SETPOINT
58.90" WC I CALIBRRTION TOLERANCE:
58.40-59.40" WC i
j ACTION LIMITS:
56,10-61.70" WC i
l REJECTION LIMIT 5:
56.00-61.80" WC l TECH SPEC ALLOWABLE:
64'.84" WC i
i r
! Calibration-Date "As Found" "As Found" "As Left" "As Left" J
j Tr ip Reset Trip Reset l
1-l07/30/06 59.00 53.80
,08/18/86 58.90 54.00 59.00 54.00 09/01/86 58.75 53.50 58.70 53.70 j
9/30/86 59.00 54.10 59.00 54.'30
- 11/21/B6 59.7 52.0 58.9
~52.4 l
1 i
i i
i i
e a
i s
}
t 4
i k
4 I
i I
l l
I I
1 i
t i
{
i i
i i
l l
1 h
-i Page
-1 l
i i
UNIT 2 CALIBRATION DATA l
l
===========
, EQUIPMENT PIECE NUMBER:
- APPLICATION:
LEVEL 3 LOW WATER LEVEL ADS" CONFIRMED l
. NOMINAL SETPOINT:
58.90" WC l
} CALIBRATION TOLERANCE:
58.40-59,40" WC i
i
( ACTION LIMITS:
56,10-61.70" WC lREJECTIONLIMITS:
56.00-61.80" WC' l
1 TECH SPEC ALLOWABLE:
64.84" WC l
i l
,i Calibration Date "As Found"
" As. Found" "As Left" "As-Left" j
Trip Reset Trip Reset l
c.._.________._.._..___________________________________________________________.-
i j
i j 07/30/86 58.90
_53.70, j
j 08/19/86 59.55 54.10-58.80 53.65 l
l 09/02/86 59.05 54.00 59.00 54.15
.l i
9/30/86 61.30 54.50 58.70 52.80 l
}11/24/86 63.40 57.10 58.50 52.60 l
l SERIAL NUMBER l 85-1-2398 i
j11/26/86 NEW SWITCH 58.8 55.0 l
12/08/86 59.9 54.9 58.6 54.1 12/22/86 58.9 54.1 58.65 54.3 l
i 1
i
)
(
r i
f l
1 1
l 1
1 i
1 t
-i I
h I
r L,_.._._--_
u
Page 1
i 1
t
' UNIT 2 CALIBRATION DATA
===========
i i EQUIPMENT PIECE NUMBER:
2B21-NO38B APPLICATION:
LEVEL 3 LOW WATER LEVEL ADS CONFIRMED
{ NOMINAL SETPOINT:
58.90" WC CALIBRATION TOLERANCE:
58.40-59.40" WC ACTION LIMITS:
56.10-61.70" WC l REJECTION LIMITS:
56.00-61.80" WC l
l TECH SPEC-ALLOWABLE:
64.84" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset
' 07/30/06 58.90 53.50
'C8/19/86 59.20 53.35 59.15 54.10
.09/02/86 59.40 34.05 58.80 53.70 i
9/30/86 59.20 53.00 59.00 53.6?
11/26/85 60.80 54.20 58.80 52.S0 12/08/86 58.4 56.2 59.0 52.4
- -12/22/86 58.8 53.1 58.75 53.2 i
i L
1 t
i i
I 1
1
,I ii i
+
1
'i i
i
?
I f
u
. _.. _.... _......._ _. -. _. _ _ __ _ _.... _. _ _ _ _ _. _ ~..
t
)
Page 1
j 1
i-
)
i
{ UNIT 2CALIBRATIONDATA j
===========
i i
! EQUIPMENT PIECE NUMBER:
.+
- APPLICATION
REACTOR HIGH LEVEL hCIC TURBINE TRIP i-l NOMINAL SETPOINT:
38.7" WC CALIBRATION TOLERANCE:
38.2-39,2" WC l
) ACTION LIMITS:
N/A l
! REJECTION LIMITS:
.36.5-40.9" WC i
! TECH SPEC ALLOWABLE:
32.8" WC
+
i r
I 1
' Calibration Date "As Fr
.d" "As Found" "As Left".
"As Left" l
Trip Reset Trip Reset.
{
08/02/8G 38.5 45.1 l
l 10/23/86 38.6 46.9 38.4 46.3 l'
11/22/86 38.2 46.0 38.2 46.0 z
l
- ]
1 a
1 t
l i'
i i
i i
i 1
4
)
1 I
l 1
i 4
I I
~
l i
}
j.
i f
I; i
l ii_.__._____...._____._~~,_ _
a l
. _ _ _ _ _ _. _ _ _ = _ _ _. _. ~. _ - _ _ -.
Page
. 1 i
4 I
i i
i i
2 I
j UNIT 2 CALIBRAITON DATA l
f
___u====_=======
1 4
. r
-EQUIPMENT PIECE NUMBER:.
i APPLICATION:
REACTOR LEVEL E HPCS INITIATION i
l i
i-NOMINAL SETPOINT:
134.O WC l
i CALIBRATIGN. TOLERANCE:
133.0-135.0" WC I
ACTION LIMITS:
128.6-139.4" WC 1
REJECTION LIMITS:
125.4-142.6" WC
,. TECH SPEC ALLOWABLE:
150.6" WC j Calibration Date "As Found" "As Found" "As'Left"
'"As Left" Trip Reset Trip Reset 7
i
..t 1 08/01/86 134.25 127,75-r 08/27/86 137.80 130.80 134.20 127.30 I 12/01/8G 131.5 124.3 134.2 127.6 i
a i
l 1
r i
(
i
)
1 l
i I
l 4
t o
1 l.
{
r i
(
1 h
i s
1 i
t I
f i
5 l
i i
i i
a i
4 t
Ib.m.-.--m,,,..--,
--,-,.---,,-......__,,..-...---_.,_m..,_.-~.
__,,.-_4
[
'Page-1
.l
)
l l UNIT 2 CALIBRATION DATA-I
{.======================
f 1
i EQUIPMENT PIECE NUMBER:
{ APPLICATION:
REACTOR LEVEL E HPCS INITIATION 1
I d
+
I, NOMINAL SETPCINT:
134.0" WC l CALIBRATION TCLERANCE:
133.0-135.0" WC
! ACTION LIMITS:
125.6-139.4" WC
(
{ REJECTION LIMITS:
125.4-142.6" WC i
- l
! TECH SPEC ALLOWABLE:
150.6" WC 1
i t
1 Calibt'ation Date "As Found" N'As Found" "As Left"-
"As Left" J
Trip Reset Ttip Reset i
]08/02/86 134.00 125.50 i
f j08/C7/86 134.50 128.00 134,50 128.00 12/01/86 136.3 129.3 133.7 127.7 i
f F
i 1
i I
J i
l t
t i
i
{-
i i
i i
4 1
i
~
l
)
4 2
t 1
i i
. ~. ~
u
- . n ~.. - - - -.,.
-..-.---.w-
+
Page 1.
t a
k j UNIT.2 CALIBRATION DATA i
hEQUIPMENTPIECENUMBER:
2B21-NO31C j. APPLICATION:
REACTOR LEVEL-2 HPCS INITIATION i
jNOMINAL SETPOINT:
134.0" WC CALIBRATION TOLERANCE:
133.0-135.0" WC _
ACTION LIMITS:
128.6-139.4" WC 1 REJECTION LIMITS:
125.4-142.6" WC j TECH SPEC ALLOWABLE:
150.6" WC.
j j Calibration Date "As Found" "As Found" "As Left" "As Left" j
Trip Reset Trip Reset 08/02/86 134.00 105.50 1 08/07/86 135.50 126.50 134.30 126.00 1j 12/01/86 133.7 125.G 133.7 125.8 1-I O
+
t I
l i
e f
t L
i i
i i
t l
t t
i
}
}
4 5
\\
l I
4
+
1
PaDe 1
1
- UNIT 2 CALIBRATION DATA EQUIPMENT PIECE NUMBER:
REACTOR LEVEL 2 HPCS INITIATION
. AF" PLICATION:
i NOMINAL SETPOINT:
134.0" WC I CALIBRATION TOLERANCE:
. 133.0-135.0" WC
' ~ACTION LIMITS:
-128.6
.J9.4" WC
! REJECTIGN LIMITS:
125,4-142.6" WC TECH SPEC ALLOWABLE:
150.6" WC a
1 ICalibration Date As Found" As Four d" "As Left"
" As Lef t" Trip Reset Trip Reset 4
- - -. ~ - - - -. - - - - - - - - - - - - - - - - _ - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
s 08/02/86 134.20 127.00 08/27/86 134.60 127.20 134.70 127.50 12/01/86 135.5 123.7 133.6 126.3 c
1 L
l
.i 8
e i
i i
1 4
I o
1 j
h.
PPp
=-w
-r r-N t'-g-1-g g
p,.e+-mp, yt
.-rewe.mey-
.w eq% c.y p-eg ri m, g +e 4--e-.,pe,mg.,
ess.,y-yp--gy 9 w e M--My---.pg-e-y+ erg-emy 17--
e:r -ep.r-
-tf9-Wg-y=(y--
~ _ _ _ _. _ _ _ _., __ _
Page
~1-i
(
Y l
r l UNIT 2 CALIBRATION DATA
~
i i
j EQUIPMENT PIECE NUMBER:
' APPLICATION:
REACTOR LOW LOW LEVEL MSIV ISOLATION L.
i; NOMINAL'SETPOINT:
134.0" WC ti CALIBRATION TOLERANCE:
133.0-135.0" WC 4
1
! ACTION' LIMITS:
128.'G-139.4" WC i
' REJECTION LIMITS:
125.4-142.6" WC i
, TECH SPEC ALLOWABLE:
150.64" WC c
j
!' Calibration Dete "As Found" "As Found" "As Left" "As Left" l
Tt*ip Reset Trip Reset l
' C8/02/86 133J5 121.7 09/24/86 133.8 123.25 134.5 124.4 i 12/03/86 134.5 122.5 134.5 123.0 e
i I
i i
i
\\
7 i
1 i
i 4
7 i
a l
e i
1 i
5
,l I
1.
j l
'1 i
}
t 1
J e
k
\\
i 4
i it._.-,____,.__.,
t Page' 1
1
' N4 1
UNIT 2 CALIBRATION DATA
==========
a IEQUIPMENT PIECE NUMBER:
2B21-N026BD APPLICATION:
REACTOR LOW LOW LEVEL MSIV ISOLATION
{ NOMINAL SETPOINT:
134.0" WC
. CALIBRATION TOLERANCE:
133.0-135.0' WC
',. ACTION LIMITS:
128.6-139.4" WC
!-REJECTION LIMITS:
125.4-142.6" WC TECH SPEC ALLOWADLE:
150.64" WC Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip-Reset
- - - - - -. - - - - - - - - - - - - -.. - ~
!08/02/86 133.8 122.5 09/24/86 138.25 128.0 133,75 124.3
'~12/03/86 130.0 116.0 134.0 123.0 i
t i
i i
I t
I I
1 i
b e
i I
I I
l 4
t i
l
t' I
Page 1
1 E
' UNIT 2' CALIBRATION DATA i
,-__ __==================
i EQUIPMENT PIECE NUMBER:
-2B21-N026CB jAPPLICATION:
REACTOR LOW LOW LEVEL-MSIV ISOLATION NOMINAL SETPOINT:
134.0" WC f
CALIBRATION TOLERANCE:
-133.0-135.0" WC i
i ACTION LIMITS:
128.6-139.4" WC i REJECTION LIMITS:
125.4-142.6" WC l TECH SPEC ALLOWABLE:
150.64" WC
' Calibration Date "As Fou~d" "As Found" "Ps Left" "As Left" Trip Reset Tr-ip Reset i08/02/86 133.9 121.0 09/24/86 134.7 122.5 134.6 122.7 i
J 12/04/86 134.5 122.0 134.4 122.0 1
l 4
4
,i s
1 i
4 b
i f
l l
4 i
[
i I
t 4
i t
p.
7 i
i i
j i
i
-,s..__.m.,..~.
._.4...,_m.,_.
~,,,,_._,_,,_.,,,_m.
__,--m
..m.,_-r___~,..,...,...,.
...._~~.g.m.,....,.,_,.-.,--,
Page.
1 1-T
. UNIT 2 CALIBRATION DATA f
===========
i-
. EQUIPMENT PIECE NUMBER:
2B21-N026DB APPLICATION:
REACTOR LOW LOW LEVEL MSIV IGOLATION 4
2l NOMINAL SETPOINT:
139.0" WC i CALIBRATION TOLERANCE:
133.0-135.0" WC 2
- - ACTION LIMITS
128.6-139.4"'WC
!REJECTIONLIMITS:
125.4-142.6" WC 1 TECH SPEC ALLOWABLE:
150.64" WC J
l ai Calibration Date "As cound" "As Found" "As Left" "As Left" Trip Reset Trip Reset-1! 08/02/86 134.5 119.8
'i 09/24/86 136.7 122.2 133.75 120.25 12/04/86 134.0 119.0 134.0 119.0 i
9 5
4 t
I I
i I
i A
4 l
1 1
+
l i
r l
4 Y
1 i
e i
i e
I t
j
_.. _, _. - _. - _ _ _ _ _,. - -. _ _. _. _..,,.... -. -., _. _ -. _ _ _, -.. _ _ -,.. _ - - _.. ~ ~. _ _ _ _. - -, _ _
Page i
U LIT, _ - COLIOPATICT4 I' A T A
_2==:
== = =:
===-==_r==-
E N.>.>' T P ". r N T.
'2 ' F P F.
t '
- n. e p.
,o_ rr 1 "a y. ~ '. <q a r
1-ARPL!CATIml:
REACTOR LEVEL ! ECCS INITIATION NOMINGL EETPOINT:
109.0" WC C,',"u.7 r' R A T t m. ' ", o"c_ c rw 4. r.
.ri,. tv. 41 q_ 2.(,,"
c m.
.e.
ACTICN L I M I T 57 -
181.2-1'36.8" NC #
at aq r r. s c. o) 1,vj iv -- e.,
,, c,, u. 0, _.1 c_= a. t.
,, r.
m is -.
,o ia 2
._4 TECH SPEC iLLOL T t ".f.:
,07,17" WC Ca 11 tn it. : r.
D+
"An F.. u r.d "
' P -- F :.u n d "
" T4.. Left" "A2 Left" 1 rip Roset Trip Reset
.. _ -.. _ _ _...... - _.. _. -..... _ _ _ _ _.. _ _ _ _ _ _... _ - - - _ _ _ _. _ _. ~ _.. _.. _ _ _
0 0 / C.2
G 109,20 175.50 eq<.>~,er 3n,.
.i
.s
,e
. v a.
,1 c-
, e a.,1 1 :,.. < e,J c
s w.s a
w.s a us
+ i a
11/1 ;~ / OG i s" e 17'4 J.
109.6 4 e i..
z,
{
)
. - ~.
Paue 1-i 1
?* UNIT 2 CALIBRATION DATA
===========
j EQUIPMENT PIECE NUMBER:
2B21-N037DA j, APPLICATION:
REACTOR LEVEL 1 ECCS~ INITIATION
! NOMINAL SETPOINT:
189.0" WC l CALIBRATION TOLERANCE:
187.0-191.O "WC 4 ACTION LIMITS:
181.E-196.8" WC
- REJECTION LIMITS
t78.8-199.2" WC TECH. SPEC ALLOWABLE:
007.17 "WC a
1 1
Celibration Dato As Found" As Found"
" As Le f t " '
As Left" j
Trip Reset Trip Reset 3
d 1
]08/03/86 189.90 169.GO
. 08/13/86 190.00 170.40 190.00 170.40 1 11/12/86 189.0 169.0 189.0-171.0 i
I k
4 i
}
-l r
i 1 -
)
i j-s.,
i 4
i i
l J
i 4
-.,e--s--,-,m,-
,,mm.gw.-,,
..r_,
.-.,,,r, y_-_
~n,y
.,m,wv.,
__g.,,%.
.ry,,,,
,-,,_..a.,cy-g--:,-.m.,re-r=-
T w-r-m t-- -
Page.
l'
' UNIT C CALIBRATION DATA i
===========
t
! EQUIPMENT PIECE NUMBER:
2B21-NO37CA iAPPLICATION:
REACTOR LEVEL 1 ECCS INITIATION
! NOMINAL SETPOINT:
189.0" WC
]CALIBRATIONTOLERANCE:
187.0-191.0"'WC i ACTION LIMITS:
181.2-196.8" WC REJECTION LIMITS:
178.8-199.2" WC
. TECH SPEC ALLOWABLE:
207.17" WC
.i Cali brat ion Dat o "As Found" As Found" "As Left" "As Left" Trip Reset' Trip Reset I
a
)
,j 08/02/06 188.50 176.00 L 08/13/86 189.50 177.50 189.50
.177.50
$ 11/12/86 190.0 178.2 189.9
'178.2 i
s i
i l
t i
I i
i f
f l
4 i
,..,m..
.m,-.
,..-.-....-._.,+,.-.,-.....,A...-...m-
.,,..., _ _ - -,,.....,,,. ~,,
.... ~.,, + -,,,,, - - - -
4 Page l'
l i
} UNIT 2, CALIBRATION DATA
- - - ~. - - - - - - -.. -. - - - -..
I EQUIPMENT PIECE NUMBER:
' APPLICATION:
REACTOR LEVEL 1 ECCS INITIATION i-l 1 NOMINAL SETPOINT:
189.0" WC '
- CALIBRATION TOLERANCE
'187.0-191.0" WC l ACTION LIMITS 5 181.2-196.8" WC
' REJECTION LIMITS:
178.8-199.2" WC j TECH SPEC ALLOWABLE:
207.17" WC Calibration Date "Os Found" "As Found"
" As t e f t "
"As Left" Trip Reset Trip Reset 1
i08/03/SG 188.40 175.80
' 08/13/86 189.60 177.00 189.60 177.00 j 11/12/85 189.0 175.0 189.0 177.0
)
i i
i 1
1 i
1 i
i 4
f i
i j
i 5,
i 1
1 i
4 1
h i
l
- l i
[
Page-
-1 1
1 i
i J
I~ UNIT 2 CALIBRATION DATA l=======================
i EQUIPMENT PIECE NUMBER:
- 2B21-NO37AB APPLICATION:
REACTOR LEVEL 2 RCIC INITIHTION l NOMINAL SETPOINT:
134.0" WC CALIBRATION TOLERANCE:
133.0-135.0" WC I
t i
l ACTION LIMIT 5:
128.6-139.4" WC i
.125.4-142.5" WC REJECTION LIMITS:
' TECH SPEC ALLOWABLE:
150.64" WC I
i I
i 1
1 i
i Calibration Date
-"As Fourd" As Found"'
"As Left" "As Left" l
l Trip Reset Trip Reset l.____________...__._.__
i s
1
+
i 08/02/86 134.20 126.80 I
8/12/86 134.75 127.5 133.75 126.50 g
'I j 11/12/86 133.3 126.6 133.4 126.3, j
i I
i t
P i
l l
i 1
s A
WWWW 4 y'* WWW.impr'v g N
.MM--
M N TMNN'Wer e.Fw&T.-9-W.'1lPWr.
N f W94.'@
Y
... _ _, -,. _ _ _... _ _. _ _ ~....
s Page 1
I
- UNIT _2 CALIBRATION D.GTA a======================
1 i
- 1. EQUIPMENT PIECE NUMEER:
jAPPLICATION:
REACTOR LEVEL 2 RCIC' INITIATION NOMINAL-SETPOINT:
134.0" WC
-i l CALIBRATION TOLERANCE:
133.0-135.0" WC 4,
- - ACTION LIMITS
1 2 8. G - 1 3 9. 4'" WC j~ REJECTION LIMITS:
125,4-142.6" WC'
( TECH OPEC ALLOWABLE:
150.64" WC
}i Calibration Date "As Found" "As Found" "As Left" "As Left" i
Trip Reset Trip Reset' i
i 1-
- 08/03/86 134.10 128.30 08/13/86 135.50 129.50 134.50 128.60 l11/12/86 135.5 128.0' 133.8 127.0
~
s l
?
i 1
1 a
h i
j r
3 4
I 4
1 1
I 4
i l
f 1
l I
I i
J t
4
+
i i
i 4
1 4
1 i
1 1-4j s
\\
l 1
4___._._,__._._.__.__,_,_.,___
~. -...
1
- Page l
~
3 j UNIT 2 CALIBRATION DATA i=======================
EQUIPMENT PIECE NUMBER:
2B21-NO37CI3 APPLICATION:
REACTOR LEVEL 2 RCIC INITIATION NOMINAL SETPOINT:
134.0" WC CALIBRATION TOLERANCE:
133.0-135.0" WC 5
- ACTION LIMITS
128.6-139.4" WC REJECTION LIMITS:
125.4-142.6" WC TECH SPEC ALLOWABLE:
150.64" WC Calibration Date As Found" "As Found" "As Left" As Left" Trip Roset Trip Reset
!----.--~~-.-------------:---.--.------------------a.------------
( 08/02/86 133.80 128.70
'08/13/86 135.00 131.00 134.50 129.75
}11/12/86 134.1 128.7 134.1 3 ?8. 0 1
. i I
g k
i l
T i
i f
i i
I i
4 r
a t
]
f I
.g I
1
,sw-,-w-w
.wp
-,rw.g o, m g - n. -
s,4w,-
an-3'y-y nm
, yqm -,q
..w e-y
,yayp,w nm,<+ w ww,m.
nmm mm p,---e m e mw -,e-p,n m w-g-. nm y,m,-g-w,w-g,m
- 9 q-gw
i j-Page 1
1' f
eUNIT 2 CALIBRATION DATA
=
e b ECUIPMENT PIECE NUMBER:
2B21-NO37DB l' APPLICATION:
REACTOR LEVEL 2 RCIC INITIATION r
i
[ NOMINAL SETPOINT:
134.0" WC CALIBRATION TOLERANCE:
133.0-135.0" WC ACTION LIMITS:
128.6-139.4" WC i PEJECTION LIMITS:
125.4-142.6" WC I TECH SPEC ALLOWABLE:
150.64" WC 1; Calibration Date "As Found" "As Found" "As Left" "As Left" i
Trip Reset Trip Reset i
I I
f t
) 08/03/86 133.90 126.80 S
i
- i. 08/13/86 135.75 129.00 134.00 127.75 i-
,= 11/12/86 134.3 127.0 134.3 127.0 l
i i
4 e
- i i
t 1,
I
,I I
i a
I 1
(
j l
l 4
-i t
l t
f l
i t
5 S
(
..w%-.,n.-.--
.~,,-y-
,-,,,,-_.,e.m--,-,m-_,.,...,,w,,,..,.,ww,.~,,,m.m..,_-,-._.-_.m%,,,~.o-,,,.,,--,,.,.,,m.,,m,,m
.. _.. ~
4 l
Page-1 1
l UNIT 2 CALIBRATION DATA i=======================
l EQUIPMENT PIECE NUMBER:
' APPLICATION:
MSL HI FLOW f50LATION NOMINAL SETPOINT:
85.0 PSID
!CALIBR4 TION TOLERANCE:
84.0-86.0 PSID 1
j ACTION LIMITS:
69.50-100.50 PSID
. REJECTION LIMITS:
69.50-100.50 PSID
} TECH SPEC ALLOWABLE:
111.0 PSID t
1 "As Found" "As Found" "As Left" "As Left" Calibration Date 3
Trip Reset Trip Reset i
il 08/02/86 85.50
-62.50 i08/29/86 85.70 61.80 85.30 61.~80 i 11/20/86 86.0 59.0 85.5 60.0 l
4 i
i i
t t
i i
i i
l i
1
)
l
~ _,. -..,,,, _.,,., -,,,...,.,.
.. _. _. _. ~, _. _. -.
't paDe-1-
o L.
b i
s.
i i UNIT 2 CALIBRATION DATA
(
l=======================
! EQUIPMENT PIECE NUMBER:
2E31-N008B l APPLICATION:
MSL HI FLOW ISOLATION.
i, -
l 4
NOMINAL SETPOINT:
85,0 PSID
' 3.
.j-p i CALIBRATION TOLERANCE:
84.0-89.-> PSID
- c:
1
! ACTION LIMITS:
69.50-100.50 PSID a
REJECTION LIMITS:
69.50-100.50 PSID
. TECH SPEC ALLOWABLE:
111.0 PSID 1
.i 3
l Calibration Date As Found" As Found" "As Left"
" As - Le f t "
Triy Reset Trip.
~
Reset i
3___________.______.-_____.____________._.._________.___..._..____.__._
4 j08/02/86 85.20 65.40 1 08/29/85 87.00 65.50 B5.00 65.40 s
a j 11/20/86 90.0 62.0 85.0' 58.O' 01/03/87 84.5 57.0 84.4
'64.8 i
1 s
'4 I
h 5
I i
~
l i
a k
5 4
f 4
a l.
s 1
]
l t
1; t
J 4
i I
Ig
_k-
?
h i
e i
t
'h 1
f 5
I 4
4 4
mm
.vr,,.-p.--r&g.m-,e---,.y-ee-w2ew,,.e.w.~,,,
,y,,,.%,.
cg ~w e,v
- p. v, ye,
.,-gy,<--p.,e
.Page 1
1 I-t i
' UNIT 2 CALIDRATION DATA
-============a========-
t f..
(' EGIIIPMENT PIECE NUMBER:
l APPLICATION:
MSL HI FLOW ISCLATION l
6 f'NOMINALSETPOINT:
85.O PSID
! CALIBRATION TOLERANCE:
84.0-86.0 PSID i
!-ACTION LIMITS:
69.50-100.50 PSID
! REJECTION LIMITS:
69.50-100.50 PSID j TECH SPEC Ai_LOWAPLd:
111.0 PSID i
i i Calibration Date "As Found" "As-Found" "As Left"
- "As'Left"
{
Trip Reset Trip Reset l
.l 2
08/02/86 G5.00 G5.60 j08/29/8G SG. 00 64.00 85.50 64.00 l
j'11/20/86 87.0 62.0 85.0
.63.O i
1 i
i I
a I
5 i
i l
l
!.I f
f I
i l
i )['
Pa D F-1 y
~I UNI T 2 CALIBRATION DRT A '
j==========-======a=v===
1 EQUIPMENT PIECE NUMBER:
' APPLICATION:
M5L HI FLOW ISCLATION
, NOMINAL SETPOINT:
85.0 PSID CALIBRATION TOLERANCE:
84.0-86.0 PSID
' ACTION LIMITS:
69.50-100.50 PSID REJECTION LIMITS:
69.50-100.50 PSID i TECH SPEC ALLOWABLE:
-111.0 PSID i
I Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset 1 08/03/86 84.40-67.00 08/29/86 84.20 68.00 85.30 69.50-11/20/86 87.0 67.0 85.0 67.0-4 i
4 1
d l
l r
L h
I 4
.f i
h
_m Page 1
I 4
UNIT 2 CALIBRATION DATA j=======================
7 EQUIPMENT PIECE NUMBER:
2E31-N009A APPLICATION:
MSL HIGH FLOW MSIV ISOLATION NOMINAL SETPOINT:
85.00 PSID CALIBRATION TOLERANCE:
84.00-85.00 PSID t
- ACTION LIMITS:
N/A REJECTION LIMITS:
69.50-100.50 PSID TECH SPEC ALLOWABLE:
116.00 PSID a
Calibration Date As Found" As Found" As Left" As Left" Ttip Reset Trip Reset f
j 8/ 2/86 85.40 67.00 I
9/25/86
' 88.00 61.00 85.50 62,00.
]12/18/86 87.0
' 60.0 85.0 62.0-i t
4 f
1 i
4 t
i
~
t i
h
+
t e
i v
.---,v.,,
r,-.-y.
y
=
.,w
-,~
r,
<--e n -
.me.__e.-,u---
3 ry--y,---
,-r.we-.--rv.-----,ys--4,-_m,7 mew..m,--evece.----
Page 1
' UNIT 2 CALIBRATION DATA j=======================
3 I EQUIPMENT PIECE NUMBER:
2E31-N009B APPLICATION:
! NOMINAL SETPOINT:
85.00 PSID CALIBRATION TOLERANCE:
84.00-86.00 PSID
. ACTION LIMITS:
N/A
, REJECTION LIMITS:
69.50-100.50 PSID TECH SPEC ALLOWABLE:
116.00 PSID
- Calibration Date "As Found" "As Found"
~"As Left" "As Left" Trip Reset Trip Reset
\\
.~
?
I 8/ 2/86 85.20 67.00 9/26/8C 88.00 62.00 84.80
'62.20 1 12/18/86 8F. 8 61.8 85.5.
61.5
- 01/03/97 86.1 61.8 85.3 63.6 i
1 i
]
i k.
I b
a I
)
/
i l
2.__.,_._._._
m, i
Page 1
4 i
e I UNIT 2 CALIBRATION DATA
!~=======================
{'
2E31-N009C jEQUIPMENT PIECE NUMBER:
l APPLICATION:
MSL HIGH FLOW MSIV ISOLATION i NOMINAL SETPOINT:
85.00 PSID i CALIBRATION TOLERANCE:
84.00-86.00'PSID 4
I j ACTION LIMITS: _
69.50-100.50 PSIC N/A REJECTION LIMITS:
-TECH SPEC ALLOWABLE:
116.00 PSID Calibration Date.
"As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset 8/ 2/86 85.20 6'O.70 9/EG/86 88.50 58.00 85.00' 56.50 j 12/18/86 86.0 54.2.
85.2 55.4 1,
J 2
f i
h 1
l i
i 4
I I
1 i
A
.}
t 1
i t
4 1
1 i
+
1 1
l
\\
l
-.. -,. -, - - - -. - - - -, -.,., - -,.-.., - _ -. - ~ ~ ~ -.. -.. -., _.. _, - _. -. ~. _. -. - -. - -.,
. _. _. - -. _. - - - -, - -,, - - ~, _
PaDe 1
4
\\
4 i
1 UNIT 2 CALIDRATION DATA 4
- -EGUIPMENT PIECE NUMBER:
2E31-N009D APPLICATION:
MSL HIGH FLOW MSIV ISOLATION NOMINAL SETPOINT:
85.00 PSID CALIBRATION TOLERANCE:
84.00-86.00 PSID 1
i ACTION LIMITS:
N/A I REJECTION LIMITS:
69.50-100.50 PSID TECH SPEC ALLOWABLE:
116.00 PSID Calibration Date "A= Found" "As Found" "As Left"
" As Le f t "
i Trip Reset Trip-Reset 8/ 2/8G 84.50 59.40 9/26/06 88.00 56.00 85.00 57.00 4
9/27/86 85.50 56.50 85.50 56.50.
12/18/86 87.6 55.0 85.5 55.0 1
0 1
i 5
4 r
o
)
1 1
(
i 4
n
___..._.,m.-
-~ -..
Page 1
l t
i l
i l UNI 7 2 CALIBRATION DATA
+,=======================
)
1,EGUIPMENT PIECE NUMBER:
lAPPLICATIOri:
M5L HIGH FLOW MSIV ISOLATION i
I NOMINAL'SETPOINT:
85.00 PSID l CALIBRATION TOLERANCE:
84.00-86.00 OSID i
l 1
)i ACTION LIMITS:
N/A l REJECTION LIMITS:
69.50-100.50 PSID I, TECH SPEC ALLOWABLE:
116.00 PSID r
[
i-I l Ca1ibration Date "As Found" "As Found"-
"As Left" "As Left" t
Trip Reset Trip-Reset i ________________________________________________________________________
i i
j 8/ 2/86 85.00 61.20 l
,10/14/86 85.5 59.5 85.0 59.O i
I l
i 1
i
)
I ri
}
t i
+
i d
1 L
1 l
4 i
l f
i i
I i
f I
f f
5 4
l i
L..,__-__._,,._,.,__.,,_,,,._..._.-..__._.._
. ~..
.. - - -.. _. _ ~ -. _. ~
Page 1
i.
a t-; UNIT 2 CALIBRATION DATA
===========
l EQUIPMENT PIECE NUMBER:
2E31-N0108 i APPLICATION:
- ' NOMINAL SETPOINT:
85.00 PSID i CALIERATION TOLERANCE:
84.00-86.00 PSID i
i ACTION LIMITS: _
N/A i REJECTION LIMITS:
69.50-100.50 PSID
{' TECH SPEC ALLOWABLE:
116.00 PSID-1 1
s l Calibration Date "As Found" "As Found" "As'Left" "As Left" l-Trip Reset Trip Reset 1
j-
.84.50 65.50
,t 8/ 2/86 l-10/14/86 86.0 63.0 85.5 60.5
}'01/03/87 81.6 60.3 84.4 63.8
?!
I s
i t
I 1
l t
i S
t.
e I
ii 4
l 4
1 I
i i
I t
I
(
).
1
. ~. - - - - - - - -
f-Page 1
I l UNIT 2 CALIBRATION DATA 4=======a====n==========
f l EQUIPMENT PIECE NUMBER:
t l APPLICATION:
MSL HIGH FLOW MSIV ISOLATION 1
NOMINPL.SETPOINT:
85.00'PSID fCALIBRATIONTOLERANCE:
84.00-86.00_PSID j ACTION LIMITS:
N/A l
ll REJECTION LIMITS:
69.50-100.60 PSID
+
2 TECH SPEC ALLOWABLE:
116.00 PSID I
I Calibration Date
'"As Found" "As Found" "As'Left" "As Left" Trip Reset Trip Reset i
1
- - - - - - - - - - - - - ~ ~ ~ - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
1 I
j-8/ 2/86 84.60 61.G0 J
{-10/14/86 89.0
'58.0 85.0 58.0
(
t i
j
.'r I
i j
l 4
i e
e t
t
'i I
i 1
i i
i
Page 1
1 I
UNIT._ CALIERATION DnTA i
=
===.a=.-=.====-..==.,
2 l
c r. i i r n., a. sir
,ecr~
- t. o"_,' u r r "' -
m '. -- A' 1 't t n..
-- c ?
S 1.
t u
-iatn.
- ur i ApptIC.:TIf" MCL I!IGH PLCW M5IV ISCLATID" o -,i L, su, s,, s...n
~i~- l,,, r,,
C c.a. w0 t a
.1:
i O c I n-(J, a.
- e
- . o c,. 3
,7 r,
- r. E s, r. p r',
- i m r_
.c. m. r% %. - a :/. m'.
r m
r
,u
>a
..r m.
e Sr' T J_ $>f i
.1 4 s_ i
! 1tT < 2" e kl/ hi t
T**
/.
bi' t*
- ___ I ;.,, c..
p _,. c a._ i t e. c; t,-
>n c I n n._-
i n mpt t-v, r r,.,t n,
ia.
-a
.1 i.
ac a
TECl' 9 PEC ALLOUGF '~ '
110.CO PSID r.,-
c,.,,nd"
'Q:
I. ".. 'it" t'
c,_-a 1.; em.,+.
,...i..,,
s_
.. c.a,
.-4 m
u
+'p
'? e E U t It' i p OP 5 id t g)I k 5 L};
g.*;
uJ. av<
v..
. As+
,3
, ", br.~w wl
's
.e a
c-I s k*
6 *
}
f'-
f i r-we -,,
e t
i i
i j
i I
i I
u--
Page.-
1 4
I.
i j
. UNIT 2 CALIBRhTION DATA
===================t
1
' EQUIPMENT PIECE NUMBER:
2E31-N011A APPLICATION:
MSL HIGH FLOW MSIV ISCLATION NOMINAL SETPOINT:
85.00 PSID I CALIBRATION TOLERANCE:
04.00-86.00 PSID
+
- ACTION LIMITS:
N/A
- l. REJECTION LIMITG:
-69.50-100.50 PSID
' TECH SPEC ALLOWABLE:
116.00 PSID i
! Calibration Date "An Found" "As Found" "As Left" "As Left" j
Trip Recet Trip Reset
-t T
8/ 2/GG 85.00 58.80 10 /14 / t'6 06.0 57.5 85.0 56.0 l
j k
I i
1 1
I i
l-<.
i I
I I
i I
.?
1 l
i i
f e
a
!i I
Page.
1 4
s t
j UNIT 2 CALIBRATION DATA
-======================z
(
EQUIPMENT PIECE NUMBER:
2E31-N011B 2 APPLICATION:
MSL HIGH FLOW MSIV ISCLATION NOMIN'AL SETPOINT:
85.00 PSID CALIBRATION TOLERANCE:
84.00-86.00 PSID ACTION LIMITS:
N/A l REJECTION LIMITS:
69.53-100.50 PSID
{ TECH SPEC' ALLOWABLE:
116.00 PSID e
4 i~ Calibration Date As Found" As Found" "As Lefs" As Left" Trip
- Reset Trip Reset 8/ 2/86 85.40 69.70
- 10/14/86 85.5 60.3 85.5 68.0
-!01/03/87 OG. 9 66.4 64.8 66.5 4
a r
i 1
l i
1 i
4 1
f I
1 l
i I.-
5 i
i i
i l.
+M g
g---g,-r-%g--
ey y
e'j-W. 9 9,i gp-,
y
's v
-twe-g,--
p u ade 7
wy*-ig,,n-..
,wOtW#-4*-T*W--*
r*
W--**MP'T4EAVWPW P ft
- M*'""E DF-7NT
8-p9'tT-*v
--F-t-
-"w-z-t.d--'t
- prege--
~.-.
~
'Page 11 9
' UNIT 2 CALIBRATION DATA
===========
EGUIPMENT PIECE NUMBER:
2E31-N011C APPLICATION:
MSL HIGH FLOW MSIV ISOLATION NOMINAL SETPOINT:
85.00 PSID CALIBRATION TCLERANCE:
84.00-86.00 PSID ACTION LIMITS:
N/A REJECTION LIMITS:
69.50-100.50 PSID TECH SPEC ALLOWABLE:
116.00 PSID Calibration Date "As Found" "As Found" "As Left" "An Left" Trip Reset Trip Reset 8/ 2/96 84.71 64.50 10/14/86 87.75 60.0 85.5 61.0 I
s
J
_.A4
-iaa A
L
.A4J-44+-+
4-X.
A a-- - - + -'-
4k a
4-n-a-64 4 -
4
.4 Page
. 1 i
.l UNIT 2~ CALIBRATION DATA
=====,===sn
n
] EQUIPMENT P!ZCE NUMBER:
'2E31-N011D I
5 APPLICATION:
MSL HIGH FLOW MSIV ISOLATION' i
j NOMINAL SETPOINT:
.85,00 PSID l CALIBRATION TOLERANCE:
84.00-86.00 PSID i
- j. ACTION LIMITS:
N/A
) REJECTION LIMITS:
69.50-100.50 PSID ITECH SPEC ALLOWABLE:
116.00 PSID I
jCalibration Date As Found" As Found" "As Left" "As Left"
'irip Reset Trip Reset
{---------------------------------...------------------------------------
i j
8/.1/86 REVISED SETPOINT 85.00 61.50 i
8/ 2/86 84.70 G0, 30 84.60 60.40
- i. 10/14/86 (30.0 59.0 85.0 58.0 i
l 1
4 t
1 1i 4
l 1
i i
l l
1
't l
l.
i J
l t
a h
l i
i t
i i
a
-.m i.-c.e-m v,-
,.r,-.4r,-m.%
.'-,wn,-,
,,,mry,m>--+-
- - -....,w
-m..
,---c.-.
1,-c %y -
cr,,*m,.-.--
s-w,,
-, ewe,-
--e-
,,,-+. - - - -,
%---mw--
r,
....... _ -. _ ~. _... _.
Page 1
i l
I i UNIT'2 CALIBRATION DATA l
?
{u=na n=======.=====
f-i j EQUIPMENT PIECE NUMBER:
CE31-N007AA t
i APPLICATION:
STEAM LINE HIGH FLLOll RCIC ISOLATION 1
NOMINAL SETPOINT:
111.4"'WC
- CALIBRATION TOLERANCE
110.4-110.4" WC i
{ACTIONLIMITS:
106.0-116.8" WC i
102.0-120.0" WC i
} REJECTION LIMITS:
TECH GPEC ALLOWABLE:
128.0" WC i,
} Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset J
fi08/04/86 111.5 106.0 f.10/ 9/86 112.0 107.S
.112.0 107.5 i
i i
I i
f f
i
?
1 L
\\
l I
i i
J L
i f
l t
i
.-. ~
~.. _ -. -,
Page 1
i 4
5~ UNIT 2. CALIBRATION-DATA
u==========u===
l l EQUIPMENT PIECE NUMBER:
{ APPLICf, TION:
STEAM.LINE HIGH FLLOW RCIC ISOLATION l
l NOMINAL SETPOINT:
111.4" WC i CALIBRATION TOLERANCE:
110.4-112.4" WC WC J
i ACTION LIMITS:
106.0-116.8" J PEJECTION LIMITS:
102.8-120.0" WC 1
4' TECH SPEC ALLOWABLE:
128.0" WC e
i r
i U
Calitwat ion Date As Found" "As Found" "As Left" As Loft" Trip.
Reset Trip Reset
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - ~ ~ - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
4 j
8/ 4/06 111.5 105.5
? 10/ 9/06 111.5 105.0 111.5-105.0 J
j h
?\\
4 i
i i
i.
I t
I
~i l
1 i
)
i t
j I
3 i
a I
i i
1 s
l i
r--m-,
+c~~-,,,~-c.wwew,v,--w,,%
---,-+--,-,m,-m-,,,w,ver,w-,
,w
-.-.--~w
~--w g-
~e-.~~-~,-v
---e,e---=,,-,r-
---.wr,, *.,,---. wee-er---r,-,---wme e
~... -
Page.
i'
{
i 4
UNIT 2 CALIBRATION DATA
===========
1 l EQUIPMENT PIECE NUMDER:
[
iAPPLICATION:
STEAM LINE HIGH FLOW RCIC ISOLATION
! NOMINAL SETPOINT:
75.4" WC
=
CALIBRATION TO'.ERANCE:
_74.4-76.4" WC 3
j ACTION LIMITS:
70.0-80.8'- WC-4 RE.TECTICN LIMITS:
66.8-04,0" WC i TECH SPEC ALLOWAELE:
128.0" WC
- Calibration Date "As Found" "As Found" "As Left" "As Left" j
Trip Reset.
Trip Reset I
i 8/ 4/86 75.7 71.0 4
,10/ 9/8G 75,5 71.5 75.5 71.5 i
I i
j i
r
(
i e
i i
1 i
4, f
i i.
+
Y l
i i!'
i i
l i
i 1
a aI.
h
~
. ~.
. - - _ ~..
.. ~ -
.Page' 1
i i
?
l.i UNIT 2 CALIBRATION DATA n===u==============a===
f
} EQUIPMENT PIECE NUMBER:
OE31-N007BD
,' APPLICATION:
STEAM LINE HIGH FLOW RCIC ISOLATION r
i NOMINAL SETPOINT:
75.4".WC
] CALIBRATION TOLERANCE:
74.4-76.4" UC i ACTION LIMITS:
70.0-80.8" WC j REJECTION LIMITS:
66.8-84.0" WC i TECH SPEC ALLOWABLE:
12,0.0" WC i
i
- Calibration Date "As Found" "As Found" "As Left" "As Left" l
Trip Reset Trip Resst 1
i 8/ 4/8G 75.7 69.5 e 10/ 9/86 80.0 69.0 75.5 67.0 i
i i
t i
1 f
i J
i 1
s
{
I e
4 I
r I
i i
f t
i I
l 4
k,
i j
Page 1
I I
' UNIT 2 CALIBRATION DATA i
i a============n========n l
1 i.EQi!IPMENT PIECE NUMBER:
2E31-N013AA l APPLICATION:
STEAM LINE HIGH FL7W RCIC ISCLATION 4
?
^
NOMINAL SETPOINT:
16E.4" WC l
{
- CALIDRATION TOLERANCE:
165.4-167.4" WC ACTION LIMITS:
161.0-171.8" WC REJECTION LIMITS:
155.8-177.0" WC i
TECH SPEC ALLOWABLE:
185.0" WC f
Calibt4ation Date "An Found" "Aa Found" "As Left" "As Left" l
Trip Reset T.-i p Reset 8/ 4/86 166.7 159.5
[
g.10/ 9/06 168.0 163.0 166.0 161.0 I
l l
f l
i i
l
(
l i
E k
I i
i r
i t
l
.1 t
'f a
l l
{
l e
1 i
j i
l 4
1
+mem m y,ew e r. w ww+www.
. m.-
Page 1
i Y
i i UNIT 2,CALIDRATION DATA
=============u==,===u
EQUIPMENT PIECE NUMBER:
2E31-N013AB APPLICATION:
STEAM LINE HIGH FLOW RCIC ISOLATION
'A NOMINAL SETPOINf:
16G.4".WC 1
- CALIBRATION TOLERANCE
155,4-167.4" WC i ACTION LIMITG:
1G1.0-171.0" WC
} REJECTION LIMITS:
155.8-17".0" WC TECH SPEC ALLOWABLE:
185.0" LC j Calibratton Date "An Found"
" A s Fo.md "
"As Left"-
"As L e f t '!
Trip Reset Trip Reset 1
{
O/ 4/GG 166.0 158.5 110/ 9/85 1CS. 0 161.0 166.5 160.0 1
I i
J i
i 1
1
,I
+
I:
i 4
.I 1
1 1
i 6
.t t
)
i E
i l
l l
l l
4 i
i
\\
r e
1 T
i I
~~,--...
4 Page 1
.: UNIT E-CALIBRATION DATA
,==e=n=======
===a==a
- EQUIPMENT PIECE NUMBER:
- AP PL I C,aT ION
STEAM LINE HIGH FLOW RCIC ISOLATION
' NOMINAL SETPOINT:
166.4" WC CALIBRATION TOLERANCE:
165.4-167.4" WC j ACTION LIMITS:
161.0-171.8" WC REJECTION LIMITS:
155.8-177.0" WC TECH SPEC ALLOWABLE-185.O" WC
- Calibration Date
'As Found" "As Found" "As Left" "As Left" Trip Reset Trip Recet C/ 4/GG 166. W 157.5
)10/ 9/06 166.0 153.0 166.0 155.0 4
l P
i i
i I
\\
1 E
1 r
t 4
o I
i k
l
. __ _y _......____ _,_.
j~
Page.
1' l
1 j UNIT 2 CALIBRATION DATA t
===u========c
} EQUIF11ENT PIECE. NUMEER:
2E31-N013BD 1 APPLICATION:
STEAM LINE HIGH FLOW RCIC ISOLATION.
.i l NOM?NAL SETPOINf:
166.4" WC-jCALIBRATICN TOLERANCE:
165.4-167.4" WC
-i 1
ACTION LIMITS:
161.0-171.8" WC
. REJECTION LIMITS:
155. 8-177. O'i. WC
{ TECH SPEC ALLOWABLE:
185.0" WC 5 Cali br stion Date "As Found" "As Found" "As Left".
"As Left" 1
l Trip Reset Trip Reset 4
T
\\
J 8/ 4/06 165.6 152.5
! 10/ 9/86 171.G 159.5 167.0 157.O
! SERIAL NUMDER I
l 86-10-3863
} 12/12/G6 NEW SWITCH 166.7 160.0 4
e 1
(
)
i 4
1 l
i i
i a
1 i
l i
l.
i a
i f
_. =
] '
j Page 1
-)
i l
i
- j. UNIT 2 CALIBRATION DATA e
j y===u================u==
l EQUIPMENT PIECE NUMBER:
2E31~N012AA f
l APPLICATION:
NOMINAL SETPOINT:
168.4" WC l
l CALIBRATION TOLERANCE:
157.4-169.4" WC l
l
! ACTION LIMITS:
'163.0-173.8" WC l
REJECTION LIMITS:
158.0-178.0" WC i
l TECH SPEC ALLOWABLE:
186.0".WC "As Found" "As Found" "As Left" "As Left"
{' Calibration Date Trip Reset Trip Roset 08/03/C,6 168.0 157.0 09/16/86 164.0 154.0 168.5 160.0 6
4 168.5 161.0 169.0 160.5 l12/17/GG 3
}
5 P
I i
t a
l Y
6 h
I f
f r
f i
i i
l 1
i l
t i
....... _ _ _............ _........ =
-.. ~,
l Page 1
I j-
! UNIT 2 CALIBRATION DATA 4
===========
i EQUIPMENT PIECE NUMBER:
2E31-N012AB-APPLICATION:
] NOMINAL SETPOINT:
168.4" WC
' CALIBRATION TOLERANCE.
167.4-169.4" WC i
bACTION LIMITS:
163.0-173.0" WC lREJECTIONLIMITS:
158.8-178.0" WC j TECH' SPEC ALLOWABLE:
186.0" WC 1
i
- 2 Celibration Date As Found" As Found" "As Left" "As Left" i
Trip Reset Trip Reset i _____________________________________________________________________---
t
(
- 08/03/86 168.0 160.0
! 09/16/86 166.0 157.0 1 G8. 0 159.0 l 12/17/8C 168.5 162.0 168.0 161.0 1
(
i l
l i
i l
a l
4 4
i i
i I
1 I
I l
i 1
4 1
l i
a 1
i
,1 i.
i
-,.e,-w.,_,w4e,-
-.#,-y,v-e-,.4
, *.. ~r r----,m+.+
,,,m,.,--e+.---
...,,...-,--v-.--,.
-,--,.,-c
.r e.c v
.._,.c~c.
--r,-,-w----,
e--~----r-,re,e-
I- - - _ _ _... _
s Page~
1
}' UNIT 2CALIBRATIONDATA i
i=m====================
1 1
i EQUIPMENT PIECE NUMBER:
! APPLICATION:
i l NOMINAL'SETPOINT:
1 ' 'S. 4 " WC l
i CALIBRATION TOLERANCE:
167.4-169.4" WC i
i j HCTION LIMITS:
163.0-173.8" WC i REJECTION LIMITS:
158.8-178.0" WC l
j TECH SPEC ALLOWABLE:
186.0" WC 1
i
} Calibration Date "As Found" "As Found" "As Left" "As Left" Reset Trip Reset l__.____.-___.__._____._._____
Trip i
08/03/86 168.0 155.0 09/1C/SG 165.0 150.0 168.5 155.0 4
{ 12/17/86 168.0 154.0 160.5 155.5 4
1 l
I f
l I
i I
i i
f f
(
I i
l l
.m..
'Page' 1-I i UNIT 2 CALIBRATION *tATA i
===========
- EQUIPMENT PIECE NUMBER
2E31-N01EBD I; APPLICATION:
i NOMINAL SETPOINT:
168.4" WC
' CALIBRATION TOLERANCE:
167.4-169.4" WC-4
" ACTION LIMITG:
163.0-173.8" WC REJECTION LIMITS:
158.8-178.0" WC TECH SPEC ALLOWABLE:
186.0" WC i
i T
! Calibration Date "As Found" "As Found"
" As Le f t "
"As Left" Trip Reset
~ Trio Reset
)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _. _ _. _ _ _ _ _. _ _ _ _ _. _ _ _ _ _ _ _ _ _ _ ~ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _. _ _ _ _ _ _ - _ _ _ _ _.
t
}08/03/85 168.5 157.0 t 09/16/86 168.0 157.0 168.0 157.0 i 12/17/06 168.0-153.0 168.0 155.5 i
1 i
i 2
1 f
j 1
i i
l
)
i e
k a
I i
)
s I
It 7
i 1
1 i
l t
b.!
4
{
Page 1
f 1
i i
I UNIT 2 CALIBRATION DATA
================c
4 fEQUIPMENTPIECENUMBER:
- APPLICATION
LOW PRESS CORE SPRAY MIN FLOW BYPASS NOMINAL SETPOINT.
23.O.0" WC
. CALIBRATION TOLERANCE:
22.4-23.6" WC 1
3 i
?
.i 4 ACTION LIMITS:
21.3-24.7" WC J -REJECTION LIMITS:
20.6-25.4" WC 4
f TECH SPEC ALLOWADLE:
3.187" WC i
! Calibration Date "As Found" "As Found" "As Left" "As Left" j
Trip Reset Trip Reset i
j t
] 07/30/86
- 22. ']
C'3. 4 j
j 10/20/86
.23.0 34.6 23.2 34.6 i
} 01/17/G7 23.4 30.5 23.4 30.5 1
4 T
l l
i y
t 4
i-k i
i r
4 i
1 I
i i
4 l
i
.,. ~ - -, - ~..
-m____.
._.,r-
- i Page 1
/
]
.i jUNIT 2 CALIBRATION DATA I
- =========u====aa====n==
EQUIPMENT PIECE NUMPER:
2E22-N006 iAPPLICATION:
HPCS MINIMUM FLOW t
4 I
NOMINAL SETPOINT:
23.00" WC i
a
) CALIBRATION TOLERANCE:
22,40-23.G0" WC f
{ ACTION LIMITS:
21.30-24.70" WC j REJECTION LIMITS:
20.D0-26.00" WC l
i
- TECH SPEC ALLOWADLE
9.70" WC a
l i
iCalibration Date "As Found" "As Found" "As Le f t ",
"As.Left" i
i Trip Reset Trip.
Penet j..____.___._.
,3.__...._..___.
1 l 07/30/G6 CI. 20 32.40 i108/15/86 23,60 32.40
- 23. GO JI.60 l11/15/r36 E3.4 34.0 23,4 34.O i
i i
a
)
e 1*
4 4
n i
c i
i i
1 1
1 i
l l
[
l F
i t
I I
l
+
c i
i
... n Page 1
i i UNIT 2 CALIBRATION DATA
,======================
EQUIPMET4T PIECE NUMBER:
2E12-N010AA APPLICATION:
RHR A MINIMUM. FLOW ii NOMINAL SETPOINT:
23.0" WC j cat IBRATION TOLERANCE:
22.4-23.6" WC 1
ACTION LIMITS:
21,3-84.7" WC 4
l PEJECTION LIMITS:
17.7-28.3" WC TECH SPEC ALLOWABLE:
1.78" WC i
i Calibration Date As Found" As Found"'
"As Left" "As Left" Trip Reset Trip Reset 1,
.07/31/86 23.0
~29.2 I 09/10/8G 21.6 28.4 22.9 29.2 12/11/86 23.2 32.0 23.0 30.0 1
u i
I i
i e
i l
1 i
4 4
I 2
I
(
)
f 1
%-__n,sy,yy_m 4.
m_.w.,.,.yw.sy-~..%,
-y,.,,
-,,.~_.__,__y
,_n, y,,,w.-._m,
,9-7,-
.,.y____m_
Page.-
1 UNIT 2 CALIBRATION DATA
=====e=u===
- EQUIPMENT PIECE NUMBER:
2E12-N010BA APPLICATION:
RHR D MINIMUM FLOW NOMINAL SETPOINT:
23.fd' WC CALIBRATION TOLERANCE:
22.4'-23.G" WC i ACTION LIMITS:
21c3-24.7" WC REJECTION LIMITS:
17.7-28.3" WC
.l TECH SPEC ALLOWABLE:
1.78" WC 1
[
t Calibration Date As Found" "As Found" "As Left" "As Left" Trip
' Fdset Tt ip Reset
_ _ _ _ _ _ - _ _ _ _ _ _ _ _ _._ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _. ( _ _ _ _ _ _ _ _ _
07/31/86 23.0 29.2 09/10/86 24.4 29.4 23.1 28.2 12/11/86 22.7 30.I 23.2 28.6 i
9 3
5 k
F 1
i J
l 4
-.. - ~,,
,.44.-,,
..,.e-w
.m-
-,- - w.
-w-.
, e-m.m.e n
.-..,--.-,ew.
-c.-,.
,-g-g r v--,
w.
.PaDe 1
UNIT 2 CALIDRATION DATA
= = - = = = = = = = = = = = = = = = = = =
=
EQUIPMENT PIECC NUMBER:
2E12-N010CA APPLICATION:
RHR C MINItiUM FLOW j NOMINAL SETPOINT:
23.0" WC
{CALIDRATION TOLERANCE:
22.4--23.6" WC i
1: ACTION LIMITS:
21.3-24.7" WC 1 REJECTION LIMITS:
17.7-28.3" WC
- TECH SPEC ALLOWABLE
1.78" WC 4
Calibration Date
" A s Foi.md "
"As Found" "As Left"
" As Le f t "
i Reset Trip Reset 7_
______ ____ Trip
< 07/31/86 23.0 28.6
$' 09/10/86 22.8 28.8 23.4 30.0 12/11/86 23.9 31.9 22.75 32.'5 t
f a
I r
1 l
3 I
?
4 I
g 1
1 I
I i
)
4 1
1 i
i I
t I
l I.-.
.. ~.
_,_......__..._....._._-__..-..-.._.....,...~.._.-__.__.-,,_,s,,__-._
.Page
,1 l
t I
UNIT 2 CALIBRATION DATA
)
===========
(
1 4
f-
- EQUIPMENT PIECE NUMDER
2E12-N010AB IAPPLICATION:
RHR A MINIMUM FLOW ALARM l
I NOMINAL SETPOINT:
25.0" WC I
CALIBRATION TOLERANCE:
24.0-26.0" WC
. ACTION LIMITS:
NA
[
[ REJECTION LIMITS:
NA TECH SPEC ALLUWABLE:
NA I
i
' Calibration Dat e "As Found" "As Found" "As Left" "As Left" I
Trip Reset Trip Reset j _____________________________________________________________.___________
07/31/86 24,4 19.8 09/10/86 22.6 16.0 24.8
'18,6 I
i 12/11/06 25.0 20.0 24.4 19.4 1
l h
i 6
4 4 -
1 1
s i
4 4
I li l
l t
J l
i.
1 I
i f
f Y
l a
3 t
i
.,-~,.-.. -_.,-,<.., _ _,-,.... u ~ -.....~ -.~ _...,.,.,_
n,.,,
l t.
Page-1 l-i i
i i
i
- i. UNIT 2 CALIBRATION DATA i
1=======================
I; i
i l EQUIPMENT PIECE NUMBER:
2E12-N010BB 1 APPLICATION:
RHR B MINIMUM FLOW ALARM i
NOMINAL SETPOINT:
25.0" WC
- CALIBRATION TOLERANCE:
24.0-26.0" WC i ACTION LIMITS:
NA 3
i REJECTION LIMITS:
NA ETECH SPEC ALLOWABLE:
NA l
i
{CalibtationDate
" As Fc+.nd" "As Found" "As Left" "As Left" i
Tr'ip Reset Tr ip Reset I
- 07/31/85 25.2 20.9 l
109/10/06 26.2 21.4 25.6 21.4 a-l 12/11/06 26.9 21.4 25.5 20.6 4
i l
i I
i J
c f
i i
]
i' f
i.
{
i.
h 4
1 i
i I
i
~,
e k
,i.
)
...-,..._.---.- -.,,._,... __.._....,.,......,. _. __ _.,;, _,.i
1 Page 1
UNIT 2 CALIBRATION DATA
===========
EQUIPMENT PIECE NUMBER:
' APPLICATION:
RHR C MINIMUM FLOW ALARM NOMINAL SETPOINT:
25.0" WC CALIBRATION TOLERANCE:
24.0-26.0" WC f
ACTION LIMITS:
NA REJECTION LIMITS:
NA TECH SPEC ALLOWABLE:
NA i
I Calibration Date "As Found" "As Found" "As Left" "As Left" Trip Reset Trip Reset l
07/31/86 25.4-17.6
[
09/10/86 25.4 17.1 25.2 17.4
-l' 12/11/8G 25.35 17.3 25.1 17.5' f
a 9
F W
k v
i n
I 1
I 1
i 4
l
(
i f
b P
... -... _, _. - _.. _ _ _,.. -..., _ _........ _,.._,,_ _. _---..._.., _... _,..-._ - -- - - _ +