9 GPU Nuclear Corporation Nuclear
- 33';;;388 Forked River,New Jersey 08731-0388 609 971-4000 Writer's Direct Dial Number:
Dr. Thomas E. Murley, Administrator July 30,1986 Region I U.S. Nuclear Regulatory Commission 631 Park Avenue King of Prussia, PA 19406
Dear Dr. Murley:
Subject:
Oyster Creek Nuclear Generating Station Docket No. 50-219 IE Bulletin 86-02, Response to Action No.1 IE Bulletin 86-02 " Static-0-Ring Differential Pressure Switches" was received at the Oyster Creek Nuclear Generating Station on July 22, 1986. Action Item No.1 required a report to be submitted on the identified switches within seven (7) days. This letter meets the requirements of Action Item No.1.
Attachment I documents the four applications of the identified SOR, Inc.
switches at the Oyster Creek Nuclear Generating Station. This information is correct as of the date of this letter.
However, it should be noted that the last two applications listed on the attachment (Reactor Low Level and Reactor Low-Low Level) are presently scheduled for replacement by an analog trip system during the present refueling outage.
If any further information is required, please contact Mr. John Rogers of my staff at (609)971-4893.
Very truly yours, w 1
- J/A re et r o.
riedlEr Vice President and Director Oyster Creek PBF/JR/ dam (0918A)
Attachment cc's: See Page 2 Sworn to and Subscrjbed before me this M aday of July,1986.
1d)
/Il A Gotary Public 'of Ne)( Jersey 8608060312 860730 PDR ADOCK 05000219 L
\\
G PDR l
GPU Nuclear Corporation is a subsidiary of the General Public Utilities Corporation
Dr. Thomas E. Murley, Administrator Regicn I - USNRC Page 2 cc: Document Control Desk (original)
U.S. Nuclear Regulatory Commission Washington, DC 20555 Mr. Jack N. Donohew, Jr.
U.S. Nuclear Regulatory Commission 7920 Norfolk Avenue, Phillips Bldg.
Bethesda, MD 20014 NRC Resident Inspector Oyster Creek Nuclear Generating Station t
h l
f t
f
o ATTACHMENT 1 Inst.
SOR System I.D.
Model System Operating Number No./ Range Installed Pressure Application Switch Function DPS-66A 103AS-B202-NX-Drywell &
Atmospheric Monitor Reactor Bldg.
1.
Opens vacuum breakers to DPS-66B JJTTX6 Suppression Pressure to Torus differental equalize pressure between Torus Range: 5" - 35" W.C.
pressure and Reactor Building RV-40A 103AS-B905-NX-Core Spray 140 psig Flow (using delta P 1.
Starts alternate Core Spray RV-40B JJTTX6 suction to across booster pump) booster pump when primary booster RV-40C Range: 10 psig 250 psig pump has low flow.
RV-40D to 90 psig discharge 2.
Automatic Depressurization System permissive.*
RE-02A 103AS-BB212-NX-ECCS 1020 psig Low-Low Water Level
- 1. Start Core Spray System RE-02B JJTTX6 ESF (using delta P)
- 2. Start Standby Gas Treatment Sys.
RE-02C Range: 10" --
- 3. Containment Isolation RE-02D 100" W.C.
- 4. Containment Spray Initation *
- 5. Reactor Isolation
- 6. Recirc Pump Trip
- 7. Reactor Bldg. Closed Cooling Water /Drywell Isolation *
- 8. Isolation Condenser Initiation
- 9. Start Emergency Diesel Generato7 RE-05/19Al 103AS-BB212-NX-RPS 1020 psig Low Water Level 1.
Reactor Scram RE-05B1 JJTTX6, Range:
(Using delta P)
RE-05A1 10" -- 100" W.C.
RE-05/19B1
- Other inputs required to initate the function.