_ _ _ - _ _ _ _ _ _ _ _ _

BEFORE THE UNITED STATES NUCLEAR REGULATORY COMMISSION In the Matter of the Facility Operating License)

)

of

)

)

PUBLIC SERVICE COMPANY OF COLORADO

)

Application for Amendment to Appendix A of Facility Operating License License No. DPR-34

\\

OF THE

(

PUBLIC SERVICE COMPANY OF COLORADO FOR THE FORT ST. VRAIN NUCLEAR GENERATING STATION This application for Amendment to Appendix A of Facility Operating License, License No. OPR-34, is submitted for NRC review and approval.

Respectfully submitted, PUBLIC SERVICE COMPANY OF COLORADO By R. O. Williams, Jr.

Vice President Nuclear Operations KELLY, STANSFIELD & 0'DONNELL Bryant O'Donnell James K. Tarpey Public Service Company Building Denver, Colorado 80202 Attorneys for Applicant

%22%h P

s ATTACHMENT 1

SUMMARY

OF PROPOSED CHANGES Attachement 1

SUMMARY

OF PROPOSED CHANGES SECTION DESCRIPTION LC0 4.4.1

1. TABLE 4.4-2.

Deleted line items 1 and 2 as they relate to the Steam Pipe Rupture Detection System whose PPS trip functions are being deleted.

The Steam Line Rupture Detection /

Isolation System (SLRDIS) replaces protection provided by the Steam Pipe Rupture Detection System under the PCRV and in the pipe cavities for each loop.

2. TABLE 4.4-3.

Added line item nos. 10a, 10b,10c, and 10d in the fonnat of the Technical Specification Upgrade Program for TRIP SETPOINTS for CIRCULATOR TRIP (pg 4.4-6a) and OPERA 8ILITY REQUIREMENTS i

for CIRCULATOR TRIP (pg 4.4-6b) for the Steam Line-Rupture Detection / Isolation System. The new fonnat has a column labelled ' ACTION' which has requirements when specifications of the OPERABILITY REQUIREMENTS are not met. The applicable ACTION statements are shown on pg 4.4-6c.

3. NOTES FOR TABLES 4.4-1 through 4.4-4 (continued)-pg4.4-8and4.4-9. Notes (j) and (s) are deleted as they i

are related only to the Steam Pipe Rupture Detection Instrumentation whose j

PPS trip functions are being deleted.

Basis for LCO 4.4.1

1. Page 4.4-12. Two-Loop Trouble. The operation of SLRDIS to effectively override a simultaneous two loop shutdown inhibit is described in this basis.
2. Page 4.4-12, High Temperature.

Deleted reference to the Steam Pipe Rupture Detection System.

I L

w..

..-.__..~,-..y__m,,

-.,,,._.~-._..,.----..,,_..-___.--_.-,--_--e

3

3. Loop Shutdown Inputs-Shutdown of Both Circulators is moved from pg 4.4-13 to new page 4.4-12a.
4. Loop Shutdown Inputs-Basis for Steam Pipe Rupture in Reactor Building has been deleted.
5. Circulator Shutdown Inputs (except circulator speed high on water turbines) paragraph moved to new page 4.4-12a.

Added paragraphs on Steam Leak Detection in the Reactor Building on pages 4.4-12a and 4.4-12b.

Paragraph on Steam Leak Detection in the Turbine Building added on page 4.4-13 and remainder of that page reformatted to account for deletion of Steam Pipe Rupture Detection System.

SR 5.4.1

1. Basis for SR 5.4.1 expanded to discuss basis for surveillance on SLRDIS.

Inserted on pg 5.4-2.

2. Table 5.4-2.

Line item I was de.leted as it is related to the Steam Pipe Rupture (Pipe Cavity) channel which is no longer s

required.

3. Table 5.4-2.

Line item 2 was deleted as it is related to the Steam Pipe Rupture (Under PCRV) channel which is no longer required.

4. Table 5.4-3.

Added line item nos. 8a, 8b, 8c and 8d in the format of the Technical Specification Upgrade Program for Surveillance Requirements on the Steam Line Rupture Detection / Isolation System which is to be installed as part of this Technical Specification Amendment.

l l

l l

.. - - -. -