1 Effective Date 4

i INFORMATION u

ONLY J ANNUNCIATOR RESPONSE i

AR-801 FLORIDA POWER CORPORATION CRYSTAL RIVER UNIT 3 P.

FSA ANNUNCIATOR RESPONSE V

i i

1 APPROVED BY:

Interpre atio Contact fU l'It u &

f (SIGNATURE ON FILE j

DATE:

/[

I l

INTERPRETATION CONTACT:

Manager, Nuclear Plant Operations Support 9710100E62 971007 PDR ADOCK 0500 2

TABLt OF CONTENTS SECTION EAR 1. 0. PI ' R P0S E........................................................

2.0 REFERENCES

1 2.1 IMPLIMENTING REFERENCES.............................

2.2 DEVELOPMENTAL REFERENCES............................................

1

................ 1 3.0 PERSONNEL INDOCTRINATION................................................

1 4.0 INSTRUCTIONS............................................................

1 5.0 FOLLOW-UP ACTIONS.......................................................

1 ENCLOSilRE 1

An n u n c i a to r Re s pon s e................................................ 2 J

AR-801 Rev. 9 Page i

4 1.0 PURPOSE 1.1 Establish a reference document for each Annunciator Window on the l

FSA Lampbox.

1.2 Establish operator actions for valid Annuncie. tor alarms on the FSA 4

Lampbox.

[

1.3 Establish a reference to other procedures which address operator actions for valid Annunciator alarms on the FSA Lampbox.

2.0 REFERENCES

2.1 IMPLEMENTING REFERENCES 2.1.1 AP-880, Fire Protection t

2.2 DEVELOPMENTAL REFERENCES 2.2.1 INPO 90-021, Good Practice OP-217, Alarm Response Procedures

()

2.2.2 Annunciator Window Engraving Drawing E-224-050 3.0 PERSONNEL INDOCTRINATION i

3.1 The Fire Service Annunciator System is powered from ACDP-40 Breaker 19.

4.0 INSTRUCTIONS 4.1 Respond to alarms on the FSA Lampbox as indicated on Enclosure 1, Annunciator Response.

5.0 FOLLOW-UP ACTIONS None

'f AR-801 Rev. 9 Page 1

= _. _ - _. _ _ _ _ _ - _

FIRE SYSTEM ANNUNCIATOR RESPONSE FS-01-01 FS-01-01 1

FIRE WTR TANK 3A LEVEL LOW

-INCICATED CONDITION: TANK LEVEL s;35'8" REDUNDANT INCICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTION FOR A VALID ALARM: REFILL TANK DISCUSSION:

REFERENCES:

DWG 208-031 FS-21 SENSING ELEMENT: FS-47-LS O

AR-801 Rev. 9 Page 2

FIRE SYSTEM ANNUNCIATOR RESPONSE FS-01-02 FS-01-02

=

FIRE WTR TANK 3B LEVEL LOW i

INDICATED CONDITION: YANK LEVEL s35'8" REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTION FOR A VALID ALARM: REFILL TANK DISCUSSION:

REFERENCES:

DWG 208-031 FS-21 SENSING ELEMENT: FS-48-LS O

AR-801 Rev. 9 Page 3

i FIRE SYSTEM ANNUNCIATOR RESPONSE FS-01-04 FS-01-04 CO* TANK PRLS8 Hl/LO INDICATED CONDITION: CARDOX TANK PRESSURE RELAY RAR ACTUATED REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

- CARD 0X PANEL WINDOW CO-1-2 ALARM

- LOCAL PRESSURE INDICATOR CO-1-PI OPERATOR ACTION FOR A VALID ALARM:

- WALK DOWN C0 SYSTEM AND ENSURE NO LEAKS

- ENSURE PROPER OPERATION OF CARD 0X UNIT DISCUSSION: CARDOX TANK RELAY RAR IS ACTUATED WHEN CARD 0X TANK PRESSU SEEN BY CO-1-PS1 IS 2325 PSIG OR s275 PSIG.

REFERENCES:

DWG 208-031 FS-21, DWG FL-16996 4 SENSING ELEMENT: CARDOX TANK RELAY RAR AR-801 Rev. 9 Page 4

FIRE SYSTEM ANNUNCIATOR RESPONSE FS-01-05 FS-01-05 i

i PUMP TEST RET WATER TO TANK 1

i a

i s

1 6

a j

INDICATED CONDITION: FLOW IN FIRE SERVICE RECIRC LINE :t540GPM EDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTION FOR A VALID ALARM: NONE DISCUSSION:

REFERENCES:

DWG 208-031 FS-21 SENSING ELEMENT: FS-12-FS O

AR-801 Rev. 9 Page 5

.. ~.. -. -. -.

- -. ~ - -...

I FIRE SYSTEM ANNUNCIATOR RESPONSE-FS-01-07 FS-01-07 i

4 FREON SYSTEM ACTIVATED INDICATED CONDITION: FREON SYSTEM ACTIVATED IN CABLE SPREADING ROOM REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

IO OPERATOR ACTION FOR A VALID ALARM: NOTIFY FIRE BRIGADE TO INSPECT SPREADING ROOM.

REFER TO AP-880 (FP)

DISCUSSION:

REFERENCES:

DWG 208-031 FS-21 SENSING ELEMENT: KIB FREON SYSTEM INTERFACE FIRING UNIT O

AR-801 Rev. 9 Page 6

4

)

l 6

FIRE-SYSTEM ANNUNCIATOR RESPONSE' FS-01-08 FS-01-08 i

FC'hTR PP & TURB DR 3A (HAZ 1)

INDICATED CONDITION: CARDOX HAZARD ZONE 1 RELAY PE ACTUATED (FWP REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

- CARD 0X PANEL WINDOW CO-1-1 ALARM O

- LOCAL WARNING BELL OPERATOR ACTION FOR A VALID ALARM:

- LOCALLY VERIFY CARDOX SYSTEM ACTUATION ON FWP-2A

- DEPRESS LOCAL SPURT PUSHBUTTON IF ADDITIONAL FLOW IS REQUIRED

- REFER TO AP-880 (FP).

DISCUSSIGN: THE CARD 0X SYSTEM WILL ACTUATE BY THE RESPONSE OF RATE COMPENSATED FIXED TEMPERATURE HEAT DETECTORS CO-3-TS1 THROUGH CO

REFERENCES:

.DWG 208-031 FS-21, DWG FL-16995 4 SENSING ELEMENT: HAZARD ZONE 1 RELAY PE O

-AR-801.

Rev. 9 Page 7

l FIRE SYSTEM ANNUNCIATOR RESPONSE FS-01-09 FS-01-09 h

i FDWTR PP & TUR8 DR 33 (HAZ 2)

EZZZZZ i

d t

INDICATED CONDITION: CARDOX HAZARD ZONE 2 RELAY PE ACTUATED (FWP-28)

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

- CARD 0X PANEL WINDOW CO-2-1 ALARM p

- LOCAL WARNING BELL OPERATOR ACTION FOR A VALID ALARM:

- LOCALLY VERIFY CARD 0X SYSTEM ACTUATION ON FWP-2B

- DEFRESS LOCAL SPURT PUSHBUTTON IF ADDITIONAL FLOW IS REQUIR

- REFER TO AP-880 (FP).

i DISCUSSION: THE CARD 0X SYSTEM WILL ACTUATE BY THE RESPONSE OF RATE i

COMPENSATED FIXED TEMPERATURE HEAT DETECTORS C0-4-TS1 TH 5

]

REFERENCES:

DWG 208-031 FS-21, DWG FL-16995 4 SENSING ELEMENT: HAZARD ZONE 2 RELAY PE i

5 I

d O

v 1

j AR-801 Rev. 9 Page 8 1

()

FIRE SYSTEM ANNUNCIATOR RESPONSE FS-01-10 FS-01-10 TURB GEN BRGS 15 (HAZARD 3)

INDICATED CONDITION: CARD 0XHAZARDZONE3RELAYPEACsDk'JO REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

- CARD 0X PANEL WINDOW CO-3-1 ALARM q

- LOCAL WARNING BELL

'U CPERATOR ACTION FOR A VALID ALARM:

- LOCALLY VERIFY CARDOX SYSTEM ACTUATION ON TURBINE CENERATOR THROUGH 5

- DEPRESS LOCAL SPURT PUSHBUTTON IF ADDITIONAL FLOW IS REQUIRED

- REFER TO AP-880 (FP).

DISCUSSION: THE CARD 0X SYSTEM WILL ACTUATE BY THE RESPONSE OF RATE COMPENSATED FIXED TEMPERATURE HEAT DETECTORS CO-5-TS1 THROUGH

REFERENCES:

DWG 208-031 FS-21, DWG FL-16995 4 SENSING ELEMENT: HAZARD ZONE 3 RELAY PE O

AR-801 Rev. 9 Page 9

___.._____.m.-_._..._

i i

FIRE SYSTEM ANNUNCIATOR RESPONSE' FS-01-11 FS-01-11 e

4 TURB OEN BRGS 6 9 (HAZARD 4) 4 INDICATED CONDITION: CARD 0X HAZARD ZONE 4 RELAY PE ACTUATED REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

- CARD 0X PANEL WINDOW CO-4-1 ALARM

- LOCAL WARNING BELL

\\

j OPERATOR ACTION FOR A VALID ALARM:

- LOCALLY VERIFY CARD 0X SYSTEM ACTUATION ON TURBINE CENERATOR BEARIN THROUGH 9 2

- DEPRESS LOCAL SPURT PUSHBUTTON IF ADDITIONAL FLOW IS REQUIRED j

- REFER TO AP-880 (FP)

]

DISCUSSION: THE CARDOX SYSTEM WILL ACTUATE BY THE RESPONSE OF RATE COMPENSATED FIXED TEMPERATURE DETECTORS CO-6-TS1 THROUGH CO-6-TS4 3

REFERENCES:

DWG 208-031 FS-21, DWG FL-16995 4 1

SENSING ELEMENT: HAZARD ZONE 4 RELAY PE 4

O AR-801' Rev. 9 Page 10

- O FIRE SYSTEM ANNUNCIATOR RESPONSE FS-01-13 FS-01-13 3

FIRE PUMP 3B RUNNING l

INDICATED CONDITION: POWER IS APPLIED TO FSP-1 MOTOR AND FSP-1 P BE RUNNING REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

1 OPERATOR ACTION FOR A VALID ALARM: NONE 4

DISCUSSION:

1 FIRE PUMP HOUSE FANS (AHF-33A & AHF-338) ARE USED FOR FIRE PUMP COMBUSTION AIR FOR DIESEL PUMP FIRE PUMPS AT LEAST ONE FAN MUS i

OPERATION ANY TIME A FIRE PUMP IS IN OPERATION EXCEPT DURING C OPERATIONS PER OI-13.

REFERENCES:

DWG 203-031 FS-14, FS-03 i

SEN5ING ELEMENT: mal-1 i

i 4

4 X

n a

AR-801 Rev. 9 Page 11

- - ~.

FIRE SYSTEM ANNUNCIATOR RESPONSE FS-01-14 FS-01-14 1

FIRE PUMP 3B CONTR PWR OFF i

4 l

I i

4 4

INDICATED CONDITION: CONTROL POWER TO FSP-1 IS OFF OR RELAY FA

-(ACDP 7 BREAKER #9)

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTION FOR A VALID ALARM:

DISCUSSION:

REFERENCES:

DWG 208-031 FS 14, FS-04 SENSING ELEMENT: mal-1 i

O AR-801 Rev, 9 Page 12

.. - - - =_ -.._..=.. - - -........

FIRE SYSTEM ANNUNCIATOR RESPONSE FS-01-15 FS-01-15 4

I CABLE SPR ROOM

~ q..

AUTO FANS OFF t

i i

E INDICAT.0 CONDITION: SELECTOR SWITCH PLACED IN THE "OFF" POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

O OPERATOR ACTION FOR A VALID ALARM: VERIFY SELECTOR SWITCH IS i

POSITION. INSTALL TEMPORARY FANS IF NECESSARY.

i DISCUSSION:

)

i RiiFERENCES:

4 SENSING ELEMENT: FSE-592 OV AR-801 Rev. 9 Page 13

=

~. _. -

i

- FIRE SYSTEM ANNUNCIATOR RESPONSE FS-01-16 FS-01 l I

l B

5 i

F.S. TANK INSTR 4

HEAT TRACE FAIL i

INDICATED CONDITION: OUTSIDE AIR TEMP s34 DEC F; HEAT TRACE FAIL REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

O OPERATOR ACTION FOR A VALID ALARM: DETERMINE IF TEMP REQUIRES A THE FIRE SERVICE SYSTEM LINEUP. CHECK HEAT TRACE LINES.

DISCUSSION: CHECK METEOROLOGICAL STATION INDICATION

REFERENCES:

DWG 208-031 FS-21 SENSING ELEMENT: FS-49-TS O

AR-801 Rev. 9 Page 14

.. _ -... _. ~ _. _.. _ _. _

i

)

l FIRE SYSTEM ANNUNCIATOR RESPONSE FS-02-01 FS-02-01 FIRE PUMP 3A OVERSPEED 4

3 1

i e

i i

i INDICATED CONDITION: FSP-2A OVERSPEED 22100 RPM

{

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTION FOR A VALID ALARM:

i

' w/

i DISCUSSION: PUSH LOCAL RESET PUSH BUTTON TO CLEAR ALARM

REFERENCES:

DWG 208-031 FS-2-7, FS-01 SENSING ELEMENT: SKID MOUNTED SPEED SWITCH 1

O) t AR-801 Rev, 9 Page 15

___..__m_

i 4

f FIRE SYSTEM ANNUNCIATOR RESPONSE FS-02-02 FS-02-02 i

FIRE PUMP 3A HI WATER TEMP d

INDICATED CONDITION: HI WTR TEMP ON COOLING WTR 2190 DEG F i

1 i

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

1 OPERATOR ACTION FOR A VALID ALARM:

SYSTEM, CHECK WATER LEVEL IN DIESEL COOLING
i I

DISCUSSION: PUSH LOCAL RESET PUSH BUTTON TO CLEAR ALARM 1

l j

REFERENCES:

DWG 208-031 FS-2-7, FS-01 SENSING ELEMENT: FS-15-TS 1

i i

1 l.

i d

i O AR-801 4

Rev 9 i

Page 16

FIRE SYSTEM ANNUNCIATOR RESPONSE FS-02-03 FS-02-03 FIRE PP 3A LO LUBE OIL PRESS INDICATED CONDITION: LO LUBE OIL PRESS s10 PSIG REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTION FOR A VALID ALARM: RdFILL WITH OIL IF NECESSARY.

DISCUSSION:

REFERENCES:

DWC 208-031 FS-2-7, FS-01 SENSING ELEMENT: FS-40-PS AR-801 Rev. 9 Page 17

4 FIRE SYSTEM ANNUNCIATOR RESPONSE FS-02-04 FS-02-04 FIRE PUMP 3A NOT IN AUTO INDICATED CONDITION: DIESEL CONTROL SWITCH NOT IN AUTO OR TEST REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTION FOR A VALID ALARM: RETURN SWITCH TO AUTO DISCUSSION:

REFERENCES:

DWG 208-031 FS-2-7, FS-01 SENSING ELEMENT: CS O

AR-801 Rev. 9 Page 18

O V

FIRE SYSTEM ANNUNCIATOR RESPONSE FS-02-05 FS-02-05 FIRE PUMP 3A Fall TO START INDICATED CONDITION: PUMP NOT RUNNING UP TO SPEED 90 SECONDS AFTER DI RECEIVES AN AUTO START REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

O, OPERATOR ACTION FOR A VALID ALARM:

DISCUSSION: PUSH LOCAL RESET PUSH BUTTON TO RESET ALARM

REFERENCES:

LNG 208-031 FS-2-7, FS-01 SENSING ELEMENT: RELAY 7R I

O l

l AR-801 Rev. 9 Page 19

d FIRE SYSTEM ANNUNCIATOR RESPONSE FS-02-06 FS-02-06 4

Z Z_ ~ _

FIRE PUMP 3A j

RUNNING i

4 i

INDICATED CONDITION: DIESEL IS RUNNING AND UP TO SPEED REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

t OPERATOR ACTION FOR A VALID ALARM: NONE 4

DISCUSSION:

i FIRE PUMP HOUSE FANS (AHF-33A & AHF-33B) ARE USED FOR FIRE PUMP C COMBUSTION-AIR FOR DIESEL-PUMP FIRE PUMPS. AT LEAST ONE FAN MUST

,^

OPERATION ANY TIME A FIRE PUMP IS IN OPERATION EXCEPT DURING COLD OPERATIONS PER 01-13.

3 4

REFERENCES:

DWG 208-031 FS-2-7, FS-01 SENSING ELEMENT: - RELAY 15R O

AR-801 Rev. 9 Page 20

r!RE SYSTEM ANNUNCIATOR RESPONSE FS 02-07 FS 02-07 FIRE PUMP 3A FUEL LEVEL LO INDICATED CONDITION: FUEL TANK LEVEL s66.5% FULL REDUND/: ' 1NDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTION FOR A VALID ALARM REFILL TANK DISCUSSION:

TEFERENCES: DWG 208-031 FS-21 J

SENSING ELEMENT FS-13-LS I

1 i O AR-801" Rev. 9 Page 21

1 f.

4 l

FIRE SYSTEM ANNUNCIATOR RESPONSE FS 02-05 FS-02-09 1

I I

1 j

FIRE PUMP 3C

]

OVERSPEED j

)

f INDICATED CONDITION: FSh-2B OVERSPEED h2100 RPM REDUNDANT INDICATION WHICH WILL VERIFY I4. ARM:

OPERATOR ACTION FOR A VALID ALARM:

DISCUSSION: PUSH LOCAL RESET PUSH BU7 0N TO CLEAR ALARM

REFERENCES:

DWG 208 031 FS-8-13, FS-02 SENSING ELEMENT: SKID MOUNTED SPEED SWITCH O

AR-801 Rev. 9 Page 22

FIRE SYSTEM ANNUNCIATOR RESPONSE FS-02-10 FS-02-10 FIRE PUMP 30 HI WATER TEMP

_I INDICATED CONDITION: HI WATER TEMP DN COOLING WTR 2190 DEC F REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTION FOR A VALID ALARMt CHECK WATER LEVEL IN DIESEL C SYSTEM.

DISCUSSION: PUSH LOCAL RESET PUSH BUTTON TO CLEAR ALARM

REFERENCES:

DWG 208-031 FS-8 13. FS-02 SENSING ELEMENT: FS-16-TS O

AR-801 Rev. 9 Page 23

q l'

)

FIRE SYSTEM ANNUNCIATOR RESPONSE FS 02-11 FS-02-11 f

)

i a

FIRE PP 3C LO LUSE OIL PRES i

4 i.

l

{

i 1

i a

ii -

INDICATED CONDITION: LO LUBE OIL PRESS s10 PSIG i

l l

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

t OPERATOR ACTION FOR A VALID ALARM REFILL WITH OIL IF NECESSARY DISCUSSION:

REFERENCES:

DWG 208-031 FS-8-13 FS-02 SENSING ELEMENT: FS-41-PS i

O AR-801 Rev. 9 Page 24

FIRE SYSTEM ANNUNCIATOR RESPONSE FS 02-12 FS-02-12 FIRE PUMP 3C NOT IN AUTO ZMZZ INDICATED CONDITION: DIESEL CONTROL SWITCH NOT IN AUTO OR TEST REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTION FOR A VALID ALARM: RETURN TO AUTO DISCUSSION:

REFERENCES:

DWG 208-031 FS-8-13. FS-02 SENSING ELEMENT: CS i

O AR-801 Rev. 9 Page 25

FIRE SYSTEM ANNUNCIATOR RESPONSE FS-02-13 FS-02-13 FIRE PUMP 3C Fall TO START INDICATED CONDITION: DIESEL NOT UP TO SPEED AND RUNNING 90 SECONDS A RECEIVING AN AUTO START SIGNAL REDUNDANhINDICATIONWHICHWILLVERIFYALARM OPERATOR ACTION FOR A VALID ALARM:

DISCUSSION: PUSH LOCAL RESET PUSH BUTTON TO CLEAR ALARM

REFERENCES:

DWG 208-031 FS-8-13 FS-02 SENSING ELEMENT: RELAY 7R O

AR-801 Rev. 9 Page 26

FIRE SYSTEM ANNUNCIATOR RESPONSE FS 02-14 CS-02-14 FIRE PUMP 3C RUNNING

~

INDICATED CONDITION: DIESEL IS RUNNING AND UP TO SPEED REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTION FOR A VALID ALARM: NONE DISCUSSION:

FIRE PUMP HOUSE FANS (AHF-33A & AHF-33B) ARE USED For, FIRE PUMP COOLING AND COMBUSTION AIR FOR DIESEL PUMP FIRE PUMPS. AT LEAST ONE FAN M OPERATION ANY TIME A FIRE PUMP IS IN OPERATION EXCEPT DURING OPERATIONS PER 01-13

REFERENCES:

DWG 208-031 FS-8-13. FS-02 SENSING ELEMENT: RELAY 15R O

AR-801 Rev. 9 Page 27

FIRE SYSTEM ANNUNCIATOR RESPONSE FS-02 15 FS-02-15 FIRE PUMP 3C FUEL LEVEL LO INDICATED CONDITION: FUEL TANK LEVEL s50% FULL REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTION FOR A VALID ALARM: REFILL TANK t

]

DISCUSSION:

i

}

REFERENCES:

DWC 208-031 FS-21 j

l SENSING ELEMENT: FS-14-LS i

s O

AR-801 Rev. 9 Page 28

FIRE SYSTEM ANNUNCIATOR RESPONSE FS-03-01 FS-03-01 MN TRANSF 31 FIRE SYS TROL l

INDICATED CONDITION: LOSS OF POWER TO CIRCUIT, ISOLATION VALVE NOT OPEN, OR CIRCUIT TROUBLE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTION FOR A VALIO ALARM: INVESTIGATE AREA FOR TAMPERING DISCUSSION:

REFERENCES:

DWG 208-031 FS-5 SENSING ELEMENT: K-2, K-5 i

O AR-801 Rev 9 Page 29

]

1 i

l.-

FIRE SYSTEM ANNUNCIATOR RESPONSE FS 03 02 FS-03 02 MN TRANSF 3 2 FIRE SYS TRBL INDICATED CONDITION: LOSS OF POWER TO CIRCUIT, ISOLATION VALVE NOT OPEN. OR CIRCUIT TROUBLE REDUNDANT INDICATION WHICH WILL VERIFY ALARM OPERATOR ACTION FOR A VALID ALARM INVESTIGATE AREA FOR TAMPERING DISCUSSION:

REFERENCES:

DWG 208-031 FS-6 SENSING ELEMENT: K-2, K-5 i

O AR-801 Rev. 9 Page 30

FIRE SYSTEM ANNUNCIATOR RESPONSE FS-03 03 FS 03-03 mN.

m_m MN TRANSF 3 3 FIRE SYS TR8L INDICATED CONDITION: LOSS OF POWER TO CIRCUIT, ISOLATION VALVE NOT OPEN, OR CIRCUIT TROUBLE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

O OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPERING DISCUSSION:

REFERENCES:

DWG 208-031 FS-07 SENSING ELEMENT: K-2, K-5 O

AR-801 Rev. 9 Page 31

~. _ _ _ _. _ _. _

6 FIRE SYSTEM ANNUNCIATOR RESPONSE FS-03-04 FS-03 04

+ Gubu UNIT TRANSF 3 FIRE SYS TRSL INDICATED CONDITION:

UNIT AUX TRANSFORMER DELUCE VALVE (FSV-72), LOSS OF POWER TO CIRCUIT ISOLATION VALVE NOT OPEN, OR CIRCUIT TROUBLE REDUNDANT INDICATION WHICH WILL VERIFY ALARM OPERATOR ACTION FOR A VALID ALARM: INVESTICATE AREA FOR TAMPERING DISCUSSION:

REFERENCES:

DWC 208 031 FS-08 SENSING ELEMENT: K-2, K-5 O

AR-801 Rev. 9 Page 32

_.. _. _ _ _ _ _ _. _ _ -. _ _., _. -. -.~.. - _ _ _... -. - - -. _, _. -,..._...._-

d J

1 FIRE SYSTEM ANNUNCIATOR RESPONSE FS-03-05 FS-03-05 11M

~

STRT UP TRAN 3 FIRE SYS TR8L INDICATED CONDITION: LOSS OF POWER TO CIRCUIT ISOLATION VALVE NOT OPEN, OR l

CIRCUIT TROUBLE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTION FOR A VALID ALARM: INVESTICATE AREA FOR TAMPERING DISCUSSION:

REFERENCES:

DWG 208-031 FS-09 SENSING ELEMENT: K-2, K-5 1

N h

4 I

i AR-801 Rev. 9 Page 33

...-n~a.~.+-m-ar--,am-

---nue-s..s--sw...ar-m,.-+wa s+

a-~ ea--mmm v i

1 l

l FIRE SYSTEM ANNUNCIATOR RESPONSE FS-03-06 FS-03-06 i

i 1

i i

j WATER CURTAIN TROUBLE 1

j 1

3 s

l i

i i

INDICATED CONDITION: LOSS OF POWER TO CIRCUIT, ISOLATION VALVE NOT OPEN, OR

{

CIRCUIT TR008LE i

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

i OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPERING OISCUSSION:

REFERENCES:

DWG 208-031 FS-22 SENSING ELEMENT: K-2 K-5 O

'AR-801 Rev. 9 Page 34

FIRE SYSTEM ANNUNCIATOR RESPONSE FS 03-07 FS-03 07 l

TURB LUBE OIL FIRE SYS TRBL INDICATED CONDITION:

CIRCUIT TROUBLE LOSS OF PCMER TO CIRCUIT, ISOLATION VALVE NOT OPEN. OR REDUNDANT INDICATION WHICH WILL VEPIFY ALARM OPERATOR ACTION FOR A VALID ALARM: INVESTICATE AREA FOR TAMPER DISCUSSION:

REFERENCES:

DWG 208-031 FS-10 SENSING ELEMENT: K-2, K-5 O

AR-801 Rev. 9 Page 35

i l

1 j

FIRE SYSTEM ANNUNCIATOR RESPONSE FS 03-08 FS-03-08 i

l

\\

t FEEDWTR PUMP FIRE SYS TRat l

)

INDICATED CONDITION:

CIRCUIT TROUBLE LOSS OF POWER TO CIRCUIT. ISOLATION VALVE NOT OPEN, OR REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

]O

~

OPERATOR ACTION FOR A VALID ALARMt INVESTICATE AREA FOR TAMPERI j

DISCUSSION:

i

REFERENCES:

DWG 208-031 FS-10 i

SENSING ELEMENT: K-2, K-5 l

i l

i.

iO 4

AR-801 Rev. 9 Page 36

-....,,--...,_.c,,

,-.m.

..,,.---.-,-_,,,._-,,--,_,_-.,-r

_-,_,-.-,,-c.-_,--

'h)

FIRE SYSTEM ANNUNCIATOR RESPONSE FS 03-09 FS-03 09 H2 SEAL OIL FIRE SYS TRBL INDICATED CONDITION:

CIRCUIT TROUBLE LOSS OF POWER TO CIRCUIT, ISOLATION VALVE NOT OPEN, OR REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

l')

O OPERATOR ACTION FOR A VALID ALARM: INVESTICATE AREA FOR TAMP DISCUSSION:

REFERENCES:

DWG 208-031 75-12 SENSING ELEMENT: K-2, K-5 rT N,)

AR-801 Rev. 9 Page 37

'x) i FIRE SYSTEM ANNUNCIATOR RESPONSE FS-03-10 FS-03-10 B/U ES XFMR TRBL INDICATED CONDITION: LOSS OF POWER TO CIRCUIT ISOLATION VALVE NOT OPEN. OR CIRCUIT TROUBLE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

/^T OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPERING DISCUSSION:

REFERENCES:

DWG 208 031 FS-22 SENSING ELEMENT: FSCP-4

(-

V AR-801 Rev. 9 Page 38

O-FIRE SYSTEM ANNUNCIATOR RESPONSE FS-03-11 FS-03 11 l

l l

FIRE PUMP HSE SPRINKLER ACT i

l l

i INDICATED CONDITION: FIRE PUMP HOUSE SPRINKLER SYSTEM ACTUATED 210 REDUNDANT INDICATION WHICH WILL VERIFY ALARMt OPERATOR ACTION FOR A VALID ALARMI CHECK INDICATED AREA FOR FIRE DISCUSSION

REFERENCES:

DWG 208-031 FS-21 SENSING LLEMENT FS-17-PS l'

LO i

.AR-801 Rev. 9 Page 39

FIRE SYSTEM ANNUNCIATOR RESPONSE FS-03-12 FS-03-12 RB MAINT BLD SPRINKLER ACT

~~

EZ 2

~

INDICATED CONDITION:

MAINTENANCE SUPPORT 8LOGFIRE SPRINKLER SYSTEM HAS ACTUA REDUNDANT INDICATION WHICH WILL VERIFY ALARM SPRINKLE TO >30 P!IG OPERATOR ACTION FOR A VALID ALARM: CHECK RBMSB FOR FIRE DISCUSSION:

REFERENCES:

SS 211-031 FS-02 SENSING ELEMENT: FS-508-PS2 O

AR-801 Rev. 9 Page 40

i FIRE SYSTEM ANNUNCIATOR RESPONSE FS 03-13 FS 03-13 l

TUR8 BLOG BEL l

119' 8PM ACT INDICATED CONDITION: SPRINKLER SYSTEM BELOW TUR8 BLOG 119' ELEVATION ACTUATED 110 PSIG REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTION FOR A VALID ALARM AP-880 (FP)

CHECK INDICATED AREA FOR FIRE. REFER TO DISCUSSION:

REFERENCES:

DWG 208-031 FS-21 SENSING ELEMENT: FS-24-PS i

~)

AR-801 Rev. 9 Page 41

FIRE SYSTEM ANNUNCIATOR RESPONSE FS-03-14 FS-03-14 TURB BLDG BEL 119' SPR ACT INDICATED CONDITION: SPRINKLER SYSTEM BELOW TURB BLDG 119' ELEVATIO ACTUATED 210 PSIG REDUNDANT INDICATION WHICH WILL VERIFY ALARM OPERATOR ACTION FOR A VALID ALARM:

AP-880 (FP)

CHECK INDICATED AREA FOR FIRE. REFER TO DISCUSSION:

REFERENCES:

DWG 208-031 FS-21 SENSING ELEMENT: FS-25-PS O

AR-801 Rev. 9 Page 42

i i

l

]

FIRE SYSTEM ANNUNCIATOR RESPONSE FS-03-15 FS-03-15 h

OUTAGE SUPP i

BLDO FIRE i

i I

r INDICATED CONDITION: FIRE OR INSTRUMENT FAILURE IN OUTAG: SUPPO i

l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

1 i

OPERATOR ACTION FOR A VALID ALARM:

{

AP-880 (FP)

CHECK INDICATED AREA FOR FIRE. REFER TO i

DISCUSSION:

REFERENCES:

DWG 211-031 FS-076 i

j SENSING ELEMENT: FS-472-FS i

i I

i i

1 s

!O i

j AR-801 Rev. 9 Page 43 i

,-,n.-,,n-,

--,,-,,-n n~.

,,,,,--,n,,-

..,-,.,-,,,.---n.,,

FIRE SYSTEM ANNUNCIATOR RESPONSE FS-04-01 FS-04 01

==

v=

MAIN TRANSF 31 FIRE INDICAiED CONDITION: DELUGE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA. REFER TO AP-880 (FP)

DISCUSSION:

REFERENCES:

DWG 208-031 FS-05 SENSING ELEMENT: K-4 AR-801 Rev 9 Page 44

l i

FIRE SYSTEM ANNUNCIATOR RESPONSE FS-04-02 FS 04-02

==

l MAIN TRANSF 3 2 FIRE INDICATED CONDITION: DELUGE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA. REFER TO AP-880 (FP)

DISCUSSION:

REFERENCES:

DWC 208-031 FS 06 SENSING ELEMENT: K-4 O

AR-801 Rev. 9 Page 45

1 O

FIRE SYSTEM ANNUNCIATOR RESPONSE FS-04-03 FS-04-03 MAIN TRANSF 3 3 FIRE INDICATED-CONDITION:

DELUCE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY

m.

REDUNDANT INDICATION WHICH WIQ l'ERIFY ALARM:

O-OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA. REFER TO AP-880 (FP)

DISCUSSION:

REFERENCES:

DWG 208-031 FS-07 SENSING ELEMENT: K-4 AR-801 Rev. 9 Page 46

i I

b-1 FIRE SYSTEM ANNUNCIATOR RESPONSE FS-04-04 FS-04-04 4

i e

i UNIT TRANSF i.

3 FIRE i

j INDICATED CONDITION: DELUCE VALVE SHOL'LD BE OPEN, OR HAS BEEN OPENED LOCALLY REDUNDANT INDICATION WHICH WILL VERIFY ALARM O

OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA. REFER TO AP-880 (FP)

DISCUSSION:

REFERENCES:

DWG 208-031 FS-08 SENSING ELEMENT: K-4 O

AR-801 Rev. 9 Page 47

.. - - - - - - - ~ ~ ~ - -

FIRE SYSTEM ANNUNCIATOR RESPONSE FS-04-05 FS-04-05 STARTUP TRANSF 3 FIRE INDICATED CONDITION: DELUCE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

O OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA. REFER TO AP-880 (FP)

DISCUSSION:

REFERENCES:

DWG 208-031 FS-09 SENSING ELEMENT: K-4 O

AR-801 Rev. 9 Page 48

. - ~

_ _ _ _ _ _ _ _ _ _ _ _ _. _ _ _ ~. _ _ _ _.. _ _ _ _ _... _ _.. _ _... _... _ _. _ _ _

~ _ _. _. _ _

i.

a 5

l l

FIRE SYSTEM ANN 4NCIATOR RESPONSE FS-04-06 FS-04-06 l

4 ZZZ ZZ WATER CURTAIN j

~~

FIHE l

i

}

j INDICATED CONDITION:

DELUGE VALVE SHOULD BE OPEN, OR i;AS BEEN OPENED LOCALLY REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

J OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA, REFER TO AF-880 (FP) 1 DISCUSSION:

REFEREh; i.S: DWG 208-031 FS-22 i

SENSING ELEMENT: K-4 4

)

i-i i

i OV AR-801 Rev. 9 Page 49

(

$ O b

FIRE SYSTEM ANNUNCIATOR RESPONSE-FS-04-07 c5 04-07 i-i TURB LUBE OIL

--~

E SYSTEM FIRE INDICATED CONDITION: DELUCE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

O-OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA. REFER TO AP-880 (FP)

DISCUSSION:

REFERENCES:

DWG 208-031 FS-10 SENSING ELEMENT: K-4 O

AR-801 Rev. 9 Page 50

.. _. - - -.-.~ -

..--- -.. - _-. ~..--. -

FIRE SYSTEM ANNUNCIATOR RESPONSE FS-04-08 FS-04-08 l

FEEDWTR PUMP CONSOLE FIRE J

I INDICATED CONDITION:

I DELUGE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY i- '

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

i OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA. REFER TO AP-880 (FP) l DISCUSSION:

4

REFERENCES:

DWG 208-031 FS-11 1

SENSING ELEMENT: K-4 AR-801 Rev. 9 Page 51

i I

FIRE SYSTEM ANNUNCIATOR RESPONSE FS-04-09 FS 4-09 l

H2 $EAL OIL UNIT FIRE INDICATED CONDITION:

DELUGE VALYS SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

Ogg OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA. REFER TO AP-880 (FP)

DISCUSSION:

REFERENCES:

OWG 208-031 FS-12 SENSING ELEMENT: K-4 O

AR-801 Rev. 9 Page 32

FIRE SYSTEM ANNUNCIATOR RESPONSE FS-04-10 FS-04-10 B/U ES XFMR FIRE 2

ZMZZ INDICATED CONDITION:

DELUCE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY REDUNDANT INDICATION WHICH W1LL VERIFY ALARM:

O OPER,* TOP ACTION FOR A VALID ALARM: CHECK INDICATED AREA. REFER TO AP-880 (EP)

DISCUSSION:

REFERENCES:

DWG 208-040 MT-140 SENSING ELEMENT: FSCP-4 s

AR-801 Rev. 9 Page 53

___._._______.____m___

FIRE SYSTEM ANNUNCIATOR RESPONSE FS-04-11 FS-04,

J j

i TURB BLDG BEL j

145' SPR ACT l

i e

i INDICATED CONDITION: TURB BLDG BELOW 145' ELEVATION SPRINKLER SYSTEM ACTUATION 210 PSIG REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA. REFER TO AP-880 (FP)

DISCUSSION:

REFERENCES:

DWG 208-031 FS-21 SENSING ELEMENT: FS-26-FS O

AR-801 Rev. 9 Page 54 L - -- ----

FIRE SYSTEM ANNUNCIATOR RESPONSE FS-04-12 FS-04-12 TURB BLDG BEL 145' SPR ACT INDICATED CONDITION: TURB BLDG BELOW 145' ELEVATION SPRINKLER SYSTEM ACTUATION 210 c3IC REDUNDANT INDICATION WHICH hit.L VERIFY ALARM:

OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA. REFER TO AP-880 (FP)

DISCUSSION:

REFERENCES:

DWG 208-031 FS-21 SENSING ELEf4ENT: FS-27-FS O

AR-801 Rev. 9 Page 55

. -. ~. -.

4 FIRE SYSTEM ANNUNCIATOR RESPONSE FS-04-13 FS-04-13 CONT COMP BEL 108' SPR ACT INDICATED CONDITION: CONTROL COMPLEX BELOW 108' ELEVATION SPRINKLE ACTUATION 210 PSIG REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTION FOR A VALID ALARM: CHECK INDICATED AREA. REFER TO AP-880 (FP)

DISCUSSION:

REFERENCES:

DWG 208-031 FS-21 SENSING ELEMENT: FS-33-FS

~

O AR-801 Rev. 9 Page 56

_=

t FIRE SYSTEM ANNUNCIATOR RESPONSE FS-05-Oi FS-05-01 l

CHARCOAL FLTR AHFL 1 TRBL INDICATED CONDITION: PURGE EXHAUST CHARCOAL FILTER DELUCE SYSTEM LOS POWER, ISOLATION VALVE NOT OPEN, OR CIRCUIT TROUBLE 8

INDANT INDICATION WHICH WILL VERIFY ALARM:

'vr>ERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMP DISCUSSION:

REFERENCES:

DWG 208-031 FS-24, FS-13 SENSING ELEMENT: K-2, K-5 O

AR-801 Rev. 9 Page 57

=.

FIRE SYSTEM ANNUNCIATOR RESPONSE FS-05-02 FS-05-02 i

i-CHARCOAL FLTR AHFL 2A TRBL

,t I

i i

1 i

i INDICATED CONDITION: AUX BLOG MAIN EXHAUST CHARCOAL FILTER DELUGE SYSTEM LOSS OF POWER, ISOLATION VALVE NOT OPEN, OR CIRCUIT TROUBLE 1

)

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

O' OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPERING d

DISCUSSION:

1

REFERENCES:

DWG 208-031 FS-25, FS-14 SENSING ELEMENT: K-2, K-5 O

AR-801 Rev. 9 Page 58

FIRE SYSTEM ANNUNCIATOR RESPONSE FS-05-03 FS-05-03 4

j CHARCOAL FLTR AHFL 28 TRBL 4

i i

1 4

4 4

INDICATED CONDITION: AUX BLDG MAIN EXHAUST CHARCOAL FILTER DELUC LOSS OF POWER, ISOLATION VALVE NOT OPEN, OR CIRCUIT TROUBLE i

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

\\

j OPERATOR ACTION FOR A VALID ALARM: INVESTICATE AREA FOR TAMPERING DISCUSSION:

REFERENCES:

DWG 208-031 FS-15 SENSING ELEMENT: K-2, K-5 O

AR-801 Rev. 9 Page 59

_.. _. _. _ _. ~.. _. _. _ _ _. _ _. _ _. _ _ _ _. _.. _ _ _ -.. _. _ _. ~ _ _ -. _ _ _ _ _. _ _ _ _ _.. _.

I i

FIRE SYSTEM ANNUNCIATOR RESPONSE FS-05-04 FS-05-04 CHARCOAL FLYR AHFL 2C TRBL INDICATED CONDITION: AUX BLDG MAIN EXHAUST CHARCOAL FILTER DELUGE SYSTEM LOSS OF POWER, ISOLATION VALVE NOT OPEN, OR CIRCUIT TROUBLE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPER DISCUSSION:

REFERENCES:

DWG 208-031 FS-16 SENSING ELEMENT: K-2, K-5 O

AR-801 Rev. 9 Page 60

m_

4

'O FIRE SYSTEM ANNUNCIATOR RESPONSE FS-05-05 FS-05-05 i

i CHARCOAL FLTR

~

AHFL 2D TRBL t

4 i

i INDICATED CONDITION: AUX BLDG MAIN EXtlAUST CHARCOAt. FILTER DELUGE LOSS OF POWER, ISOLATION VALVE NOT UPEN, OR CIRCUIT TROUBLE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPERING DISCUSSION:

i

REFERENCES:

DWG 208-031 FS-17 4

i SENSING ELEMENT: K-2, K-5 i

e J

V AR-801 Rev. 9 Page 61

4 FIRE SYSTEM ANNUNCIATOR RESPONSE FS-05-06 FS-05-06 l

ZZZZ Z

CHARCOAL FLTR AHFL-4A TRBL INDICATED CONDITION: CTRL COMPLEX EMERGENCY CHARCOAL FILTER DELUGE LOSS OF POWER, ISOLATION VALVE NOT OPEN, OR CIRCUIT TROUBLE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

'l OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOP, TAMPERING DISCUSSION:

REFERENCES:

DWG 208-031 FS-18 SENSING ELEMENT: K-2, K-5 O

AR-801 Rev, 9 Page 62

FIRE SYSTEM ANNUNCIATOR RESPONSE FS-05-07 FS-05-07

?

CHARCOAL FLTR AHFL-4B TRBL t

INDICATED CONDITION:

LOSS OF POWER, ISOLATION VALVE NOT OPEN, OR CIRCUIT TROUBLECT REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

O OPERATOR ACTION FOR A VALID ALARM: INVESTICATE AREA FOR TAMPERING DISCUSSION:

REFERENCES:

DWG 208-031 FS-19 SENSING _ ELEMENT: K-2, K-5 O

AR-801 Rev. 9 Page 63 Y

FIRE SYSTEM ANNUNCIATOR RESPONSE FS-05-08 FS-05-08 CHARCOAL FLTR AHFL 15 TRBL INDICATED CONDITION: NUCLEAR SAMPLE ROOM CHARC0AL FILTER DELUGE S OF POWER, ISOLATION VALVE NOT OPEN, OR CIRCUIT TROUBLE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE AREA FOR TAMPERING DISCUSSION:

REFERENCES:

DWC 208-031 FS-20 SENSING ELEMENT: K-2, K-5 AV AR-801 Rev. 9 Page 64

. - ~.. _. _.. _.. _ _.. _.._

i 1

=

FIRE SYSTEM ANNUNCIATOR RESPONSE FS-05-09 FS-05-09 l

ADMIN BLDG WAREHOUSE FIRE INDICATED CONDITION: FIRE OR INSTRUMENT FAILURE IN WAREHOUSE OR ADMIN REDUNDANT INDICATION WHICH WILL VERIFY ALARM OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA DISCUSSION:

REFERENCES:

SENSING ELEMENT:

O

\\j-AR-801 Rev. 9 Page 65

_ _. _. _. _ _ _. _ _ _ _ _ _ _. _ _. _ _ _. _ _ _ _ ~ _.. -. _. _ _ _ _. _. _. _. _.... _

1 FIRE SYSTEM ANNUNCIATOR RESPONSE FS-05-10 FS-05-10 5

4 i

OFFICE BLDG TROUBLE / FIRE k.

i i

4 INDICATED CONDITION: RUSTY BUILDING FIRE OR INSTRUMENT FAILURE i

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

J OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA i

DISCUSSION:

3

REFERENCES:

DWG 208-031 FS-21 SENSING ELEMENT: ZONE 1-3' ALARM i

4 i

I t

O l

AR-801 Rev. 9 Page 66 E

4 FIRE SYSTEM ANNUNCIATOR RESPONSE FS-05-11 FS-05-11 CONTROL BLDG TROUBLE / FIRE INDICATED CONDITION: FIRE OR INSTRUMENT FAILURE IN CONTROL BLOG REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTION FOR A VALID ALARM:

INSPECT AREA REFER TO AP-880 (FP)

DISCUSSION:

REFERENCES:

DWG 208-031 FS-21 SENSING ELEMENT: ZONE 4-11 ALARM (D

V AR-801 Rev. 9 Page 67

. ~

1 i

l l

D l

G FIRE SYSTEM ANNUNCIATOR RESPONSE FS- 05 -l'2 FS-05-12 i

i l

SWITCH GEAR RM TROUBLE / FIRE INDICATED CONDITION: FIRE OR INSTRUMENT FAILtlRe IN SWITCHGEAR ROOM REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTION FOR A VALID ALARM:

INSPECT AREA. REFER TO AP-880 (FP)

DISCUSSION:

REFERENCES:

DWG 208-031 FS-21 SENSING ELEMENT: ZONE 12-13 ALARM O

AR-801 Rev. 9 Page 68

_-_._._._.m FIRE SYSTEM ANNUNCIATOR RESPONSE FS-05-13 FS-05-13 I

4 FIRE PROT TROUBLE j

4

-~_

j i

J INDICATED CONDITION: FIRE PROTECTION TROUBLE PLANT OR OFFICE AREA C REDUNDANT INDICATION WHICH WILL VERIFY ALARM: ALARM PANELS LOCATE ELEV. CONTROL COMPLEX AND 1st FLOOR OF RUSTY BLDC IN TELEPHONE ROOM qV OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA l

DISCUSSION: THIS ALARM MAY COME IN WHEN THE HALON PROTECTION SYSTEM IS PLACED IN " TEST"

REFERENCES:

DWG 208-031 FS-21 SENSING ELEMENT: PLANT AREA CAB, OFFICE AREA CAB O

AR-801 Kev. 9 Page 69

6 l

FIRE SYSTEM ANNUNCIATOR RESPONSE FS-05-14 FS-05-14 EMER DSL GEN ROOM TROUBLE INDICATED CONDITION: LOSS OF POWER OR CIRCUIT FAILURE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA.

DISCUSSION:

REFERENCES:

DWG 208-031 FS-23 SENSING ELEMENT: OR, RSR, TSR O

AR-801 Rev. 9 Page 70

FIRE SYSTEM ANNUNCIATOR RESPONSE FS-05-15 FS-05-15 EMER DSL GEN ROOM FIRE

-~~~

E2 INDICATED C.,ht,ITION:

ONE OF TWENTY SENSORS HAS ACTUATED. FSV-101 SHOUL OPEN.

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

O OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA DISCUSSION:

REFERENCES:

DWG 208-031 FS-23 SENSING ELEMENT: OR AR-801 Rev. 9 Page 71

___....__.._______.._____.._._____.___.__.-._._..._._._.._.__...m__

FIRE SYSTEM ANNUNCIATOR RESPONSE FS-06-01 FS-06-01

==

t CHARCOAL FLTR AHFL 1 FIRE 1

e i

i

i 1

l INTICATED CONDITION:

DELUGE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY l.

j REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

'e

[

. OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA. REFER T t

DISCUSSION:

i

REFERENCES:

DWG 208-031 FS-24. FS-13 3

3, SENSING ELEMENT: K-4 i

4 l

l i

1 a

s i O AR-801 Rev. 9 Page 72

.. -.. _ _ _ _ _. -.. _ _ _ _ _. - ~. - - _ _ _ _ _ _. _ _ _ _.

4 1

1

- Oh FIRE SYSTEM ANNUNCIATOR RESPONSE FS-06-02 FS-06-02 l

CHARCOAL FLTR AHFL 2A FIRE INDICATED CONDITION: DELUCE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA. REFER T0-AP-880 DISCUSSION:

REFERENCES:

DWG 208-031 FS-25, FS-14 SENSING ELEMENT: K-4 O

AR-801 Rev. 9 Page 73

.... _ -. -. _ - - -. ~ _,. -

Q FIRE SYSTEM ANNUNCIATOR RESPONSE FS-06-03 FS-06-03

~

ZZZZE CHARCOAL FLTR AHFL 28 FIRE a

i

)

l 4

1 INDICATED CONDITION: DELUGE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTION FOR A VALID ALARM: 7NSPECT AREA. REFER TO AP DISCUSSION:

i

REFERENCES:

DWG 208-031 FS-15 SENSING ELEMENT: K-4 O

AR-801 Rev. 9 Page 74

0 d

"k FIRE SYSTEM ANNUNCIATOR RESPONSE FS-06-04 FS-06-04 CHARCOAL FLTR l

AHFL 2C FIRE 1

a 4

i i

INDICATED CONDITION: DELUCE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA, REFER TO AP-880 (FP)

DISCUSSION:

REFERENCES:

DWC 208-031 FS-16 1

SENSING ELEMENT: K-4 i

i i

'O 1

i AR-801 Rev. 9 Page 75

1 FIRE SYSTEM ANNUNCIATOR RESPONSE FS-06-05 FS-06-05 i

CHARCOAL FLTR AHFL 2D FIRE l

a-INDICATED CONDITION:

DELUGE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA, REFER TO AP-880 (FP)

DISCUSSION:

REFERENCES:

DWG 208-031 FS-17 SENSING ELEMENT: K-4 O

d AR-801 Rev. 9 Page 76

O FIPF SYSTEM ANNUNCIATOR RESPONSE FS 06-06 FS-06-06 1

ZZZ_-

M CHARCOAL FLTR AHFL-4A FIRE INDICATED CONDITION: DELUGE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY REDUNDANT 01 CATION WHICH WILL VERIFY ALARMt OPERATOR At.ON FOR A VALID ALARMt INSPECT AREA, REFER TO AP-880 (FP)

DISCUSSION:

REFERENCES:

DWG 208-031 FS-18 SENSING ELEMENT: K-4 O

AR-801 Rev. 9 Page 77

4 4

FIRE SYSTEM ANNUNCIATOR RESPONSE FS-06-07 FS-06-07 I

6 C'[RCOAL FLTR AHPL 4B :'IME

,i 1

l

.I INDICATED CONDITION: DELUCE VALVE SHOULD BF. OPEN. OR HAS BEEN OPENE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA. REFER TO AP-880 j

DISCUSSION:

l

REFERENCES:

DWG 208-031 FS-19 SENSING ELEMENT: K-4 j

1 i

l l

l

O e

4 -

AR-801 Rev 9 Page 78

FIRE SYSTEM ANNUNCIATOR RESPONSE FS-06-08 FS 06-08 CHARCOAL FLTR l

AHFL 15 FIRE

-m.

INDICATED CONDITION: DELUGE VALVE SHOULD BE OPEN, OR HAS BEEN OPEAED LOCALLY REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTION FOR A VALID ALARMr INSPECT AREA. REFER TO DISCUSSION:

REFERENCES:

DWG 208-031 FS-20 SENSING ELEMENT: K-4 O

AR-801 Rev. 9 Page 79

O FIRE SYSTE" ANNbNC1/iTOR RESPONSE FS-06-09 FS-06-09 1

TSC l

l TROUBLE l

INDICATED CONDITION: ALARM AT PYROTRONICS PANEL

'a Q

F.EDUNDANT INDICATION WHICH WILL VERIFY ALARM:

NM (h

OPERATOR ACTION FOR A VALID ALARM: INVESTICATE TSC FIRE SYSTEM OISCUSSION:

REFFRENCES: D4 209-031 FS-39 SENSING ELEMENT: TSC FIRE PROTECTION CONTF,0L PANEL F

O AR-801 Rev. 9 Page 80

J 4

FIRE SYSTEM ANNUNCIATOR RESPONSE FS-06-10 FS-06-10

)

T,.

TSC FIRE INDICATED CONDITION: FIRE OR INSTRUMENT FAILURE IN TSC REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTION FOR A VALID ALARM: INVESTICATE TSC AREA DISCUSSION:

REFERENCES:

DWG 209-031 FS-39 SENSING ELEMENT: TSC FIRE PROTECTION CONTROL PANEL O

AR-801 Rev. 9 Page 81

FIRE SYSTEM ANNUNCIATOR RESPONSE FS-06-11 FS-06-11 TSC FILTER AHFL 20 TROUBLE INDICATED CONDITION: ALARM AT LOCAL PANEL REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTION FOR A VALID ALARM: INVESTICATE TSC FILTER ROOM DISCUSSION:

REFERENCES:

DWC 209-031 FS-39 SENSING ELEMENT: T5C FIRE PROTECTION CONTROL PANEL O

AR-801 Rev, 9 Page 82

1 i

1 i

FIRE SYSTEM ANNUNCIATOR RESPONSE FS-06-12 FS-06-12 J

1 2

i i-l a

i, TSC FILTER AHFL 20 FIRE

)

I i

i i

l l

INDICATED CONDITION: FIRE OR INSTRUMENT FAILURE IN AHFL-20 1

REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

i OPERATOR ACTION FOR A VALID ALARM: INVESTIGATE TSC FILTER ROOM DISCUSSION:

REFERENCES:

209-031 FS-39 SENSING ELEMENT: TSC FIRE PROTECTION CONTROL PANEL i

O AR-801 Rev. 9 Page 83

FIRE SYSTEM ANNUNCIATOR RESFONSE FS-06-13 FS-06-13 RECORD STORE VAULT FIRE INDICATED CONDITION: WATER FLOW INTO RECORD VAULT SPRINKLER SYSTEM REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

O-OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA FOR FIRE.

NOTIFY ADMINISTRATIVE SUPERVISOR.

DISCUSSION:

REFERENCES:

DWG 208-031 FS-21 SENSING ELEMENT: FS-70-FI O

AR-801 Rev. 9 Page 84

FIRE SYSTEM AtJNUNCIATOR RESPONSE FS-06-14 FS-06-14 CONT COMPLEX FIRE INDICATED CONDITION: DELUCE VALVE SHOULD BE OPEN, OR HAS BEEN OPENED LOCALLY REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTION FOR A VALID ALARM: INSPECT AREA. REFER TO A DISCUSSION:

REFERENCES:

DWG 208-031 FS-24 SENSING ELEMENT: K-4 AR-801 Rev. 9 Page 85

e P

FIRE SYSTEM ANNUNCIATOR RESPONSE FS 06-15 FS-06 CONT COMPLEX FIRE SYS TRBL i

INDICATED CONDITION:

LOSS OF POWER TO CIRCUIT, ISOLATION VALVE NOT OPEN, OR CIRCUIT TROUBLE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

OPERATOR ACTION FOR A VALIO ALARM: INVESTICATE AREA FOR TAMPERING.

IN 'ESTIGATE LOSS OF CONTINUITY IN HALON SYSTEM FIRING CIRCUIT.

DISCUSSION:

REFERENCES:

DdG 208 031 FS-24 SENSING ELEMENT: K-5, K-2 O

AR-801 Rev. 9 Page 86 (LAST PAGE)