l (MC) Rev. 5 Effective Date IV I I INFORMATION ONLY ANNUNCIATOR RESPONSE AR-954 FLORIDA POWER CORPORATION CRYSTAL RIVER UNIT 3 WDD ANNUNCIATOR RESPONSE t

l APPROVED BY:

Interpretation Contact

_? bd S b - b r /)?/ ?

(SIGNATURE ON FILE)'

DATE:

_/0/7/97 0

II

't/

INTERPRETATION CONTACT:

Supervisor, Nuclear Operations Administrative Shift DOh 050 DR 302 F

PDR-

l IARLE OF CONTENTS SECTION PEE 1.0 PURP05E.................................................................

1 2.0 REEERENCES..............................................................

1 2.1 IMELEENHNG REEERENCES...............................

2. 2 DEVELOPMLNTAL REEERENCES......................................

.............. 1 L0 PERSONNE L INDOCIRINATION................................................ 1 4. 0 I N51BQCHQNS............................................................ 1 M LLOW-UP ACTION 5.......................................................

1 ENCLO5URES 1

Ann u n c i a t or R e s pon s e................................................ 2 k

AR-954-Rev. 5 Page i

I 1.0 PU E SE O

1.1 Establish a reference document for each Annunciator Window on the WD-WR Panel Lampbox.

1.2 Establish operator actions for valid Annunciator alarms on the WD-WR Panel Lampbox.

1.3 Establish a reference to other procedures which address operator actions for valid Annunciator alarms on the WD-WR Panel Lampbox.

LO REEERENCES 2.1 IMP _LEMENIING REFERENCES 2.1.1 OP-415, Waste Disposal Evaporators 2.2 QEYELOP_ MENTAL REFERENCES 2.2.1 INPO 90-021, Good Practica OP-217, Alarm Response Procedures 2.2.2 Annunciator Window Engraving Drawing E-224-050, 3.O PERSONNEL _INQQCIRINAT10N None 4.0 INSTRUCIIONS 4.1 Respond to alarms on the WD-WR Panel Lampbox as indicated on, Annunciator Response.

5.0 FOLLOW-UP ACTIONS None O

AR-954 Rev. 5 Page 1

i MCL0lVEL1 (Page 1 of 15)

RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WR-1-2 D-1-2 NEUTRAll2ER TANK MIXER TRIP INDICATED CONDITION:

- MIXER (WDMX-1) TRIPPED OUT ON OVERLOAD REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

- MIXER RUN INDICATING LAMPS ON WD PANEL OPERATOR ACTION FOR A VALID ALARM:

. DETERMINE CAUSE OF OVERLOAD CONDITION O

DISCUSSION:

THE MIXER IS NO LONCER USED.

REFERENCES:

DWG 208-06D WD-31 SENSING ELEMENT: SWCR 49 CONTACTS OV AR-954 Rev. 5 Page 2

. ~. ~.

O EEL 0luRL1 (Page 2 of 15)

RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WR-1-3 0-1-3 WASTE GAS DECAY TK 3A PRESS HIGH l

INDICATED CONDITION:

- TANK PRESSURE >83 PSIG REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

- TANK PRESSURE INDICATOR ON WD PANEL OPERATOR ACTION FOR A VALID ALARMt

- ASSOCIATED WASTE GAS DECAY TANK IS FULL. LINEUP TO TANK WITH <80 PSIG IN IT.

DISCUSSION:

CONSIDER REDUCING PRESSURE IN WASTE CAS DECAY TANK 3A BY USING RECYCLE VALVES PER OP-412A, WASTE CAS DISPOSAL SYSTEM.

REFERENCES:

DWG 208-060 WD-05 SENSING-ELEMENT: WD-204-PS2 O

AR-954 Rev. 5 Page 3

O fELOSilRL1 (Page 3 of 15)

RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WR-1-4 0-1-4 I

WASTE GAS DECAY TK 38 PRESS HIGH l

i l

INDICATED CONDITION:

- TANK PRESSURE >83 PSIG l

REDUNDANT INDICATION WHICH WILL VERIFY ALARM

- TANK PRESSURE INDICATOR ON WD PANEL OPERATOR ACTION FOR A VALID ALARM:

- ASSOCIATED WASTE-GAS DECAY TANK IS FULL. LINEUP TO TANK WITH <80 PSIG IN IT.-

DISCUSSION:

CONSIDER REDUCING PRESSURE IN WASTE CAS DECAY TANK 3B BY USING RECYCLE VALVES PER OP-412A, WASTE CAS DISPOSAL SYSTEM. CONSIDER GOING TO THE 'C' TANK AS THE 'A' TANK IS USED FOR SAMPLING.

REFERENCES:

DWG 208-060 WD-05 SENSING ELEMENT: WD-205-PS2 O

AR-954 Rev. 5 Page 4

O

[NCLOSURE 1 (Page 4 of 15)

RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD WR-1-5 D-1-5 WASTE GAS DECAY TK 3C PRESS HIGH INDICATED CONDITION:

- TANK PRESSURE >83 PSIG REDUNDANT INDICATION WHICH WILL VERIFY ALARM -

- TANK PRESSURE INDICATOR ON WD PANEL OPERATOR ACTION FOR A VALIO ALARM:

- ASSOCIATED WASTE GAS DECAY TANK IS FULL. LINEUP TO TANK WITH <80 PSIG IN IT.

DISCUSSION:

CONSIDER REDUCING PRESSURE IN WASTE GAS DECAY TANK 3C BY USING RECYCLE VALVES PER OP-412A, WASTE CAS DISPOSAL SYSTEM.

CONSIDER COING TO THE '8' TANK AS THE 'A' TANK IS USED FOR SAMPLING.

REFERENCES:

DWG 208-060 WD-05 SENSING ELEMENT: WD-206-PS2 O

AR-954 Rev. 5 Page 5

~- - ---- -.-._-.~. -.

O

[ELQSURE 1 (Page 5 of 15)

RADWASTE DISPOSAL ANNUNCIATOR RESPONit WD-WR-1-6 D-1-6 i

Ll0VID WASTE

--~~

DRUM FlLL LEVEL Hl0H INDICATED CONDITION:

- DRUM LEVEL >2.5' REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

- VALVE WDV-653 INDICATING LAMPS ON WASTE DROM PANEL OPERATOR ACTION FOR A VALID ALARM:

- ENSURE VALVE WDV-653 CLOSES

- CHECK FOR IMPROPER DRUM MIX

- CHECK FOR POSSIBLE HIGH FLOW RATE O

- CHECK FOR POSSIBLE LEAKING DRUM INLET MANIFOLD DISCUSSION:

THIS EQUIPMENT IS NO LONGER USED.

REFERENCES:

DWG 208-060 WD-127 SENSING ELEMENT: WD-142-LS O

AR-954 Rev. 5 Page 6

O LNCLOSURE 1 (Page 6 of 15)

RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WR-1-7 D-1-7 RC EVAP CONCENTRATOR LEVEL HIGH-INDICATED CONDITION:

- CONCENTRATOR LEVEL >20" REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

- RC EVAP FEED TANK PUMP WDP-16A/B INDICATING LAMPS ON WD PANEL OPERATOR ACTION FOR A VALID ALARM:

- ENSURE PUMP (WDP-16A/B) TRIPS

- SECURE RC EVAP COND COOLING WATER, STEAM SUPPLY, AND VACUUM PUMP DISCUSSION:

ALARM COULD BE DEFEATED PER OP-415

REFERENCES:

DWG 208-060 WD-143 SENSING ELEMENT: WD-174-LS I

O 1

V AR-954 Rev. 5 Page 7 M

BCL0iME_.1 (Pape 7 of 15)

RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD WR-1-8 D 1-8 RC EVAP FEED TANK LEVEL HIGH INDICATED CONDITION:

- TANK LEVEL >92%

REDUNDANT INDICATION WHICH WILL VERIFY ALARM

- TANK LEVEL INDICATION ON WD PANEL OPERATOR ACTION FOR A VALID ALARM:

- CHECK LINEUP FOR CAUSE OF ALARM

- IF LEVEL CONTINUES TO INCREASE OPEN DRAIN VALVE DISCUSSION:

ALARM COULD BE DEFEATED PER OP-415

REFERENCES:

DWG 208-060 WD-137 SENSING ELEMENT: WD-161-LS2 O

AR-954 Rev. 5 Page 8

O GCL0iEL1 (Page 8 of 15)

RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD WR-2-1 0-2-1 RC EVAP


~~

FEED TANK DENSITY HIGH INDICATED CONDITION

- FEED TANK SPECIFIC CRAVITY >1.2 REDUNDANT INDICATION WHICH WILL VERIFY ALARMt

- TANK DENSITY INDICATOR ON WD PANEL OPERATOR ACTION FOR A VALID ALARM

- DETERMINE CAUSE OF HICH DENSITY AND RESOLVE

- TRANSFER WATER TO CONC. WASTE STORACE TANK OR TO CONC. BORIC ACID STO TANK.

DISCUSSION:

ALARM COULD BE DEFEATED PER OP-415

REFERENCES:

-DWG 208 060 WD-137 SENSING ELEMENT WD-162 PSA

.n

. n - - ~_

O AR-954 Rev. $

Page 9

O ENCL 01URL1 (Page 9 of 15)

RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WR 2-2 0-2-2 RC EVAP DISTILLATE RESERVOIR LEVEL HIGH INDICATED CONDITION

- TANK LEVEL AT 30" REDUNDANT INDICATION WHICH WILL VERIFY ALARM

- RESERVOIR LEVEL INDICATOR ON WD PANEL OPERATOR ACTION FOR A VALID ALARMt

- SECURE STEAM SUPPLY AND COOLING WATER FLOW TO EVAPORATOR O

DISCUSSION:

ALARM COULD BE DEFEATED PER OP-415

REFERENCES:

DWC 208-060 WD-137 SENSING ELEMENT WD-160-LS1 O

AR-954 Rev. 5 Page 10

O UfCLOSURI_1 (Page 10 of 15)

RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WR-2-3 0-2-3 RC EVAP DISTILLATE CONDUCTIVITY Hl0H INDICATED CONDITION:

- DISTILLATE CONDUCTIVITY >2 pMHOS 1

REDUNDANT INDICATION WHICH WILL VERIFY ALARM

- DISTILLATE REJECT / DISCHARGE VALVE INDICATION ON WD PANEL

- DISTILLATE CONDUCTI'!ITY INDICATOR ON WD PANEL OPERATOR ACTION FOR A VALID ALARM:

- ENSURE AUTO ACTION INITIATED (SEE DISCUSSION)

O

- DETERMINE CAUSE OF ALARM AND RESOLVE

- CHECK FEED TANK CONCENTRATION AND FOR FOAMING IN TANK DISCUSSION:

THE AUTO ACTION WILL OPEN THE DISTILLATE REJECT VALVE (WDV-722)/(WDV-719) AND SHUT THE DISTILLATE DISCHARGE VALVE (WDV-721)/(WDV-720) IF RC DISTILLATE PUMP 3A (WDP-17A) OR 3B (WDP-178) IS RUNNING. THE AI ARM COULD BE DEFEATED PER OP-415.

REFERENCEst DWG 208-060 WD-143 SENSING t(EMENT: WD-159-CS O

AR-954 Rev 5 Page 11

O fELOSURL1 (Page 11 of 15)

RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WR-2-4 0-2-4 RC EVAP CONCENTRATOR VACUUM LOW INDICATED CONDITION:

- CONCENTRATOR VACUUM <15" HG REDUNDANT INDICATION WHICH WILL VERIFY ALARM

- CONCENTRATOR VACUUM INDICATOR ON WD PANEL OPERATOR ACTION FOR A VALID ALARM:

- CHECK SEAL WATER, VACUUM WATER SEPARATOR, AND STEAM SUPPLY, AND FOR POSSIBLE CODLING WATER FLUCTUATIONS.

DISCUSSION:

ALARM COULD BE DEFEATED PER OP-415

REFERENCES:

DWG 208-060 WD-143' SENSING ELEMENT: WD-164-PSA O

AR-954 Rev. 5 Page 12

i l

l O

GCLOSURE 1 (Page 12 of 15) l RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WR-2-5 D-2-5 MC EVAP FEED TANK LEVEL LOW INDICATED C0t.uITION

- TANK LEVEL <14" REDUNDANT INDICATION WHICH WILL VERIFY ALARMt

- TANK LEVEL INDICATOR ON WD PANEL OPERATOR ACTION FOR A VALID ALARM:

- DETERMINE REASON FOR LOW LEVEL BY CHECKING VALVE LINEUP AND RESTORE.

DISCUSSION:

ALARM COULD BE DEFEATED PER OP-415

REFERENCES:

DWG 208-060 WD-143 SENSING ELEMENT: WD-161-LS1 O

AR-954 Rev. 5 Page 13

1 i

l i

s ENCLOSURE 1

]

(Page 13 of 15) l RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WR-2-6 D-2-6 i

RC EVAP FEED TANK TEMP LOW INDICATED CONDITION:

- FEED TANK TEMPERATURE <150 DEG F REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

- FEED TANK HEATER INDICATING LAMPS (WDHE-2) ON WD PANEL

- FEED TANK TEMPERATURE INDICATOR ON WD PANEL 4

OPERATOR ACTION FOR A VALID ALARM:

- IF RC EVAPORATOR PACKAGE IS IN OPERATION:

O

- ENSURE FEED TANK LEVEL >29.2%

- MANUALLY CONTROL HEATERS IF DESIRED

- CHECK OUT OPERATION OF HEATER CONTROL CIRCUITRY DISCUSSION:

ALARM COULD BE DEFEATED PER OP-415

REFERENCES:

DWG 208 060 WD-50 SENSING ELEMENT: WD-163-TE O

AR-954 Rev. 5 Page 14

e 4

ENCLOSUE_1 (Page 14 of 15)

RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WR-2-7 D-2-7 i

RC EVAP DISTILLATE l

RESERVOIR I

LEVEL LOW INDICATED CONDITION:

- TANK LEVEL <10" REDUNDANT INDICATION WHICH WILL VERIFY ALARM:

- SELECTED RC EVAP DISTILLATE PUMP INDICATING LAMPS ON WD PANEL

- RESERVOIR LEVEL INDICATOR ON WD PANEL OPERATOR ACTION FOR A VALID ALARM:

- CHECK VALVE LINEUP, STEAM SUPPLY AND COOLING WATER

- ENSURE AUTO ACTION INITIATED (SEE DISCUSSION)

DISCUSSION:

THE AUTO ACTION TRIPS SELECTED RC EVAP DISTILLATE PUMP (WDP-17A/178).

ALARM COULD BE DEFEATED PER OP-415.

REFERENCES:

DWG 208-060 WD-143 4

SENSING ELEMENT: WD-160-LS3 g\\

I'R J AR-954 Rev. 5

(

Page 15 a

Y e

i MCLOSEL.1 (Page 15 of 15)

RADWASTE DISPOSAL ANNUNCIATOR RESPONSE WD-WR-2-5 D-2-8 i

I

~~

STOR NK TEMP HilLO l

INDICATED CONDITION:

l

- CONC BORIC ACID STORAGE TANK WDT-8A OR 88 TEMP >164 OR <152 DEG F REDUNDANT INDICATION WHICH WILL VERIFY ALARM

- STORACE TANK HEATER INDICATING LAMPS ON WD PANEL

- TANK TEMPERATURE INDICATOR ON WD PANEL OPERATOR ACTION FOR A VALID ALARM:

- INVESTIGATE HEATER CONTROL CIRCUITRY FOR MALFUNCTION.

i l

DISCUSSION:

)

ALARM COULD BE DEFEATED PER OP-415 4

REFERENCES:

DWG 208-060 WD-52 WD-53 1

SENSING ELEMENT: WD-80-TS, WD-83-TS m

i O

AR-954 Rev. 5 Page 16 (LAST PACE)