Proposed Tech Specs SR 3.3.7.3,replacing Analytical Limits Currently Specified as Acceptance Criteria with Allowable Values,Per Calculation E4C-098,change Notice 25
ML20210P597
Person / Time
Site: San Onofre  
Issue date: 08/11/1999
From:
SOUTHERN CALIFORNIA EDISON CO.
To:
Shared Package
ML20210P577 List:
References
NUDOCS 9908130038
Download: ML20210P597 (8)


Text

.

ATTACHMENT C PROPOSED TECHNICAL SPECIFICATION SURVEILLANCE REQUIREMENTS 3.3.7.3 AND 3.3.7.4 SAN ONOFRE UNIT 2 (REDLINE AND STRIKEOUT) l l

l l'

9908130038 990811 "

PDR ADOCK 05000361 P

pg L.

DG-Undervoltage Start 3.3.7 SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.3.7.1 Perform CHANNEL CHECK.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> SR 3.3.7.2 Perform CHANNEL FUNCTIONAL TEST.

24 months SR 3.3.7.3 Perform CHANNEL CALIBRATION with setpoint 24 months Allowable Values as follows:

a.

Degraded Voltage Function:c 4101 V and 1.A Dropout?2/41961V..,, -

% I d, ?...,-

,,,,z 11.

Pickupisf4281)

SDVSS (Sustained Degraded Grid Voltage

~

Signal):

Time delay:

1.

127D c 1.0 seccada and s M 2.17 seconds.

ii.

162D 2 00 seconds and s H B 128 seconds.

DGVSS (Degraded Grid Voltage with SIAS Signal):

Time delay:

i.

127D 2 M 1'.83 seconds and s M 2.17 seconds.

ii.

162S 2 4-144.'16 seconds and s 4:494'.44 seconds.

iii.162T 2' 0-650i88 seconds and s

~

4-651._62 seconds.

b.

Loss of Voltage Function 2 3554 V-end 1

s 3700 V Time delay: i 0.95 seconds and s 4-051.0 seconds at 0 V.

SR 3.3.7.4 Vcrify Response Tims of rcquired 00-LOV 24 mcaths on a channci is within 1.0; seccada.

STAGCERED TEST BASM SAN ON0FRE--UNIT 2 3.3-34 Amendment No. 127

i l

l l

ATTACHMENT D PROPOSED TEC11NICAL SPECIFICATION SURVEILLANCE REQUIREMENTS 3.3.7.3 AND 3.3.7.4 l

SAN ONOFRE UNIT 3 (REDLINE AND STRIKEOUT) i i

I l

l l

l l

l

DG-Undervoltage Start 3.3.7 SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.3.7.1 Perform CHANNEL CHECK.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> SR 3.3.7.2 Perform CHANNEL FUNCTIONAL TEST.

24 months SR 3.3.7.3 Perform CHANNEL CALIBRATION with setpoint 24 months Allowable Values as follows:

j DegradedVoltageFunction?2 4101 "

I a.

ond A.4 2 7 5 "....

l ii{ Dropout W;3196.(V i.

Pickup 4 4281 V, 1

SDVS5 (Sustained Degraded Grid Voltage Signal):

Time delay:

1.

1270 sM 2.17 seconds.

ii.

1620 m 00 seconds and s 4-30.128 seconds.

DGVSS (Degraded Grid Voltage with SIAS Signal):

Time delay:

i.

1270 2 -h61;83 seconds and s M 2.17 seconds ~

t 11.

162524rHN16secondsands 4:494.'44 seciihds.

iii.162T 2 h650.88 seconds and s

-h651.62 seconds.

b.

Loss of Voltage Function 2 3554 V-end a

s,~

Time delay:

0.95 seconds and-c s 4-051.0 seconds at 0 V.

SR 3.3.7.4 "arify Response Time cf required 00-LO" 24 months en a channel is within 1.05 seconds.

STA00ERED TEST BASE SAN ON0FRE--UNIT 3 3.3-34 Amendment No. 116

1 ATTACIIMENT E PROPOSED TECIINICAL SPECIFICATION SURVEILLANCE REQUIREMENT 3.3.7.3 SAN ONOFRE UNIT 2

DG-Undereoltage Start 3.3.7 SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.3.7.1 Perform CHANNEL CHECK.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> SR 3.3.7.2 Perform CHANNEL FUNCTIONAL TEST.

24 months SR 3.3.7.3 Perform CHANNEL CALIBRATION with setpoint 24 months Allowable values as follows:

a.

Degraded Voltage Function:

i.

Dropout 2 4196 V ii.

Pickup s 4281 V SDVS (Sustained Degraded Grid Voltage Signal):

Time delay:

1.

127D s 2.17 seconds.

ii.

1620 s 128 seconds.

DGVSS (Degraded Grid Voltage with SIAS Signal):

Time delay:

1.

1270 2 1.83 seconds and s 2.17 l

seconds, ii.

162S 2 4.16 seconds and s 4.44 l

seconds, iii.162T 2 0.88 seconds and s 1.62 l

seconds.

b.

Loss of Voltage Function 2 3554 V Time delay: s 1.0 seconds at 0 V.

l I

SAN ONOFRE--UNIT 2 3.3-34 Amendment No. 127

)

ATTACIIMENT F PROPOSED TECIINICAL SPECIFICATION SURVEILLANCE REQUIREMENT 3.3.7.3 SAN ONOFRE UNIT 3

DG-Undervoltage Start j

3.3.7 l

SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.3.7.1 Perform CHANNEL CHECK.

12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> SR 3.3.7.2 Perform CHANNEL FUNCTIONAL TEST.

24 months i

SR 3.3.7.3 Perform CHANNEL CALIBRATION with setpoint 24 months Allowable Values as follows:

a.

Degraded Voltage Function:

1.

Dropout 2 4196 V ii.

Pickup s 4281 V SDVS (Sustained Degraded Grid Voltage Signal):

l Time delay:

i.

127D s 2.17 seconds.

ii.

1620 s 128 seconds.

DGVSS (Oegraded Grid Voltage with SIAS Signal):

Time delay:

1.

127D 2 1.83 seconds and s 2,17 l

seconds, ii.

162S 2 4.16 seconds and s 4.44 l

seconds, iii. 162T 2 0.88 seconds and s 1.62 l
seconds, b.

Loss of Voltage Function 2 3554 V I

Time delay: s 1.0 seconds at 0 V.

l

?.

SAN ON0FRE--UNIT 3 3.3-34 Amendment No. 116