ML20210D269
| ML20210D269 | |
| Person / Time | |
|---|---|
| Site: | Farley |
| Issue date: | 05/04/1987 |
| From: | ALABAMA POWER CO. |
| To: | |
| Shared Package | |
| ML19292H205 | List: |
| References | |
| NUDOCS 8705070102 | |
| Download: ML20210D269 (22) | |
Text
ENCLOSURE 2 Proposed Changed Pages From the December 19, 1986 Submittal Unit 1 Revision Page 3/4 4-9 Replace Page 3/4 4-10 Replace Page 3/4 4-12 Replace Page 3/4 4-13 Replace Page 3/4 4-15 Replace Page B3/4 4-3 Replace Page B3/4 4-3a Add Unit 2 Revision Page 3/4 4-9 Replace Page 3/4 4-10 Repl ace Page 3/4 4-12 Replace Page 3/4 4-13 Repl ace Page 3/4 4-15 Replace Page B3/4 4-3 Replace Page B3/4 4-3a Add
%50 $h [5
$8 P
J
REACTOR COOLANT SYSTEM 3/4.4.6 STEAM GENERATORS LIMITING CONDITION FOR OPERATION
==========================--:
-=========_________=-
=
3.4.6 Each steam generator shall be OPERABLE.
APPLICABILITY:
MODES 1, 2, 3 and 4.
ACTION:
With one or more steam generators inoperable, restore the inoperable generator (s) to OPERABLE status prior to increasing Tavg above 200 F.
SURVEILLANCE REQUIREMENTS
======================-----==========================================
4.4.6.0 Each steam generator shall be demonstrated OPERABLE by performance of the following augmented inservice inspection program and the requirements of Specification 4.0.5.
4.4.6.1 Steam Generator Sample Selection and Inspection - Each steam generator shall be determined OPERABLE during shutdown by selecting and inspecting at least the minimum number of steam generators specified in Table 4.4-1.
Steam Generator Tube # ample Selection and Inspection - The steam S
4.4.6.2 generator tube minimum sample size, inspection result classification, and the corresponding action required shall be as specified in Table 4.4-2.
The inservice inspection of steam generator tubes shall be performed at the f requencies specified in Specification 4.4.6.3 and the inspected tubes shall be verified acceptable per the acceptance criteria of Specification 4.4.6.4.
The tubes selected for each inservice inspection shall include at least 3% of the total number of tubes in all steam generators. When applying the exceptions of 4.4.6.2.a through 4.4.6.2.c, previous defects or imperfections in the area repaired by sleeving are not considered an area requiring reinspection. The tubes selected for these inspections shall be selected on a random basis except:
a.
Where experience in similar plants with similar water chemistry indicates critical areas to be inspected, then at least 50% of the tubes inspected shall be from these critical areas.
b.
The first sample of tubes selected for each inservice inspection (subsequent to the preservice inspection) of each steam generator shall include:
- When referring to a steam generator tube, the sleeve shall be considered a part of the tube if the tube has been repaired per Specification 4.4.6.4.a.9.
FARLEY-UNIT 1 3/4 4-9 AMENDMENT N0.
REACTOR COOLANT SYSTEM SURVEILLANCE REQUIREMENTS (Continued)
==========================-----=====================---================-----
1.
All nonplugged tubes that previously had detectable wall penetrations greater than 20%.
2.
Tubes in those areas where experience has indicated potential problems.
3.
At least 3% of the total number of sleeved tubes in all three steam generators or all of the sleeved tubes in the generator chosen for the inspection program, whichever is less. These inspections will include both the tube and the sleeve.
4.
A tube inspection (pursuant to Specification 4.4.6.4.a.8) shall be performed on each selected tube.
If any selected tube does not permit the passage of the eddy current probe for a tube or sleeve inspection, this shall be recorded and an adjacent tube shall be selected and subjected to a tube inspection.
c.
The tubes selected as the second and third samples (if required by Table 4.4-2) during each inservice inspection may be subjected to a partial tube inspection provided:
1.
The tubes selected for these samples include the tubes from those areas of the tube sheet array where tubes with imperfections were previously found.
2.
The inspections include those portions of the tubes where imperfections were previously found.
The results of each sample inspection shall be classified into one of the following three categories:
Category Inspection Results I
C-1 Less than 5% of the total tubes inspected are degraded tubes and none of the inspected tubes are defective.
C-2 One or more tubes, but not more than 1% of the total tubes inspected are defective, or between 5% and 10% of the total tubes inspected are degraded tubes.
C-3 More than 10% of the total tubes inspected are degraded tubes or more than 1% of the inspected tubes are defective.
Note:
In all inspections, previously degraded tubes or sleeves must exhibit significant (greater than 10%) further wall penetrations to be included in the above percentage calculations, i
1 FARLEY-UNIT 1 3/4 4-10 AMENDMENT NO.
j
REACTOR COOLANT SYSTEM SURVEILLANCE REQUIREMENTS (Continued)
====------=
4.4.6.4 Acceptance Criteria a.
As used in this Specification:
1.
Imperfection means an exception to the dimensions, finish or contour of a tube or sleeve from that required by fabrication drawings or specifications. Eddy-current testing indications below 20% of the nominal wall thickness, if detectable, may be considered as imperfections.
2.
Degradation means a service-induced cracking, wastage, wear or general corrosion occurring on either inside or outside of a tube or sleeve.
3.
Degraded Tube means a tube, including the sleeve if the tube has been repaired, that contains imperfections greater than or equal to 20% of the nominal wall thickness caused by degradation.
4.
% Degradation means the percentage of the tube or sleeve wall tnickness affected or removed by degradation.
5.
Defect means an imperfection of such severity that it exceeds the plugging or repair limit. A tube or sleeve containing a defect is defective.
6.
Plugging or Repair Limit means the imperfection depth at or beyond which the tube shall be repaired (i.e., sleeved) or removed from service by plugging and is greater than or equal to 40% of the nominal tube wall thickness. For a tube that has been sleeved, through wall penetration of greater than or equal to 31% of sleeve nominal wall thickness in the sleeve requires the tube to be removed from service by plugging.
7.
Unserviceable describes the condition of a tube or sleeve if it leaks or contains a defect large enough to affect its structural integrity in the event of an Operating Basis Earthquake, a loss-of-coolant accident, or a steam line or feedwater line break as specified in 4.4.6.3.c, above.
8.
Tube Inspection means an inspection of the steam generator tube from the point of entry (hot leg side) completely around the U-bend to the top support of the cold leg. For a tube that has been repaired by sleeving, the tube inspection should include the sleeved portion of the tube.
9.
Tube Repair refers to mechanical sleeving, as described by Westinghouse report WCAP-11178 Rev. 1, which is used to maintain a tube in service or return a tube to service.
This includes the removal of plugs that were installed as a corrective or preventive measure.
FARLEY-UNIT 1 3/4 4-12 AMENDMENT NO.
REACTOR COOLANT SYSTEM SURVEILLANCE REQUIREMENTS (Continued)
==========================------- -----,===========---------==========.._--
=
- 10. Preservice Inspection means an inspection of the full length of each tube in each steam generator performed by eddy current techniques prior to service to establish a baseline condition of the tubing. This inspection shall be performed af ter the field hydrostatic test and prior to initial POWER OPERATION using the equipment and techniques expected to be used during subsequent inservice inspections, b.
The steam generator shall be determined OPERABLE after completing the corresponding actions (plug or repair of all tubes exceeding the plugging or repair limit) required by Table 4.4-2.
4.4.6.5 Reports a.
Following each inservice inspection of steam generator tubes, the number of tubes plugged or repaired in each steam generator shall be reported to the Commission within 15 days of the completion of the plugging or repair effort.
b.
The complete results of the steam generator tube and sleeve inservice inspection shall be submitted to the Commission in a Special Report pursuant to Specification 6.9.2 within 12 months following the completion of the inspection. This Special Report shall include:
1.
Number and extent of tubes and sleeves inspected.
2.
Location and percent of wall-thickness penetration for each indication of an imperfection.
3.
Identification of tubes plugged or repaired.
c.
Results of steam generator tube inspections which fall into Category C-3 shall be considered a REPORTABLE EVENT and shall be reported pursuant to 10CFRSO.73 prior to resumption of plant operation. The written report shall provide a description of investigations conducted to determine the cause of the tube degradation and corrective measures taken to prevent recurrence.
FARLEY-UNIT 1 3/4 4-13 AMENDMENT NO.
t
TABLE 4.4-2 STEAM GENERATOR TUBE INSPECTION IST SAtiPLE INSPECTION 2ND SAMPLE INSPECTION 3RD SAMPLE INSPECTION Sample Size Result Action Required Result Action Required Result Action Required E
A minimum of C-1 None N/A N/A N/A N/A Z
S Tubes per
{
S.G.
C-2 Plug or repair C-1 None N/A N/A
~
defective tubes and j
inspect additional C-2 Plug or repair C-1 None 25 tubes in this defective tubes and i
S.G.
inspect additional C-2 Plug or repair 4S tubes in this defective tubes S.G.
C-3 Perform action for C-3 result of first j
sample l
C-3 Perform action for N/A N/A C-3 result of first w2 sample I
a i
.L C-3 Inspect all tubes All other in this S.G., pl ug S.G.s are None N/A N/A or repair defective C-1 tubes and inspect 2S tubes in each Some S.G.s Perform action for N/A N/A other S.G.
C-2 but no C-2 result of additional second sample S.G.s are C-3 Notification to Additional Inspect all tubes N/A N/A l
NRC pursuant to S.G. is in each S.G. and E
10CFRSO.73 C-3 plug or repair i
9 defective tubes.
Notification to i
9 NRC pursuant to 10CFRSO.73 8
I S = 3 N % Where N is the number of steam generators in the unit, and n is the number of steam generators n
inspected during an inspection i
REACTOR COOLANT SYSTEM BASES
=========================
-=======================----===========
3/4.4.6 STEAM GENERATORS The Surveillance Requirements for inspection of the steam generator tubes ensure that the structural integrity of this portion of the RCS will be maintained. The program for inservice inspection of steam generator tubes is based on a modification of Regulatory Guide 1.83, Revision 1.
Inservice inspection of steam generator tubing is essential in order to maintain surveillance of the conditions of the tubes in the event that there is evidence of mechanical damage or progressive degradation due to design, manufacturing errors, or inservice conditions that lead to corrosion.
Inservice inspection of steam generator tubing also provides a means of characterizing the nature and cause of any tube degradation so that corrective measures can be taken.
The plant is expected to be operated in a manner such that the secondary coolant will be maintained within those chemistry limits found to result in negligible corrosion of the steam generator tubes.
If the secondary coolant chemistry is not maintained within these limits, localized corrosion may likely result in stress corrosion cracking. The extent of cracking during plant operation would be limited by the limitation of steam generator tube leakage between the primary coolant system and the secondary coolant system (primary-to-secondary leakage = 500 gallons per day per steam generator).
Cracks having a primary-to-secondary leakage less than this limit during operation will have an adequate margin of safety to withstand the loads imposed during normal operation and by postulated accidents. Operating plants have demonstrated that primary-to-secondary leakage of 500 gallons per day per steam generator can readily be detected by radiation monitors of steam generator blowdown. Leakage in excess of this limit will require plant shutdown and an unscheduled inspection, during which the leaking tubes will be located and plugged or repaired.
Wastage-type defects are unlikely with proper chemistry treatment of the secondary coolant. However, even if a defect should develop in service, it will be found during scheduled inservice steam generator tube examinations.
Plugging or repair will be required for all tubes with imperfections exceeding 40% of the tube nominal wall thickness.
If a sleeved tube is found to have through wall penetration of greater than or equal to 31% of sleeve nominal wall thickness in the sleeve, it must be plugged. The 31% limit is derived from R.G.1.121 calculations with 20% added for conservatism.
The portion of the tube and the sleeve for which indications of wall degradation must be evaluated can be summarized as follows:
- 1. Indications of degradation in the entire length of the sleeve must be evaluated against the sleeve plugging limit.
- 2. Indication of tube degradation of any type including a complete guillotine break in the tube between the bottom of the upper joint and the top of the lower roll expansion does not require that the tube be removed from service.
FARLEY-UNIT 1 83/4 4-3 AMEN 0 MENT NO.
t
= - _ -
REACTOR COOLANT SYSTEM BASES 333333333333333333333333333332323333333333333333323E2322333333333333332233333333 3.'The tube plugging limit continues to apply to the portion of the tube j
in the entire upper joint region and in the lower roll expansion. As noted above the sleeve plugging limit applies to these areas also.
- 4. The tube plugging limit continues to apply to that portion of the tube above the top of the upper joint.
Steam generator tube inspections of operating plants have demonstrated the i
capability to reliably detect degradation that has penetrated 20% of the original tube wall thickness.
Whenever the results of any steam generator tubing inservice inspection fall into Category C-3, these results will be reported to the Commission pursuant to 10CFR50.73 prior to resumption of plant operation.
Such cases will be considered by the Commission on a case-by-case basis and may result in a i
requirement for analysis, laboratory examinations, tests, additional eddy-current inspection, and revision of the Technical Specifications, if necessa ry.
i i
i i
i l
1 4
)
FARLEY-UNIT 1 B3/4 4-3a AMEN 0 MENT NO.
REACTOR COOLANT SYSTEM 3/4.4.6 STEAM GENERATORS LIMITING CONDITION FOR OPERATION l
3.4.6 Each steam generator shall be OPERABLE.
i j
APPLICABILITY:
MODES 1, 2, 3 and 4.
ACTION:
i With one or more steam generators inoperable, restore the inoperable generator (s) to OPERABLE status prior to increasing Tavg above 200 F.
SURVEILLANCE REQUIREMENTS azzzzzzzsazzazzazzzzzmazzzzzzzzazzzzzzzzzz=zzzzzzzz=mz=s=mz=zz=zzzzzzzzzz=zzzzzzz 1
4.4.6.0 Each steam generator shall be demonstrated OPERABLE by performance of the following augmented inservice inspection program and the requirements of Specification 4.0.5.
4.4.6.1 Steam Generator Sample Selection and Inspection - Each steam generator shall be determined OPERABLE during shutdown by selecting and inspecting at least the minimum number of steam generators specified in Table 4.4-1.
i 4.4.6.2 Steam Generator Tube # Sample Selection and Inspection - The steam i
generator tube minimum sample size, inspection result classification, and the corresponding action required shall be as specified in Table 4.4-2.
The inservice inspection of steam generator tubes shall be performed at the j
frequencies specified in Specification 4.4.6.3 and the inspected tubes shall be i
verified acceptable per the acceptance criteria of Specification 4.4.6.4.
The tubes selected for each inservice inspection shall include at least 3% of the i
total number of tubes in all steam generators. When applying the exceptions of 4.4.6.2.a through 4.4.6.2.c, previous defects or imperfections in the area repaired by sleeving are not considered an area requiring reinspection. The tubes selected for these inspections shall be selected on a random basis except:
a.
Where experience in similar plants with similar water chemistry Indicates critical areas to be inspected, then at least 50% of the j
tubes inspected shall be from these critical areas.
i b.
The first sample of tubes selected for each inservice inspection 1
(subsequent to the preservice inspection) of each steam generator shall include:
)
- When referring to a steam generator tube, the sleeve shall be considered a part j
of the tube if the tube has been repaired per Specification 4.4.6.4.a.9.
4 I
4 FARLEY-UNIT 2 3/4 4-9 AMENDMENT NO.
i
REACTOR COOLANT SYSTEM SURVEILLANCE REQUIREMENTS (Continued)
=============================--
--=========-----------
1.
All nonplugged tubes that previously had detectable wall penetrations greater than 20%.
2.
Tubes in those areas where experience has indicated potential problems.
3.
At least 3% of the total number of sleeved tubes in all three steam generators or all of the sleeved tubes in the generator chosen for the inspection program, whichever is less. These inspections will include both the tube and the sleeve.
4.
A tube inspection (pursuant to Specification 4.4.6.4.a.8) shall be performed on each selected tube.
If any selected tube does not permit the passage of the eddy current probe for a tube or sleeve inspection, this shall be recorded and an adjacent tube shall be selected and subjected to a tube inspection.
c.
The tubes selected as the second and third samples (if required by Table 4.4-2) during each inservice inspection may be subjected to a partial tube inspection provided:
1.
The tubes selected for these samples include the tubes from those areas of the tube sheet array where tubes with imperfections were previously found.
2.
The inspections include those portions of the tubes where imperfections were previously found.
The results of each sample inspection shall be classified into one of the following three categories:
Category Inspection Results C-1 Less than 5% of the total tubes inspected are degraded tubes and none of the inspected tubes are defective.
C-2 One or more tubes, but not more than 1% of the total tubes inspected are defective, or between 5% and 10% of the total tubes inspected are degraded tubes.
C-3 More than 10% of the total tubes inspected are degraded tubes or more than 1% of the inspected tubes are defective.
Note:
In all inspections, previously degraded tubes or sleeves must exhibit significant (greater than 10%) further wall penetrations to be included in the above percentage calculations.
FARLEY-UNIT 2 3/4 4-10 AMENDMENT NO.
REACTOR COOLANT SYSTEM SURVEILLANCE REQUIREMENTS (Continued)
=============
4.4.6.4 Acceptance Criteria a.
As used in this Specification:
1.
Imperfection means an exception to the dimensions, finish or contour of a tube or sleeve from that required by fabrication 1
drawings or specifications. Eddy-current testing indications below 20% of the nominal wall thickness, if detectable, may be considered as imperfections.
2.
Degradation means a service-induced cracking, wastage, wear or general corrosion occurring on either inside or outside of a tube or sleeve.
3.
Degraded Tube means a tube, including the sleeve if the tube has been repaired, that contains imperfections greater than or equal to 20% of the nominal wall thickness caused by degradation.
1 4.
% Degradation means the percentage of the tube or sleeve wall thickness affected or removed by degradation.
5.
Defect means an imperfection of such severity that it exceeds the plugging or repair limit. A tube or sleeve containing a defect is defective.
i 6.
Plugging or Repair Limit means the imperfection depth at or beyond which the tube shall be repaired (i.e., sleeved) or removed from service by plugging and is greater than or equal to 40% of the nominal tube wall thickness. For a tube that has been sleeved, through wall penetration of greater than or equal to 31% of sleeve nominal wall thickness in the sleeve requires the tube to be removed from service by plugging.
7.
Unserviceable describes the condition of a tube or sleeve if it leaks or contains a defect large enough to affect its structural integrity in the event of an Operating Basis Earthquake, a loss-of-coolant accident, or a steam line or feedwater line break as specified in 4.4.6.3.c, above.
8.
Tube Inspection means an inspection of the steam generator tube from the point of entry (hot leg side) completely around the U-bend to the top support of the cold leg. For a tube that has been repaired by sleeving, the tube inspection should include the sleeved portion of the tube.
9.
Tube Repair refers to mechanical sleeving, as described by i
Westinghouse report WCAP-lll78 Rev. 1, which is used to maintain a j
tube in service or return a tube to service.
This includes the removal of plugs that were installed as a corrective or preventive measure.
l j
FARLEY-UNIT 2 3/4 4-12 AMENDMENT NO.
REACTOR COOLANT SYSTEM SURVEILLANCE REQUIREMENTS (Continued)
=====================================================================
- 10. Preservice Inspection means an inspection of the full length of each tube in each steam generator performed by eddy current techniques prior to service to establish a baseline condition of the tubing. This inspection shall be performed after the field hydrostatic test and prior to initial POWER OPERATION using the equipment and techniques expected to be used during subsequent inservice inspections.
b.
The steam generator shall be determined OPERABLE after completing the corresponding actions (plug or repair of all tubes exceeding the plugging or r epair limit) required by Table 4.4-2.
4.4.6.5 Reports a.
Following each inservice inspection of steam generator tubes, the number of tubes plugged or repaired in each steam generator shall be i
reported to the Commission within 15 days of the completion of the plugging or repair effort.
b.
The complete results of the steam generator tube and sleeve inservice inspection shall be submitted to the Commission in a Special Report pursuant to Specification 6.9.2 within 12 months following the completion of the inspection. This Special Report shall include:
1.
Number and extent of tubes and sleeves inspected.
2.
Location and percent of wall-thickness penetration for each l
indication of an imperfection.
3.
Identification of tubes plugged or repaired.
c.
Results of steam generator tube inspections which fall into Category C-3 shall be considered a REPORTABLE EVENT and shall be reported pursuant to 10CFR50.73 prior to resumption of plant operation. The written report shall provide a description of investigations conducted j
to determine the cause of the tube degradation and corrective measures j
taken to prevent recurrence.
I 4
s i
FARLEY-UNIT 2 3/4 4-13 AMENDMENT NO.
i f
i TABLE 4.4-2 STEAM GENERATOR TUBE INSPECTION l
3 IST SAMPLE !NSPECTION 2ND SAMPLE INSPECTION 3RD SAMPLE INSPECTION l
O Sample Size Result Action Required Result Action Required Result Action Required I
E:
5 A minimum of C-1 None N/A N/A N/A N/A S Tubes per j
S.G.
C-2 Plug or repair C-1 None N/A N/A N
defective tubes and inspect additional C-2 Plug or repair C-1 None j
25 tubes in this defective tubes and i
S.G.
inspect additional C-2 Plug or repair 4S tubes in this defective tubes S.G.
C-3 Perform action for C-3 result of first i
samp1e C-3 Perform action for N/A N/A i
C-3 result of first 4
sample i
w C-3 Inspect all tubes All other in this S.G., plug S.G.s are None N/A N/A or repair defective C-1 i
tu:st. : and inspect i
2S tubes in each Some S.G.s Perform action for N/A N/A j
other S.G.
C-2 but no C-2 result of
(
additional second sample j
S.G.s are C-3
- }
Notification to Additional Inspect all tubes N/A N/A l
NRC pursuant to S.G. is in each S.G. and g
10CFRSO.73 C-3 plug or repair
{
g defective tubes.
j g
Notification to z
j NRC pursuant to l
10CFRSO.73 2o r
S = 3 N % Where N is the number of steam generators in the unit, and n is the number of steam generators r
1 n
inspected during an inspection j
i
REACTOR COOLANT SYSTEM BASES E3333333333333333333333333333333333333333333333333333333333333333333333333333333 3/4.4.6 STEAM GENERATORS The Surveillance Requirements for inspection of the steam generator tubes ensure that the structural integrity of this portion of the RCS will be maintained. The program for inservice inspection of steam generator tubes is based on a modification of Regulatory Guide 1.83, Revision 1.
Inservice inspection of steam generator tubing is essential in order to maintain surveillance of the conditions of the tubes in the event that there is evidence of mechanical damage or progressive degradation due to design, manufacturing errors, or inservice conditions that lead to corrosion.
Inservice inspection of steam generator tubing also provides a means of characterizing the nature and cause of any tube degradation so that corrective measures can be taken.
The plant is expected to be operated in a manner such that the secondary coolant will be maintained within those chemistry limits found to result in negligible corrosion of the steam generator tubes.
If the secondary coolant chemistry is not maintained within these limits, localized corrosion may likely result in stress corrosion cracking. The extent of cracking during plant operation would be limited by the limitation of steam generator tube leakage between the primary coolant system and the secondary coolant system (primary-to-secondary leakage = 500 gallons per day per steam generator).
Cracks having a primary-to-secondary leakage less than this limit during operation will have an adequate margin of safety to withstand the loads imposed during normal operation and by postulated accidents. Operating plants have demonstrated that primary-to-secondary leakage of 500 gallons per day per steam generator can readily be detected by radiation monitors of steam generator blowdown. Leakage in excess of this limit will require plant shutdown and an unscheduled inspection, during which the leaking tubes will be located and plugged or repaired.
Wastage-type defects are unlikely with proper chemistry treatment of the secondary coolant. However, even if a defect should develop in service, it wili be found during scheduled inservice steam generator tube examinations.
Plugging or repair will be required for all tubes with imperfections exceeding 40% of the tube nominal wall thickness.
If a sleeved tube is found to have through wall penetration of greater than or equal to 31% of sleeve nominal wall thickness in the sleeve, it must be plugged. The 31% limit is derived from R.G. 1.121 calculations with 20% added conservatism. The portion of the tube and the sleeve for which indications of wall degradation must be evaluated can be summarized as follows:
- 1. Indications of degradation in the entire length of the sleeve must be evaluated against the sleeve plugging limit.
- 2. Indication of tube degradation of any type including a complete guillotine break in the tube between the bottom of the upper joint and the top of the lower roll expansion does not require that the tube be removed from service.
FAP1EY-UNIT 2 B3/4 4-3 AMENDMENT NO.
[i REACTOR COOLANT SYSTEM BASES l
- 3. The tube plugging limit continues to apply to the portion of the tube in the entire upper joint region and in the lower roll expansion. As noted above the sleeve plugging limit applies to these areas also, i
- 4. The tube plugging limit continues to apply to that portion of the tube t
above the top of the upper joint.
Steam generator tube inspections of operating plants have demonstrated the capability to reliably detect degradation that has penetrated 20% of the original tube wall thickness.
I Whenever the results of any steam generator tubing inservice inspection fall into Category C-3, these results will be reported to the Commission pursuant to 1
10CFR50.73 prior to resumption of plant operation. Such cases will be considered by the Comsn1ssion on a case-by-case basis and may result in a requirement for analysis, laboratory examinations, tests, additional eddy-current inspection, and revision of the Technical Specifications, if necessary.
3 i
i 1
i 1
FARLEY-UNIT 2 B3/4 4-3a AMENDMENT NO.
i
,,,_g-m
,aa
,m,w-,, -, -,,,
,s
-,m -mm-4 won-, - - - - - - - -
ENCLOSURE 3 Significant Hazards Evaluation Pursuant to 10CFR50.92 for the Proposed Steam Generator Tube Repair Technical Specification Change l
+ie..w w.
-- --, -~,,,.
--m.7w g
9,-
.v,-m._.,
..%vg-y y
,w.,
m,.e
,44--
ga 9
'c e
NS-RCSCIr87-009, Rev.1 PAGE 2 OF 6 REPAIR OF SIEAM GENERAIIR 'IUBES USING SIEEVES J. M. FARIEY NUCIEAR PIANT UNIIS 1 AND 2 SIMIFICANT HAZARDS CCNSIIERATION ANAINSIS INIBOIIX:rIN As required by 10 CPR 50.91 (a)(1) this analysis is provided to dammstrate
]
that a rW license amendment to implanant repair of tubes using tube sleeves for the J. M. Farley Unit 1 and 2 steam generators tor e=As no significant ba w ds consideration. In accordance with the three factor test of 10 CPR 50.92(c), inplementatim of the sq-:::1 license emendment was analyzed using the following standards and found not to: 1) involve a significant increase in the probability or omsequences for an Maarit previously evaluated; or 2) create the possibility of a new or different kind of accident from any accident previously evaluated; or 3) involve a significant reduction in a margin of safety.
Due to the inportance of the barrier provided by the steam generator tubes, maintenance of tube bundle integrity has been provided for by regular inspecticr1 of the tubes and removal fran service of tubes whidt have indication of degradation in avr=== of specified criteria. A repair method using sleeves placed inside the t,**=
at the locaticr1 of the degradation has been developed. 'Ihe sleeves are short lengths of tubing with an outside diameter less than the inside diamater of the degraded tube. 'Ihe sleeve is placed inside the tube and is -joined at the tcp and bottczn to sound portiens i
of the tube. 'Ihe installed sleeve in a degaded or defective tube restores the integrity of the barrier provided by the tubes between the primary and eeocnaary fluids Using existing '1w:hnical Specification tube plugging criteria, tubes with indications of degradation in excess of the plugging criteria would have to be renoved fran service. Removal of a tube fran service results in a reduction of reactor coolant flow through the steam generator. 'Ihis amall lL-
T NS-RCSCIe87-009, Ruri.1 PAGE 3 CF 6 reduction in flw has an inpact on the margin in the reactor ocolant flw j
thrcia#1 the steam y-- tcr in IDCA analyses and en the heat transfer efficiency of the steam p-ter. Repair of a tube with slesving maintains the tube in service and results in a exts analler f1w re& action. 'Iherefore the pecposed amendment would minimina less of margin in reactor rmlant system f1w and assist in assuring that mininaan flw rates are maintained in aw===
of that required for operaticzi at A111 pcuer. Also minimizing the j
reduction in fim has operaticnal benefits and minimizes the increase in heat flux across the tubes remaining in service. Increased heat fluxes have been anarciated with an incrmaw potential for tube acerosicn.
'the st- -: = = ' amendment would pedify Tactinical Specifimtion 4.4.6, " Steam Generatcrs" and its bases to alls for the repair of a steam generator tube.
CLirrently, Farley Units 1 and 2 Technical Specifications permits cmly the removal frtan service by plugging for those steam generator tubes with addy current indicaticns shwing greater than 40% through wall cracking. 'Ihese specificaticos were established before the slesving repair method whicts would permit tubes to be repaired and returned to safe operation was developed.
'Ihe p --:M Technical Fificaticn change would permit Alabama Power l
Otmpany the opticn of repairing degraded or defective tubes utilizing sleeves or the removal of G-gas d or defective tubes from service by plugging in the J. M. Farley Units 1 and 2 steam generators. 'Ihe r ur i.ed amendment also includes criteria for allowable wall degradation in the sleeve and in the tube in the region of the sleeve to tube joint.
ANAINSIS l
l e nfermance of the st- -:- =- amendments to the standards for a determination of no significant hazard as defined in 10 Cm 50.92 (three factor test) is shown in the follwing:
i
- 1) Operation of the Farley Nuclear Plant Unit 1 and 2 in accordance with the st,--d license amendment does not involve a significant increase in the probability or consequences of an accident previously evaluated.
l
s NS-RGiCIr87-009, Rev. 1 PAGE 4 OF 6
' Die supporting technical ard safety evaluaticms of the subject amendment (Westirupause WCAP 11178, Rev.1, "J. M. Farley TJnits 1 and 2, Steam Generator Slesving Report, Mechanical Sleeves" (Proprietary); WCAP 11179, Rev.1, "J. M. Farley T. hits 1 ard 2, Stamm Generator Slesving Report, Mechanical Sleeves" (Non-PIcprietary); and SBCIr86-352, Rev.1) demonstrate that repair of degraded tubes using sleeves will result in tube bundle integrity cxmsistant with the original design basis, i
'Ihe sleeve omfiguration has been designed and analyzed in accordance with the rules of the ASME Boiler and Pressure Vaamal Code. Fatigue and stress analyses of the sleeved tube ama-blies pra*M acomptable results. Mechanical testing has shown that the structural t..fd1 of the sleeves under normal, faulted and upset ocnditions is within acceptable limits. Imak rate testing has demcmstrated that the leak rates of the joints between the sleeve and the existing tube under normal, faulted and upset canditicos are well below acceptable ratas.
'Ihe existing Technical Specification leakage rate requii Am and accident analysis assunpticms ruunain unchanged in the event significant l
leakage fran the sleeve would coeur. Any leakage throucA the sleeved region of the tube due to potential l~~m14M tube (-i.ws datico is fully l
bounded by leak-before-break consideratons and ultimately the existing steam generator tube rupture analysis included in the Farley Nuclear Plant Final Safety Analysis Report. 'Ihe pc gwd Technical Specification change does not adversely inpact any other previously evaluated design basis amMant. 'Ihe results of the qualificatico testing, analyses, and plant operating experience d ennstrate that the sleeve naa m hly is an acomptable means of maintaining tubes in service. Furthermore, per Regulatory Guide 1.03 ram-nandaticos, the sleeved tube can be acmitared l
through periodic inspections with pa e=d. addy current techniques.
l Plugging limit criteria are established in the technical =p=~ifications for the tube in the region of the sleeve and the sleeve. 'these maamnus demonstrate that installation of sleeves which span C-viaded areas of the tube will restore the tube to its original design basis.
l
l',
o O
T NS-RCSC2r87-009, Rav.1 PAGE 5 0F 6
- 2) 'the pg license amendment does not create the possibility of a new or different kind of wida'it fran any -ida'it previously evaluated.
Inplementaticn of the proposed tube ( p..$sd.im repair method does not introduce significant changes to the plant design basis. Repair of tubes does not provide a mechanism to result in an amidarit cutside of the sleeved area. Any hypothetical amidarit as a result of potential tube or sleeve (==p. dation in the repaired particn of the tube would be bounded by the existing tube rupture amidarit analysis.
- 3) 'Ihe p -- _- M license amendment does not involve a significant reduction in a margin of safety.
'Ihe sleeve repair of degraded steam generators tubes has been demonstrated to restore the integrity of the tube bundle under normal and postulated accident ocnditions. 'Ihe safety factors used in the design of sleeves for the repair of degraded tubes are consistent with the safety factors in the ASME Boiler and Pressure Vammal Code used in steam generator design. 'Ihe plugging limit criteria for the sleeve has been established using the method of Regulatory Guide 1.121. 'Ihe design of the sleeve joints has been verified by testing to preclude significant leakage during normal and postulated amidant cmditions.
'Ihe effect of sleeving on the design transients and amida'it safety analyses has been reviewed based on the insullation of the pavi==
runhar of sleeves aead.
'Iha installaticn of sleeves can be evaluated as the equivalent of eczna level of steam generator tube plugging. 'the J.
M. Farley Units 1 and 2 steam generators are currently licensed to 5 pm. wad. steam generator tube plugging (SGTP) and Alabama PcWer Otmpany has sukunitted a 10 percent steam generator tube plugging analysis to the NRC for use at Farley Units 1 and 2 to evaluate the effects of tube plugging and reduced reactor coolant systen (RCS) flow in the steam generators. An evaluation has shown that flow restriction for a steam generator tube plugging level of 10% is greater than for the equivalent l
. ~
_ _ _ _ _, _.,. ~ ~. _ _.
NS-RCSC2r87-009, Rev.1 PAGE 6 0F 6 ocabination of WM tube plugging and up to the pav4== rannbar of sleeves PM to be installed of the design described in Ref.1. A IIx:A evaluation has shown that system parameters for this plugging level are within their allowable limits (i.e., peak clad temperature, DGR, RCS pressure, etc.). 'Ihm calculated reacter coolant flowrate with the maxinum raunbar of sleeves WM to be installed is greater than the tbamal design flow; therefore, the ncn-IDCA safety analyses and design j
transients are not adversely 4==+M by steem p
.ter slesving.
Accordingly, there is no decrease in the safety nargins defined in the plant Technical Spar !fications.
Inplementation of tube repair by slesving will decrease the ramber of tubes Milch must be taken cut of service with tube plugs. Installation of tube plugs rema the BCS flow nazgin, thus inplementaticm of tube repair by sleeving will maintain the margin of flow that would otherwise be IM M in the event of increased plugging. maad on the above, it is ocmcluded that the st - :1 change does not result in a significant 1
reduction in a loss of margin with respect to plant safety as defined in the Final Safety Analysis Report or the haaan of the plant technical vificaticms.
l CCNCIUSICN maad cm the roc iing analysis it is concluded that operaticm of J. M.
Farley Nuclear Plant Units 1 ard 2 in acocedance with the pur-ed amendment does not result in the creation of an unreviewed safety question, an increase in the probability of an -idant previously evaluated, create the possibility of a new or different kind of -idant frczn any -idant previously evaluated, nor re m any margins to plant safety. 'Iberefore, the license amendment does not involve a Significant Hazards Otmsideration as defined in 10 CTR 50.92.
REFERENCE 1.
Mestinghouse WCAP 11178, Rev.
1, "J.
M.
Farley Units 1 and 2, Steam Generator Sleeving Report, Mechanical Sleeves" (Proprietary)
/
g ENCLOSURE 1 J. M. FARLEY NUCLEAR PLANT - UNITS 1 AND 2 STEAM GENERATOR SLEEVING REPORT (MECHANICAL SLEEVES)