NUSCO IN-SERVICE INSPECTION REPORT t

CLASS I & II SYSTEMS l

MILLSTONE NUCLEAR POWER STATION UNIT #2 P.O. BOX 128 WATERFORD. CONNECTICUT 06385 O

OWNER:

l I

Northeast Utilities Energy Company P.O. Box 270 Hartford, Connecticut 06101 Commercial Service Date December 26, 1975 Report Date: January 20, 1987 O

B705050362 070430 PDR ADOCK 0500 6

O SECTION I OWNER'S DATA REPORT (FORM NIS-1)

O O

l' j

a 1

i NUSCO l

t I

TABLE OF CONTENTS i

4 SECTION TITLE i

}.

I Owner's Data Report (NIS-1 & NIS-2) l II Introduction I

i i

6 III NDE Procedures, Equipment and Personnel Qualifications E

l 1

IV Exclusions. Exceptions And Deferred Items 5

5 1

i f

V Conditions Noted

?

4 f

i r

VI Examination Results j

VII Corrective Measures Recommended and Taken I

- 1 i

i i

'l e

J I

4 I

i O

7 1

,-.m.-

...y y-,-,:-e---,9-w-,... -

,,,,,,,_,7p-

+.w-ry.

-.w.,

.g

-,w,%

e

,,,,,m y

,4,-,.,rg

,----my-.

9---wwy.,p-wp

FORM NIS-1 OWNERS' DATA REPORT FOR INSERVICE INSPECTIONS As required by the Provisions of the ASME Code Rules O

Northeast Nuclear Energy Company, P.O. Box 270. Hartford, CT 06101

1. Owner (Name and Address of Owner)

Millstone Nuclear Power Station, P.O. Box 128 Waterford, CT 06385

2. Plant (Name and Address of Plant)

!^

C

3. Plant Unit
4. Owner Certificate of Authorization (if required)
5. Commercial Service Date 12/26/75
6. National Board Number for Unit 20914
7. Components Inspected Manufacturer Component or Manufacturer or Installer State or National Appurtenance or Installer Serial No.

Province No.

Board No.

Pressurizer Wolds & Pon M-CE. Inc.

67605 N/A 20918 Rx Coolant Pipinn 28 Weld M-CE. Inc.

502-19 N/A N/A Replacement RPV Head Studs (5)

M-CE. Inc.

N/A N/A N/A SG #1 Manway Boltine M-CE, Inc.

67510 N/A 20928 SG #2 Manway Bolting M-CE, Inc.

67511 N/A 20929 Valve

/m Bolting (Various)

N/A N/A N/A Pressurizer Manway Bolting M-CE, Inc.

N/A N/A 20918 Safety Inject.

Piping Welds M-DRAVO N/A N/A N/A Shutdown Cool-ing Pinine Welds M-DRAVO N/A N/A N/A Przr Spray Pipine Welds M-DRAVO N/A N/A N/A Aux. Pzr.

Snrav Welds M-DRAVO N/A N/A N/A Loop 2A Chg.

Line Welds M-BECHTEL N/A N/A N /A Loop 1B, Cold Leg Drain Pipe M-BECHTEL N/A N/A N/A Loop 1, Hot Leg Drain Pipe M-BECHTEL N/A N/A N/A Loop 1B, Cold Len Drain M-BECHTEL N/A N/A N/A Loop 1A, Cold Lee Drain Pipe M-BECHTEL N/A N /A N/A Note: Supplemental sheets in form of lists, sketches, or drawings may be used provided (1) size is 8% in. x 11 m.,

(2) information in items 1 through 6 on this data report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.

l This form (E00029) rnay be obtained from the Order Dept., ASME,345 E. 47th St., New York, N.Y. 10017 SECTION I Page 1

FORM NIS-1 (back)

T

8. Examination Dates 9/29/86 to 12/12/86 9. Inspection Interval from 12/26/85 to.12/26/1995
10. Abstract of Examinations. Include a list of examinations and a statement concerning status of work required for current interval.

See Section VI for: Class I Systems Class II Systems

11. Abstract of Conditions Noted.

See Section V

12. Abstract of Corrective Measures Recommended and Taken See Section VII We certify that the statements made in this report are correct and the examinations and corrective men-sures taken conform to the rules of the ASME Code,Section XI.

Date 3 27 19 87 Signed N N8 do By

(/

  1. U l/ O Owner

/

Certificate of Authorization No. (if applicable)

Expiration Date CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler ndfressure Vessel Inspectors and/or the State or Province of CT and employed by 888 M3 of 8MYdV

[)

f/M/f6 have insg//1 E(*he components described in this Owners' Data Report during the period

(

ecte

/

to

. and state that to the best of my knowledge and belief, the Owner

/

has performed examinations and taken corrective measures described in this Owners' Data Report in accordance with the requirements of the ASME Code,Section XI.

I By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Data Report. Furthermore, neither the Inspector nor his employe shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or sonw cted vith this inspection.

Date

.Td 19 h

Commissions 07

/

Inspededr's Signature National Board, State, Province and No.

Abbreviations:

NUSCo; Northeast Utilities Service Company NNECo; Northeast Nuclear Energy Company H.S.B.;

Hartford Steam Boiler EBASC0; EBASCo Services Incorporated SECTION I Page 2

i l

FORM NIS-1 OWNERS' DATA REPORT FOR INSERVICE INSPECTIONS j

As required by the Provisions of the ASME Code Rules

(~h Northeast Nuclear Energy Company, P.O. Box 270, Hartford, CT 06101

1. Owner (Name and Address of Owner)

Millstone Nuclear Power Station, P.O. Box 128 Waterford, CT 06385

2. Plam (Name and Address of Plant)
3. Plant Unit
4. Owner Certificate of Authorization (if required) e 20914
5. Commercial Service Date 12/26/75
6. National Board Number for Unit
7. Components inspected Manufacturer Component or Manufacturer or Installer State or National Appurtenance or Installer Serial No.

Province No.

Board No.

Loop 2A, Cold Lee Drain Pipe M-BECHTEL N/A N/A N/A Loop 2B, Cold Lee Drain Pipe M-BECHTEL N/A N/A N/A Class 2 Shut-M-BECHTEL down cooling i iping N/A N/A N/A Class 1 Pipins, (VARIOUS)

N/A N/A N/A mmonrts Class'2 Piping, Supports (VARIOUS)

N/A N/A N/A Class 3 PipinE.

N /A N/A N/A Supports (VARIOUS) w a

Note: Supplemental sheets in form of lists. sketches, or drawings may be used provided (1) size is 8% in. x 11 in.,

(2) information in items 1 through 6 on this data report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.

This form (E00029) may be obtained from the Order Dept., ASME,345 E. 47th St., New York, N.Y. 10017 SECTION 1 Page 3

FORM NIS 1 (back)

8. Examination Dates 9/29/86 12/12/86 9. Inspection Interval from 12/26/M to I?/26/95 to
10. Abstract of Examinations. Include a list of examinations and a statement concerning status of work required for current interval. See Section VI for: Class I Systems Class II Systems
11. Abstract of Conditions Noted.

See Section V

12. Abstract of Corrective Measures Recommended and Taken See Section VII We certify that the statements made in this report are correct and the examinations and corrective mea-sures taken conform to the rules of the ASME Code,Section XI.

3)37 19 87. Signed NNb Cd By Date Owner 4

(/ W LAJ Certificate of Authorization No. (if applicable)

Expiration Date CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel

$1nspectors and/or the State or Province of CE and employed by 888 I# I of j/w/e& O have inspected the components described in this Owners' Data Report during the period

/O 9/,34 /56

/A//4 / f f,-

. and state that to the best of my knowledge and belief, the Owner to h

has performed examinations and taken corrective measures described in this Owners' Data Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Data Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Date 6

19 bT

[//7

[

N Commissions

'InspMtor's Signature National Board, State, Province and No.

Section I Page 4

I 4

T f

O y

.I f

T f

SECTION II l

INTRODUCTION 9

r I

1 J

O J

I J

T f

l t

1 l

P 4

1 I

r t

i 3

t b

4 L

I I

I i O r

l l

INTRODUCTION k

1.

Volumetric, surface and visual examinations were performed as required by Section XI, of the ASME Boiler and Pressure Vessel Code, j

1980 Edition, including the Winter 1981 Addenda.

2.

All records, examination data sheets, personnel certificates, equipment and material certificates for the examinations performed are on file at the Millstone Nuclear Power Station Unit #2.

3.

All items listed in this report are creditable items to the second interval in-service inspection ten-year Class I and Class I program, with the exception of the preservice examination of four reactor c

vessel head closure studs and the additional examinations required by IWB-2430.

4.

The examinations listed in this report were performed by personnel from the Northeast Utilities Service Company, Nuclear Engineering and Operations Group and EBASCO Services Incorporated.

5.

In addition to the second interval creditable items listed above, several items were examined that are creditable to the first ten-year in-service program. These items will be noted throughout the content of this report by specific notations relative to those exams.

Og

O SECTION III NDE PROCEDURES, EQUIPMENT AND 1

PERSONNEL QUALIFICATIONS O

b 1

..-o

ULTRASONIC TEST INSTRUMENT LIST O

l MANUFACTURER MODEL SERIAL NUMBER Krautkramer Branson USL-38 180454 Krautkramer Branson USL-48 213051 i

Krautkramer Branson USL-48 213222 EPOCH 2002 330 l

EPOCH 2002 382 EPOCH 2002 383 EPOCH 2002 397 4

i MAGNETIC TEST INSTRUMENT LIST 6

O i

VANUFACTURER MODEL SERIAL NUMBER 1

Parker Probe DA200 8916 Parker Probe DA200 8949 l

Parker Probe DA200 8950 1

Parker Probe B300 984 i

1

. -. ~.

=-.

ULTRASONIC TRANSDUCER LIST lp U

MANUFACTURER FREQUENCY (MHZ)

MODEL/ SIZE SERIAL NUMBER ARE0 TECH 1.00 MHZ 1" Dia.

K05696 2

ARE0 TECH 1.00 1" Dia.

K05697 RTD 2.00 2 (10x18) 86-75 RTD 2.00 2 (10x18) 86-76 ARE0 TECH 2.25 1/2 x'1" A26435 ARE0 TECH 2.25 1/2 x 1" A26436 ARE0 TECH 2.25 1/4" Dia.

A28551 ARE0 TECH 2.25 1/2" Dia.

B07524 i

ARE0 TECH 2.25 1/4" Dia.

C26026 ARE0 TECH 2.25 1/4" Dia.

D12127 l

(}

ARE0 TECH 2.25 1/2" Dia.

D16065 ARE0 TECH 2.25 1/2" Dia.

G03502 ARE0 TECH 2.25 3/8" Dia.

G08209 ARE0 TECH 2.25 3/8" Dia.

G08229 ARE0 TECH 2.25 1/4" Dia.

H12310.

ARE0 TECH 2.25 3/4" Dia.

H22381 ARE0 TECH 2.25 1/4" Dia.

J05546 ARE0 TECH 2.25 1/2" Dia.

K10325 4

ARE0 TECH 2.25 1/2" Dia.

lL01969 j;

ARF 0 TECH 2.25 3/4" Dia.

LO8874 ARE0 TECH 2.25 3/4" Dia.

LO8973 i

ARE0 TECH 2.25 1/2 x 1/2.

L19511 ARE0 TECH 2.25 3/4" Dia.

M10902

j. ()

ARE0 TECH 2.25 1/2" x 1" M31135 ARE0 TECH 5.00 3/8" Dia.

F10506 1.

i

.m.._._-

4 1

1 l-NDE MATERIAL LIST 4

I t

j.

MANUFACTURER ITEM

- TYPE BATCH NUMBER ARE0 TECH UT COUPLANT EXOSEN 20 0424852001 l-ARE0 TECH UT COUPLANT EX0SEN 20 0115812001 MAGNAFLUX SPOTCHECK: CLEANER SKC-NF-ZC-7B 86B001 MAGNAFLUX SPOTCHECK: PENETRANT

- SKL-HF/S 84H027 MAGNAFLUX SPOTCHECK: PENETRANT ZL-54 86C03W i

j MAGNAFLUX SPOTCHECK: DEVELOPER SKD-NF-ZP-9B 84E003 i

4 l

i a

l I

I i

i i

I l

I t

i l

i 1

1 l

NUSCO NDE PROCEDURES p

NUMBER REVISION AND DATE TITLE C

NU-LP-1 4

7/16/86 Liquid penetrant examina-tion.

NU-MP-1 4

5/19/86 Magnetic particle examina-tion.

NU-UT-1 5

7/10/86

. Ultrasonic examination (UT) procedure general require-ments.

NU-UT-2 4

7/17/86 UT procedure for austenitic piping welds.

NU-UT-3 3

7/3/86 UT procedure for ferritic and dissimilar metal piping welds.

NU-UT-15 1

4/2/84 UT procedure for pressurizer c

welds.

NU-UT-17 2

7/28/86 UT procedure for nozzle to

~

safe-end welds at Millstone Unit #2.

NU-UT-20 2

7/21/86 UT procedure for nozzle inner radius area at Millstone Unit 2.

NU-UT-23 2

7/21/86 UT procedure for component bolts, studs and nuts.

NU-UT-26 0

7/28/86 UT procedure for primary coolant pipe welds at Millstone Unit 2.

NU-VT-1 5

8/5/86 Procedure for visual examin-ations.

O

ULTRASONIC CALIBRATION BLOCK LIST O

BLOCK NUMBER DRAWING NUMBER

  • REVISION UT-4 25203-29449 Sh. 5 1

UT-15 25203-29449 sh. 30 2

i UT-16 25203-29449 Sh. 31 1

i UT-17 25203-29449 Sh. 33 1

i UT-20 25203-29449 Sh. 3 1

UT-21 25203-29449 Sh. I 1

l j

UT-27 25203-29449 Sh. 20 1

j UT-28 25203-29449 Sh. 21 1

UT-29 25203-29449 Sh.' 22 1

c UT-41 25203-28409 (41) 2 UT-46 25203-28409 (46) 2

{

UT-47 25203-28409 (47) 2 i

UT 25203-28409 (50) 2 i

MRIR #843340 1

(Shut Down Heat Exchanger Bolt)

ROMPUS #793100 11W Block #797081 1

I

  • Formally Combustion-Engineering Drawings, i

l l

O

,-,w.,.

i J

s OUALIFICATIONS O

V NUSCO PERSONNEL j

NAME METHODS / LEVELS EYE CERTIFICATIONS UT PT MT VT P. J. Durand II II II II 7/9/86 R. J. Fuller III III III II 9/29/86 J. F. Pinto II II II II 2/19/86 T. E. Davis II II II II 6/4/86 EBASCO SERVICES INCORPORATED PERSONNEL l

UT PT MT VT EYE CERTIFICATIONS J. Bagley III 1/22/86 II i

J. Burke I

II II 9/9/86 c

A. Carreiro II 8/13/86 j

J. December I

I I

9/18/86 J. Everett II

-3/28/86 B. Focer I

9/18/86 I

]

G. Kowalski II II II 3/23/86 C. Noel I

I I

I 4/23/86 i-J. O'Neil II II II I

1/10/86 T. Pedersen III II II 1/11/86 i

D. Roeters II II I

3/28/86 J. Strum II II II 5/8/86 L. Valenzuela II II II II 7/14/86 J. Vanderifnde II II II II 9/18/86 1

i O

r

.--_. ~.. _..

)

i e

I I

i 1

2 r

i i

i 4

1 SECTION IV i

j 4i o

EXCLUSIONS, EXCEPTIONS. AND DEFERRED ITEMS i

I e

4 J

I i

i t

4 I

4 4

a 1

t i

l i

4 i

I i

l i

t

EXCLUSIONS, EXCEFTIONS, AND DEFERRED ITEMS 1.

The Millstone Unit #2, 1986 Refueling Outage was the first outage of the first period in the second Ten-Year Interval. There were no 4

exclusions, exceptions, or deferred items during this outage.

i 2.

The ASME Section XI, Code Category B-F, Trimetalic Welds that were

(

deferred during the 1985 refueling outage of the first Ten-Year interval were examined.

i i

3.

Five Category C-D, shutdown heat exchanger bolts that were deferred I

]

during the first interval due to the lack of a UT calibration block 4

were also examined.

I c

4 I

4 t

i l

I I

l 4

l i

i 1.. _ _.. _. _ _, =.

l@

I a

1 i

\\

\\

i 1

i i

'I i,

i k

l SECTION V 4

1 1

i i

CONDITIONS NOTES i

4 i

l i

I, l

j i

I E

t

}

i t

I a

t f

b 2

i o

i 4

I 1

sl@

I-l a

f l

4

.__,,.c,-

.m

,w------m--e..

-y,,,.---.wm9-,,-.r.,.y

---,,--,4..,-,e--....s-we,-_,-..m--,-,,.-,

---r,,

CONDITIONS NOTED f-~ -

1.

Volumetric, surface, and visual examinations were performed as required by Section XI of the ASME Boiler and Pressure Vessel Code, j

1980 Edition, including the Winter '81 Addenda. However, the extent of examinations for Class 1, (B-J) and Class 2 (C-F & C-C), are still determined by the 1974 Edition, including the Summer '75 Addenda as required and/or permitted by 10CFR50.55a.

2.

Four reactor vessel closure head studs were replaced this refueling outage. See Section VI, Category B-G-1, for Preservice Examination Results.

C

/""%

3.

Category B-J, Item B9.40, Socket Weld Examinations were expanded by U

five additional welds due to unacceptable indications discovered in Weld BPD-C-1015. These additional welds were selected in accordance with the requirements of IWB-2430(a) of the applicable code.

4 i

4.

Category B-J, Item B9.40 socket veld examinations were expanded a second time by twenty welds due to unacceptable indications discovered in weld BPD-C-1025. These welds were selected in accor-i dance with the requirements of IWB-2430 (b) of the applicable code.

4 5.

For specific details to the final disposition of the unacceptable velds noted above, see the attached NIS-2 reports, i

l

.4.aa.aa.-_,A a4.m eb mww.-._

.m.a_a-4 h__.a. hm-Mw..--,.

g. -.. -

_,aa an. 4 2

.A

,e m aw.waa-m_.

..--2,

-_----s.-

w.

-.a Y

f i

e i

5 a

i t

I i.

A l

SECTION VI I

J f

EXAMINATION RESULTS 4

)

i 1

4 i.

l I

I I

i l

I i

I l

I

)

I l

t 4

i I

1 4

b I

4 I

i s

...,.---.-,.- w

-e m e,

,-m,-,y..,,. -~~.

s.,-.-.

,--~_,,-9

__.,...ny,,,

e,-, - -

-,,-,,e--.

i

--.--------,-.v.,__

w

---,. --.,,,-emm

1 l

} --

CATEGORY B-D 1

Examination Area:

Full Penetration Welds of Nozzles in Vessels (Inspection Program B) 4 j

Examination Method: Volumetric (UT) 0*-45'-60' or 60'-70* scans r

i 4

ITEM NUMBER RESULTS REMARKS 1

I i

PR-NTH-1 Acceptable Laminar indications seen on 0* scan i

9 PR-NTH-3 Acceptable Acceptable per IWB-3511-2 t

PR-T-IR-1 Acceptable None i

PR-T-IR-3 Acceptable None f

l I

I

[

l t

J t

i l

i i

i i

i I

I l

1

('

l 1

k i

i 1

(

e f

CATEGORY B-F

,- s I

Examination Area:

Pressure Retaining Dissimilar Metal Welds i

Examination Method: Volumetric (UT) 0*-45*-60*

Safe-End Scans Surface (PT)

ITEM NUMBER RESULTS REMARKS BPD-C-1017 Acceptable PT Exam (2" Dia. Pipe)

BPD-C-3000 Acceptable PT Exam (2" Dia. Pipe)

]

BPS-C-1001 Acceptable PT and UT Exams e

BPS-C-1025A Acceptable UT Exam Only*

BPV-C-5001 Acceptable PT and UT Exams l

BPY-C-3000 Acceptable PT Exam (3" Dia. Pipe)

BSD-C-2001 Acceptable PT and UT Exams BSI-C-2001 Acceptable PT and UT Exams

  • BSI-C-3001 Acceptable PT and UT Exams BSI-C-4000 Acceptable UT Exam Only*

I P-14-C-3 Acceptable UT Exams Only*

P-18-C-3 Acceptable UT Exams Only*

P-4-C-1 Acceptable UT Exams Only*

P-9-C-3 Acceptable UT Exams Only*

j

  • These items are trimetalic welds that were deferred dur'ing the first ten-year interval. Credit for these examinations will be applied to that interval. These velds will be examined again during the second ten-year interval for credit applied to that interval.

O I V

. _ ~. _. _ _ _ ~.. _.. _ _. _.

t Category B-M-2 Examination Area: Valve Bodies Examination Method: Visual (VT) 1 Item Number Results Remarks l

SI-237 Acceptable Also liquid penetrant examined the valve seat 1

l area and found it to be l

j acceptable.

a i

1 t

d l

1 t

l 1

i t

i l

i T

4 h

1 i

i I

4 i

i 1

l i

4 l

l

l 1

Category B-P l

Examination Area: Pressure Retaining Components l

Examination Method: Visual VT-2, During The Hydrostatic Test of the Reactor Cooling System i

Item Number Results Remarks PR-B-PEN-1 Acceptable Note 1 l

PR-B-PEN-2 Acceptable Note 1 J

PR-S-PEN-1 Acceptable Note 1 1

PR-T-PEN-1 Acceptable Note 1 PR-T-PEN-2 Acceptable Note 1 PR-T-PEN-3 Acceptable Note 1 PR-T-PEN-4 Acceptable Note 1 i

)

PR-T-PEN-5 Acceptable Note 1 i

i 1

i Note 1 These items were examined during the Hydrostatic Test of the Reactor Coolant System.

t l

5 l

l, i

1 i

)

i I

t

~

- - - - - - ~ - -

-,n,n, e --

-. -. - - -. - ~

r Category C-C Examination Area:

Integrally Welded Attachments to Vessels Examination Method: Surface NT or PT Item Number Results Remarks i

402007 Acceptable None 402048 Acceptable None 402049 Acceptable None i

502019 Acceptable None 312019 Acceptable None*

J i

  • This exam completed utilizing MT examination techniques. All others were completed using PT examination.

i

(

i I

1 l

i

]

I i

I 1

I t

l I

I l

4 4

i I

i

Category C-D Examination Area: Pressure Retaining Bolting Exceeding 1" Diameter Examination Method: Volumetric (UT)

Item Number Results Remarks s

5 studs randomly Acceptable UT examination completed

  • selected "B" shutdown heat exchanger
  • These items and exams were a deferral item from the 1985 Refueling Outage. Completing these exams fulfill the 1974 ASME Code Edition including the 1975 Summer Addenda Category C-D Requirements for the first Ten-Year Interval.

C O

l

[

1 1

?

1

~ _ _ _., _. _ _. _ -. ~. _ _,.. -

_ _ ~.

Category C-F Examination Area: Pressure Retaining Welds in Piping Examination Method: Surface (PT) or (MT) and when noted Volumetric (UT)

Item Number Results Remarks FWB-CG-04 Acceptable MT and UT completed HSI-CF-06 Acceptable PT completed HSI-CF-32 Acceptable PT and UT completed MSA-CG-05 Acceptable MT and UT completed MSB-CG-09 Acceptable NT and UT completed SI-CF-A-111 Acceptable PT completed SI-CF-A-114 Acceptable PT completed SI-CF-A-120 Acceptable PT completed SI-CF-B-021 Acceptable PT completed C

SI-CF-B-127 Acceptable PT indications acceptable O

per Table IWB-3514-3 of the ASME Code.

SI-CF-C-012 Acceptable PT cad UT completed SI-CF-F-040 Acceptable PT indication acceptable per Table IWB-3514-3 of the ASME Code.

SI-CF-X-01 Acceptable PT completed SI-CF-X-08 Acceptable PT completed-SI-CF-X-56 Acceptable PT completed SI-CF-X-63 Acceptable PT completed SIT-CF-D4 Acceptable PT completed O

I i

f f

i 4

e i

1 i

}

4 1

l l

1 1

SECTION VII i

,1 CORRECTIVE MEASURES RECOMMENDED AND TAYD

/

1 1

J

+

1 l

l

}

k l

l 1

1 4

i 1

2 4

l l

Corrective Measures Recommended and Taken See attached NIS-2 Reports for specific repairs and i

replacements performed during this refueling outage.

f 1

j i

4 i

4 i

c i

i 5

I t

e i

i i

+

l 4

4

FORM NIS-2 OWNER'S ISPORT OF REPAIRS OR REPLACEMENTS AS Required by the Provisions cf ASME Coda Secticn XI 1.

Owner - Northeast Nuclear Energy Co.

Date - 3/17/87 P.O. Box 128, Waterford, Ct. 06385 NIS-2-1 Sheet 1 of 2 I1.

Plant - Millstone Nuclear Power Station Unit - 2

\\s /

Waterford, Connecticut 3.

Work Performed By - Northeast Nuclear Energy Co.

Waterford, Ct. 06385 Work Order Number - M2-86-12145 4.

Identification of System - REACTOR COOLANT SYSTEM-5.

(a) Applicable Construction Code Edition - 1969 Addenda - S69 Code Cases - N/A (b) Applicable Edition of Section XI Utilized for Repairs or Replacements - 1980, W81 Addenda Code Cases - N/A 6.

Identification of Components Repaired or Replaced, and Replacement Components Name of Component RC-035D Name of Mfr - HENRY VOGT CO.

Mfr's Serial No. - H961ABE National Board No. - N/A CRN No. - N/A Other Ident. - MPSN-386-015-115 Year Built - 1986 Repaired, Replaced, ASME Code Stamp - YES or Replacement - REPLACED g(Yes or No)

'- 7.

Description of Work - REPLACED VALVE DUE TO UNACCEPTABLE SURFACE INDICATIONS 8.

Tests Conducted:

Hydrostatic Test __X__ Pneumatic Nominal Operating Pressure Other Pressure 2290 PSIG Test Temp __532_deg. F 9.

Remarks - UNACCEPTABLE SURFACE (PT) INDICATIONS FOUND ON ROUTINE INSERVICE !

INSPECTION j

)

l d

FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS A3 Required by the Provicicna cf ASME Coda Sectirn XI NIS-2-1 Sheet 2 of 2 J

CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this e

repair /repla ment conforms to Section XI of the ASME Code.

Signed CA AMS 3/?(/9 7

/( wner o1UOwVeW() Designee Title tate' CERTIFICATE OF INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the SQte or Province of CT

, employed by

/Ed' Ith of nae r#o+0 have inspected the Ab/ece 7

described in this report on M //2.

19 PL arid state that to the best of my knowledge and belief, this repair or replacement has been constructed in accordance with Section XI of the ASME Code.

By signing this certificate, fjneithertheInspectornorhisemployermakesanywarranty, expressed or

(_/ implied, concerning the repair or replacement described in this Report.

Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising form or connected with this inspection.

Date YM82 Nf^

Commissions OI ///d (Ilispector) i i

FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS 1

A3 Required by the Provicien2 cf ASME Coda Secticn XI

______________________________________________________________________________l 1.

Owner - Northeast Nuclear Energy Co.

Date - 3/17/87 P.O. Box *18, Waterford, Ct. 06385 NIS-2-2 Sheet 1 of 2

(/T2.

Plant - Millstone Nuclear Power Station Unit - 2

\\_

Waterford, Connecticut 3.

Work Performed By - Northeast Nuclear Energy Co.

Waterford, Ct. 06385 Work Order Number - M2-86-03306 4.

Identification of System - REACTOR COOLANT SYSTEM 5.

(a) Applicable Construction Code Edition - 1969 Addenda - S69 Code Cases - N/A (b) Applicable Edition of Section XI Utilized for Repairs or Replacements - 1980, W81 Addenda Code Cases - N/A 6.

Identification of Components Repaired or Replaced, and Replacement Components Name of Component - STUD #3, #4, #21, #45 Name of Mfr - COMBUSTION ENG.

Mfr's Serial No. - N/A National Board No. - N/A PDCR No. - N/A Other Ident. - MPSN-M2-NB-28 Year Built - 1974 Repaired, Replaced, ASME Code Stamp - NO or Replacement - REPLACED (Yes or No)

~

7.

Description of Work - REPLACED STUDS DUE TO UNACCEPTABLE SURFACE INDICATIONS (THREAD DAMAGE AND CORROSION) 8.

Tests Conducted:

Hydrostatic Test __X__ Pneumatic Nominal Operating Pressure Other Pressure 2290 PSIG Test Temp __532_deg. F 9.

Remarks -

O

FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS An Required by the Provicicn2 cf ASME Coda Secticn XI NIS-2-2 Sheet 2 of 2 O,------------------------------------------------------------------------------

CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this repair / replacement conforms to Section XI of the ASME Code.

Signed

/bMO Eb A 6. S -

3 l2Cl87

'(Owner 66 6wneV's Designee Title Datd CERTIFICATE OF INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of G/

, employed by M4 I4I

~

of //eA S have inspected the A'ce*e,.e w described in this report on

'd /# 7 19 f6 and state that to the best of my knowledge and belief, this repair or replacement has been constructed in accordance with Section XI of the ASME Code.

By signing this certificate, rN neither the Inspector nor his employer makes any warranty, expressed or i

implied, concerning the repair or replacement described in this Report.

s Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising form or connected with this inspection.

Date NA> /D IM 2h Commissions CI N//h (Inspector) i O

FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS As Required by the Provis:icn2 cf ASME Coda Sectirn XI 1.

Owner - Northeast Nuclear Energy Co.

Date - 3/17/87 P.O. Box 128, Waterford, Ct. 06385 NIS-2-3 Sheet 1 of 2

(~]2.

Plant - Millstone Nuclear Power Station Unit - 2

(_/

Waterford, Connecticut 3.

Work Performed By - Northeast-Nuclear Energy Co.

Waterford, Ct. 06385 W

Work Order Number - M2-86-03322 4.

Identification of System - MAIN STEAM SYSTEM 5.

(a) Applicable Construction Code ASME SECTION III, CLASS 2 Edition - 1983 Addenda -W84 Code Cases -

N/A (b) Applicable Edition of Section XI Utilized for Repairs or Replacements - 1980, W81 Addenda Code Cases - N-416 6.

Identification of Components Repaired or Replaced, and Replacement Components Name of Component MS-12B Name of Mfr - HENRY VOGT CO.

Mfr's Serial No. - 840603-6 National Board No. - N/A PDCR No. - N/A Other Ident. - MPSN-386-015-054 Year Built - 1986 Repaired, Replaced, ASHE Code Stamp - YES or Replacement - REPLACED (Yes or No)

-s 7.

Description of Work - REPLACED VALVE 8.

Tests Conducted:

Hydrostatic Test Pneumatic Nominal Operating Pressure X

Other Pressure 900 PSIG Test Temp __532_deg. F 9.

Remarks -

O

FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS Ao Required by the Provicicn3 cf ASME Coda Section XI NIS-2-3 Sheet 2 of 2 O

\\

/

CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this repair / replacement conforms to Section XI of the ASME Code.

Signed b

lr. 6. S.

3l26l87 (Owner o9 Owd4Vld Designee Title Date CERTIFICATE OF INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of C7

, employed by 4*~#

?f[

of 2/u r#o~ o have inspected the ap/uc-e T described in this' report on AL/ 3 9 19 FA and state that to the best of my knowledge and belief, this repair or replacement has been constructed in accordance with Section XI of the ASME Code.

By signing this certificate, o

{s neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the repair or replacement described in this Report.

Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising form or connected with this inspection.

Date

'O b8e Commissions 07 N ///h (Tnspector)

O

FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS As Required by the Proviciera cf ASME Coda Secticn XI 1.

Owner - Northeast Nuclear Energy Co.

Date - 3/17/87 P.O. Box 128, Waterford, Ct. 06385 NIS-2-4 Sheet'l of 2 f)2.

Plant - Millstone Nuclear Power Station Unit - 2

\\/

Waterford, Connecticut i

3.

Work Performed By - Northeast Nuclear Energy Co.

Waterford, Ct. 06385 Work Order Number - M2-86-03321 4.

Identification of System - MAIN STEAM SYSTEM 5.

(a) Applicable Construction Code -

ASME SECTION III, CLASS 2 Edition - 1983 Addenda - W84 Code Cases - N/A (b) Applicable Edition of Section XI Utilized for Repairs or Replacements - 1980, W81 Addenda Code Cases - N-416 6.

Identification of Components Repaired or Replaced, and Replacement Components Name of Component MS-12A Name of Mfr - HENRY VOGT CO.

Mfr's Serial No. - 840803-3 National Board No. - N/A PDCR No. - N/A Other Ident. - MPSN-386-015-051 Year Built - 1986 Repaired, Replaced, ASME Code Stamp - YES or Replacement - REPLACED O(YesorNo) 7.

Description of Work - REPLACED VALVE 8.

Tests Conducted:

Hydrostatic Test Pneumatic Nominal Operating Pressure X

Other Pressure 900 PSIG Test Temp __532_deg. F 9.

Remarks -

O i

FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS h Required by the Provicicca cf ASME Coda Secticn XI NIS-2-4 Sheet 2 of 2 rh V ____________________________________________________________________________

CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this repair / replacement conforms to Section XI of the ASME Code.

Signed A?lv ASS slach)

/(Dwner oV Own'el^d Designee Title

'Dat'e CERTIFICATE OF INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of C7 employed by AM.T *

  • of No.st A o have inspected the 4cdce--Y described in this report on

/l/A9 19 f 7 and state that to the best of my knowledge and belief, this repair or replacement has been constructed in accordance with Section XI of the ASME Code.

By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or O,'s implied, concerning the repair or replacement described in this Report.

Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising form or connected with this inspection.

Date ] 'o N )

kWP" Commissions C r (Y///9 (InVpector)

O

FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS A3 Required by the Provicicna cf ASME Coda Secticn XI 1.

Owner - Northeast Nuclear Energy Co.

Date - 3/17/87 P.O. Box 128, Waterford, Ct. 06385 NIS-2-5 Sheet 1 of 2

[\\ 2.

Plant - Millstone Nuclear Power Station Unit - 2

\\-

Waterford, Connecticut 3.

Work Performed By - Northeast Nuclear Energy Co.

Waterford, Ct. 06385

~

Work Order Number - M2-86-08288 4.

Identification of System - MAIN STEAM SYSTEM 5.

(a) Applicable Construction Code ASME SECTION III, CLASS 2 Edition - 1980 Addenda -W80 Code Cases - N/A (b) Applicable Edition of Section XI Utilized for Repairs or Replacements - 1980, W81 Addenda Code Cases - N-416 6.

Identification of Components Repaired or Replaced, and Replacement Components Name of Component MS-432B Name of Mfr - HENRY VOGT CO.

Mfr's Serial No. -

UNKNOWN National Board No. - N/A PDCR No. - N/A Other Ident. - MPSN-284-246-1 Year Built - 1984 Repaired, Replaced, ASME Code Stamp -

YES or Replacement - REPLACED (Yes or No)

Name of Component - PIPE Name of Mfr - SOUTHWEST FAB.

Mfr's Serial No. -

HT-263218 National Board No. - N/A CRN No. - N/A Other Ident. - MPSN-386-005-894 Year Built - 1985 Repaired, Replaced, ASME Code Stamp -

NO or Replacement - REPLACED (Yes or No) 7.

Description of Work - REPLACED VALVE AND ATTACHED PIPE 8.

Tests Conducted:

Hydrostatic Test Pneumatic Nominal Operating Pressure X

Other Pressure 900 PSIG Test Temp __532_deg. F 9.

Remarks -

O

FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS An Required by the Provicicn2 cf ASME Coda Secticn II NIS-2-5 Sheet 2 of 2

/

CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this repair / replacement conforms to Section XI of the ASME Code.

Signed AAL1 b T V'

~}$50 -

EbCN7

'(Owner dB OLdkPs Designee Title

'Dat6

~

CERTIFICATE OF INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of C7

, employed by M q

.2*2~

of //A 77oe o have inspected the we h e J described in this report on

/1/rc 19 94 and state that to the best of my knowledge and belief, this repair or replacement has been constructed in accordance with Section XI of the ASME Code.

By signing this certificate, c

expressed or v / neither the Inspector nor his employer makes any warranty, implied, concerning the repair or replacement described in this Report.

Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising form or connected with this inspection.

Date Mid W

// P+-

Commissions CT

/N[

(Inspector) 1 0

FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS A3 Required by the Provicicn2 ef ASME Coda Secticn XI 1.

Owner - Northeast Nuclear Energy Co.

Date - 3/17/87 P.O. Box 128, Waterford, Ct. 06385 NIS-2-6 Sheet l'of 2 f'N 2.

Plant - Millstone Nuclear Power Station Unit - 2 x

Waterford, Connecticut 3.

Work Performed By - Northeast Nuclear Energy Co.

Waterford, Ct. 06385 Work Order Number - M2-86-10912

'4.

Identification of System - MAIN STEAM SYSTEM 5.

(a) Applicable Construction Code - ASME SECTION III, CLASS 2 Edition - 1983 Addenda - W83 Code Cases - N/A (b) Applicable Edition of Section XI Utilized for Repairs or Replacements - 1980, W81 Addenda Code Cases - N-416 6.

Identification of Components Repaired or Replaced, and Replacement Components Name of Component MS-191A Name of Mfr - FISCHER CONTROLS Mfr's Serial No. - 10047540 National Board No. - N/A CRN No. - N/A Other Ident. - MPSN-285-232-1 Year Built - 1986 Repaired, Replaced, ASME Code Stamp - YES or Replacement - REPLACED e

(Yes or No) 7.

Description of Work - REPLACED VALVE 8.

Tests Conducted:

Hydrostatic Test Pneumatic Nominal Operating Pressure X

Other Pressure 900 PSIG Test Temp __532_deg. F 9.

Remarks -

J

FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS An Required by the Provicion2 cf ASME Coda Section XI NIS-2-6 Sheet 2 of 2

\\ / ----------------------------_------------_-------------_-_-_------_--------_--

CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this repair / replacement conforms to Section XI of the ASME Code.

1?&Yb A A S.

s)xh 7 Signed

'fowner & OGriMUs Designee Title

'Dat6 CERTIFICATE OF INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the St g or Province of C7

, employed by Mf Z of _ //u A o have inspected the f e #ce e 'r described in this' report on

/2/2e 19 fft-an'd state thrt to the best of my knowledge and belief, this repair or replacement has been constructed in accordance with Section XI of the ASME Code.

By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or

(']/ implied, concerning the repair or replacement described in this Report.

v Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising form or connected with this inspection.

Date MO /#)

/W" Commissions CI Nd C1nspector)

OV l

FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS An Required by the Proviairca cf ASME Coda Secti:n XI l.

Owner - Northeast Nuclear Energy Co.

Date - 3/17/87 P.O. Box 128, Waterford, Ct. 06385 NIS-2-7 Sheet 1 of 2

[\\.

Plant - Millstone Nuclear Power Station Unit - 2 2

\\/

Waterford, Connecticut 3.

Work Performed By - Northeast Nuclear Energy Co.

Waterford, Ct. 06385 Work Order Number - M2-86-09800 4.

Identification of System - MAIN STEAM SYSTEM 5.

(a) Applicable Construction Code - ASME SECTION III, CLASS 2 Edition - 1983 Addenda - W83 Code Cases - N/A (b) Applicable Edition of Section XI Utilized for Repairs or Replacements - 1980, W81 Addenda Code Cases - N-416 6.

Identification of Components Repaired or Replaced, and Replacement Components Name of Component MS-191B Name of Mfr - FISCHER CONTROLS Mfr's Serial No. - 10047541 National Board No. - N/A CRN No. - N/A Other Ident. - MPSN-285-232-2 Year Built - 1986 Repaired, Replaced, ASME Code Stamp - YES or Replacement - REPLACED

{

(Yes or No) 7.

Description of Work - REPLACED VALVE 8.

Tests Conducted:

Hydrostatic Test Pneumatic Nominal Operating Pressure X

Other Pressure 900 PSIG Test Temp __532_deg. F 9.

Remarks -

l OV

FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS As Required by the Proviciona cf ASME Coda Section XI NIS-2-7 Sheet 2 of 2 j

'v__--_------_-------------_--_-___-----__--------_-_-_____--_________-_-_-_--_.

CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this e

repair / replacement conforms to Section XI of the ASME Code.

/hv A. E s.

shcle7 x

Signed

/(Owner Al DwhWP a Designee Title

'Date CERTIFICATE OF INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of C7

, employed by nrn IeE of

""fIh

% m //* 4, have inspected t'he Abheem r-described in this report on

'%</

19 F7 and state that to the best of my

~

knowledge and belief, this repair or replacement has been constructed in accordance with Section XI of the ASME Code.

By signing this certificate, Q(,/ implied, concerning the repair or replacement described in this Report.

neither the Inspector nor his employer makes any warranty, expressed or Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising form or connected with this inspection.

Date 5/6 /D l U* E "

Commissions Ci W /// 9 (I'nspector)

FORM NIS-2 OWNER *S REPORT OF REPAIRS OR REPLACEMENTS As Required by the Provicion] cf ASME Cod 3 Section XI 1.

Owner - North cat Nuclecr En:rgy Co.

Date - 3/17/87 P.O. Box 128, Waterford, Ct. 08385 NIS-2-8 Sheet 1 of 2 r~N 2.

Plant - Millstone Nuclear Power Station Unit - 2

(,)

Waterford, Connecticut 3.

Work Performed By - Northeast Nuclear Energy Co.

Waterford, Ct. 06385 Purchase Order No. - 746062 4.

Identification of System - MAIN STEAM SYSTEM 5.

(a) Applicable Construction Code Edition - 1971 Addenda - W71 Code Cases -

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements - 1980, W81 Addenda Code Cases -

6.

Identification of Components Repaired or Replaced, and Replacement Components Name of Component MS-245 Name of Mfr - DRESSER Mfr's Serial No. - BN4966 National Board No. - N/A CRN No. - N/A Other Ident. - N/A Year Built - 1973 Repaired, Replaced, ASME Code Stamp - YES or Replacement - REPAIRED e

(Yes or No)

\\ / Name of Component MS-247 Name of Mfr - DRESSER Mfr's Serial No. - BN4961 National Board No. - N/A CRN No. - N/A Other Ident. - N/A Year Built - 1973 Repaired, Replaced, ASEE Code Stamp - YES or Replacement - REPAIRED (Yes or No)

Name of Component MS-242 Name of Mfr - DRESSER Mfr's Serial No. - BN4964 National Board No. - N/A CRN No. - N/A Other Ident. - N/A Year Built - 1973 Repaired, Replaced.

ASME Code Stamp - YES or Replacement - REPAIRED (Yes or No) 7.

Description of Work - REPLACED VALVE DISC, RETESTED VALVE 8.

Tests Conducted:

Hydrostatic Test Pneumatic Nominal Operating Pressure X

Other Pressure 900 PSIG Test Temp __532_deg. F 9.

Remarks - VALVES REPAIRED BY WYLE LABORATORIES UNDER LISTED QA PURCHASE I

ORDER.

O m

i i

FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS As Required by the Provicicn3 cf ASME Coda Section XI NIS-2-8 Sheet 2 of 2 O

V __________________-_--_______-______-__-______-___________-_________-________.

CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this repair / replacement conforms to Section XI of the ASME Code.

Signed Mu A E.S z) 2 <-/ p ?

/ (~ Owner ok) Ow~n##V Designee Title

'Datd CERTIFICATE OF INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the Statp or Province of C ~i'

, employed by Mrs To L of >#4 r Pb-o have inspected th'e /'v A4c/

described in this report on

/1/14 19 26 and state that to the best of my knowledge and belief, this repair or replacement has been constructed in cccordance with Section XI of the ASME Code.

By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or p/ implied, concerning the repair or replacement described in this Report.

(#

Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising form or connected with this inspection.

Date ll1' lb'?

kWE~

Commisaions cT W //) 4 (Ins'pector)

/

)

O V

FORM NIC-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS As Required by the Proviciona cf ASME Code Section II 1.

Owner - Northeast Nuclear Energy Co.

Date - 3/17/87 P.O. Box 128, Waterford, Ct. 08385 NIS-2-9 Sheet 1 of 2 (3'- 2. Plant - Millstone Nuclear Power Station Unit - 2 Waterford, Connecticut 3.

Work Performed By - Northeast Nuclear Energy Co.

Waterford, Ct. 06385 Work Order Number - M2-86-11524 4.

Identification of System - SERVICE WATER SYSTEM 5.

(a) Applicable Construction Code - ANSI B31.1 Edition - 1983 Addenda -

Code Cases -

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements - 1980, W81 Addenda Code Cases -

6.

Identification of Components Repaired or Replaced, and Replacement Components Name of Component - 6"-JGD-24 Name of Mfr - N/A Mfr's Serial No. - N/A National Board No. - N/A CRN No. - N/A Other Ident. - N/A Year Built - 1986 Repaired, Replaced, d

ASME Code Stamp - No or Replacement - REPLACED

)(Yes or No) 7.

Description of Work - REPLACED TAPPING SADDLE 8.

Tests Conducted:

Hydrostatic Test __X__ Pneumatic Nominal Operating Pressure Other Pressure 94 PSIG Test Temp __70__deg. F 9.

Remarks - MECHANICAL JOINT CONNECTION, NO WELDING INVOLVED.

HYDROSTATIC TEST PRESSURE IN ACCORDANCE WITH APPROVED ISI PROGP.AM RELIEF REQUEST

FORM CIS-2 OWNER'S REPORT CF REPAIRS OR REPLACEMENTS A2 Required by the Proviciona cf ASME Coda Secti",a XI NIS-2-9 Sheet 2 of 2 AL)

CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this repair / replacement conforms to Section XI of the ASME Code.

AES.

3)zcl97 Signed ML

/(Owner oV Oddebtb Designee Title

'Dat'e

~

CERTIFICATE OF INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the Sta te or Province of Cr

, employed by NQ T*4 of AV+cr /L-o have inspecte4 the.creeer described in this report on

/ ?/t s 19 64 and state that to the best of my knowledge and belief, this repair or replacement has been constructed in

[ ) accordance with Section XI of the ASME Code.

By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the repair or replacement described in this Report.

x/

Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising form or connected with this inspection.

W Y ll]

Date VWl')

bY5 Commissions (Inspector)

O

FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS A3 Required by the Provicions cf ASME Coda Section XI 1.

Owner - Northeast Nuclear Energy Co.

Date - 3/17/87 P.O. Box 128, Waterford, Ct. 06385 NIS-2-10 Sheet'l of 2

() 2.

Plant - Millstone Nuclear Power Station Unit - 2

\\/

Waterford, Connecticut 3.

Work Performed By - Northeast Nuclear Energy Co.

Waterford, Ct. 06385 Work Order Number - M2-87-00565 4.

Identification of System - SERVICE WATER SYSTEM 5.

(a) Applicable Construction Code - ANSI B31.1 Edition - 1983 Addenda -

Code Canes -

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements - 1980, W81 Addenda Code Cases -

6.

Identification of Components Repaired or Replaced, and Replacement Components Name of Component - 3"-HUD-32 Name of Mfr - N/A Mfr's Serial No. - N/A National Board No. - N/A PDCR No. - N/A Other Ident. - MPSN-187-008-3 MPSN-386-005-898 Year Built - 1986 Repaired, Replaced, O(_,ASMECodeStamp-NO or Replacement - REPLACED (Yes or No) 7.

Description of Work - REPLACED PIPE AND ELBOW 8.

Tests Conducted:

Hydrostatic Test __X__ Pneumatic Nominal Operating Pressure Other Pressure __110 PSIG Test Temp __70__deg. F 9.

Remarks - HYDROSTATIC TEST PRESSURE IN ACCORDANCE WITH APPROVED ISI PROGRAM RELEIF REQUEST O

FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS A3 Required by the Proviairna cf ASME Coda Secti n XI NIS-2-10 Shtst 2 of 2 O ______________________________________________________________________________

LJ CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this repair / replacement conforms to Section XI of the ASME Code.

Signed A?ik AE.S.

s/x/87 TDwner o80wnFr&P Designee Title

' Daf,e CERTIFICATE OF INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the Stag or Province of W

, employed by NTP f/L of //A da+ a have inspected the ewA c, o described in this report on

/ t_/,o 19 %

and state that to the best of my

~

knowledge and belief, this repair or replacement has been constructed in cccordance with Section XI of the ASME Code.

By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or

~

(^)Furthermore, implied, concerning the repair or replacement described in this Report.

neither the Inspector nor his employer shall be liable in any

~

manner for any personal injury or property damage or a loss of any kind crising form or connected with this inspection.

Date lA h d'V) 0 %1 )~

Commiasions CT Y /// 9

" lIne6ector) 4 l

O

FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS A3 Required by the Provicions cf ASME Code Section II 1.

Owner - Northeast Nuclear Energy Co.

Date - 3/17/87 P.O. Box 128, Waterford, Ct. 06385 NIS-2-11 Sheet 1 of 2 O

. (,j 2.

Plant - Millstone Nuclear Power Station Unit - 2 Waterford, Connecticut 3.

Work Performed By - Northeast Nuclear Energy Co.

Waterford, Ct. 06385 e

Work Order Number - M2-86-08438 4.

Identification of System - SERVICE WATER SYSTEM 5.

(a) Applicable Construction Code - ANSI B31.1 Edition - 1983 Addenda -

Code Cases -

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements - 1980, W81 Addenda Code Cases -

6.

Identification of Components Repaired or Replaced, and Replacement Components Name of Component JGD-1 Name of Mfr - N/A Mfr's Serial No. - N/A National Board No. - N/A CRN No. - N/A Other Ident. - N/A Year Built - 1986 Repaired, Replaced, c

ASME Code Stamp - NO or Replacement - REPLACED

(

)(YesorNo) 7.

Description of Work - REPLACED PORTION OF PIPE DOWNSTREAM OF 2-SW-3B 8.

Tests Conducted:

Hydrostatic Test __X__ Pneumatic Nominal Operating Pressure Other Pressure 94 PSIG Test Temp __70__deg. F 9.

Remarks - HYDROSTATIC TEST PRESSURE IN ACCORDANCE WITH APPROVED ISI PROGRAM RELIEF REQUEST O

FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS An Required by the Proviciona cf ASME Codo Section XI NIS-2-11 Sheet 2 of 2 O

O ______________________________________________________________________

CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this repair / replacement conforms to Section XI of the ASME Code.

YAf 1

A.Es glec/97 Signed

  1. f0wner cd CnYeWs Designee Title

'Dat'e CERTIFICATE OF INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of CT

, employed by hTn

.Z 4 1~

of Ab rA o have inspected the geo/ ecoew described in this report on

/ 2 /r c 19 frX an'd state that to the best of my knowledge and belief, this repair or replacement has been constructed in cecordance with Section XI of the ASME Code.

By signing this certificate,

) neither the Inspector nor his employer makes any warranty, expressed or s/ implied, concerning the repair or replacement described in this Report.

Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind crising form or connected with this inspection.

Date N /M 7 89 2~

Commissions 07

/// @

~ ~

(Irispector)

FORM NIS-2 OWNER'S REPORT OF REFAIRS OR REPLACEtniaCS As Required by the Provicions cf ASME Code Section XI 1.

Owner - Northeast Nuclear Energy Co.

Date - 3/17/87 P.O. Box 128, Waterford, Ct. 06385 NIS-2-12 Sheet 1 of 2

[

) 2.

Plant - Millstone Nuclear Power Station Unit - 2 4

\\/

Waterford, Connecticut 3.

Work Performed By - Northeast Nuclear Energy Co.

Waterford, Ct. 06385 Work Order Number - M2-86-11643 4.

Identification of System - SERVICE WATER SYSTEM 5.

(a) Applicable Construction Code - ANSI B31.1 Edition - 1983 Addenda -

Code Cases -

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements - 1980, W81 Addenda i

Code Cases -

6.

Identification of Components Repaired or Replaced, and Replacement Components Name of Component - 2"-HCD-60 Name of Mfr - N/A Mfr's Serial No. - N/A National Board No. - N/A CRN No. - N/A Other Ident. - N/A Year Built - 1986 Repaired, Replaced, ASME Code Stamp - NO or Replacement - REPLACED c

(Yes or No) 7.

Description of Work - REPLACED PIPE AND ELBOWS 8.

Tests Conducted:

Hydrostatic Test __X__ Pneumatic Nominal Operating Pressure Other Pressure 94 PSIG Test Temp __70__deg.

F 9.

Remarks - HYDROSTATIC TEST PRESSURE IN ACCORDANCE WITH APPROVED ISI PROGRAM RELIEF REQUEST i

1 I

O

FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS As Required by the Proviciona cf ASME Code Section XI NIS-2-12 Sheet 2 of 2 CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this repair / replacement conforms to Section XI of the ASME Code.

Signed NL 3lZfl0 ')

Yu Designee Title

' Date (Owner od/Osr a

CERTIFICATE OF INSPECTION I, the undersigned, holding a valid commission issued by the National Board of, Boiler and Pressure Vessel Inspectors and the State or Province of employed by _N 9/

f6 of _ 2/m <fe o have inspected the 4pgentf described in this report on

/%<

19 i and state that to the best of my knowledge and belief, this repair or rep acement has been constructed in accordance with Section XI of the ASME Code.

By signing this certificate, O neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the repair or replacement described in this Report.

Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind i

arising form or connected with this inspection.

b Date 4#7

    1. 2~

Commissions (Irtfipector) i i

!O

FORM MIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS As Recired by the Prov1Cion3 cf ASME Code Section XI 1.

Owner - Northeast Nuclear Energy Co.

Date - 3/17/87 P.O. Box 128, Waterford, Ct. 06385 NIS-2-13 Sheet 1 of 2

(

) 2.

Plant - Millstone Nuclear Power Station Unit - 2 Waterford, Connecticut 3.

Work Performed By - Northeast Nuclear Energy Co.

Waterford, Ct. 06385 Work Order Number - M2-86-02260 4.

Identification of System - SERVICE WATER SYSTEM 5.

(a) Applicable Construction Code - ANSI B31.1 Edition - 1983 Addenda -

Code Cases -

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements - 1980, W81 Addenda Code Cases -

6.

Identification of Components Repaired or Replaced, and Replacement Components Name of Component - 24"-JGD-6 Name of Mfr - N/A Mfr's Serial No. - N/A National Board No. - N/A CRN No. - N/A Other Ident. - N/A Year Built - 1973 Repaired, Replaced,

(

ASME Code Stamp - NO or Replacement - REPAIRED (Yes or No) 1 7.

Description of Work - WELD REPAIRED EROSION / CORROSION ON PIPE ID 8.

Testa Conducted:

Hydrostatic Test __X__ Pneumatic Nominal Operating Pressure Other Pressure 94 PSIG Test Temp __70__deg. F 9.

Remarks - HYDROSTATIC TEST PRESSURE IN ACCORDANCE WITH APPROVED ISI PROGRAM RELIEF REQUEST l

O

FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS A3 Required by the Proviciona cf ASME Code Section XI NIS-2-13 Sheet 2 of 2 CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this repair / replacement conforms to Section XI of the ASME Code.

AES 3hch7 Signed A'Lu K W s Designee Title

'Dafe

./lOwner CERTIFICATE OF INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Doller and Pressure Vessel Inspectors and the ftate or Province of C-1*

., employed by N_ff J ff of

.,N w E v-s have inspected }he

>e ma -

described in this report on

/L/_u 19 XL and state that to the best of my knowledge and belief, this repair or replacement has been constructed in accordance with Section XI of the ASME Code.

By signing this certificate, O neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the repair or replacement described in this Report.

Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising form or connected with this inspection.

Date h d _

kb M I ///h Commissions (Inspector)

O

FORM NIC-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS As Required by the Proviciona cf ASME Code Section XI 1.

Owner - Northeast Nuclear Energy Co.

Date - 3/17/87 P.O. Box 128, Waterford, Ct. 06385 NIS-2-14 Sheet 1 of 2 A(,) 2.

Plant - Millstone Nuclear Power Station Unit - 2 Waterford, Connecticut 3.

Work Performed By - Northeast Nuclear Energy Co.

Waterford, Ct. 06385 s

Purchase Order No. - 746062 4.

Identification of System - REACTOR COOLANT SYSTEM 5.

(a) Applicable Construction Code - Edition - 1971 Addenda - W71 Code Cases -

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements - 1980, W81 Addenda Code Cases -

6.

Identification of Components Repaired or Replaced, and Replacement Components Name of Component RC-201 Name of Mfr - DRESSER IND.

Mfr's Serial No. - N/A National Board No. - N/A CRN No. - N/A Other Ident. - N/A Year Built - 1973 Repaired, Replaced, ASME Code Stamp - YES or Replacement - REPAIRED

(

(

)(YesorNo) 7.

Description of Work - REPLACED DISC, RETESTED VALVE 8.

Tests Conducted:

Hydrostatic Test __X__ Pneumatic Nominal Operating Pressure Other Pressure _2290 PSIG Test Temp _532__deg. F 9.

Remarks - VALVE REPAIRED BY WYLE LABORATORIES UNDER LISTED QA PURCHASE ORDER.

HYDROSTATIC TEST PERFORMED IN LIEU OF LEAK TEST AFTER REINSTALLATION.

1 l

i 1

($$)

l 4

i FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS A2 Required by the Proviciona cf ASME Coda Secticn XI NIS-2-14 Sheet 2 of 2

(,)_____--_-_______-_--_--__--____----_-______--_______-_-__-__-_----_-_-________

/~N CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this repair / replacement conforms to Section XI of the ASME Code.

Signed Ah b bS.

3l2Cl$ 7

/(Dwner oV OwnbhGs Designee Title tat 6 CERTIFICATE OF INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler ap Pressure Vessel Inspectors and the State or Province of C

, employed by A/ca 76 of A. < A n have inspected th'e h,u described in this report on

/Z/>s 19 XC an'd state that to the best of my knowledge and belief, this repair or replacement has been constructed in accordance with Section XI of the ASME Code.

By signing this certificate, o

Oneither the Inspector nor his employer makes any warranty, expressed or implied, concerning the repair or replacement described in this Report.

Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising form or connected with this inspection.

Date NJ /M AW)~

Commissions 0 T W lJl E

'~'

(Insbector)

O

FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS As Required by the Proviciona cf ASME Code Section XI I

l.

Owner - Northeast Nuclear Energy Co.

Date - 3/17/87 P.O. Box 128, Waterford, Ct. 06385 NIS-2-15 Sheet 1 of 2 fs

('--)2.

Plant - Millstone Nuclear Power Station Unit - 2 Waterford, Connecticut 3.

Work Performed By - Northeast Nuclear Energy Co.

Waterford, Ct. 06385 Work Order Number - M2-86-ll422 4.

Identification of System - REACTOR COOLANT SYSTEM 5.

(a) Applicable Construction Code - ASME SECTION III, CLASS 1 Edition - 1971 Addenda - W71 Code Cases - N/A (b) Applicable Edition of Section XI Utilized for Repairs or Replacements - 1980, W81 Addenda Code Cases -

6.

Identification of Components Repaired or Replaced, and Replacement Components Name of Component RC-040 Name of Mfr - VELAN MFR. CO.

Mfr's Serial No. - N/A National Board No. - N/A CRN No. - N/A Other Ident. - N/A Year Built - 1973 Repaired, Replaced.

ASME Code Stamp - YES or Replacement - REPAIRED

)(YesorNo)

}

7.

Description of Work - REMOVED UNACCEPTABLE DYE PENETRANT INDICATIONS BY j

GRINDING 8.

Tests Conducted:

Hydrostatic Test __X__ Pneumatic i

Nominal Operating Pressure Other Pressure _2290 PSIG Test Temp _532__deg. F 9.

Remarks - DYE PENETRANT INDICATIONS FOUND DURING ROUTINE INSERVICE INSPECTIONS l

l O

FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACIDENTS A2 Required by the Provicien2 cf ASME Coda Secticn XI NIS-2-15 Sheet 2 of 2 CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this repair / replacement conforms to Section XI of the ASME Code.

Alb A E.8.

sizcle7 Signed

/(Owner oV OwMP s Designee Title

'Date CERTIFICATE OF INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors anj the State or Province of Cf

, employed by N5/7 [" T of 4-hd h o have inspected the Age

~

ere described in this report on

/b/14 19 Tk and state that to the best of my knowledge and belief, this repair or replacement has been constructed in accordance with Section XI of the ASME Code.

By signing this certificate, O, ' neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the repair or replacement described in this Report.

Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising form or connected with this inspection.

Date l 0 /V)

/W2m Commissions C f W ///

(Inspector)

OO

FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS An Required by the Provici:na cf ASME Coda Secticn XI 1.

Owner - Northeast Nuclear Energy Co.

Date - 3/17/87 P.O. Box 128, Waterford, Ct. 06385 NIS-2-16 Sheet 1 of 2 I I 2.

Plant - Millstone Nuclear Power Station Unit - 2

\\- '

Waterford, Connecticut 3.

Work Performed By - Northeast Nuclear Energy Co.

Waterford, Ct. 06385

~

Work Order Number - M2-86-08655 4.

Identification of System - AUXILIARY FEEDWATER SYSTEM 5.

(a) Applicable Construction Code - ANSI B31.1 Edition - 1983 Addenda -

Code Cases -

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements - 1980, W81 Addenda Code Cases -

6.

Identification of Components Repaired or Replaced, and Replacement Components Name of Component MS-4A Name of Mfr - ANCHOR DARLING Mfr's Serial No. - E-615-1-1 National Board No. - N/A CRN No. - N/A Other Ident. - MPSN-285-303-1 Year Built - 1985 Repaired, Replaced, ASME Code Stamp - YES or Replacement - REPLACED t

(Yes or No) 7.

Description of Work - REPLACED VALVE 8.

Tests Conducted:

Hydrostatic Test __X__ Pneumatic Nominal Operating Pressure-Other Pressure __1375 PSIG Test Temp __70__deg. F 9.

Remarks -

bU i

FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS A2 Required by the Provicien:s cf ASME Coda Sectica XI NIS-2-16 Sheet 2 of 2 v _____________________________________________________________________________.

CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this repair / replacement conforms to Section XI of the ASME Code.

Signed A

A 6S-3l2Cl27 I'(Owner M DWnM s Designee Title

'Dat'e CERTIFICATE OF INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the Stap or Province of Cf

, employed by X/cc S G of he #m h a v e i n s p e c t e d t h'e A e /o e n e - c described in this report on N/r o 19 K/

an'd state that to the best of my knowledge and belief' t'his repair or replacement has been constructed in accordance with Section XI of the ASME Code.

By signing this certificate, p neither the Inspector nor his employer makes any warranty, expressed or

\\ j implied, concerning the repair or replacement described in this Report.

Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising form or connected with this inspection.

Na/JO OrL Commissions [T $ ///?

Date (In6pector)

'v'

F FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS As Required by the Provicien2 ef ASME Coda Secticn XI 1.

Owner - Northeast Nuclear Energy Co.

Date - 3/17/87 P.O. Box 128, Waterford, Ct. 06385 NIS-2-17 Sheet 1 of 2 I")2.

Plant - Millstone Nuclear Power Station Unit - 2

\\-

Waterford, Connecticut 3.

Work Performed By - Northeast Nuclear Energy Co.

Waterford, Ct. 06385 Work Order Number - M2-86-09502

~

M2-86-12203 4.

Identification of System - SERVICE WATER SYSTEM 5.

(a) Applicable Construction Code - ANSI B31.1 Edition - 1983 Addenda -

Code Cases -

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements - 1980, W81 Addenda Code Cases -

6.

Identification of Components Repaired or Replaced, and Replacement Components Name of Component - 8"-JGD-4 Name of Mfr - N/A Mfr's Serial No. - N/A National Board No. - N/A PDCR No. - N/A Other Ident. - MPSN-286-128-1 TO MPSN-286-128-6 e

Year Built - 1986 Repaired, Replaced, ASME Code Stamp - NO or Replacement - REPLACED (Yes or No) 7.

Description of Work - FABRICATED AND INSTALLED NEW SPOOLPIECE 8.

Tests Conducted:

Hydrostatic Test __X__ Pneumatic Nominal Operating Pressure Other Pressure __110 PSIG Test Temp __70__deg.

F 9.

Remarks -

O

FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS Au Required by the Proviticna cf ASME Coda Secticn XI NIS-2-17 Sheet 2 of 2 g

i/

'~-

CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this repair /repl cement conforms to Section XI of the ASME Code.

Signed in AEs gJze/8 7

/IOwner Mr"OkFdf's Designee Title

' Date CERTIFICATE OF INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler andJressure Vessel Inspectors and the StaD or Province of 87 employed by NM ZC 4 of 4/At r #4a 6 have inspected the' Xr,A e,,,,#

described in this report on

/L/tc 19 SL an'd state that to the best of my knowledge and belief, this repair or replacement has been constructed in accordance with Section XI of the ASME Code.

By signing this certificate,

'N neither the Inspector nor his employer makes any warranty, expressed or s

implied, concerning the repair or replacement described in this Report.

Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising form or connected with this inspection.

CT W/// 9 N1/x ")

NW" Commiasions Date (F6spector)

(~%.

V

FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS Aa Required by the Provisiona cf ASME Coda Section XI 1.

Owner - Northeast Nuclear Energy Co.

Date - 3/17/87 P.O. Box 128, Waterford, Ct. 06385 NIS-2-18 Sheet 1 of 2

[~S 2.

Plant - Millstone Nuclear Power Station Unit - 2 l

\\_

Waterford, Connecticut 3.

Work Performed By - Northeast Nuclear Energy Co.

Waterford, Ct. 06385 Work Order Number - M2-86-09226 M2-86-10435 M2-86-10001 M2-86-09227 M2-86-10169 M2-86-09126 M2-86-10658 M2-86-10657 M2-86-10656 4.

Identification of System - REACTOR COOLANT SYSTEM 5.

(a) Applicable Construction Code - Edition - 1971 Addenda - W71 Code Cases -

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements - 1980, W81 Addenda Code Cases -

a g x 6.

Identification of Components Repaired or Replaced, and Replacement

(_,)

Components Name of Component RC-039 Name of Mfr - VELAN MFR. CO.

Mfr's Serial No. 3 National Board No. - N/A CRN No. - N/A Other Ident. - MPSN-79-097 Year Built - 1979 Repaired, Replaced.

ASME Code Stamp - YES or Replacement - REPLACED (Yes or No)

Name of Component RC-413 Name of Mfr - ROCKWELL INT.

Mfr's Serial No. - AU-123 National Board No. - N/A CRN No. - N/A Other Ident. - MPSN-80-578 Year Built - 1980 Repaired, Replaced, ASME Code Stamp - YES or Replacement - REPLACED (Yes or No)

Name of Component RC-414 Name of Mfr - VALCOR ENG.

Mfr's Serial No. - N/A National Board No. - N/A CRN No. - N/A Other Ident. - N/A Year Built - 1982 Repaired, Replaced, ASME Code Stamp - NO or Replacement - REPAIRED (Yes or No)

Name of Component RC-415 Name of Mfr - VALCOR ENG.

Mfr's Serial No. - N/A National Board No. - N/A OYearBuilt-CRN No. - N/A Other Ident. - N/A 1982 Repaired, Replaced, ASME Code Stamp - NO or Replacement - REPAIRED (Yes or No)

I FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS A3 Required by the Provicion2 cf ASME Codo Section II NIS-2-18 Sheet 2 of 2

(

Name of Component RC-416 Name of Mfr - VALCOR ENG.

\\,

Mfr's Serial No. - N/A National Board No. - N/A CRN No..- N/A Other Ident. - N/A' Year Built - 1982 Repaired, Replaced, ASME Code Stamp - NO or Replacement - REPAIRED (Yes or No)

Name of Component RC-417 Name of Mfr - VALCOR ENG.

Mfr's Serial No. - N/A National Board No. - N/A-CRN No. - N/A Other Ident. - N/A Year Built - 1982 Repaired, Replaced, ASME Code Stamp - NO or Replacement -' REPAIRED (Yec or No) 7.

Description of Work - REMOVED SUBASSEMBLY, REPLACED / REPAIRED VALVES, REINSTALLED SUBASSEMBLY 8.

Tests Conducted:

Hydrostatic Test __X__ Pneumatic Nominal Operating Pressure Other Pressure _2290 PSIG Test Temp _532__deg. F 9.

Remarks -

CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this repair / replacement conforms to Section XI of the ASME Code.

Wc k.$ S-3lKl87 Signed i

'(Owner bh D'dbEd s Designee Title Date w

CERTIFICATE OF INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of W

employed by AT1 f'1 of A'n rf,~o have inspected the Acpu r described in this report on

/6/t1 19 fL and state that to the best of my knowledge and belief,'this repair or replacement has been constructed in eccordance with Section XI of the ASME Code.

By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the repair or replacement described in this Report.

Os Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising form or connected with this inspection.

Me Commissions

/ // )

Date

  1. 7 (Idspector) l

FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS As Required by the Provicicna cf ASME Coda Sectica II 1.

Owner - Northeast Nuclear Energy Co.

Date - 3/17/87 P.O. Box 128, Waterford, Ct. 06385 NIS-2-19 Sheet 1 of 2

[

12.

Plant - Millstone Nuclear Power Station Unit - 2

\\~s' Waterford, Connecticut 3.

Work Performed By - Northeast Nuclear Energy Co.

Waterford, Ct.'06385 Work Order Number - M2-86-06087 M2-86-10662 M2-86-10661 M2-86-09101 M2-86-10663 M2-86-10664 M2-86-06805 M2-85-12254 4.

Identification of System - REACTOR COOLANT SYSTEM 5.

(a) Applicable Construction Code - ASME Section III Edition - 1980 Addenda - S80 Code Cases - N/A (b) Applicable Edition of Section XI Utilized for Repairs or Replacements - 1980, W81 Addenda Code Cases - N/A 6.

Identification of Components Repaired or Replaced, and Replacement o

Components Name of Component RC-422 Name of Mfr - VALCOR ENG.

Mfr's Serial No. - 214150003-1 National Board No. - N/A CRN No. - N/A Other Ident. - MPSN-286-051-1 Year Built - 1982 Repaired, Replaced, ASME Code Stamp - NO or Replacement - REPLACED (Yes or No)

Name of Component RC-423 Name of Mfr - VALCOR ENG.

Mfr's Serial No. - N/A National Board No. - N/A CRN No. - N/A Other Ident. - N/A Year Built - 1982 Repaired, Replaced, ASME Code Stamp - NO or Replacement - REPAIRED (Yes or No)

Name of Component RC-424 Name of Mfr - VALCOR ENG.

Mfr's Serial No. - 214150003-2 National Board No. - N/A CRN No. - N/A Other Ident. - MPSN-286-051-1 Year Built - 1982 Repaired, Replaced, ASME Code Stamp - NO or Replacement - REPLACED (Yes or No)

Name of Component RC-425 Name of Mfr - VALCOR ENG.

Mfr's Serial No. - N/A National Board No. - N/A CRN No. - N/A Other Ident. - N/A

[s l'\\ Year Built - 1982 Repaired, Replaced, i

ASME Code Stamp - NO or Replacement - REPAIRED (Yes or No)

FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS A3 Required by the Provicicna cf ASME Codo Secticn II NIS-2-19 Sheet 2 of 2

' 7.

Description of Work - REMOVED SUBASSEMBLY, REPLACED / REPAIRED VALVES, REINSTALLED SUBASSEMBLY 8.

Tests Conducted:

Hydrostatic Test __X__ Pneumatic Nominal Operating Pressure Other a

Pressure _2290 PSIG Test Temp _532__deg. F 9.

Remarks -

CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this repair / replacement conforms to Section XI of the ASME Code.

iib.

3/X/87 Signed h k

/(Owner c(f Ownshs Designee Title

'Dat'e r

O(_/

CERTIFICATE OF INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Cf

, employed by L/ v o 7t 'E of

/Jer#a />

have inspected the Deckowouu described in this report on

'46 c 19 GT, and s'ta'te that to the best of my knowledge and belief,'this repair or replacement has been constructed in accordance with Section XI of the ASME Code.

By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the repair or replacement described in this Report.

Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind crising form or connected with this inspection.

Date

/fd M2e Commissions

~

(Inspector)

U

FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEtENTS Aa Required by the Provicicna cf ASME Coda Section II 1.

Owner - Northeast Nuclear Energy Co.

Date - 3/17/87 P.O. Box 128, Waterford, Ct. 06385 NIS-2-20 Sheet 1 of 2

/~ '

Plant - Millstone Nuclear Power Station Unit - 2 k

2.

Waterford, Connecticut 3.

Work Performed By - Northeast Nuclear Energy Co.

Waterford, Ct. 06385 Work Order Number - M2-86-08656 4.

Identification of System - AUXILIARY FEEDWATER SYSTEM 5.

(a) Applicable Construction Code - ANSI B31.1 Edition - 1983 Addenda -

Code Cases -

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements - 1980, W81 Addenda Code Cases -

6.

Identification of Components Repaired or Replaced, and Replacement Components Name of Component MS-4B Name of Mfr - ANCHOR DARLING Mfr's Serial No. - E-615-1-2 National Board No. - N/A CRN No. - N/A Other Ident. - MPSN-285-303-2 Year Built - 1985 Repaired, Replaced, ASME Code Stamp - YES or Replacement - REPLACED fs (Yes or No)

('

7.

Description of Work - REPLACED VALVE 8.

Tests Conducted:

Hydrostatic Test __X__ Pneumatic Nominal Operating Pressure Other Pressure __1375 PSIG Test Temp __70__deg. F 9.

Remarks -

FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS A7 Required by the Provigicna cf ASME Codra Secticn XI NIS-2-20 Sheet 2 of 2 (3

\\s-) ______________________________________________________________________________

CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this repair / replacement conforms to Section XI of the ASME Code.

bnh*

/r E S.

3lWl27 Signed

'(~ Owner d/ Olfh F s Designee Title

'Date CERTIFICATE OF INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Cf

, employed by Ak/? S*T of

/,dur m e have inspected the /w%<-r described in this report on

/LA e 19 F5 and state that to the best of my knowledge and belief,'this repair or replacement has been constructed in accordance with Section XI of the ASME Code.

By signing this certificate, g) neither the Inspector nor his employer makes any warranty, expressed or s,/ implied, concerning the repair or replacement described in this Report.

Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising form or connected with this inspection.

Date ' c/E7 Nb Commissions CTW ///Y (Inspector) s

FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS Aa Required by the Provicienn cf ASME Coda Sectien XI 1.

Owner - Northeast Nuclear Energy Co.

Date 23-1987 P.O. Box 128, Waterford, Ct. 06385 NIS-2-21 Sheet 1 of 2

(

) 2.

Plant - Millstone Nuclear Power Station Unit - 2 Waterford, Connecticut 3.

Work Performed By - Northeast Nuclear Energy Co.

Waterford, Ct. 06385 Work Order Number - M2-86-11041 4.

Identification of System - SERVICE WATER SYSTEM 5.

(a) Applicable Construction Code ANSI B31.1 Edition - 1983 Addenda -

Code Cases -

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements - 1980, W81 Addenda Code Cases -

6.

Identification of Componenets Repaired or Replaced, and Replacement Components Name of Component "C"

SERVICE WATER Name of Mfr. - BYRON JACKSON PUMP Name of Mfr - HAYWARD-TYLER National Board No.

N/A PDCR No. -

N/A Other Ident. - N/A Year Built - 1983 Repaired, Replaced, c

(~

ASME Code Stamp - N/A or Replacement - REPAIRED (Yes or No) 7.

Description of Work - WELD REPAIRED AREAS OF CORROSION / EROSION IN WELDS 8.

Tests Conducted:

Hydrostatic Test __X__ Pneumantic Nominal Operating Pressure Other Pressure 110 Test Temp __70__deg.

F 9.

Remarks -

l I

FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS An Required by the Provioicna cf ASME Coda Secticn II NIS-2-21 Sheet 2 of 2 (8)---_-__---_-_-_-_-_---_-_--_-_----_---___---_-_---______-----_-_-----_-_-____.

CERTIFICATE OF COMPLIANCE We certify that the statements made in this reprot are correct and this repair / replacement conforms to Section XI of the ASME Code.

~

Signed i

A 2s.

r/2c/2, IlOwnerl6r"OWd6V's Designee Title

' Dat'e CERTIFICATE OF INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Y

employed by NIX M of

/>m-r 4 o have inspected Jhe a m o<

described in this report on

/ /9s 19 AE and state that to the best of my knowledge and belief, this repair or replacement has been constructed in accordance with Section XI of the ASME Code.

By signing this certificate,

~

neither the Inspector nor his employer makes any warranty, expressed or

{\\ implied, concerning the repair or replacement described in this Report.

lFurthermore, neither the Inspector nor his employer shall be liable in any sm, manner for any personal injury or property damage or a loss of any kind crising form or connected with this inspection.

  1. [8/k 7//o M /

AN~

Commissions Date (T' spector )

n i

O

FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS Au Required by the Provicicn2 cf ASME Coda Secticn XI 1.

Owner - Northeast Nuclear Energy Co.

Date 23-1987 P.O. Box 128, Waterford, Ct. 06385 NIS-2-22 Sheet 1 of 2 f3

'",)

2.

Plant - Millstone Nuclear Power Station Unit - 2 t

Waterford, Connecticut 3.

Work Performed By - Northeast Nuclear Energy Co.

Waterford, Ct. 06385 Work Order Number - M2-86-12379 4.

Identification of System - SERVICE WATER SYSTEM 5.

(a) Applicable Construction Code ANSI B31.1 Edition - 1983 Addenda -

Code Cases -

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements - 1980, W81 Addenda Code Cases -

6.

Identification of Componenets Repaired or Replaced, and Replacement Components Name of Component - 24"-JGD-3 Name of Mfr. - N/A Mfr Serial No. - N/A National Board No. -

N/A PDCR No. -

N/A Other Ident. - N/A Year Built - 1983 Repaired, Replaced, ASME Code Stamp - NO or Replacement - REPAIRED

[

) (Yes or No) 7.

Description of Work - WELD REPAIRED AREAS OF CORROSION / EROSION IN WELDS 8.

Tests Conducted:

Hydrostatic Test __X__ Pneumantic Nominal Operating Pressure Other Pressure 94 Test Temp __70__deg. F 9.

Remarks - HYDROSTATIC TEST CONDUCTED IN ACCORDANCE WITH APPROVED ISI PROGRAM RELIEF REQUEST v

l

FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS A2 Required by the Provicienn cf ASME Coda Secticn XI NIS-2-22 Sheet 2 of 2 m

CERTIFICATE OF COMPLIANCE We certify that the statements made in this reprot are correct and this repair / replacement confo s to Section XI of the ASME Code.

Signed AB. S.

7/.Ta/8 7

'(Owner Wr bPJs Designee Title

'Dafe CERTIFICATE OF INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors anp the_ State or Province of (M'

employed by.Nf9 L4 T of

//Ar#x o have inspected the 4'p^ ' d i described in this report on

/4/29 19 bd and state that to the best of my

~

knowledge and belief, this repair or replacement has been constructed in accordance with Section XI of the ASME Code.

By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the repair or replacement described in this Report.

O, Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising form or connected with this inspection.

Yh /P) bD W Commissions (W/ll Date (Irfspector) 6 kJ l

i FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS Aa Required by the Proviaienn ef ASME Coda Sectica XI 1.

Owner - Northeast Nuclear Energy Co.

Date 23-1987 P.O. Box 128, Waterford, Ct. 06385 NIS-2-23 Sheet 1 of 2

/~T ty,/ 2.

Plant - Millstone Nuclear Power Station Unit - 2 Waterford, Connecticut 3.

Work Performed By - Northeast Nuclear Energy Co.

Waterford, Ct. 06385 H

Work Order Number - M2-86-12011 4.

Identification of System - REACTOR BUILDING CLOSED COOLING WATER 5.

(a) Applicable Construction Code ANSI B31.1 Edition - 1983 Addenda -

Code Cases -

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements - 1980, W81 Addenda Code Cases -

6.

Identification of Componenets Repaired or Replaced, and Replacement Components Name of Component RB-332 Name of Mfr. - J. E. LONERGAN Mfr Serial No. - N/A National Board No. -

N/A PDCR No. -

N/A Other Ident. - N/A Year Built - 1974 Repaired, Replaced, e

ASME Code Stamp - NO or Replacement - REPAIRED

[ ] (Yes or No) x 7.

Description of Work - VALVE CUT OUT, GASKET REPLACED, WELDED BACK IN PLACE 8.

Tests Conducted:

Hydrostatic Test Pneumantic Nominal Operating Pressure X

Other Pressure Test Temp deg. F 9.

Remarks - 3/4" VALVE EXEMPT FROM HYDROSTATIC TESTING O

FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS As Requirrd by tha Praviciona of ASME Coda S;ction XI i

NIS-2-23 Sheet 2 of 2 g

Q )------------------------------------------------------------------------------

CERTIFICATE OF COMPLIANCE We certify that the statements made in this reprot are correct and this repair / replacement confor s to Section XI of the ASME Code.

Signed A 6. S -

3l30l97

  1. (Owner Mr MWM Designee Title bats CERTIFICATE OF INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler an P essure Vessel Inspectors and the Statg or Province of

, employed by Nr4 2'4 of B..e rA* o have inspected the Ate, e described in this report on

/2/rs 19 FC and state that to the best of my knowledge and belief, this repair or replacement has been constructed in accordance with Section XI of the ASME Code.

By signing this certificate,

~

neither the Inspector nor his employer makes any warranty, expressed or

[d urthermore,,s\\ implied, concerning the repair or replacement described in th

\\

F neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising form or connected with this inspection.

Date b4 /D MN~

Commissions 6

N/h (Idspector) l

FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS Aa Required by the Proviaicn2 cf ASME Coda Section XI 1.

Owner - Northeast Nuclear Energy Co.

Date 23-1987 P.O. Box 128, Waterford, Ct. 06385 NIS-2-24 Sheet 1 of 2

(

2.

Plant - Millstone Nuclear Power Station Unit - 2 Waterford, Connecticut 3.

Work Performed By - Northeast Nuclear Energy Co.

Waterford, Ct. 06385 Work Order Number - M2-86-11918 I

4.

Identification of System - CHEMICAL VOLUME CONTROL SYSTEM 5.

(a) Applicable Construction Code ASME SECTION III, CLASS 2 Edition - 1983 Addenda -

Code Cases -

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements - 1980, W81 Addenda Code Cases -

6.

Identification of Componenets Repaired or Replaced, and Replacement Components Name of Component CH-326 Name of Mfr. - J. E. LONERGAN Mfr Serial No. - N/A National Board No. -

N/A PDCR No. -

N/A Other Ident. - N/A Year Built - 1974 Repaired, Replaced, ASME Code Stamp - YES or Replacement - REPAIRED c

{)(YesorNo) 7.

Description of Work - VALVE CUT OUT, GASKET REPLACED, WELDED BACK IN PLACI 8.

Tests Conducted:

Hydrostatic Test Pneumantic Nominal Operating Pressure X

Other Pressure Test Temp deg. F 9.

Remarks - 3/4" VALVE EXEMPT FROM HYDROSTATIC TESTING

\\

(_)

FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS Au Required by the Pr vicicna of ASME Codo Secticn XI NIS-2-24 Sheet 2 of 2

['N q,) ___________________ --_-_-____-_. ________-____-_-_-__________________-____-.

CERTIFICATE OF COMPLIANCE We certify that the statements made in this reprot are correct and this repair / replacement conforms to Section XI of the ASME Code.

bAdl A ES.

shele7 Signed

' (Owner (fr '6WY's Designee Title

' Dat'e CERTIFICATE OF INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of C'7~

, employed by AM G 2df of Ab77+o have inspected phe At o m e described in this report on

/4/tc 19 8C and state that to the best of my knowledge and belief, this repair or replacement has been constructed in accordance with Section XI of the ASME Code.

By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or

,3

('d Furthermore,) implied, concerning the repair or replacement described in this Report.

neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising form or connected with this inspection.

Date dM NN~

Commissions C

/Of (inspector)

FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS An Required by the Provicien2 cf ASME Coda Sectica II 1.

Owner - Northeast Nuclear Energy Co.

Date 26-1987 P.O. Box 128, Waterford, Ct. 06385 NIS-2-87-025 Sheet 1 of 2 s / 2.

Plant - Millstone Nuclear Power Station Unit - 2 Waterford, Connecticut 3.

Work Performed By - Northeast Nuclear Energy Co.

Waterford, Ct. 06385 Work Order Number - M2-85-05727 M2-85-12716 M2-86-10452 4.

Identification of System - SERVICE WATER SYSTEM 5.

(a) Applicable Construction Code - ANSI B31.1 Edition - 1983 Addenda -

Code Cases -

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements - 1980, W81 Addenda Code Cases -

6.

Identification of Componenets Repaired or Replaced, and Replacement Components Name of Component - STRAINER L1A Name of Mfr. - R. P. Adams COVER Mfr's Serial No. - N/A National Board No. - N/A g-g PDCR No.

q j

- N/A Other Ident. - MPSN-285-224-1 Year Built - 1985 Repaired, Replaced.

ASME Code Stamp - NO or Replacement -

REPLACED (Yes or No)

Name of Component - STRAINER L1C Name of Mfr. - R. P. Adams COVERS Mfr's Serial No. - N/A National Board No. - N/A PDCR No. - N/A Other Ident. - MPSN-285-224-1 Year Built - 1985 Repaired, Replaced, ASME Code Stamp - NO or Replacement -

REPLACED (Yes or No) 7.

Description of Work - REPLACED COVERS ON STRAINERS 8.

Tests Conducted:

Hydrostatic Test __X__ Pneumantic Nominal Operating Pressure Other Pressure 94 Test Temp __70__deg. F 9.

Remarks -

O

FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS An Required by the Provicienn cf ASME Coda Secticn XI NIS-2-87-025 Sheet 2 of 2 O _____________________________________________________________________

y CERTIFICATE OF COMPLIANCE We certify that the statements made in this reprot are correct and this repair / replacement conforms to Section XI of the ASME Code.

A E S.

3/zc/av Signed c!(OwnerC6r % r(&'s Designee Title

'Dat'e CERTIFICATE OF INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler aAd Pressure Vessel Inspectors and the State or Province of

( 'P employed by Mt'e f v'/

of n<he have inspected the %/~ -e described in this report on

/'vis 19 86 and state that to the best of my knowledge and belief, this repair or replacement has been constructed in accordance with Section XI of the ASME Code.

By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the repair or replacement described in this Report.

V Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising form or connected with this inspection.

Date kh /W

/2Mh Commissions I[///9 (Ir(spector) i l