Forwards Equipment Qualification Branch Addl Comment on Preliminary Review of External Events Analyses Re Probabilistic Safety Assessment
ML20209D327
Person / Time
Site: Seabrook  
Issue date: 09/21/1984
From: Brocoum S
Office of Nuclear Reactor Regulation
To: Thadani A
Office of Nuclear Reactor Regulation
Shared Package
ML20209C800 List:
References
FOIA-87-6 NUDOCS 8410020092
Download: ML20209D327 (2)


Text

_ _ _ _ - _ _ _ _ _ _ _ _ _.

/

'o, UNITED STATES y

g NUCLE AFLREGULATORY COMMISSION p

WASHINGTON. D. C. 20555 s.,.....J SEP 211984 i

MEMORANDUM FOR:

Ashok Thadani, Chief Reliability and Risk Assessment Branch Division of Safety Technology l

[JamesP. Knight,AssistantDirectorfor THRU:

Components & Structures Engineering

/

g/ ; -

Division of Engineering FROM:

Stephan Brocoum, Acting Chief Geosciences Branch Division of Engineering

SUBJECT:

PRELIMINARY REVIEW 0F THE EXTERNAL EVENTS ANALYSES IN THE SEABROOK STATION PROBABILISTIC SAFETY ASSESSMENT (PSA) - ADDITIONAL COMMENT l

Attached to this memorandum is an additional review coment to be l

transmitted to the Seabrook applicants.

O

/. 5 hn~

Stepha,1 Brocoum, Acting Chief Geosciences Branch Division of Engineering

Enclosure:

As stated cc:

R. Vollmer J. Knight s

Fo T M - 8 7-oo 4 F. Rowsome S. Brocoum L. Reiter bhf R. Frahm T. Sullivan S. Davis P. Sobel A. Masciantonio ipz4+92m xk

Equipment Qualification Branch Preliminary Coment on Seabrook PSA 5.

With respect to relay chatter, there are those relay trips which may require resetting at local panels, resulting in failure to reset if the operator is presented with a scenario for which he has not been trained or no procedure is available for guidance. Failure to reset is equivalent to relay failure. Please provide additional information on the analysis of relay chatter and address the impact on the various systems. Lack of operator action to reset under conditions of stress leading to relay failure should be considered.

_ _ _ _ _ _ _ _ _ _ _ _ _ _ - _ _ _ _ - _ - _ _ _ _ _ _ _ _. _ _ _ _ _ _ _ _ _ _ _ _ _ _ - _ - - -. _ - _ - _ _ _ - _ _ -.. - - - _ - -