' Attachment I to WO 99-0051

+

_,Page,1 of 1 PLANT SYSTEMS p

3/4.7.5 ULTIMATE HEAT SINK 1

LIMITING CONDITION FOR OPERATION 3.7.5 The ultimate heat sink (UHS) shall be OPERABLE with:

a. The crest of the UHS dam below the rip rap cover and corresponding water level at or above elevation 1070 Mean Sea Level, USGS datum, and
b. The plant inlet water temperature of less than or equal to 90*F.

APPLICABILITY: MODES 1,2,3, and 4.

)

ACTION:

With the requirements of the above specification not satisfied, be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

NOTE: Until September 30,19981999, the following ACTIONS supersede the above ACTION:

a.

With the plant inlet water temperature >90*F but <95 F:

1.

within one hour verify two trains of residual heat remos al. two trains of component cooling water, and two trains of essential service water are

OPERABLE, 2.

verify at least once per hour that the plant inlet water temperature is <95 F, and 3.

within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> restore the plant inlet water temperature to 90*F or less.

4.

With any of the above requirements not satisfied, be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

b.

With the UHS Inoperable for any reason other than temperature, be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

SURVEILLANCE REQUIREMENTS I

4.7.5 The UHS shall be determined OPERABLE:

a.

At least once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> by verifying the above required water temperature and water level to be within their limits, and b.

At least once per 12 months by verifying that the crest of the UHS dam below the i

j rip rap cover is at or above elevation 1070 Mean Sea Level, USGS datum.

l WOLF CREEK - UNIT 1 3/4 7-13 Amendment No. 448 l

9907090206 990630 t

PDR ADocK 05000482 PM p

l Attachment II to WO 99-0051 Page,1 of 1 9

LIST OE' COttfITMENTS

)

The following table identifies those actions committed to by Wolf Creek Huclear Operating Corporation (WCNOC) in this document.

Any other statements in this submittal are provided for information purposes and are not considered to be commitments.

Please direct questions regarding these commitments to Mr.

{

Michael J.

Angus, Manager Licensing and Corrective Action at Wolf Creek Generating Station, (316) 364-4077 COMMITMENT Duo Date/ Event None

.