ML20207R391

From kanterella
Jump to navigation Jump to search
Monthly Operating Rept for Feb 1987
ML20207R391
Person / Time
Site: Harris 
Issue date: 02/28/1987
From: Watson R, Westmoreland J
CAROLINA POWER & LIGHT CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
HO-876017-(O), NUDOCS 8703170184
Download: ML20207R391 (5)


Text

__ ____

OPERATING DATA REPORT-DOCKET NO. 050-400 DATE 3/5/87

. COMPLETED BY'J.'H. Westmoreland TELEPHONE (919) 362-2597' OPERATING STATUS 1.-Unit'Name: Shearon Harris' Unit 1

2. Reporting-Period: February 1987 Notes:
3. Licensed' Thermal Power-(MWt): 2775 Power Ascension Testing in
4. Nameplate Rating (Gross MWe): 950 Progress.

5 ' Design Electrical Rating (Net-MWe): 900

6. Maximum Dependable Capacity (Gross-MWe): 950
7. Maximum Dependable Capacity (Net-MWe): 900
8. If Changes Occur in. Capacity Ratings (Items Number 3 Through 7) Since Last Report, Give Reasons: N/A
9. Power-Level To Which Restricted, If Any (Net-MWe):

None

10. Reasons.For Restrictions, If Any:

N/A This Month Yr.-to-Date

. Cumulative

'11. Hours in Report Period 672 962 962

12. Number Of Hours Reactor Was Critical 644 803 803
13. Reactor Reserve Shutdown Hours 0

0 0

14. Hours Generator On-Line 610 678 678
15. Unit Reserve Shutdown Hours

.0 0

0

16. Gross. Thermal Energy Generated (MWH) 605154.24 655,070.94 655,070.94
17. Gross Electrical Energy Generated (MWH) 148050 152200 152200
18. Net' Electrical Energy Generated (MWH) 118886 118886 118886

-19. Unit Service Factor N/A N/A N/A

20. Unit _ Availability Factor N/A N/A N/A
21. Unit. Capacity Factor (Using MDC Net)

N/A N/A N/A 22.' Unit Capacity Factor (Using DER Net)

N/A N/A N/A

23. Unit Forced Outage Rate N/A N/A N/A-
24. Shutdowns Scheduled Over Next 6 Months (Type, Date, and Duration of Each);
25. If Shut Down At End Of Report Period, Estimsted Date of Startup:

i

26. Units In Test Status (Prior to Commercial Operation):

Forecast Achieved INITIAL CRITICALITY 12/30/86 1/3/87-INITIAL ELECTRICITY 1/11/87 1/19/87 COMMERCIAL OPERATION 4/6/87 N/A I

1 f-i.

A 1

CEH087/ attach 3464/1/OS4

  1. V

/

G703170184 870228 PDR ADOCK 05000400=

/

R PDR.

CP&LICO.

PLANT PERFORMANCE DATA SYSTEM.

APPENDIX B - AVERAGE DAILY POWER LEVEL HARRIS UNIT 1 DOCKET NO. 050-400 COMPLETED BY J. H. WESTMORELAND TELEPHONE (919)362-2597 February 1987 DAY AVG. DAILY POWER LEVEL DAY AVG. DAILY ~ POWER' LEVEL (MWE-NET)

(MWE-NET) 1 102 17 173 2

118 18 188 3

111 19 186 4-108 20 311 5

105 21 319 6

96 22 295 7

160 23 339 8

177 24 341 9

182

'25 335 10 131 26 331 11.

180 27 248 12 201 28 13 16 14 15 15 56 16 163 1.16 - 8 CEH087/ attach 3464/2/OS4

m UNIT S!!UTDOWNS AND POWER REDUCTIONS DOCKET NO.

050-400 UNIT NAME:

Harris DATE:

3/5/87 COMPLETED BY:

J. H. Westmoreland REPORT MONTH: February 1987 TELEPHONE:

(919) 362-2597 i

% pf' Licensee y

Cause & Corrective cm n

No.

Date o*

Event en Action to 3

k j($

Report #

$[

y Prevent Recurrence S

Ii-E

  1. 5 G

$u E

~

a e

mu u

87-005 2/13/87 5

8.53 B

5 N/A XX PUMPXX Unit was removed from grid to Test 1B Vacuum Pump and to calibrate steam _

generator level control instrumentation. Tests were completed and unit returned to service.87-006 2/14/87 F

24.10 B

5 N/A.

HH PUMPXX Unit was taken off line to repair main feedwater pump "1A" Discharge leak. Leak was repaired and unit returned to service.

1 2

3 4

F: Forced Reason:

Method:

Exhibit G-Instructions S: Scheduled A-Equipment Failure (Explain) 1-Manual for Preparation of Data B-Maintenance or Test 2-Manual Scram.

Entry Sheets for Licensee C-Refueling 3-Automatic Scram.

Event Report (LER) File D-Regulatory Restriction 4-Continued (NUREG-0161)

E-Operator Training & License Examination 5-Reduced Load F-Administrative 6-Other 5

G-Operational Error (Explain)

Exhibit I-Same Source H-Other (Explain)

CEH086/ attach 3464/3/054

UNIT SHUTDOWNS AND POWER REDUCTIONS DOCKET NO.

050-400 UNIT NAME:

Harris DATE:-

3/5/87-COMPLETED BY:

J. H. Westmoreland REPORT-MONTH: February 1987 TELEPHONE:

(919) 362-2597 g.

  • - en 3 Licensee v

Cause & Corrective No.

Date y

yy{

Event E*

Action to c

yg o,

ga:

Report #

j,,

d Prevent. Recurrence R

85

.5" RB 8"

j s

o x

x mv v

87-007 2/27/87 F

58:23 A

2 87-008 HH PUMPXX Hanual Reactor Trip initiated due to loss of feedwater. ' Root cause investigation in progress.

1 2

3 4

F: Forced Reason:

Method:

Exhibit G-Instructions S: Scheduled A-Equipment Failure (Explain) 1-Manual for Preparation of Data B-Maintenance or Test 2-Manual Scram.

Entry Sheets for Licensee C-Refueling 3-Automatic Scram.

Event Report (LER) File D-Regulatory Restriction 4-Continued (NUREC-0161)

E-Operator Training & License Examination 5-Reduced Load F-Admini strative 6-Other 5

C-Operational Error (Explain)

Exhibit 1-Same Source H-Other (Explain)

CEH086/ attach 3464/5/OS4

Carolina Power & Light Company l

v o,~ a m.., r v v - =,, e n-,

l HARRIS NUCLEAR PROJECT l

P. O. Box 165 i

New Hill, North Carolina 27562 MAR 121987 File Number:

SHF/10-15505 Letter Number:

HO-876017 (0)

Document Control Desk United States Nuclear Regulatory Commission Washington, D.C.

20555 HARRIS NUCLEAR PROJECT DEPARTMENT UNIT NO. 1 DOCKET NO. 50-400 LICENSE NO. NPF-63 MONTHLY OPERATIONS REPORT

Dear Sirs:

In accordance with Technical Specifications 6.9.1.5 for the Harris Nuclear Plant, Unit No. 1, Carolina Power & Light Company herewith submits the report of operation statistics and shutdown experience for the month of February 1987.

Yours very truly, R. A. Watson Vice President Harris Nuclear Project MWH:skm l

Enclosure i

cc:

Dr. J. Nelson Crace (NRC)

Messrs.

J. M. Taylor (NRC)

C. F. Maxwell (NRC-SHNPP)

R. G. Oehl (DOE) i i

I MEM/HO-8760170/ PACE 1/0S1