. _. _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
007, t e ggg Docket No. 50-219 Mr. E. E. Fitzpatrick Vice President and Director Oyster Creek Nuclear Generating Station Post Office Box 388 Forked River, New Jersey 08731
Dear Mr. Fitzpatrick:
SUBJECT:
REQUEST FOR ADDITIONAL INCORMATION, OYSTER CREEK SE15MIC REEVALUATION (TAC h0. 68217)
During the meeting with GPU Nuclear Corporation (GPUN/ licensee) and your consultants on May 25, 1988, the staff had indicated reservation with regards to the Power Spectral Der.sity (PSD) function developed by URS/Blume (a licensee consultant). The conputed PSD function started having unacceptable (15%) excursions below the target PSD after 1.5 Hz.
Frequent excursions of larger magnitudes were indicated after 3 Hz.
Intuitivel felt that such excursions (or dips below the target PSD)y, however, the staff could be acceptable if the responses at higher elevations using the computed PSD (corresponding to Oyster Creek input notion) are shown to be higher than those using the target PSD. The staff's consultant, Brookhaven National Laboratory, has developed a computer Code whereby the structural respenses can be obtained by using the input motion PSD functions.
As this is a state-of-the-art development, the staff decided to use the available Code for cccparing responses. The infomation needed from the licensee to perfom these analyses it as follows:
1.
Digital Power Spectral Censity computed from the Oyster Creek Time-History.
2.
Digitized Target Power Spectral Density as conputed from a suite of corparable actual earthquakes.
3.
Oyster Creek Tire History in digitized form.
4 Structural model properties of the Reactor Euilding - Geometry, Passes.
[
Moment of Inertia, Arcas, Beam Properties. Parpings, spring constants, etc.
5.
Soil springs and darping used in the prior simplified analyses.
It is preferable to have the data requested in 1, 2 and 3 on floppy disks which can be directly used as input in the analysis. You are requested to I
respond to this request for additional infomation by October 31,19FS, so L
that the staff can conplete its review at an early date.
I 8810170300 881012 j
PDR ADOCK 05000229 P
pm
,i bF &
///
s e
e
-?-
The reporting and/or recordkcepina requirements contained in this letter affect fewer than ten respondents; therefore, OMB clearance is ret required under P.L.97-511.
Sincerely, 6
Alexander W. Drcmerick, Project Mar.ager Project Directorate I-4 Division of Reactor Projects I/II Office of Nuclear Reactor Regulation cc: See next page DISTRIBUTION Docket File NRC & Local'PORs PDI-4 RF SAVarg3 BABoger SMNorris AWDromerick OGC E. Jordan R. Grimes ACRS (10)
S W
ick:ah J
10/LQ/88 10/g/88 10/ /88 4
J OFot
'ft
O Fr. f. E. Fitzpatrick Oyster Creek Nuclear Cyster Creek Nuclear Generating Station Generating Station cc:
Ernest L. Blake. Jr.
Resident Inspector Shaw. Pittran. Fetts and Trowbridge c/o U.S. NRC 2300 N Street. NW Fest Office Box 445 Washington, D.C.
20037 Forked River New Jersey 00731 J.B. Liberwan. Esquire Comissioner Pishop. Liberman. Cook, et al.
New Jersey Cepartrent of Energy I',55 Avenue of the Anericas 101 Comerce Street New York. New York 10036 Newark, New Jersey 07107 Mr. David M. Scott, Chief Regional Administrator, Region !
Bureau of Nuclear Engineering U.S. Nuclear Regulatory fom itsien Department of Environrental rrotection 475 Allendale Road CN 411 King of Prussia. Pennsylvania 19406 Trenton, hew Jersey 026?5 SkV Licensing Manager GPU Nuclear Corporation l
1 Upper Pond Road Parsippany. New Jersey 07058 Deputy Attorney General State of kew Jersey Departrent of Law and Public Safety 36 West State Street - CN 112 i
Trenten. New Jersey 08625 Mayor Lacey Township 818 West Lacey Road i
Forked River. New Jersey 08731 Licensing Manager 1
Oyster Creek Nuclear Generating Station Mail Step: Site Emargency Bldg.
P. C. Box 388 l
Forked River. New Jersey 08731
\\
1 I
i i
i l
l