Concludes That Plant Can Be Safely Returned to Operation for at Least One Addl Fuel Cycle Based on Review of Info Provided in Util 881021 & 1110 Ltrs Re IGSCC Insps.Insps That Were Performed Meet Guidelines of Generic Ltr 88-01
ML20206H877
Person / Time
Site: FitzPatrick 
Issue date: 11/18/1988
From: Capra R
Office of Nuclear Reactor Regulation
To: Brons J
POWER AUTHORITY OF THE STATE OF NEW YORK (NEW YORK
References
GL-88-01, GL-88-1, TAC-69162, NUDOCS 8811230413
Download: ML20206H877 (6)


Text

- _ _ _ _ _ _ _ _ _ _ _

Novenbar 18, 1988 o.

Docket No. 50-333 OfSTRIBUTION

( nochet fileJ PDI-1 Pdg Local PDR RCapra DLaBarge CVogan Mr..ichn C. Rrons SVarga EJordan Senior Vice President, Nuclear BBoger OGC Ceneration ACRS (10)

JPartlow Power Authority of the State NRC POR RKoo of New York CCheng RPermann 123 Main Street White Plains, New York 10601

Dear Mr. Rr,

ons:

SUBJECT:

IGSCC INSPECTIONS - RffUEL 8/ CYCLE 9 REFUELING OUTAGE RE:

JAMES A. FIT 7 PAW ICK NUCLEAR POWER PLANT (TAC 69162)

Your submittals dated November 10,1988 (JPN-89-061 and 88-062) infonned us that, during the current refueling outage, a total of 92 welds in the reactor coolant system pipino were ultrasonically inspected by personnel cualified in accordance with the EPRI-BWROG train'.ng program. Nine welds with IGSCC indications were repaired using weld overlays; two welds which had previous IGSCC indications were inspected, found not to contain IGSCC, and will continue to be monitored in the future; four welds with IGSCC indications were evaluated and found to be acceptable; three of the six bi-retallic welds in the PHR loops that contain Inconel 182 weld butter were inspected with no IGSCC indications fourd; and nine safe-end to nozzle welds were inspected with no !GSCC indications found. All of the welds which were previously overlayed were reinspected and found to still rcet the full structural or standard design requirements without the need for additional overlays. However, the three weld overlays applied to the "B" Core Spray loop during the 1987 refuelino outage were not inspected, since you have.nade a comitnent to replace the piping during the 1989 mid-cycle maintenance outage. Also during the 1989 mid-cycle maintenance outace, you have comitted to inspect welds 28-33, 28 11? And 28-37.

Additionally. your letter of October ?1,1988 transmitted infomation t

concerning two IGSCC cracks found in the heat affected rene of a weld in the downtomer of the

'8" Core Spray loop inside the reactor vessel. A descriptien of the location, orientation, repr.ir methed used, results of this and other I

in-vessel inspections, stress analysis related to the Core Sprav repair, and safety evaluation were provided.

Based on our review of the infonration you provided and the intended use of the Hydrogen Water Chemis:ry System during Cycle 9, we find that the inspections anc repairs that were performed, as well as the cra:k growth analysis date that was f uteitted, reet the guidelines of Generic Lv tter 08-01.

l Therefore, we conclude that the Fit 7 Patrick facility can be safely returned 1

ol p

m11 ro m miti n Q

ppR ADocK OSOOgJ c?

John C. Brons 2

November 18, 1988 to operation for at least one additional fuel cycle, provided the mid. cycle insp0ction results are satisfactory, with assurance that the integrity of the reactor coolant pressure boundary will be maintained.

.he Safety Cyalvation which provides tbc basis for the above conclusions will be transmitted ui, der separate cover.

Sincerely, original algned by Robert A. Capra, Director Project Directorate I.1 Division of Reactor Projects, I/!!

cc: See next page 1

l 3

i 1

l i

~

~ ~

......N.O p:.....p.d..::........."...':

ENTB
PDI.1 0FC I.1 FPI.1

.......:.........j:l:CYt.heng

.. :...... 4..p :

DLaBargej
RCapra NAME :CVoga DATE,1 / /88 11/tf'/8A
11/t7/88
11/lV/88

?

0FFICIAL RECORD COPY

1 l

Mr. John C. Brons Power Authority of the State of New York James A. FitzPatrick Nuclear Power Plant ec:

Mr. Gerald C. Goldstein Assistant General Counsel Ms. Donna Ross Power Authority of the State New York State Energy Office of New York 2 Empire State Plaza 16th Floor 10 Columbus Circle Albany, New York 12223 New York, New York 10019 Resident Inspector's Office U. S. Nuclear Regulatory Comission Regional Administrator, Region I Post Office Box 136 U.S. Nuclear Regulatory Comission Lycoming, New York 13093 475 Allendale Road King of Prussia, Pennsylvania 19406 Mr. Radford J. Converse Mr. A. Klaus. 3 Resident Manager James A. FitzPatrick Nuclear Senior Vice F.>esident - Appraisal and Compliance Services Power Plant Power Autharity cf the State Post Office Box 41 of New York Lycoming, New York 13093 10 Columbus Circle New York, New York 10019 Mr. J. A. Gray, Jr.

Mr. George Wilverding, Manager Director Nuclear Licensing - BWR Nuclear Safety Evaluation Pcuer Authority of the State Power Authority of the State of New York of New York 123 Main Street 123 Main Street White /lcins, New York 10601 White Plains, New York 10601 Mr. Robert P. Jones, Supervisor Mr. R. E. Beadle Town of Scriba Vice President Nuclear Support i

R. O. #4 Power Authority of the State Oswegc, New York 13126 of New York 123 Main Streat Mr. J. P. Bayne, President White Plains, New York 10601 Power Authnrity af the State of New York Mr. S. S. Zulla 10 Coltebus Circle Vice President Nuclear Engineering New York, New York 10019 Power Authority of the State of New York Mr. Richard Patch 123 Main Street Quality Assurance Superintendent White Plains, New York 10601 James A. FitzPatrick Nuclear Power Plant Mr. R. Burns Post Office Box 41 Vice President 88uclear Operations 1.ycoming, New York 13093 Power Authcrity of the Stata of New York Charlie Donaldson, Esquire 12314ain Street Assistant Attorney General White Plains, New York 10601 New York Department of Law 120 $ roadway New York, New York 10271

___,.~-...__,.m..,______.._-____..,c_

m

.9..v

Novemb r 18, 1988 Docket No. 50-333 DISTRIBUTION Docket file PDI-1 Rdg local PDR RCapra DLaBarge CVogan Mr..lohn C. Brons SVarga EJordan Senior Vice President, Nuclear B8oger OGC Generation ACRS (10)

JPartlow Power Authority of the State NRC PDR RKoo of New York CCheng RHemann 123 Main Street White Plains, New York 10601

Dear Mr. Brons:

SURJECT:

IGSCC INSPECTIONS - RERJEL 8/ CYCLE 9 REFUELING OUTAGE RE:

JAMES A. FITZPATRICK NUCLEAR POWER PLANT (TAC 69162)

Your submittals dated November 10,1988 (JPN-88-061 and 88@2) infonned us that, during the current refueling outage, a total of 92 eelds in the reactor coolant system piping were ultrasonically inspected by personnel qualified in accordance with the EPRI-BWROG training program. Nine welds with IGSCC indications were repaired using wid overlays; two welds which had previous IGSCC indications were inspected, found not to corsain IGSCC, and will continue to be monitored in the future; four welds with IGSCC indications were evaluated and found to be acceptable; three of the six bi-retallic welds in the RHR loops that contain Inconel 182 weld butter were inspected with no IGSCC indications found; and nine safe-end to nozzle walds were inspected with no IGSCC indications found. All of the welds which were previously overlayed were reinspected and found to still meet the full structural or standard design requirements without the need for additional overlays.

However, the three weld overlays applied to the "B" Core Spray 1000 during the 1987 refueling outage were not inspected, since you have made a comitment to replace the piping during the 1989 mid-cycle maintenance outage. Also during the 1989 mid-cycle maintenance outage, you have comitted to inspect welds 28-33, 78-11? and 28-37.

Additionally, your letter of October 21, 1988 transmitted information concerning two IGSCC cracks fcund in the heat affected zone of a weld in the downcomer of the "R" Core Spray 1000 inside the reactor vessel. A description of the location, orientation, repair method used, results of this and other in-vessel inspections, stress analysis related to the Core Spray repair, and safety evaluation were provided.

Rased on our review of the infomation you provided and the intended use of the Hydrogen Water Chemistry System during Cycle 9, we find that the inspections and repairs that were performed, as well as the crack growth analysis data that was submitted, meet the guidelines of Generic Letter 88-01.

Therefore, we conclude that the FitrPatrick facility car be safely returned

John C. Brons November 18, 1988 to operation for at least one additional fuel cycle, provided the mid-cycle inspection results are satisfactory, with assurance that the integrity of the reactor coolant pressure boundary will be maintained.

The Safety Evaluation which provides the basis for the above conclusions will be transmitted under separate cover.

Sincerely, original signed by Robert A. Capra, Director Pro.iect Directorate I-1 Division of Reactor Pro.iects, I/II cc: See next page 1

~

0FC I.1 PDI.1
EMTB,,gg.:PDI.1 p,/ :

4,g :.....p.....:............:............:...........

4 NAME :CVoga

DLaBarg
CYCheng
RCapra DATE -

/ /88 11/I<f'/88

11/(T/88
11/l?/88 OFFICIAL RECORD COPY 1

,-.,,~_,m.

.-,_m-

__-_.,,-__.--m-.

.~.

Mr. John C. Brons James A. Ff tzPatrick Nuclear Power Authority of the State of New York Power Plant cc:

Mr. Gerald C. Goldstein Ms. Donna Ross Assistant General Counsel New York State Energy Office Power Authority of the State 2 Empire State Plaza of New York 16th Floor 10 Columbus Circle Albany, Nsw York 12223 New York, New York 10019 Resident Inspector's Office U. S. Nuclear Regulatory Comission Regional Administrator, Region !

Post Office Box 136 U.S. Nuclear Regulatory Comission Lycoming, New York 13093 475 Allendale Road King of Prussia, Pennsylvania 19406 Pr. Radford J. Converse Nr. A. Klausman Resident Manacer James A. FitzPatrick Nuclear Senior Vice Presidec', - Appraisal and Compliance Services Power Plant Power Authority of the State Post Office Box 41 of New York Lycoming, New York 13093 10 Columbus Circle Nm YorP, New York 10019 Mr. J. A. Gray, Jr.

Nr. George Wilverding, Manager Director N'Elear Licensing - BWR Nuclear Safety Evaluation Power Authurity of the State Power Authority of the State of New York of New York 123 Main Street 123 Main Street White Plains, New York 10601 White Plains, New York 10601 Mr. Robert P. Jones, Supervisor Mr. R. E. Beedle Town of Scriba Vice President Nuclear Support R. D. f4 Power Authcrity of the State Oswego, New York 13126 of New York 123 Main Street Mr. J. P. Bayne, Presidant White Plains, New York 10601 Power Authority of the Stata of New York Mr. S. S. Zulla 10 Columbus Circle Vice President Nuclear Engineering New York, New York 10019 Power Authority of the State i

of New York Mr. Richard Patch 123 Main Street Quality Assuraitce Superintendent White Plains, New York 10601 James A. FitzPatrick Nuclear Power Plant Mr. R. Burns Post Office Box 41 Vice President Nuclear Operations Lycoming New York 13093 Power Authority of the State of New York l

Charlie Donaldson, Esquire 123 Main Street Assistant Attorney General White Plains, New York 10601 New York Department of Law 120 Broadway New York, New York 10271 I

l}