18691-A-001 DESIGN CRITERIA DOCUMENTS COVER SHEET For NORTHEAST UTILITIES SERVICE COMPANY CONNECTICUT YANKEE POWER STATION NEW SWITCHGEAR BUILDING PROJECT JOB NO:
18691-1 DISCIPLINE:
ARCHITECTURAL o
MW WDH &
- o
'l8' rLecids uscM cnnt
,gg, 0
COORDINATION SIGN OFF 8704070145 870401 PDR ADOCK 05000213 g
R PDR
=.
- 2 kf/f)'g[
0 87 Issued for use l
OUp AROJEU REV*
DATE OATE DATE REVl510 N DESCRIFil0N O RIGINATO R SUPV.
ENG.
5 NO.
8 APPROVA L
18691-A-001 REVISION INDEX SHEET Page Revision i
0 ii 0
1 0
2 0
3 0
4 0
4 i
Rev. O
18691-A-001 CONTENTS
.P, ggg
1.0 INTRODUCTION
1 2.0 GOVERNING CODES, REGULATIONS, AND REFERENCE DOCUMENTS 1
3.0 GENERAL CRITERIA 2
T J
l 1
1 1
ii Rev. 0 4
_-..,e..
w.~..
~.-
/
18691-A-001 1.Q INTRODUCTION These criteria shall govern the design of the new switchgear building, connecting corridor, and related facilities for the Connecticut Yankee Atomic Power Plant.
2.0 GOVERNING CODES, REGULATIONS. AND REFERENCE DOCUMENTS Unless specifically stated otherwise, the design of all structures and facilities shall be based on applicable portions of the following codes and standards. Where conflict occurs between criteria, the more restrictive shall apply.
2.1 CODES The BOCA Basic National Building Code - 1984, as amended by a.
Connecticut State Building Authorities b.
OSHA (Occupational Safety and Health Administration)
Standards - Title 29 CFR, Part 1910-81 (as applicable) 2.2 REGULATORY REQUIREMENTS a.
10 CFR 21 (General) b.
10 CFR 50, Appendices A, B, and R Standard Review Plan Sections (NUREG-0800), as applicable c.
d.
Branch Technical Positions, as applicable e.
Generic Letter 86-10, as applicable 2.3 REFERENCE STANDARDS AND GUIDES a.
ANSI (American National Standards Institute)
N45.2.2 Packaging, Shipping, Receiving, Storage and Hand-ling of Items for Nuclear Power Plants (latest issue) b.
Applicable ASTM (American Society for Testing and Materials)
Standards (latest issue)
AWS (American Welding Society) D1.1-85 c.
d.
Underwriter's Laboratory, as applicable 2.4 DESIGN REFERENCES AND GUIDES j
a.
Bechtel Architectural Standards (latest issue) b.
Project Design Criteria - Other Disciplines (Civil, Mechani-cal, Electrical),
1 Rev. 0
l 18691-A-001 3.0 GENERAL CRITERIA 3.1 GENERAL DESIGN CONSIDERATIONS a.
Functional b.
Durability c.
Low maintenance d.
Minimum initial cost e.
Consistent with existing conditions 3.2 MATERIALS AND FINISHES 3.2.1 General aterials of construction and interior finishes shall be suitable for the intended use in consideration of the criteria outlined in Section 3.1.
3.2.2 Roofing a.
The switchgear building and connecting corridor roof shall be UL Class A, granule surfaced, single ply modified bituminous membrane roofing with 1/4 inch per foot minimum slope and de. signed to resist the uplift requirements of the BOCA building code.
3.2.3 Walls The switchgear building shall have reinforced concrete exterior and interior walls The connecting corridor shall have uninsulated metal walls.
3.2.4 Insulation Insulation R value for roof shall be provided to meet the mechanical HVAC requirements.
3.2.5 Floors All floors shall be concrete.
l
)
i l
l 2
Rev. O l
_ _.., _ _ _ ~
18691-A-001 3.2.6 Ceiling Ceilings shall be exposed.
?
1 3.2.7 Doors Hollow metal doors with pressed steel frames shall.have manufacturer i
standard primer. UL labeled fire-rated doors shall meet regulatory requirements per Section 2.2.
Three-hour fire-rated tornado pressure resistant doors to switchgear room (at third level) shall meet seismic requirements specified in civil / structural design criteria.
It shall have manufacturer standard primer.
Door hardware shall be compatiable to existing NUSCO hardware.
3.2.8 Fireproofine Fireproofing of structural steel shall be UL approved meeting the regulatory requirements per Section 2.2.
3.3 SANITARY FACILITIES j
No sanitary facilities shall be provided.
3.4 SECURITY l
Security provisions shall be incorporated on two doors (entrance and egress) at switchgear room level as per NUSCO direction. All other i
security by NUSCO.
3.5 LIVE, DEAD, SEISMIC, AND WIND LOADS j
Refer to civil / structural design criteria for live, dead, seismic, and wind loads on roofs, exterior walls, and floors.
3.6 HVAC Refer to mechanical design criteria for HVAC requirements.
3.7 FIRE PROTECTION f
Refer to mechanical design criteria for fire detection, suppression i
and protection requirements. Switchgear room and battery room at third level shall be enclosed with 3-hour fire-rated walls and floors, j
Penetrations through fire-rated walls and floors shall be sealed per existing NUSCO penetration details, specifications, and procedures.
I i
3 Rev. O
i DRAWING LIST l
DRAWING TITLE Civil / Structural 83117-20029 Plan - Plant Column Grid 83117-10030 Sheet 1 Switchgear Building Plan - Finish Grading and Drainage 83117-50100 Sheet 1 Concrete Standard Details 83117-50101 Sheet 1 Switchgear Building Sheet Piling Plan -
Sections and Details 83117-50101 Sheet 2 Switchgear Building Concrete Floor Plans El.
13' 6" and 27' 6" 83117-50101 Sheet 3 Switchgear Building Concrete Floor Plans El.
41' 6", 58' 6", and 68' 6" 84227-50101 Sheet 4 Switchgear Building Wall Elevations Reinforcing
- Embeds Details 83117-50101 Sheet 5 Switchgear Building Wall Elevations Rein-forcing - Embeds Details 83117-50101 Sheet 6 Switchgear Building Wall Elevations Rein-forcing Embeds Details 83117-50101 Sheet 7 Switchgear Building Wall Elevations Rein-forcing - Embeds Details 83117-50101 Sheet 8 Switchgear Building Wall Elevations Rein-forcing - Embeds Details 83117-51115 Sheet 1 Structural Steel Standard Details 83117-51115 Sheet 2 Structural Steel Standard Details 83117-51115 Sheet 3 Structural Steel Standard Details 83117-51116 Sheet 1 Switchgear Building Steel Framing El. 27' 6" and 41' 6" 83117-51116 Sheet 2 Switchgear Building Steel Framing Room El. 58' 6" 83117-51116 Sheet 3 Switchgear Building Embeds and Misc. Details-t 1
4 0
L A_
DRAWING TITLE 83117-51116 Sheet 4 Switchgear Building Embeds and Misc. Details 83117-51117 Sheet 1 Switchgear Building Stairs Plans - Sections and Details Architectural 83117-14017 Sheet 1 Switchgear Building Floor Plans at El. 13' 6" and 27' 6" 83117-14017 Sheet 2 Switchgear Building Floor Plan at El. 41' 6" and Roof Plan 4
83117-14017 Sheet 3 Switchgear Building Elevations 83117-14017 Sheet 4 Switchgear Building Door, Room Finish, and Painting Schedules Mechanical / Layout 83117-24140 Sheet 1 Switchgear Floor and Equipment Drains, Plans El. 13' 6", 27' 6", and 41' 6" 83117-27084 Sheets 1 Switchgear Building General Arrangements to 5 Floor El. 13' 6", 27' 6", 41' 6", 58' 6",
and 68' 6" and Sections A and B 83117-22082 Sheets 1 Switchgear Building Penetration Locations through 4 Plan El. 13' 6", 27' 6", 41' 6", 58' 6", and 68' 6" 83117-24139 Sheets 1 Switchgear Building Area Piping Drawing and 2 Plan El. 13' 6", 27' 6", and 41' 6" 7
Electrical 83117-35061 Sheet 1 Switchgear Building Lighting Plan 83117-35061 Sheet 2 Switchgear Building Lighting Legend, Materials, Lighting Distribution Panels, and Misc. Details 83117-33065 Switchgear Building Grounding and Lightning Protection Plans and Details i
a
- -.