MONTHYEARIR 05000414/19970081997-12-19019 December 1997 Notice of Deviation from Insp on 971012-1122.Deviation Noted:On 971020,licensee Had Not Performed Alarm Set Point Adjustment Evaluation Discussed in Violation 50-414/97-08-01 ML20059C0531993-12-10010 December 1993 Notice of Deviation from Insp on 931101-05.Deviation Noted:. Licensee Had Not Completed Required Analysis or Fully Addressed Recommendations of NRC SER in Area of Class 1E Vital Battery Loads for Station Blackout ML20247R7321989-07-25025 July 1989 Notice of Deviation from Insp on 890528-0701.Deviation Noted:Exterior Fire Protection Functional Capability Test Does Not Test Pumps to Determine Ability to Attain Satisfactory Performance at Shutoff ML20211A5241987-02-0606 February 1987 Notice of Deviation from Insp on 861226-870125 ML20205P4131986-04-18018 April 1986 Corrected Notice of Deviation from Insp on 851226-860201 ML20205P2621986-04-18018 April 1986 Notice of Deviation from Insp on 851226-860201 ML20133E8981985-07-12012 July 1985 Notice of Deviation from Insp on 850508 ML20140C5831984-05-0202 May 1984 Notice of Deviation from Insp on 840403-06 1997-12-19
[Table view] Category:TEXT-INSPECTION & AUDIT & I&E CIRCULARS
MONTHYEARIR 05000413/19993021999-10-12012 October 1999 NRC Operator Licensing Retake Exam Repts 50-413/99-302 & 50-414/99-302 (Including Completed & Graded Tests) for Tests Administered on 990921-23.Two Out of Three RO Candidates & One SRO Passed Retake Exam IR 05000413/19993011999-09-30030 September 1999 NRC Operator Licensing Exam Repts 50-413/99-301 & 50-414/99-301 (Including Completed & Graded Tests) for Tests Administered on 990524-27,0603,07-10 & 16.Eight of Fourteen Applicants Passed Exam IR 05000413/19990051999-09-24024 September 1999 Insp Repts 50-413/99-05 & 50-414/99-05 on 990718-0828. Violations Noted.Major Areas Inspected:Licensee Operations, Maint,Engineering & Plant Support IR 05000413/19990041999-08-13013 August 1999 Insp Repts 50-413/99-04 & 50-414/99-04 on 990606-0717. Non-cited Violations Noted.Major Areas Inspected:Operations, Maintenance,Engineering & Plant Support ML20210H2211999-07-22022 July 1999 Notice of Violation from Insp on 990314-0424.Violation Noted:Sss Was Not Inoperable for Thirteen Days Because Electrical Breakers Associated with SSS Motor Control Ctr Were Mispositioned ML20209E2831999-07-0101 July 1999 Insp Repts 50-413/99-03 & 50-414/99-03 on 990425-0605. Non-cited Violations Noted.Major Areas Inspected:Operations, Maintenance,Engineering & Plant Support IR 05000413/19990111999-06-0202 June 1999 Insp Repts 50-413/99-11 & 50-414/99-11 on 990422-23 & 0503. No Violations Noted.Major Areas Inspected:Licensee Identified Frost & Ice Buildup Which Affected Unit 1 Ice Condenser Lower Inlet Doors IR 05000413/19990021999-05-20020 May 1999 Insp Repts 50-413/99-02 & 50-414/99-02 on 990314-0424.No Violations Noted.Major Areas Inspected:Aspects of Licensee Operations,Maint,Engineering & Plant Support PNO-II-99-017, on 990515,indication of Main Generator Ground Fault Was Received While Performing Turbine Startup in Preparation for Placing Unit on Line.Licensee Is Conducting Investigation to Determine Actual Cause of Ground1999-05-18018 May 1999 PNO-II-99-017:on 990515,indication of Main Generator Ground Fault Was Received While Performing Turbine Startup in Preparation for Placing Unit on Line.Licensee Is Conducting Investigation to Determine Actual Cause of Ground ML20206U4161999-05-10010 May 1999 Insp Repts 50-413/99-10 & 50-414/99-10 on 990314-0424. Violation Being Considered for Escalated Enforcement Action Noted.Major Areas Inspected:Operations PNO-II-99-015, on 990503,shutdown in Excess of 72 H Occurred. Licensee Is Still Conducting Investigation Into Cause of Main Generator Protection Lockout & Making Preparations to Inspect & Remove Any Excessive Fouling from Inside Afws1999-05-0505 May 1999 PNO-II-99-015:on 990503,shutdown in Excess of 72 H Occurred. Licensee Is Still Conducting Investigation Into Cause of Main Generator Protection Lockout & Making Preparations to Inspect & Remove Any Excessive Fouling from Inside Afws IR 05000413/19990011999-04-0606 April 1999 Insp Repts 50-413/99-01 & 50-414/99-01 on 990124-0313. Violations Noted.Major Areas Inspected:Operations,Maint, Engineering & Plant Support ML20207A5881999-02-17017 February 1999 Notice of Violation from Insp on 981213-990123.Violation Noted:Licensee Made Change to Procedures as Described in Updated Final Safety Analysis Rept & Failed to Perform Written Safety Evaluation IR 05000413/19980121999-02-17017 February 1999 Insp Repts 50-413/98-12 & 50-414/98-12 on 981213-990123. Violations Noted.Major Areas Inspected:Operations,Maint, Engineering & Plant Support IR 05000413/19980111999-01-11011 January 1999 Insp Repts 50-413/98-11 & 50-414/98-11 on 981101-1212.No Violations Noted.Major Areas Inspected:Licensee Operations, Maint,Engineering & Plant Support IR 05000413/19980151999-01-0404 January 1999 Insp Repts 50-413/98-15 & 50-414/98-15 on 981102-06 & 16-20. No Violations Noted.Major Areas Inspected:Licensee Corrective Action Program by Sampling Activities Defined in Nuclear Sys Directive 210,rev 1 IR 05000413/19980161998-12-0404 December 1998 Insp Repts 50-413/98-16 & 50-414/98-16 on 980915-1101.No Violations Rept Encl.Major Areas Inspected:Licensee Maint, Surveillance & Engineering Programs Involving Unit 2 Ice Condenser IR 05000413/19980101998-11-23023 November 1998 Insp Repts 50-413/98-10 & 50-414/98-10 on 980927-1031.No Violations Noted.Major Areas Inspected:Licensee Operations, Engineering & Plant Support ML20155B3821998-10-19019 October 1998 Insp Repts 50-413/98-13 & 50-414/98-13 on 980807-0915. Apparent Violations Being Considered for Escalated Enforcement Action.Major Areas Inspected:Review Ice Condenser Related Problems,Which Led to Forced Shutdown ML20154C4301998-09-14014 September 1998 Notice of Violation from Insp on 980705-0815.Violation Noted:Licensee Failed to Establish Adequate Surveillance Procedures IR 05000413/19980081998-09-14014 September 1998 Insp Repts 50-413/98-08 & 50-414/98-08 on 980705-0815. Violations Noted.Major Areas Inspected:Operations,Maint & Engineering PNO-II-98-037A, on 980807,update Shutdown in Excess of 72 H Made.Licensee Has Cleaned & Satisfactorily Inspected IC Flow Channels.Licensee Identified Discrepancies in Bolting of IC Intermediate Deck Door Frames & Hinges.Conditions Addressed1998-08-28028 August 1998 PNO-II-98-037A:on 980807,update Shutdown in Excess of 72 H Made.Licensee Has Cleaned & Satisfactorily Inspected IC Flow Channels.Licensee Identified Discrepancies in Bolting of IC Intermediate Deck Door Frames & Hinges.Conditions Addressed IR 05000413/19980091998-08-26026 August 1998 Insp Repts 50-413/98-09 & 50-414/98-09 on 980816-0826. Examples of Two Apparent Violations Noted.Major Areas Inspected:Operations,Maint,Engineering & Plant Support PNO-II-98-037, on 980808,shutdown in Excess of 72 H Occurred. Licensee Inspected Approximately Half of Unit 2 Ice Condenser Bay Flow Channels from Intermediate Deck W/No Ice Obstructions in Excess of TS Limit Identified1998-08-10010 August 1998 PNO-II-98-037:on 980808,shutdown in Excess of 72 H Occurred. Licensee Inspected Approximately Half of Unit 2 Ice Condenser Bay Flow Channels from Intermediate Deck W/No Ice Obstructions in Excess of TS Limit Identified ML20236V7351998-07-27027 July 1998 Notice of Violation from Insp on 980524-0704.Violation Noted:Licensee Failed to Identify & Take Prompt C/A Following Unit 1 Upper Surge Tank over-temp Events on 960120,980111 & 0507 IR 05000413/19980071998-07-27027 July 1998 Insp Repts 50-413/98-07 & 50-414/98-07 on 980524-0704. Violations Noted.Major Areas Inspected:Operations, Maintenance,Engineering & Plant Support,Including Physical Security IR 05000413/19980051998-06-22022 June 1998 Insp Repts 50-413/98-05 & 50-414/98-05 on 980412-0523.No Violations Noted.Major Areas Inspected:Operations,Maint, Engineering & Plant Support ML20236J7471998-06-11011 June 1998 Notice of Violation from Insp on 980222-0411.Violation Noted:Adminstrative & Surveillance Procedures Not Implemented as Evidenced by Listed Examples IR 05000413/19980061998-06-0505 June 1998 Insp Repts 50-413/98-06 & 50-414/98-06 on 980511-15. Violations Noted.Major Areas Inspected:Facts Surrounding Event Associated W/Degradation of CNS Unit Auxiliary Feedwater Sys During Rapid down-power on 980507 PNO-II-98-025, on 980507,AFW Sys Declared Inoperable.Licensee Isolated Valves 1CM-127 & 2CM-127 in Units 1 & 2, Respectively,To Prevent Recurrence Until Permanent Corrective Actions Can Be Developed1998-05-11011 May 1998 PNO-II-98-025:on 980507,AFW Sys Declared Inoperable.Licensee Isolated Valves 1CM-127 & 2CM-127 in Units 1 & 2, Respectively,To Prevent Recurrence Until Permanent Corrective Actions Can Be Developed IR 05000413/19980031998-04-30030 April 1998 Insp Repts 50-413/98-03 & 50-414/98-03 on 980222-0411. Violations Being Considered for Escalated Enforcement Action.Major Areas Inspected:Aspects of Licensee Operations, Maint,Engineering & Plant Support IR 05000413/19980041998-04-20020 April 1998 Insp Repts 50-413/98-04 & 50-414/98-04 on 980302-06.No Violations Noted.Major Areas Inspected:Observation & Evaluation of Biennial Emergency Preparedness Exercise for Plant ML20217G5661998-03-23023 March 1998 Insp Repts 50-413/98-01 & 50-414/98-01 on 980111-0221. Violations Noted.Major Areas Inspected:Operation,Maint, Engineering & Plant Support ML20217G5551998-03-23023 March 1998 Notice of Violation from Insp on 980111-0221.Violation Noted:Licensee Failed to Perform Written Safety Evaluation for Closing Valves 1CA-6 & 2CA-6 IR 05000413/19980021998-02-17017 February 1998 Partially Withheld Insp Repts 50-413/98-02 & 50-414/98-02 on 980112-13 (Ref 10CFR2.790).No Violations Noted.Major Areas Inspected:Plant Support,Including Malevolent Use of Vehicles at Plant ML20203L6301998-02-0909 February 1998 Insp Repts 50-413/97-15 & 50-414/97-15 on 971123-980110. Violations Noted.Major Areas Inspected:Operations,Maint & Plant Support ML20203L6251998-02-0909 February 1998 Notice of Violation from Insp on 971123-980110.Violation Noted:Changes to Radiological Conditions in 1B Residual Heat Removal Pump Room Not Logged to Reflect Changes in Dress Requirements ML20199L6301998-02-0202 February 1998 Notice of Violation from Insp & Exam on 971117-21 & 971201-19.Violation Noted:As of 971219,selected Officers from Site Security Force Had Not Been Retrained to Perform non-licensed Operator Emergency Tasks for Starting Ssf PNO-II-97-066, on 971230,RCS Leakage Requiring Forced Unit Cooldown Occurred.No Radioactive Release Outside of Reactor Containment Facilities Due to Leakage.Licensee Informed States on Nc & Sc1997-12-31031 December 1997 PNO-II-97-066:on 971230,RCS Leakage Requiring Forced Unit Cooldown Occurred.No Radioactive Release Outside of Reactor Containment Facilities Due to Leakage.Licensee Informed States on Nc & Sc PNO-II-97-064, on 971229,inadvertent Safety Injection Occurred Due to Operators Failing to Perform Step Which Resulted in Cold Leg Injection Valve Being Left Open. Licensee Engineers Performing Evaluation1997-12-29029 December 1997 PNO-II-97-064:on 971229,inadvertent Safety Injection Occurred Due to Operators Failing to Perform Step Which Resulted in Cold Leg Injection Valve Being Left Open. Licensee Engineers Performing Evaluation ML20197F2481997-12-19019 December 1997 Notice of Violation from Insp on 971012-1122.Violation Noted:Licensee Failed to Follow Radiation Protection Procedures in That,Current Radiation Dose Rates Were Not on Vacuum Cleaner Label as Required IR 05000414/19970081997-12-19019 December 1997 Notice of Deviation from Insp on 971012-1122.Deviation Noted:On 971020,licensee Had Not Performed Alarm Set Point Adjustment Evaluation Discussed in Violation 50-414/97-08-01 ML20197F2861997-12-19019 December 1997 Insp Repts 50-413/97-14 & 50-414/97-14 on 971012-1122. Violations Noted.Major Areas Inspected:Operations,Maint, Engineering & Plant Support ML20199G0351997-11-10010 November 1997 Notice of Violation from Insp on 970831-1011.Violations Noted:Licensee Failed to Follow Procedures for Security Badge Access Control as Evidenced.On 970909,security Failed to Destroy & Unassign Access Badge of Terminated Individual IR 05000413/19970121997-11-10010 November 1997 Insp Repts 50-413/97-12 & 50-414/97-12 on 970831-1011. Violations Noted.Major Areas Inspected:Operations, Maintenance,Engineering & Plant Support as Well as Results of Announced Inspection by Regional Security Inspector ML20211L3051997-09-26026 September 1997 Notice of Violation from Insp on 970720-0830.Violation Noted:On 970727,technician Failed to Correctly Review Drawing Number CNEE-2792-01.02,connection Diagram,Main Steam Sys Terminal Cabinet 2SMTC1,rev 12 IR 05000413/19970111997-09-26026 September 1997 Insp Repts 50-413/97-11 & 50-414/97-11 on 970720-0830. Violations Noted.Major Areas Inspected:Operations,Maint, Engineering & Plant Support IR 05000413/19970101997-09-11011 September 1997 Insp Repts 50-413/97-10 & 50-414/97-10 on 970623-0731.No Violations Noted.Major Areas Inspected:Licensee Calculations,Analysis & Other Engineering Documents ML20210N7341997-08-18018 August 1997 Insp Repts 50-413/97-09 & 50-414/97-09 on 970608-0719. Violations Noted.Major Areas Inspected:Aspects of Licensee Operations,Maint,Engineering & Plant Support ML20210N7111997-08-18018 August 1997 Notice of Violation from Insp on 970608-0719.Violation Noted:On 970424,operations Test Group Technician Failed to Open Valve 2NV-873 as Required by Step 2.2.3 of PT/2/A/4200/01C,resulting in Closed Test Vent Flowpath 1999-09-30
[Table view] |
Text
_- - -. . = . - - - . . - - _ . _ . . - - . - --- . . .
APR 181986 4
ENCLOSURE 2 NOTICE OF DEVIATION i
Duke Power Company Docket Nos. 50-413 and 50-414 Catawba Units I and 2 License Nos. NPF-35 and CPPR-117 j
! The following deviation was identified during an inspection conducted on
. December 26, 1985 - February 1, 1986.
The licensee informed the NRC in FSAR, Rev.13,. paragraph 7.4.7.1, that
- the instrumentation and controir required for hot shutdown outsic;e the
! control room in the auxiliary building on the auxiliary shutdown panels were listed on Tables 7.4.7-1, 7.4.7-2, and 7.4.7-3.
l I Contrary to the above, all instrumentation and controls listed in
! Tables 7.4.7-1, 7.4.7-2, and 7.4.7-3 were not installed on the auxiliary snutdown panels. #
j 1
J Please provide, in writing within 30 days of the date of this Notice, a i description of corrective actions regarding these deviations, actions taken to avoid further deviations, and the dates when these actions were or will be completed, i Security or safeguards information should be submitted as an enclosure to i
facilitate withholding it from public disclosure as required by 10 CFR 2.790(d)
- or 10 CFR 73.21.
I l
Date: ,
i i
i f
l 4
i 4
3 j 8605210297 860418
~
j $DR ADOCK 05000413 PDR
! l t
i l
i i -
t
, . APR 181995 i
ENCLOSURE 1 NOTICE OF VIOLATION Duke Power Company Docket No. 50-413 Catawba Unit 1 License No. NPF-35
, The following violations were identified during an inspection conducted on December 26, 1985 - February 1, 1986. The Severity Levels were assigned in
! accordance with the NRC Enforcement Policy (10 CFR Part 2, Appendix C).
I
- 1. Technical Specifications 6.8.1 requires written procedures shall be established, implemented, and maintained covering the applicable procedures l recommended in Appendix A to Regulatory Guide 1.33, Revision 2.
i j a. Periodic Test (PT)/1/A/4350/02B, Diesel Generator "1B" Operability
- Test, requires in step 12.42 verification that the fuel oil transfer
! valve 1FD-62 (D/G Eng. Fuel Oil Day Tank 18 Fill) has maintained level i > 70 inches.
- Contrary to the above, on December 23, 1985 and January 6, 1986, step
- 12.42 was erroneously signed off as being completed; however, at these i times, IFD-62 was inoperable. These procedures along with a procedure
, dated December 19, 1985, were all signed off by management as having j met all acceptance criteria based on an alternate method to maintain level although IFD-62 was not functioning properly.
- b. Administrative Policy Manual (APM), Chapter 4.2, Administrative Instructions for Permanent Station Procedures, Section 4.2.7.a requires that a procedure completion package contain all required enclosures.
l Contrary to the above, Section 4.2.7.a was not implemented in that, 33 completed periodic test packages associated with Unit I diesel generator operation occurring between December 2, 1985, and January 20, 1986, did not contain all of the enclosures.
I
- c. Operations Management Procedure (OMP) 2-28, Revision 6, Diesel
! Generator Logbook, Section 8.14 requires a Test Failure / Invalid Test -
j Description Sheet for each " valid failure," " invalid failure," and-f t
i i
i i
f f
i I
f I
i
J APR 181986 Duke Power Company 2 Docket No. 50-413
.. Catawba Unit 1 License No. NPF-35
" invalid test" with checks in the appropriate box on the sheet and full explanation. This section also requires the shift supervisor to review and sign-off on the completed sheet.
Contrary to the above, Section 8.14 was not' implemented in that, of 30 data sheets associated with this procedure for "1B" diesel generator for start attempts 356 through 386, two data sheets were not filled out. One of these data sheets, although not filled out, was still signed-off by the shift supervisor.
This is a Severity Level IV violation (Supplement I).
- 2. 10 CFR 50, Appendix B, Criterion XVI and Topical Report Quality Assurance P ogram (Duke-1-A), Section 17.2.16 require measures be established to assure that conditions adverse to quality such as failures, malfunctions, deficiencies, deviations, defective material and equipment, and nonconformances are promptly identified and correct and that the measures shall assure that the cause of the condition is determined and corrective action taken to preclude repetition.
]
Contrary to the .above, measures did not assure that the cause of the
! condition was determined and corrective action taken to preclude repetition :
j in that, a failure to perform hourly fire watches as required occurred on October 8,1985. Corrective action was taken for this failure. Subsequent to completion of this corrective action, failures to perform required hourly fire watches occurred again on November 7, December 17, and December 26, ;
, 1985.
This is a Severity Level IV violation (Supplement I). i Pursuant to 10 CFR 2.201, you are required to submit to this office within 30 days of the date of this Notice, a written statement or explanation in reply, including: (1) admission or denial of the alleged violations; (2) the reasons for the violations if admitted; (3) the corrective steps which have been taken i and the results achieved; (4) corrective steps which will be taken to avoid r further violations; and (5) the date when full compliance will be achieved.
i i
Security or safeguards information should be submitted as an enclosure to ,
i facilitate withholding it from public disclosure as required by 10 CFR 2.790(d) ,
or 10 CFR 73.21. ?
I Date:
r 1
i h
e APR 181986 ENCLOSURE 2 NOTICE OF DEVIATION .
Duke Power Company Docket Nos. 50-413 and 50-414 Catawba Units 1 and 2 License Nos. NPF-35 and CPPR-117 The following deviation was identified during an inspection conducted on December 26, 1985 - February 1, 1986.
The licensee informed the NRC in FSAR, Rev.13, paragraph 7.4.7.1, that the instrumentation and controls required for hot shutdown outside the control room in the auxiliary building on the auxiliary shutdown panels were listed on Tables 7.4.7-1, 7.4.7-2, and 7.4.7-3.
Contrary to the above, all instrumentation and controls listed in Tables 7.4.7-1, 7.4.7-2, and 7.4.7-3 were not installed on the auxiliary shutdown panels.
Please provide, in writing within 30 days of the date of this Notice, a description of corrective actions regarding these deviations, actions taken to avoid further deviations, and the dates when these actions were or will be completed.
Security or safeguards information should be submitted as an enclosure to facilitate withholding it from public disclosure as required by 10 CFR 2.790(d) or 10 CFR 73.21.