Concurs W/Util 860522 & 0730 Revised Plans for Partial GE Type Hfa Relay Replacement in Current Outage,W/Remaining Replacements by Cycle 12R Outage,Per IE Bulletin 84-02
ML20205F590
Person / Time
Site: Oyster Creek
Issue date: 08/11/1986
From: Kister H
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To: Fiedler P
GENERAL PUBLIC UTILITIES CORP.
References
IEB-84-02, IEB-84-2, NUDOCS 8608190253
Download: ML20205F590 (2)


Text

I

\\

AUG 111986 Docket No. 50-219 GPU Nuclear Corporation ATTN: Mr. P. B. Fiedler Vice President and Director Oyster Creek Nuclear Generating Station P. O. Box 388 Forked River, NJ 08731 Gentlemen:

Subject:

IE Bulletin 84-02 Deferment Request IE Bulletin 84-02 (March 12, 1984) set forth directives concerning the failure, replacement and surveillances of GE HFA relays being used in class IE safety systems. The Bulletin required operational plants to implement an entire HFA relay replacement program within two years from the date of IE Bulletin 84-02.

Your letter to the Office of Inspection and Enforcement dated July 18, 1984 delineated your plans to accomplish the bulletin requirements. Your most recent letters to Region I dated May 22, 1986 and July 30, 1986 proposed a partial deferral of the HFA replacement program, provided a revised plan, and requested our concurrence.

The Region I staff finds acceptable your revised plans for partial HFA replace-ment in the current outage, with the remaining replacements by Cycle 12R outage, as outlined in your July 30, 1986 request. Our basis for acceptance is our understanding that the relays involved in the deferral are all normally deener-gized ones that are tested quarterly during plant operation. Your implementa-tion of your IE Bulletin 84-02 commitments will be verified in future NRC inspections.

Sincerely, Original Signed By:

Harry B. Kister, Chief l

Projects Branch No. I l

Division of Reactor Projects l

cc:

M. Laggart, BWR Licensing Manager Licensing Manager, Oyster Creek Public Document Room (PDR)

Local Public Document Room (LPDR)

Nuclear Safety Information Center (NSIC)

NRC Resident Inspector State of New Jersey J. Donohew, NRR R. Baer, IE l

OFFICIAL RECORD COPY OYC LTR BLOUGH - 0001.0.0 8608190253 860G11 11/29/80 S Eh h l

$DR ADOCK 03000219 p[

PDR

f,

oc bec w/ encl

Region I Docket Room (with concurrences)

Management Assistant, DRMA (w/o enc 1)

Section Chief, DRP W. Baunack C. Anderson W. Bateman RI:0RP

DRP RI:DRP Blough Anderson Kister 8/d/86 8/f/86 8//C/86 0FFICIAL RECORD COPY OYC LTR BLOUGH - 0002.0.0 11/29/80 vw