4 TABLE 8.4-1 ENVIRONNENTAL RADIOLOGICAL MONITORING PROGRAM SAMPLING OR TYPE AND FREQUENCY EXPOSURE PATHWAY

. COLLECTION FREQUENCY OF ANALYSIS AND/OR SAMPLE SAMPLING OR MONITORING LOCATIONS Onsite or Hear Field" Radiolodine Canister 1.

Airborne a.

Radiolodine and D-01, Onsite Station 1, 0.6 mi NW Continuous sampler I-131 analysis Particulates D-02, Onsite Station 2, 0.3 at NE operation with sample biweekly D-03, Onsite Station 3, 0.4 mi S collection weekly D-04, Collins Road, 0.9 mi W Particulate Sampler:

D-05, Bennitt Farm, 0.9 al NE D-06, Pheasant Trail, 0.9 mi SE Gross beta analysis s

followgng filter N

change

\\\\

Sampling Trains N

Test and maintensnce N

weekly b.

Far Field" Radiolodine Canisters g

c.

M D-07, Clay Products, 2.0 mi S Continuous sampler I-131 whgn analyses e

D-08, Prairie Parks, 4.0 mi SW operation with are made m

D-09, Coal City, 7.5 mi S particulate filter D-10, Goose Lake eschange weekly Particulate Sampler:

Village, 3.8 mi SW and radioiodine D-II, Morris, 8.0 mi W canister eschange Gross beta when b,c D-12, Lisbon, 10.0 mi NW bi-weekly analyses are made D-13, Minooka, 4.5 mi N D-14, Channahon, 3.5 mi NE Sampling Train D-15, Joliet, 12.5 mi NE D-16, Elwood, 8.0 mi E-Test and maintenance D-17, Wilmington, 8.0 mi SE weekly EN 5:5 "5

GE 8609130330 860001 PDR ADOCK 05000237 R

PDR

TABLE 8.4-1 (Cont'd)

EXPOSURE PATHWAY SAMPLING OR TYPE AND FREQUENCY AND/OR SAMPLE SAMPLING OR MONITORING LOCATIONS COLLECTION PREQUENCY OF ANALYSIS 2.

Direct Fadiation a.

At Air Sampling Sites Quarterly Camma dose quarterly Same locations as fixed air sampling locations in Item 1.

b.

Inner Ring d

i 101-1, 1.0 mi N 101-2, 1.0 mi N 102-1, 1.3 mi NE 102-2, 1.4 mi NE 105-1, 0.9 al SE 105-2, 0.9 mi SE 109-1, 0.8 mi S 109-2, 0.8 mi S 110-1, 0.5 mi SW 110-2, 0.6 mi SW 111-1, 0.7 mi SW 111-2, 0.7 mi SW 112-1, 0.9 mi SW 112-2, 0.9 mi SW S

y 113-1, 0.9 mi W g

113-2, 0.9 mi W o

w 114-1, 0.8 mi NW E

114-2, 0.8 mi NW 115-1, 1.0 mi NN 115-2, 1.0 mi NW c.

Outer Ring 201-1, 4.5 mi N 201-2, 4.5 mi N 202-1, 5.0 mi NNE 202-2, 5.0 mi NNE 203-1, 4.5 mi NE 203-2, 4.5 mi NE

$5 55 "5

0;e C

'g TABLE 8.4-1 (Cont'd)

EXrO50RF. PAinwAY SANPLING OR TYPE AND FREQUENCY AND/OR SAMPLE SAMPLING OR MONITORING LOCATIONS COLLECTION FREQUENCY OF ANALYSIS d

3.

Waterborne,e a.

Surface D-21, Illinois River at Weekly collection Gamma isotopic EJ6E RR Bridge, 1 mi W composited monthly monthly D-22, Illinois River at Morris, Quarterly Tritium and gross 8 mi W beta quarterly D-31, Goose Lake Corp. of England, Quarterly Tritium and gross 2.0 mi S beta quarterly 4

D-33, Pond West of MFRP, 0.8 mi S Quarterly Tritium and gross beta quarterly b.

Lake Water D-34A&B, Dresden Road and County Weekly Gamma isotopic and Road gross beta analysis weekly c.

Well Water D-23, Thorsen Well, 2.0 mi S

. Quarterly Gross beta, gross alpha and tritium g

a quarterly g

d.

Cooling D-18 Inlet, Unit 1, at Station Weekly collection Cross beta analysis i

Water D-19, Discharge, Unit 1, at Station weekly Sample D-20, Discharge, Unit 2/3, at Station e.

Sediment D-27, Dresden Lock & Dam, 0.5 mi W Annually Gamma isotopic from annually Shoreline "S

r* u

e s

T TABLE 8.4-1 (Cont'd)

EXPOSURE PATHWAY SAMPLING OR TYPE AND FREQUENCY AND/OR SAMPLE SAMPLING OR MONITORING LOCATIONS COLLECTION FREQUENCY OF ANALYSIS 4.

Ingestion l

a.

Milk' D-24, Clow Farm, 5.0 mi NE Weekly collection I-131 analysis when animals in on all samples pasture (May to Oct.):

monthly, November to March D-25, Vince Biros Farm, 11.5 mi SW D-26, Trotter's Dairy, 6.1 mi S b.

Fish D-28, Dresden Pool of Illinois River, Sealannually Camma footopic 0.5 mi W analysis on edible portions of each sample m

O E

,7 ui R

a

=

" See Figure 8.4-1 b F:r field samples are analysed when near field results are inconsistent with previous measurements cnd radioactivity is confirmed as having its origin in airborne effluents released from the station, or ct the discretion of the Emergency Planning Supervisor.

  • A gamma isotopic analysis shall be performed whenever the gross beta concentration in a sample exceeds by five times (5m) the average concentration of the preceding calender quarter for the sample location.

O See rigure 8.4-2

  • See Figure 8.4-3 EE Ge V

.-