ML20203E205
| ML20203E205 | |
| Person / Time | |
|---|---|
| Site: | Crystal River |
| Issue date: | 12/09/1997 |
| From: | FLORIDA POWER CORP. |
| To: | |
| References | |
| AR-503, NUDOCS 9712160414 | |
| Download: ML20203E205 (97) | |
Text
..
d Docun ent Transmittal #: 79423' Date: 12/9/97-
- TC:
NRC (DC DESK)
MAC: N/A
' Destination:
==
Description:==
i Copy Copy Totals DUcument:
Revision:
Comment:
INFO CNTL M,S_TR AR0503-19 24 1
0' O
4.
4 5k.
Instructions to the Addressee:
Pl:ase verify the document (s) received agrees with the above information.
Operations department must attach old document (s) or portions of document (s) superseded by the above
- to this transmittal.
The signature indicates acknmledgment of receipt of the above document (s) and that documents have been updated. Retum signed and dated transtrAtal to Document Control within 15 working days of
(
transmittal date to mail code:
NA1C-Florida Power Corporation Document Control, NA1C s[Q(/-
Crystal River Energy Complex
~# f 15760 W. Power Line st_
- { hM" Crystal Rwer, FL 344284708 Signature of Addressee:
Date:
9712160414 971209 inst is IIIIIII I tili" 11 PCR ADOCK 05000302
'El H, HH H 'I 110
' 11
- * * *
- a 8 '
F PDR,
3
' - - a 4
Rev. 19 y
\\
12[ 9,lD Effective Date 9
WFORMA'JO \\'
y
- ONLY
~
ANNUNCIATOR RESPONSE AR-503 FLORIDA POWER CORPOPATION CRYSTAL RIVER UNIT 3 ICS K ANNUNCIATOR RESPONSE l
APPROVED BY:
Interpretation Contact i
~
n,.d & $- & n fr' O
(SIGNATUR.E ON FILE)
/ 2 !?/9 7 DATE:
/.
/
,O%
INTERPRETATION CONTACT:
_ Manager, Nuclear Plant Operations
$ aport
ya f
TABLE OF CONTENTS
/%O SECTION-PAGE
- LO_f51R20$E................................................................. 1 -
LO_RE FE RE NCES.............................................................. 1 -
2.1 IMPLEMENTING REFERENCES.............................................
1 2.2 DEVELOPMENTAL REFERENCES........................................... 1 3. 0 PE RSONNE L INDOCTRINATION............................................... 1 4.0 INSTRUCTIQNS............................................................
2 5.0 FOLLOW-UP ACTIQNS.......................................................
2 i
ENCLOSURE
-1 Annunciator Response...............................................
3 5
i t
L i
e t
AR-503 Rev. 19 Page 1
~
.p-
.9 1.0 PUREQSE O
i 1.1 Establish a reference document for each Annunciator Window on the ICS-CY3 Lampbox, i
l 1.2
-Establish operator actions for valid Annunciator alarms on the ICS-CY3 Lampbox.
1.3 Establish'a refe.ence to other procedures which address operator i
actions for valid Annunciator alarms on the ICS-CY3 Lampbox.
l L.0 REEEBfEES-2.1 LMEl.EMENIIELBEFERENCES 2.1.1 E0P, Emergency Operating Procedure 2.1.2 AP-581 - Loss of NNI-X 2.1.3
-AP-582 - Loss of NNI-Y 2.1.4 OP-501 - Reactor Non Nuclear Instrumentation 2.1.5 OP-504 - Integrated Control System 2.1.6 OP-605 - Feedwater System 2.1.7 AP-545 - Plane Runback 2.1.8 OP-608 - OTSG's-and Main Steam System 2.1.9 OP-209 - Plant Cooldown 2.2 DEVELQEMENTAL REFEREEES 2.2.1 INPO 9G-021, Good Practice OP-217, Alarm Response Procedures 2.2.2 Annunciator Window Engraving Drawing E-224-049 LO PERSONNEL INQQCIRINATI_QN 3.1 The Annunciator System is powered from VBOP-5 Breaker 28.
O AR-503 Rev. 19 Page 1
l l
o-l 4
4.0 IPSTRUCTIONS i
\\
4.1 Respond to alarms on the ICS-CY3 Lampbox as indicated on,
Annunciator Response, j
5.0 FOLL.0W-UP ACTIDNS None O
k O
AR-503 Rev. 19 Page 2
3 i
ENCLOSURE 1 (Page 1 of 93)
ICS-K ANNUNCIATOR RESPONSE ICS-CG-01-01 K-01,
i I
I POWER l
l FAILURE -
1 I
EVENT POINT 1143 INDICATED CONDITION:
o NNI-X 24V DC BUS POWER FAILURE.
'f REDUNDANT INDICATION WHICH WILL VERIFY _ ALARM:
T o NNI-X POWER LIGHT IS OFF, LOCATED ON THE REDUNDANT INSTRUMENT PANEL.
o NNI-X POWER SUPPLY MONITOR HAS NO INDICATING LIGHTS ON, LOCATED IN NNI CABINET 3.
o S-1 AND S-2 SWITCHES ARE TRIPPED OFF, LOCATED IN NNI CABINET 2.
OPERATOR ACTIONS FOR A VALIt) ALARM:
o REFER TO AP-581.
o REFER TO OP-501 FOR REENERGIZING NNI-X DC POWER SUPPLIES.
DISCUSSION:
REDUNDANT POWER SOURCES TO NNI-X DC POWER SUPPLIES IS VBDP-1 BKR 8 AND VBDP-5 BKR.25.
A LOSS OF A POSITIVE OR NEGATIVE BUS SHOULD TRIP BOTH S-1 AND S-2.
REFERENCES:
NNI DRAWINGS SENSING ELEMENT: VARIOUS NNI COWACTS.
o
-AR-503 Rev. 19 Page 3
I --
4 ENCLOSURE 1-(Page 2 of 93)
ICS-K ANNUNCIATOR RESPONSE--
ICS-CY3-01-01 K-01-01 I
I POWER
'l FAILURE l
l EVENT POINT 1144 INDICATED CONDITION:
o NNI-X 120V AC BUS FAILURE.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o NN1-X POWER LIGHT IS OFF, LOCATED ON THE REDUNDANT INSTRUMENT PANEL.
OPERATOR ACTIOW. FOR A VALID ALARua o REFER TO AP-581.
o REFER TO OP-501 FOR REENERGIZING NNI-X AC BUS.
DISCUSSION:
REDUNDANT POWER SOURCES TO NNI-X AC BUS IS VBDP-1 BKR 11 AND VBDP-5 BKR 7.
THIS ALARM INDICATES A LOSS OF 120V AC FIELD LOADS HAS OCCURRED.
REFERENCES:
NNI DRAWINGS SENSING ELEMENT:
VARIOUS NNI CONTACTS.
AR-503 Rev. 19 Page 4
1 f
ENCLOSURE 1 (Page 3 of 93)
ICS-K ANNUNCIATOR RESPONSE ICS-CY3-01-03 K-01-03 TRANSMITTER POWER SUPPLY ON BACKUP EVENT POINT 0933 INDICATED CONDITION:
o TRANSMITTER P(MER SUPPLY CABINET "A" PRIMARY POWER SELECTOR SWITCH IS IN "Alff0" AND STANDBY POWER SELECTOR SWITCH IS IN " STANDBY" AND PRIMARY POWER IS LOST.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
(^
o RED STANDBY POWER ON LIGHT ON TRANSMITTER POWER SUPPLY CABINET LOCATED IN
\\
THE CRD ROOM IS ON.
OPERATOR ACTIONS FOR A VALID ALARM:
o STABILIZE ANY PLANT TRANSIENT THAT MAY RESULT FROM A TRANSMITTER POWER FAILURE.
o CONTACT ELECTRIC SHOP.
o VERIFY VBDP-1 BREAKER 1 IS ON.
DISCUSSION:
THE TRANSMITTER POWER SUPPLY CABINET IN THE CRD ROOM PROVIDES POWER TO OVER 50 NON-VITAL TRANSMITTERS IN THE PLANT, NORMAL POWER SUPPLY TO THE "A" CABINET IS VBDP-1 BKR-1 WITH A BACKUP FROM VBDP-5 BKR-11. A POWER SEEKING ABT IS INSTALLED TO SELECT ONE OF THESE POWER SOURCES.
TO RESTORE NORMAL SYSTEM LINEUP AFTER A TRANSFER HAS OCCURRED THE STANDBY POWEP SWITCH MUST BE PLACED IN RESET THEN BACK TO AUTO AFTER NORMAL POWER HAS-BEEN RECOVERED.
REFERENCES:
DRAWING EC-210-586
, O)
SENSING ELEMENT:
POWER AVAILABLE RELAY j
AR-503 Rev. 19 Page $
i l
1 e
ENCLOSURE 1 (Page 4 of 93) y ICS-K ANNUNCIATOR RESPONSE ICS-CY3-01-03 K-01-03
~
TRANSMITTER POWER SUPPLY ON BACKUP l
EVENT POINT 0934 INDICATED CONDITION:
o TRANSMITTER POWER SUPPLY CABINET "B" PRIMARY POWER SELECTOR SWITCH IS IN "AUT0"-AND STANDBY POWER SELECTOR SWITCH IS IN " STANDBY" AND PRIMARY FOWER IS LOST.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
(
o RED STANDBY POWER ON LIGHT ON TRANSMITTER POWER SUPPLY CABINET LOCATED IN THE CRD ROOM IS ON.
OPERATOR ACTIONS FOR A VALID ALARM:
o CONTACT ELECTRIC SHOP.
o VERIFY VBDP-2 BREAKER 1 IS ON.
DISCUSSION:
THE TRANSMITTER POWER SUPPLY CABINET IN THE CRD ROOM PROVIDES POWER TO OVER 50 NON-VITAL TRANSMITTERS IN THE PLANT. NORMAL POWER SUPPLY TO THE "B" CABINET IS VBDP-2 BKR-1 WITH A BACKUP FROM VBDP-6 BKR-14.
THERE IS A POWER SEEKING ABT INSTALLED TO SELECT A POWER SOURCE FROM THESE SOURCES. TO RESTORE NORMAL SYSTEM LINEUP AFTER A TRANSFER HAS OCCURRED THE STANDBY POWER SWITCH MUST BE PLACED IN RESET THEN BACK TO A'
S AFTER NORMAL POWER HAS BEEN RECOVERED.
J
REFERENCES:
DRAWING EC-210-587 SENSING ELEMENT:
POWER AVAILABLE RELAY AR-503 Rev. 19 Page 6
ENCLOSURE-1
,q-(Page 5 of 93)
Q ICS-K ANNUNCIATOR RESPONSE ICS-CY3-01-05 K-01-05 CNTRL TRANSFER -
TO-REMOTE S/D PNL.
j EVENT POINT 2036 INDICATED CONDITION:
o "A" REMOTE SHUTDOWN TRANSFER SWITCH IS IN RSP POSITION, LOCATED IN REMOTE SHUTDOWN AUX RELAY CABIWET "A".
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o RED TRANSFER INDICATOR LIGHT IS ON, LOCATEP ON THE RSP.
OPERATOR ACTIONS FOR A VALID ALARM:
o REPOSITION SWITCH AS NECESSARY.
DISCUSSION:
THIS ALARM INDICATES THAT CONTROL OF "A" SIDE COMPONENTS HAS BEEN REMOVED FROM THE CONTROL ROOM.
CONTROL SHOULD BE REGAINED FROM THF CONTROL ROOM OR THE REMOTE SHUTDOWN PANEL SHOULD BE MANNED.
REFERENCES:
DRAWING 208-082 SHEET RS-17 SENSING ELEMENT:
RRR-SPA-I-17 AR-503 Rev. 19 Page 7
\\_ m ENCLOSURE 1 (Page 6 of 9k)
ICS-K ANNUNCIATOR RESPONSE ICS-CY3-01-05 K-01-05 i
CNTRL TRANSFER TO g
REMOTE S/D PNL I
EVENT POINT 2037 INDICATED CONDITION:
o "B" REMOTE SHUTDOWN TRANSFER SWITCH IS IN RSP POSITION, LOCATED IN REMOTE SHUTDOWN AUX RELAY CABINET "B".
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o RED TRANSFER INDICATOR LIGHT IS ON, LOCATED ON THE RSP.
OPERATOR ACTIONS FOR A VALID ALARM:
o REPOSITION SWITCH AS NECESSARY.
DISCUSSION:
THIS ALARM INDICATES THAT CONTROL OF "B" SIDE COMPONENTS HAS BEEN REMOVED FROM THE CONTROL ROOM.
CONTROL SHOULD BE REGAINED FROM THE CONTROL ROOM OR THE REMOTE SHUTDOWN PANEL SHOULD BE MANNED.
REFERENCES:
DRAWING 208-082 SHEET RS-18 SENSING ELEMENT:
RRR-SPB-1-17
-\\
\\
AR-503 Rev. 19 Page 8
ENCLOSURE 1 (Page 7 of 93) p ICS-K ANNUNCIATOR RESPONSE ICS-CY3-01-05 K-01-05 CNTRL TRANSFER TO REMOTE S/D PNL EVENT POINT 2038 INDICATED CONDITION:
- o "AB" REMOTE SHUTDOWN TRANSFER SWITCH IS IN RSP POSITION, LOCATED ON REMOTE SHUTDOWN PANEL, REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o RED TRANSFER INDICATOR LIGHT IS ON, LOCATED ON RSP, OPERATOR ACTIONS FOR A VALID ALARM:
o REPOSITION SWITCH AS NECESSARY.
DISCUSSION:
THIS ALARM INDICATES-THAT CONTROL OF "AB" COMPONENTS HAS BEEN REMOVED FROM THE CONTROL ROOM, CGNTROL SHOULD BE REGAINED FROM THE CONTROL ROOM OR THE REMOTE SHUTDOWN PANEL SHOULD BE MNNED.
REFERENCESi DRAWING 208-082 SHEET RS-10 SENSING ELEMENT: CS-ISAB t
AR-503 Rev. 19 Page 9
.. ~
. _.._..~..
ENCLOSURE 1 (Page 8 of 93)
A ICS-K ANNUNCIATOR RESPONSE ICS-CY3-01-05 K-01-05 CNTRL TRAN5FER' TO-RE'.10TE S/D PNL-EVENT POINT 2039 INDICATED CONDITION:
o "NON-SAFETY" REMOTE SHUTDOWN TRANSFER SWITCH IS IN RSP POSITION, LOCATED ON REMOTE SHUTDOWN PANEL.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o RED TRANSFER INDICATOR LIGHT IS ON, LOCATED ON RSP.
4 OPERATOR ACTIONS FOR A VALID ALARM:
o REPOSITION SWITCH AS NECESSARY.
DISCUSSION:
THIS ALARM INDICATES THAT CONTROL OF "NON-SAFETY" COMPONENTS HAS BEEN REMOVED FROM THE CONTROL ROOM.
CONTROL SHOULD BE REGAINED FROM THE CONTROL ROOM OR THE REMOTE SHUTDOWN PANEL SHOULD BE MANNED.
REFERENCES:
DRAWING 208-082 SHEEf RS-09 SENSING ELEMENT: CS-ISNS
~
AR-503 Rev. 19 Page.10
. =.
ENCLOSURE 1 (Page 9 of 93)'
O ICS-K ANNUNCIATOR RESPONSE ICS-CY3-02-01 K-02-01 NNIY-I I
POWER
.l l
FAILURE I
1 EVENT POINT 1145 INDICATED CONDITION:
o NNI-Y 24Y DC BUS POWER FAILURE.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
[V]
o NNI-Y POWER LIGHT IS OFF, LOCATED ON THE REDUNDANT INSTRUMENT PANEL.
o NNI-Y POWER SUPPLY MONITOR HAS NO INDICATING LIGHTS ON, LOCATED IN NNI CABINET 7.
o S-1 AND S-2 SWITCHES ARE TRIPPED OFF; LOCATED IN NNI CABINET 8.
OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO AP-582.
o REFER TO OP-501 FOR REENERGIZING NNI-Y DC POWER SUPPLIES.
DISCUSSION:
REDUNDANT POWER SOURCES TO NNI-Y DC POWER SUPPLIES ARE VBDP-6 BKR 25 AND VBDP-7 BKR 18.
A-LOSS OF A POSITIVE OR NEGATIVE BUS SHOULD TRIP BOTH S-1 AND S-2.
REFERENCES:
NNI DRAWINGS SENSING ELEMENT: VARIOUS NNI CONTACTS.
O AR-503 Rev. 19 Page 11--
ENCLOSURE 1-(Page 10 of 93)
ICS-K ANNUNCIATOR. RESPONSE ICS-CY3-02-01 K-02-01 I
I POWER.
l
'l FAILURE -
l l
EVENT POINT 1146 INDICATED CONDITION:
o NNI-Y 120V AC BUS FAILURE.
I J
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O o NNI-Y POWER LIGHT IS OFF, LOCATED ON THE REDUNDANT INSTRUMENT PANEL.
C'
.0PERATOR ACTIONS FOR A VALID ALARM:
o REFER TO AP-582.
o REFER TO OP-501 FOR REENERGIZING NNI-Y AC BUS.
DISCUSSION:
'l REDUNDANT POWER SOURCES TO NNI-Y AC BUS ARE VBDP-6 BKR 10 AND VBDP-7 BKR 17 THIS ALARM INDICATES A LOSS OF 120V AC FIELD LOADS HAS OCCURRED.
REFERENCES:
NNI-DRAWINGS SENSING ELEMENT:.VARIOUS NNI CONTACTS.
(
AR-503 Rev. 19 Page 12
ENCLOSURE 1 (Page 11-of 93)
-i
{;
o ICS-K ANNUNCIATOR RESPONSE ICS-CY3-02-02 K-02-02 I
ics NNI TROUBLE l
EVENT POINT 0773 2
v INDICATED CONDITION:
o SASS POWER SUPPLY FAILURE.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o RED LED INDICATOR IS OFF, LOCATED ON ONE OF THE SASS POWER SUPPLIES.
i.
f OPERATOR ACTIONS FOR A VALID ALARM:
i
[
o ENSURE PLANT STABLE.
o NOTIFY I&C SHOP.
4 DISCUSSION:
i THE SASS SYSTEM HAS REDUNDANT FEEDS FROM BOTH NNI X AND NNI-Y. THESE
. INPUTS SUPPLY SEPARATE POWER SUPPLIES FOR EACH SASS RACK. POWER IS
.THEN AUCTIONEERED INSIDE THE RACK TO' SUPPLY EACH SASS MODULE, IF ONE OF THESE POWER SUPPLIES FAILS THERE SHOULD BE NO EFFECT ON THE SASS RACK.
REFERENCES:
NNI DRAWINGS SENSING ELEMENT: VARIOUS NNI C0ifTACTS.
[
I-AR-503 Rev. 19-Page 13'
~
ENCLOSURE 1-(Page 12 of 93)-
ICS-K ANNUNCIATOR RESPONSE ICS-CY3-02-02 K-02-02 ICS NNI TROUBLE EVENT POINT 0778 INDICATED CONDITION:
o POSITIVE 24V NNI-Y POWER SUPPLY FAILURE.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o POSITIVE WHITE " SUPPLY" INDICATOR LIGHT IS OFF, LOCATED ON THE NNI-Y (A
POWER SUPPLY MONITOR IN NNI CABINET 7.
o + 24 V NNI-Y POWER SUPPLY INDICATF'rNO AMPS OR VOLTAGE.
OPERATOR ACTIONS FOR A VALID ALARM:
o ENSURE PLANT STABLE.
o CONTACT I&C SHOP.
DISCUSSION:
THIS ALARM INDICATES ONE OF TWO REDUNDANT POWER SUPPLIES TO NNI-Y
+24V BUS HAS BEEN LOST. THIS CONDITION SHOULD NOT EFFECT NNI BUS POWER.
REFERENCES:
- DRAWING NNI DRAWINGS SENSING ELEMENT: VARIOUS NNI CONTACTS.
AR-503 Rev. 19 Page 14
l
~
ENCLOSURE 1 p
(Page 13 of 93)
(
'ICS-K ANNUNCIATOR RESPONSE ICS-CY3-02-02 K-02-02 ICS NNI TROUBLE I
EVENT POINT 0779 INDICATED CONDITION:
o NEGATIVE 24V NNI-Y POWER SUPPLY FAILURE.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o NEGATIVE WHITE " SUPPLY" INDICATOR LIGHT IS OFF, LOCATED ON THE NNI-Y
. 's POWER SUPPLY MONITOR IN NNI CABINET 7.
o - 24 V NNI-Y POWER SUPPLY INDICATES NO AMPS OR VOLTAGE.
OPERATOR ACTIONS FOR A VALID ALARM:
o ENSURE PLANT STABLE.
o CONTACT I&C SHOP.
DISCUSSION:
THIS ALARM INDICATES ONE OF TWO REDUNDANT POWER SUPPLIES TO NNI-Y -24V BUS HAS BEEN LOST. THIS CONDITION SHOULD NOT EFFECT NNI BUS POWER.
REFERENCES:
DRAWING NNI DRAWINGS SENSING ELEMENT: VARIOUS NNI CONTACTS.
AR-503 Rev. 19 Page-15 i
~
ENCLOSURE 1 (Page I4 of 93)
ICS-K ANNUNCIATOR RESPONSE ICS-CY3-02-02 K-02-02' ICS NNI TROUBLE EVENT POINT 0960 i
INDICATED CONDITION:
o NNI-X I20V AC FIELD LOADS TRANSFERRED FROM VBDP-5 TO VBDP-1.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o NORMAL FEEDER TO NNI-X FROM VBDP-5 SWITCH 7 IS OPEN.
o NNI-X FEEDER RED STATUS LIGHT IS OFF, LOCATED ON VBDP-5 CIRCUIT STATUS PANEL.
OPERATOR ACTIONS FOR A VALID ALARM:
o ENSURE PLANT STABLE.
o CONTACT I&C SHOP.
DISCUSSION:
THIS ALARM INDICATES AN AUTOMATIC BUS TRANSFER DEVICE HAS ACTUATED THAT SWAPS FROM THE NORMAL POWER SUPPLY TO THE ALTERNATE POWER SUPPLY FOR NNI-X I20V AC-FIELD LOADS.
ONCE NORMAL POWER IS REGAINED THE ABT WILL TRANSFER BACK TO NORMAL SUPPLY AFTER 45 SECONDS.
REFERENCES:
NNI DRAWINGS SENSING ELEMENT: VARIOUS NNI CONTACTS.
AR-503 Rev. 19 Page 16
ENCLOSURE 1-(Page 15 of 93)
ICS-K ANNUNCIATOR RESPONSE ICS-CY3-02-02 K-02-02
- ICS NNI TROUBLE EVENT POINT 0962 INDICATED CONDITION:
o ICS 120V AC FIELD LOADS TRANSFERRED FROM VBDP-4 TO VBDP-2.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O o ICS FEEDER RED STATUS LIGHT IS OFF, LOCATED ON VBDP-4 CIRCUIT STATUS PANEL.
o NORMAL FEEDER TO ICS FROM VBDP-4 SWITCH 25 IS OPEN.
OPERATOR ACTIONS FOR A VALID ALARM:
o ENSURE PLANT STABLE.
o CONTACT I&C SHOP.
DISCUSSION:
THIS ALARM INDICATES AN AUTOMATIC BUS TRANSFER DEVICE HAS ACTUATED THAT SWAPS FROM THE NORMAL-POWER SUPPLY TO THE ALTERNATE POWER SUPPLY FOR ICS 120V AC FIELD LOADS.
E ONCE NORMAL POWER IS RECAINED THE ABT WILL TRANSFER BACK TO NORMAL 4
SUPPLY AFTER 45 SECONDS.
REFERENCES:
NNI-DRAWINGS SENSING ELEMENT: VARIOUS NN1 CONTACTS AR-503 Rev. 19 Page 17
.. ~.
=_
ENCLOSURE 1 (Page 16 of 93)
ICS-K ANNUNCIATOR RESPONSE ICS-CY3-02 K-02-02 ICS NNI TROUBLE EVENT POINT 1110 INDICATED CONDITION:
o ICS CABINET FAN FAILURE.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o ICS CABINET COOLING FANS NOT RUNNING.
- 4 o ICS CABINET FILTERS DIRTY.
OPERATOR ACTIONS FOR A VALID ALARM:
o HAVE I&C SHOP CHANGE FILTERS.
DISCUSSION:
CONSIDERATION SHOULD BE GIVEN TO OPENING BOTH FRONT AND BACK DOORS ON THE ICS CABINETS TO PROVIDE COOLING WHILE FANS ARE NOT-OPERABLE.
HOWEVER, WITH THE REDUCED SHIELDING OF THE OPEN 000R, RADIO FREQUENCY INTERFERENCE CAN POTENTIALLY CAUSE UNDESIRABLE AND UNPREDICTABLE EFFECTS ON THE: SYSTEM OPERATION,
REFERENCES:
NNI DRAWINGS-SENSING ELEMENT: VARIOUS NNI CONTACTS.
O U
AR-503 Rev. 19 Page 18
iw-ENCLOSURE 1
' e (Page 17 of-93) i ICS-K ANNUNCIATOR RESPONSE-ICS-CY3-02-02--
'K-02-02 ICS NNl TROUBLE EVENT POINT 1111 INDICATED CONDITION:
o POSITIVE 24V ICS POWER SUPPLY FAILURE.
REDUNDANT INDICATION WHICH WILL VERIFY-ALARM:
O4 o POSITIVE WHITE " SUPPLY" INDICATOR LIGHT IS OFF, LOCATED ON THE ICS POWER SUPPLY MONITOR IN ICS CABINET 2.
o + 24 V ICS POWER SUPPLY INDICATES NO AMPS OR VOLTAGE.
OPERATOR ACTIONS FOR A VALID ALARM:
o ENSURE PLANT STABLE.
o CONTACT I&C SHOP.
DISCUSSION:
THIS ALARM INDICATES FONE OF TWO REDUNDANT POWER 'UPPLIES TO ICS +24V BUS'HAS BEEN LOST. 'THIS CONDITION SHOULD NOT -..TECT ICS POWER.
T
REFERENCES:
NNI DRAWINGS SENSING ELEMENT: VARIOUS NNI CONTACTS.
1 l
_ AR-503_
Rev. 19 Page 19
l
=.
l ENCLOSURE 1-(Page 18 of 93)-
V ICS-K ANNUNCIATOR RESPONSE ICS-CY3-02-02 K-02-02 i.
' NNI TROUBLE EVENT POINT 1113 i
INDICATED CONDITION:
o NEGATIVE 24V ICS POWER SUPPLY FAILURE.
1 i
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
1 o NEGATIVE WHITE " SUPPLY" INDICATOR.IGHT IS OFF, LOCATED ON THE ICS POWER
\\
SUPPLY MONITOR IN ICS CABINET 2.
o - 24 V ICS POWER SUPPLY INDICATES NO AMPS OR VOLTAGE.
OPERATOR ACTIONS FOR A VALID ALARM:
1 o ENSURE PLANT STABLE.
o CONTACT I&C SHOP.
e DISCUSSION:
THIS ALARM INDICATES ONE OF TWO REDUNDANT POWER SUPPLIES TO ICS -24V BUS HAS BEEN LOST. THIS CONDITION SHOULD NOT EFFECT ICS POWER.
t
=
REFERENCES:
NNI DRAWINGS SENSING ELEMENT: VARIOUS NNI CONTACTS.
'AR-50'3 Rev. 19 Page 20-
4:'
ENCLOSURE 1--
(Page 19 of 93)
O
'ICS-K ANNUNCIATOR RESPONSE' ICS-CY3-02-02 K-02-02 ICS NNI TROUBLE EVENT POINT 1147 INDICATED CONDITION:
o POSITIVE 24V NNI-X POWER SUPPLY FAILURE.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o POSITIVE WHITE " SUPPLY" INDICATOR LIGHT IS OFF, LOCATED ON THE NNI-X POWER SUPPLY MONITOR IN NNI CABINET 3.
o +24 V NNI-X POWER SUPPLY INDICATES-NO AMPS OR VOLTAGE.
OPERATOR ACTIONS FOR A VALID ALARM:
o ENSURE PLANT STABLE, o NOTIFY THE I&C SHOP.
DISCUSSION:
THIS ALARM INDICATES ONE OF TWO REDUNDANT POWER SUPPLIES TO NNI-X +24V BUS HAS BEEN LOST. THIS CONDITION SHOULD NOT EFFECT NNI BUS POWER,
REFERENCES:
DRAWING NNI DRAWINGS SENSING ELEMENT:- VARIOUS NNI CONTACTS.
l
-AR-503 Rev. 19.
.Page 21
ENCLOSURE 1 (Page 20 of 93)
ICS-K ANNUNCIATOR RESPONSE ~
ICS-CY3-02 K-02-02 j
-i
'=,
NNI TROUBLE EVENT POINT 1148-INDICATED CONDITION:
o NEGATIVE 24V NNI-X POWER SUPPLY FAILURE.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O o NEGATIVE WHITE " SUPPLY" INDICATOR LIGHT IS OFF, LOCATED ON THE NNI-X POWER SUPPLY MONITOR IN-NNI-X CABINET 3.
o - 24 V NNI-X POWER SUPPLY INDICATES-NO AMPS OR \\'OLTAGE.
OPERATOR ACTIONS FOR A VALID ALARM:
o ENSURE PLANT STABLE.
o CONTACT I&C SHOP.
DISCUSSION:
THIS ALARM INDICATES ONE OF TWO REDUNDANT POWER SUPPLIES TO NNI-X -24V BUS HAS BEEN LOST. THIS CONDITION SHOULD NOT EFFECT NNI BUS POWER.
REFERENCES:
DRAWING NNI DRAWINGS SENSING ELEMENT: VARIOUS NNI CONTACTS.
AR-503 Rev. 19 Page 22
ENCLOSURE 1
-(Page 21 of 93) l
.ICS-K ANNUNCIATOR RESPONSE
=ICS-CY3-02-02 K-02-02
,~
ICS NNI TROUBLE EVENT POINT 1149 INDICATED CONDITION:
o NNI-X CABINET FAN FAILURE.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
/
o NNI-X CABINET COOLING FANS NOT RUNNING.
\\
o NNI-X CAGINET FILTERS DIRTY.
OPERATOR' ACTIONS FOR A VALID ALARM:
o HAVE.I&C SHOP CHANGE FILTERS.
DISCUSSION:
CONSIDERATION SHOULD BE GIVEN TO OPENING BOTH FRONT AND BACK DOORS ON
.THE'NNI. CABINETS TO PROVIDE COOLING WHILE FANS ARE NOT OPERABLE.
HOWEVER, WITH THE REDUCED SHIELDING OF THE OPEN 000R, RADIO FREQUENCY INTERFERENCE CAN POTENTIiLLY CAUSE UNDESIRABLE AND UNPREDTCTABl.E EFFECTS ON THE SYSTEM OtERATION.
REFERENCES:
NNI DRAWINGS SENSING ELEMENT: VARIOUS NNI CONTACTS.
O AR-503 Rev. 19 Page'23
4-ENCLOSURE 1 (Page 22-of 93)
LJ ICS-K ANNUNCIATOR' RESPONSE ICS-CY3-ul-02 K-02-02 ICS NNi TROUBLE -
EVENT POINT 1150 INDICATED CONDITION:
o NNI-Y CABINET FAN FAILURE.
r,EDUNDANT INDICATION WHICH WILL VERIFY ALARM:
/'O o NNI-Y CABINET COOLING FANS NOT RUNNING.
< h o NNI-Y CABINET FILTERS DIRTY.
OPERATOR ACTIONS FOR A VALID ALARM:
o HAVE I&C SHOP-CHANGE FILTERS.
t DISCUSSION:
CONSIDERATION SHOULD BE GIVEN TO OPENING BOTH FRONT AND BACK DOORS ON THE NNI CABINETS TO PROVIDE COOLING'WHILE FANS ARE NOT OPERABLE.
.HOWEVER, WITH THE REDUCED SHIELDING OF THE OPEN 000R, RADIO FREQUENCY INTERFERENCE CAN POTENTIALLY CAUSE UNDESIRABLE AND UNPREDICTABLE EFFECTS ON THE SYSTEM OPERATION.
REFERENCES:
NNI DRAWINGS SENSING ELEMENT: -VARIOUS NNI CONTACTS.
O AR-503-Rev. 19 Page 24 i
L
~
ENCLOSURE 1 (Page 23 of 93)'
.f.sl ICS-K ANNUNCIATOR RESPONSE
-ICS-CY3-02-02 K-02-02
~
ICS NNI
- t TROUBLE EVENT POINT 1744 INDICATED CONDITION:
o NNI-Y 120V AC FIELD LOADS TRANSFERRED FROM VBDP-6 TO VBDP-7.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
(D o NORMAL FEEDER TO NNI-Y FROM VBDP-6 SWITCH 10 IS OPEN.
()
o NNI-Y FEEDER RED STATUS LIGHT IS OFF, LOCATED ON VBDP-6 CIRCUIT STATUS PANEL.
OPERATOR ACTIONS FOR A VALID ALARM:
o ENSURE PLANT STABLE.
o CONTACT I&C SHOP.
DISCUSSION:
THIS.. ALARM -INDICATES AN AUTOMATIC BUS TRANSFER DEVICE HAS ACTUATED THAT SWAPS FROM THE NORMAL POWER SUPPLY TO THE ALTERNATE POWER SUPPLY
.FOR NNI-Y 120V AC FIELD LOADS.
ONCE NORMAL POWER IS REGAINED THE ABT WILL TRANSFER BACK TO NORMAL SUPPLY-'AFTER 45 SECONDS.
REFERENCES:
NNI DRAWINGS SENSING ELEMENT: VARIOUS NNI CONTACTS.
t
,z.
'AR-503 -
Rev. 19 Page 25
.-.=- - _.-..- - --.-.- -..-.
_...-..~.-
i MCLOSURE 1 i
(Page 24 f 93)
[
O ICS-K ANNUNCIATOR RESPONSE ICS-CY3-02-03 K-02-u3 l
1 t
5 I
ICS/NNI s
FUSE BLOWN EVENT POINT-1107
[
INDICATED CONDITION:
o ICS FUSE BLOWN, LOCATED IN ICS CABINET I FUSE PANEL.
r REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O o FUSE PANEL LOCATED IN ICS CABINET 1 AMBER FUSE B',0WN INDICATION.
OPERATOR ACTIONS FOR A VALID ALARM:
o ENSURE PLANT STABLE.
o REFER OP-504 FOR FUSE INFORMATION.
o CONTAt LC SHOP.
DISCUSSION:
THIS ALARM INDICATES A FUSE IS BLOWN THAT FEEDS ICS COMPONENTS.
OP-504 WILL HELP OETERMINE EQUIPMENT EFFECTED.
r
REFERENCES:
NNI DRAWINGS
- SENSING ELEMENT
FUSE INDICATIbN RELAY O
i AR-503 Rev. 19-Pege 26
~=.
~ - - ~,.. -
l ENCLOSURE 1 (Page 25 of 93)
ICS-K ANNUNCIATOR RESPONSE ICS-CY3-02-03 K-02-03
~
ICS/NNI FUSE BLOWN EVENT POINT 1108 l
4 INDICATED CONDITION:
-o ICS FUSE BLOWN, LOCATED IN ICS CABINET I.5USE PANEL.
I i
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o FUSE PANEL LOCATED IN ICS CABINET 3 AMBER FUSE B!.0WN INDICATION.
OPERATOR ACTIONS FOR A VALID ALARM:
o ENSURE PLANT STABLE.
o REFER TO OP-504 FOR FUSE INFORMATION.
a o CONTACT I&C SHOP.
DISCUSSION:
THIS ALARM INDICATES A FUSE IS BLOWN THAT FEEDS ICS COMPONENTS.
OP-504 WILL HELP DETERMINE EQUIPMENT EFFECTED.
t
REFERENCES:
NNI DRAWINGS SENSING ELEMENT:
FUSE INDICATION RELAY i
AR-503 Rev. 19 Page 27
I ENCLOSURE 1 (Page 26 of 93)
RJ ICS-K ANNUNCIATOR RESPONSE ICS-CY3-02-03 K-02-03 icsMNl
[
FUSE BLOWN EVENT POINT 1109 i
INDICATED CONDITION:
o-ICS FUSE BLOWN, LOCATED IN ICS CABINET 4 FUSE PANEL.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O o FUSE PANEL LOCATED IN ICS CABINET 4 AMBER FUSE BLOWN INDICATION.
1 O
OPERATOR ACTIONS FOR A VALID ALARM o ENSURE PLANT STABLE.
o REFER TO OP-504 FOR FUSE INFORMATION.
o CONTACT I&C SHOP.
DISCUSSION:
THIS ALARM INDICATES A FUSE IS BLOWN THAT FEEDS ICS COMPONENTS.
OP-504 WILL HELP DETERMINE EQUIPMENT EFFECTED.
REFERENCES:
NNI DRAWINGS SENSING ELEMENT:
FUSE INDICATION RELAY O
-AR-503 Rev. 19 Page 28
. +. - -... -...
. - -..., _. _. - -.., _,. _ ~,. _ _ _ _ -.
i ENCLOSURE 1 (Page 27 of.93) t O
-ICS-K ANNUNCIATOR RESPONSE ICS-CY3-02-03 K-02-03 q
ICS/NNI FUSE BLOWN i
EVENT POINT 1136 l
INDICATED CONDITION:
o NNI-X FUSE IS BLOWN, LOCATED IN NNI CABINET-1 FUSE PANEL.
l
'l REDUNDANT 1NDICATION WHICH WILL VERIFY ALARM:
i O.
o FUSE PANEL LOCATED IN THE BACK OF NNI CABINET 1-AMBER FUSL., LOWN INDICATION.
OPERATOR ACTIONS FOR A VALID ALARM:
o ENSURE PLANT STABLE.
o REFER TO OP-501 FOR FUSE INFORMATION.
o CONTACT I&C SHOP.
DISCUSSION:
THIS ALARM INDICATES A FUSE IS BLOWN THAT FEEDS NNI-X COMPONENTS.00-501 WILL HELP DETERMINE EQUIPMENT EFFECTED.
REFERENCES:
NNI DRAWINGS SENSING ELEMENT:
FUSE INDICATION RELAY O
l AR-503I Rev. 19 Page 29
.~
ENCLOSURE _,1 (Page 28 of 93)
O ICS-K ANNUNCIATOR RESPONSE ICS-CY3-02-03 K-02-03 ICS/NNI FUSE BLOWN L
I EVENT POINT 1137 INDICATED CONDITION:
o NNI-X FUSE IS BLOWN, LOCA7ED IN NNI CABINET 2 FUSE PANEL.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O o FUSE PANEL LOCATED IN THE BACK OF NNI CABINET 2 AMBER FUSE BLOWN INDICATION.
OPERATOR ACTIONS FOR A VALID ALARM:
o ENSURE PLANT STABLE.
o REFER TO OP-501 FOR FUSE INFORMATION.
o CONTACT I&C SHOP.
DISCUSSION:
THIS ALARM INDICATES A FUSE 15 BLOWN THAT FEEDS NNI-X COMPONENTS.
OP-50) WILL HELP DETERMINE EQUIPMENT EFFECTED.
REFERENCES:
NNI DRAWINGS SENSING ELEMENT:
FUSE INDICATION RELAY AR-503 Rev. 19 Pagc 30
ENCLOSURE 1 i
(Page 29 of 93)
ICS-K ANNUNCIATOR RESPONSE IC5-CY3-02-03 K-02-03 ICS/NNI FUSE BLOWN 1
EVENT POINT 1138 P
INDICATED CONDITION:
o NNI-X FUSE IS BLOWN, LOCATED IN NNI CABINET 4 FUSL PANEL.
t l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o FUSE PANEL LOCATED IN THE BACK OF NNI CABINET 4 AMBER FUSE BLOWN O
INDICATION.
i OPERATOR ACTIONS FOR A VALID ALARM:
i-o ENSURE PLANT STABLE.
o REFER TO OP-501 FOR FUSE INFORMATION.
l o CONTACT I&C SHOP.
DISCUSSION:
THIS ALARM INDICATES A FUSE IS BLOWN THAT FEEDS NNI-X COMPONENTS.
OP-501 WILL HELP DETERMINE EQUIPMENT EFFECTED.
REFERENCES:
NNI DRAWINGS SENSING ELEMENT:
FUSE INDICATION RELAY O
t AR-503 Rev. 19 Page 31
. -.. ~
LNCLOSURE.1 (Page 30 of 93)
,7
\\
/
~~
ICS-K ANNUNCIATOR RESPONSE IC5-CY3-02-03 K-02-03 ICS/NNI FUSE BLOWN EVENT POINT 1139 INDICATED CONDITION:
o NNI-X FUSE IS BLOWN, LOCATED IN NNI CABINET 1 FUSE PANEL.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
(~;
o FUSE PANEL LOCATED IN THE FRONT OF NNI CABINET 1 AMBER FUSE BLOWN V
INDICATION.
OPERATOR ACTIONS FOR A VALID ALARM:
o ENSURE PLANT STABLE.
o REFER TO OP-50I FOR FUSE INFORMATION.
o CONTACT I&C SHOP.
DISCUSSION:
THIS ALARM INDICATES A FUSE IS BLOWN THAT FEEDS NNI-X COMPONENTS.
OP-501 WILL HELP DETERMINE EQUIPMENT EFFECTED.
REFERENCES:
NNI DRAWINGS SENSING ELEMENT:
FUSE INDICATION RELAY t-'y
'_/i s
AR-503 Rev. 19 Page 32
ENCLOSURE 1 (Page 31 of 93)
O l
ICS-K ANNUNCIATOR RESPONSE-ICS-CY3-02-03 K-02-03 f
icamNI FUSE BLOWN i
EVENT POINT.1140 INDICATED CONDITION:
o NNI-Y FUSE IS BLOWN, LOCATED IN NNI CABINET 6 FUSE PANEL.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O' o FUSE PANEL LOCATED IN THE BACK OF NNI CABINET 6 AMBER FUSE BLOWN INDICATION.
OPERATOR ACTIONS FOR A VALID ALARM:
o ENSURE PLANT STABLE.
o REFER TO OP-501 FOR FUSE INFORMATION.
o CONTACT I&C SHOP.
DISCUSSION:
THIS ALARM INDICATES A FUSE IS BLOWN THAT FEEDS NNI-Y COMPONENTS.
OP-501 WILL HELP DETERMINE EQUIPMENT EFFECTED.
4
REFERENCES:
NNI DRAWINGS SENSING ELEMENT:
FUSE INDICATION RELAY O
AR-503 Rev.'19 Page 33
ENCLOSURE 1 (Page 32 of 93)
O ICS-K ANNUNCIATOR RESPONSE IC5-CY3-02-03 K-02-03 t
ICS/NNI FUSE 1
Bt OWN EVENT POINT 1141 INDICATED CONDITION:
o NNI-Y FUSE 15 BLOWN, LOCATED IN NNI CABINET 6 FUSE PANEL.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o FUSE PANEL LOCATED IN THE FRONT OF NNI CABINET 6 AMBER FUSE BLOWN INDICATION.
OPERATOR ACTIONS FOR A VALID ALARM:
o ENSURE PLANT STABLE.
o REFER TO OP-501 FOR FUSE INFORMATION.
'a CONTACT I&C SHOP.
DISCUSSION:
THIS ALARM INDICATES A FUSE IS-BLOWN THAT FEEDS NNI-Y COMPONENTS.
OP-501.WILL HELP DETERMINE EQUIPMENT EFFECTED.
REFERENCES:
NNI-DRAWINGS SENSING ELEMENT:
FUSE INDICATION RELAY O
AR-503 Rev. 19 Page 34
_ ~.. _. _ _ _ _.. _ _ _. _ _. _ _ _ _ _ _ _
l 1
ENCLOSURE 1 (Page 33 of 93)
O 1
IC5-K ANNUNCIATOR RESPONSE-IC5-CY3-02-03 K-02-03
[
c ICS/NNI FUSE BLOWN P
EVENT POINT 1142 INDICATED CONDITION:
o NNI-Y FUSE IS BLOWN, LOCATED IN NNI CABINET 8 FUSE PANEL.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O o FUSE PANEL LOCATED IN THE BACK OF NNI CABINET 8 AMBER FUSE BLOWN INDICATION.
OPERATOR ACTIONS FOR A VALID ALARM:
o ENSURE PLANT STABLE.
o REFER TO OP-501 FOR FUSE INFORMATION.
o CONTACT I&C SHOP.
DISCUSSION:
THIS ALARM INDICATES A FUSE IS BLOWN THAT FEEDS NNI-Y COMPONENTS.
OP-501 WILL HELP DETERMINE EQUIPMENT EFFECTED.
REFERENCES:
NNI DRAWINGS SENSING ELEMENT:
FUSE INDICATION RELAY O
AR-503 Rev. 19 Page 35-
.. ~.
i ENCLOSURE 1 (Page 34 of 93)
O-ICS-K ANNUNCIATOR RESPONSE ICS-CY3-03-01 K-03-01 I
l l
l ICS POWER I
l FAILURE I
l I
I EVENT POINT 1115 1
INDICATED CONDITION:
o ICS 24V DC BUS POWER FAILURE.
REDUNDANT INDICATION WHICH WILL-VERIFY ALARM:
4 o ICS POWER LIGHT IS OFF LOCATED ON THE REDUNDANT INSTRUMENT PANEL.
o ICS POWER SUPPLY MONITOR, LOCATED IN ICS CABINET 2, HAS NO INDICATING LIGHTS'ON.
o S-1 AND S-2 SWITCHES ARE TRIPPED OFF, LOCATED IN Ir' CABINET 2.
OPERATOR ACTIONS FOR A VALID ALARM:
o TRIP BOTH MAIN FEED PUMPS.
o REFER TO E0P-02.
o REFER TO OP-504 FOR REENERGIZING NNI POWER SUPPLIES.
DISCUSSION:
POWER SUPPLY TO ICS DC BUSSES IS, VBDP-4 BKR.23 AND VBDP-2 BKR.3.
A LOSS OF A POSITIVE OR NEGATIVE BUSS SHOULD TRIP BOTH S-1 AND S-2.
1
REFERENCES:
-NNI DRAWINGS SENSING ELEMENT: VARIOUS NNI CONTACTS.
AR-503 lRev. 19 Page 36
=, ',
we v,--e, g
-,e--
w ---, - - - -
~w
l ENCLOSURE 1 1
(Page 35 of 93)
O ICS-K ANNUNCIATOR RESPONSE ICS-CY3-03-01 K-03-01 I
E I
I ICS POWER -
l l
FAILURE l
l l
l EVENT POINT 1117 INDICATED CONDITION:
4 o ICS 120V AC BUS POWER FAILURE.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o ICS POWER LIGHT IS OFF, LOCATED ON REDUNDANT INSTRUMENT PANEL.
i OPERATOR ACTIONS FOR A VALID ALARM:
o TRIP BOTH MAIN FEED PUMPS.
o REFER TO E0P-02.
DISCUSSION:
POWER ~ SUPPLY TO ICS AC BUS IS, VBDP-4 BKR 25 AND VBDP-2 BKR 4
?
REFERENCES:
NNI DRAWINGS SENSING ELEMENT: VARIOUS NNI CONTACTS.
O AR-503 Rev. 19 Page 37
i ENCLOSURE 1 (Page 36 of 93) l I
ICS-K ANNUNCIATOR RESPONSE ICS-CY3-03-02 K-03-02 SASS MISMATCH EVENT POINT 0084 b
- INDICATED CONDITION:
o RCS LOOP "A" Th INPUTS TO SASS MISMATCHED BY >3T.
.r REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
i O
- o Th TEMPERATURE INDICATOR, RC-4A-TIl.
o Th COMPUTER POINT, R-212.
OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO OP-501 DISCUSSION:
THE NORMAL SASS SIGNAL SOURCE FOR Th LOOP "A" IS THE SELECTED
-TRANSMITTER ON RC-4A-MS, RCS Th SELECTOR SWITCH, RC-4A-MS WILL SELECT THE INPUT TO THE CONTROL BOARD INDICATOR. THE NON-SELECTED INPUT GOES TO THE COMPUTER POINT.
k
REFERENCES:
NNI DRAWINGS SENSING ELEMENT: :-VARIOUS NNI CONTACTS s
O i
AR-503 Rev._19 Page-38
.... =.-. -.
ENCLOSURE 1 (Page 37 of 93)
ICS-K ANNUNCIATOR RESPONSE ICS-CY3-03-02 K-03-02 l
4 SASS MISMATCH l
t EVENT POINT 0088 INDICATED CONDITION:
l o RCS LOOP "A" Tc INPUTS TO SASS MISMATCHED BY >3T.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
l o LOOP "A" Tc INDICATOR. RC-5A-TI2.
\\
o Tc COMPUTER POINT, R-214.
o Tc COMPUTER POINT, R-215.
OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO OP-501 DISCUSSION:
l
~ THE NORMAL SASS SIGNAL SOURCE FOR Tc LOOP "A" IS THE TRANSMITTER SELECTED ON RC-5A-MS2, THE COMPUTER POINTS FOR LOOP "A" Tc ARE HARD WIRED AND ARE VALID RECARDLESS OF THE POSITION OF THE SELECTOR SWITCH, RC-5A-MS2. THE
. CONTROL BOARD INDICATOR..RC-5A-TI2 WILL INDICATE WHATEVER IS SELECTED ON RC-5A-MS2.
REFERENCES:
. NNI DRAWINGS SENSING L.EMENT: VARIOUS NNI CONTACTS AR-503 Rev. 19 Page 39
~
ENCLOSURE 1-1 (Page 38 of 93) l O
ICS-K ANNUNCIATOR RESPONSE ICS-CY3-03-02 K-03-02 t
i SASS MISMATCH EVENT POINT 0195 I
INDICATED CONDITION:
o STEAM GENERATOR "A" STARTUP LEVEL INPUTS TO SASS MISMATCHED BY >7.5".
i REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o 0TSG "A" 5/U LEVEL INDICATOR SP-1A-LI2.
o OTSG "A" S/U LEVEL COMPUTER POINT, S-287.
OPERATOR ACTIONS FOR A VALID ALARM:
b o REFER TO OP-501 i
DISCUSSION:
THE NORMAL SASS SIGNAL SOURCE FOR S/U LEVEL OTSC "A" IS THE TRANSMITTER SELECTED ON SP-1A-MS2.
01SG "A" S/U LEVEL SELECTOR SWITCH, SP-1A-MS2 WILL SELECT THE INPUT TO THE CONTROL BOARD INDICATOR. THE NON-SELECTED INPUT GOES TO THE COMPUTER POINT.
1
~
REFERENCES:
NNI DRAWINGS SENSING ELEMENT: VARIOUS NNI CONTACTS i
O i
k
-AR-503-Rev. 19 Page 40
i ENCLOSURE 1
[
(Page 39 of 93)
O ICS-K ANNUNCIATOR RESPONSE ICS-CY3-03-02 K-03-02 i
SASS-MISMATCH i
3 EVENT POINT 0258 INDICATED' CONDITION:
o STEAM CENERATOR "A" OPERATE LEVEL INPUTS TO SASS MISMATCHED BY >8.8".
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O o OTSG "A" OPERATE LEVEL INDICATOR, SP-1A-LIR1.
o OTSG "A" OPERATE LEVEL COMPUTER POINT, S-284.
ODERATOR ACTIONS FOR A VALID ALARM:
o REFER TO OP-501
\\
DISCUSSION:
THE NORMAL SASS SIGNAL SOURCE FOR OTSG "A" OPERATE LEVEL IS THE TRANSMITTER SELECTED ON SP-1A-MS1, OTSG "A" OPERATE LEVEL SELECTOR SWITCH, SP-1A-MS1 WILL SELECT THE INPUT TO THE CONTROL BOARD INDICATOR. THE NON-SELECTED INPUT GOES TO THE COMPUTER POINT.
i
REFERENCES:
NNI DRAWINGS SENSING ELEMENT: VARIOUS NNI CONTACTS 9-h AR-503-Rev. 19 Page 41
-N yrm - -:
T-7 ay 3,
1 w- + - - - -
eme,-
ww me-+--
7-n=
-e-,
,,-iac e----.----gi-
'a-wwe
-ew--++-*fm-
- w,-'
,e---
+e-
_ ~
ENCLOSURE 1 (Page 40 of 93)
O ICS-K ANNUNCIATOR RESPONSE ICS-CY3-03-02 K-03-02 A
SASS MISMATCH j
EVENT POINT 0260 INDICATED CONDITION:
o LOOP "A" FEEDWATER TEMPERATURE INPUTS TO SASS MISMATCHED BY >15T.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O o LOOP "A" FEEDWATER TEMPERATURE INDICATOR SP-5A-TI.
o LOOP "A" FEEDWATER TEMPERATURE COMPUTER POINT, S-290.
OPERATOR ACTIONS FOR A VALID ALARM:
l o REFER TO OP-501
(
i.
DISCUSSION:
THE NORMAL SASS SIGNAL SOURCE FOR LOOP "A" FEEDWATER TEMPERATURE IS THE TRANSMITTER SELECTED ON SP-5A-SEL.
LOOP "A" FEEDWATER TEMPERATURE SELECTOR SWITCH, SP-5A-SEL WILL SELECT THE INPUT TO THE CONTROL BOARD INDICATOR. THE NON-SELECTED INPUT GOES TO THE COMPUTER POINT.
REFERENCES:
NNI DRAWINGS SENSING ELEMENT: VARIOUS NNI CONTACTS O
AR-503 Rev. 19 Page 42
.. ~. _ _ -, _ _. _. _. -. _ - -. _ - - - _. _ -. _. _. _
. _ _ _ _ _........ _ _ _ _ _ _. _.. _ _ _ _. _ _ _ _ _ _. _ ____i r
i e
ENCLOSURE 1 (Page 41 of 93)
ICS-K ANNUNCIATOR RESPONSE ICS-CY3-03-02 K-03-02 t
[
SASS l
MISMATCH l
l EVENT POINT 0262 INDICATED CONDITION:
(
o LOOP "A" FEEDWATER FLOW INPUTS TO SASS MISMATCHED BY >.18 MII.LON LBM/HR.
.t REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o LOOP "A" FEEDWATER FLOW INDICATOR, SP-8A-FIR 1.
O o LOOP "A" FEEDWATER FLOW COMPUTER POINT, S-301.
OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO OP-501 DISCUSSION:
THE NORMAL SASS SIGNAL SOURCE FOR LOOP "A" FEEDWATER FLOW IS THE SELECTED TRANSMITTER ON SP-8A-MS.
LOOP "A" FEEDWATER FLOW SELECTOR SWITCH, SP-8A WILL SELECT THE INPUT TO THE CONTROL BOARD INDICATOR. THE NON-SELECTED INPUT GOES TO THE COMPUTER POINT.
I
REFERENCES:
NNI DRAWINGS b
SENSING ELEMENT: VARIOUS NNI CONTACTS
'O T
'AR-503 Rev. 19-Page 43
~.... _ _. _.... _.... _, -.,.
ENCLOSURE 1 (Page 42 of 93)
ICS-K ANNUNCIATOR RESPONSE ICS-CY3-02-02 K-03-02 SASS MISMATCH EVENT POINT 0761 INDICATED CONDITION:
o Tave INPUTS TO SASS MISMATCHED BY >3T.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O-l o Tave INDICATOR RC-A/B-tai.
o Tave DIGITAL INDICATOR RC-12-Tal.
OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO OP-501 DISCUSSION:
THE SASS SIGNAL SOURCE FOR Tave IS THE SELECTED LOOP ON RC-12-TAS.
THE Tave AUT0/ MANUAL TRANSFER SWITCH, RC-12-TAS SELECTS THE INPUT TO THE DIGITAL CONTROL BOARD INDICATOR, RC-12-TAI. THE NON-SELECTED INPUT l
GOES TO THE CONTROL BOARD EDGEWISE INDICATOR, RC-7A/B-TAI.
REFERENCES:
NNI DRAWINGS SENSING ELEMENT: VARIOUS NNI CONTACTS O
AR-503 Rev. 19 Page 44 m,.
ENCLOSURE 1 l
(Page 43 of 93)
-j O
f 1
ICS-K ANNUNCIATOR RESPONSE ICS-CY3-03-02 K-03-02 s
1 SASS i
MISMATCH i
l EVENT POINT 0762 i
I INDICATED CONDITION:
o-LOOP "A" FEEDWATER A P INPUTS TO SASS MISMATCHED BY >3 PSID.
l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O o LOOP "A" FEEDWATER A P COMPUTER POINT A-302.
o LOOP "A" FEEDWATER A P COMPUTER POINT A-303.
4 OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO OP-501 DISCUSSION:
THE NORMAL SASS $1GNAL SOURCE FOR LOOP "A" FEE 0 WATER A P IS THE SELECTED TRANSMITTER IN NNI CABINET 3.
e
REFERENCES:
NNI DRAWINGS SENSING ELEMENT: VARIOUS NNI CONTACTS O
AR-503 Rev. 19 Page 45
_. _ _ _. _ _. _ _ -. _ _ _. _..,. _ - _ _ _. _ -,. _. _ - _. ~... _ _......
ENCLOSURE.1 (Page 44 of 93)
ICS-K ANNUNCIATOR RESPONSE ICS-CY3-03-02 K-03 l SASS MISMATCH EVENT POINT 0771 INDICATED CONDITION:
o TURBINE HEADER PRESSURE "A" INPUTS TO SASS MISMATCHED BY >18 PSIG.
REDUNDANT INDICATION WHICH WILL VERIFY AliM:
o TURBINE HEADER PRESSURE "A" INDICATOR SP-10A-PIR1 o TURBINE HEADER PRESSURE "A",
PT1-Y, COMPUTER POINT T-228.
O o TURBINE HEADER PRESSURE "A",
PT2-X, COMPUTER POINT T-230 OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO OP-501 r
DISCUSSION:
THE NORMAL SASS SIGNAL SOURCE FOR "A" TURBINE HEADER PRESSURE IS THE TRANSMITTER SELECTED IN NNI CABINET 3.
TURBINE HEADER PRESSURE SELECTOR LOCATED IN NNI CABINET 3 WILL SELECT
.THE INPUT TO THE CONTROL BOARD INDICATOR. THE NON-SELECTED INPUT COES TO THE COMPUTER POINT.
COMPUTER POIN1 T228 MONITORS TRANSMITTER SP-10A-PT1 COMPUTER POIMT T230 MONITORS TRANSMITTER SP-10A-PT2.
REFERENCES:
NNI DRAWINGS SENSING ELEMENT: VARIOUS NNI CONTACTS O
AR-503 Rev. 19 Page 46
_.m
__-._._.-.-____._m I
ENCLO5URE l (Page 45 of 93).
O
-IC5-K ANNUNCIATOR RESPONSE ICS-CY3-03-02 K-03-02 l
4 i
SASS MISMATCH EVENT POINT 0783 INDICATED CONDITION:
o A Tc INPUTS TO SASS MISMATCHED BY >0.61.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O o A Tc INDICATOR RC-8-DT1.
o DIFFERENCE BETWEEN RC-5A-TI2 AND RC-58-TI2.
OPERATOR AGIONS FOR A VALID ALARM:
o REFER TO OP-501 DISCUSSION:
THE NORMAL SASS SIGNAL SOURCE FOR A Tc IS NNI-X OR NNI-Y SELEGED IN NNI CAB'WT 5.
THE A Tc CONTROL BOARD INDICATOR, RC-8-DT1 INDICATES THE INPUT SELECTED IN THE NNI CABINET.
i
REFERENCES:
NNI DRAWINGS SENSING ELEMENT: VARIOUS NNI CONTACTS a
f AR-503 Rev. 19 Page 47
I ENCLOSURE 1 (Page 46 of 93)
ICS-K ANNUNCIATOR RESPONSE ICS-CY3-03-02 K-03-02 SASS MISMATCH EVENT POINT 0784 INDICATED CONDITION:
l o RCS NARROW RANGE PRESSURE INPUTS TO SASS MISMATCHED BY >24 PSIG.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O o RCS PRESSURE RECORDER, RC-3A-PIR1.
o RCS PRESSURE RECORDER, RC-3A PIR2.
4 OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO OP-501 DISCUSSION:
THE NORMAL SASS SIGNAL SOURCE FOR RCS PRESSURE IS, RPS-A OR RPS-B SELEGED IN NNI CABINET 3.
REFERENCES:
NNI DRAWINGS SENSING ELEMENT: VARIOUS NNI CONTACTS
]
V AR-503 Rev. 19 Page 48
l i
ENCLOSURE 1 (Page 47 of 93)
O ICS-K ANNUNCIATOR RESPONSE ICS-CY3-03-02 K-03-02 i
SASS MISMATCH I
i EVENT POINT 0785 INDICATED CONDITION:
o PRESSURIZER LEVEL INPUTS TO SASS MISP.ATCHED BY >9.6.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O o PRESSURIZER LEVEL INDICATION, RC-1-LI3.
o PRESSURIZER LEVEL INDICATION, RC-1-LI4.
1 i
OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO OP-501 i
DISCUSSION:
THE NORMAL SASS' SIGNAL SOURCE FOR PRESSURIZER LEVEL IS THE TRANSMITTER SELECTED ON RC-1-MS.
REFERENCES:
NNI DRAWINGS SENSING ELEMENT: VARIOUS NNI CONTACTS O
AR-503
.Rev._19 Page 49
p ENCLOSURE 1 (Page 48 of 93)
O ICS-K ANNUNCIATOR RESPONSE ICS-CY3-03-02 K-03-02 i
SASS MISMATCH I
EVENT POINT 0786 INDICATED CONDITION:
-o RCS LOOP "B" Th INPUTS TO SASS MISMATCHED BY >3%.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o Th TEMPERATURE INDICATOR, RC-4B-TIl O,
o Th COMPUTER POINT, R-213 i
OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO OP-501 DISCUSSION:
THE NORMAL SASS SIGNAL SOURCE FOR Th LOOP "B" IS THE TRANSMITTER SELECTED ON RC-48-MS.
RCS Th SELECTOR SWITCH, RC-48-MS WILL SELECT THE INPUT TO THE CONTROL BOARD INDICATOR.
THE NON-SELECTED INPUT GOES TO THE COMPUTER POINT.
REFERENCES:
NNI DRAWINGS i
SENSING ELEMENT: VARIOUS NNI CONTACTS O
i l
l e
9 ENCLOSURE 1 (Page 49 of 93)
ICS-K ANNllNCIATOR RESPONSE ICS-CY3-03-02 K-03-02 SASS MISMATCH EVENT POINT 0788 INDICATED CONDITION:
l 0 RCS LOOP "B" Tc INPUTS TO SASS MISMATCHED BY >3T.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
Ol o Tc LOOP "B" INDICATOR, RC-58-TI2.
o Tr. COMPUTER POINT, R-216.
o Tc COMPUTER POINT, R-217.
OPERATOR \\CTIONS FOR A VALID ALARM:
o REFER TO OP-501 DISCUSSION:
THE NORMAL SASS SIGNAL SOURCE FOR Tc LOOP "B" IS THE TRANSMITTER SELECTED ON RC-58-MS2.
THE COMPUTER POINTS FOR LOOP "B" Tc ARE HARD WIRED AND ARE VALID REGARDLESS OF THE POSITION OF THE SELECTOR SWITCH, RC-58-MS2. THE l
CONTROL BOAhD INDICATOR, RC-5B-TI2 WILL INDICATE WHATEVER IS SELECTED ON RC-5B-MS2,
REFERENCES:
NNI DRAWINGS SENSING ELEMENT: VARIOUS NNI CONTACTS AR-503 Rev. 19 Page 51
ENCLO5d;;E 1 (Page 50 of 93)
ICS-K ANNUNCIATOR RESPONSE ICS-CY3-03-02 K-03-02 SASS MISMATCH 4
EVENT POINT 0793 INDICATED CONDITION:
o STEAM GENERATOR "B" STARTUP LEVEL INPUTS TO SASS MISMATCHED BY >7.5".
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O o OTSG "B" S/U LEVEL INDICATOR, SP-18-LI2.
o OTSG "B" S/U LEVEL COMPUTER POINT, S-293.
OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO OP-501 DISCUSSION:
THE NORMAL SASS SIGNAL SOURCE FOR S/U LEVEL OTSG "B" IS THE TRANSMITTER SELECTED ON SP-1B-MS2.
OTSG "B" S/U LEVEL SELECTOR SWITCH, SP-18-MS2 WILL SELECT THE INPUT TO THE CONTROL BOARD INDICATOR. THE NON-SELECTED INPUT GOES TO THE COMPUTER POINT.
REFERENCES:
NNI DRAWINGS SENSING ELEMENT: VARIOUS NNI CONTACTS O
-AR-503 Rev. 19~
Page 52
t ENCLOSURE 1 (Page 51 of 93)
ICS-K ANNUNCIATOR RESPONSE ICS-CY3-03-02 K-03-02
[
i SASS MISMATCH EVENT POINT 0796 1
INDICATED CONDITION:
l o STEAM GENERATOR "B" OPERATE LEVEL INPUTS TO SASS MISMATCHED BY >8.8".
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O o OTSG "B" OPERATE LEVEL INDICATOR, SP-18-LIR1.
o OTSG "B" OPERATE LEVEL COMPUTER POINT, 5-291.
OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO OP-501 DISCUSSION:
THE NORMAL SASS SIGNAL SOURCE FOR OTSG "B" OPERATE LEVEL IS THE TRANSMITTER SELECTED ON SP-1B-MS1.
OTSG "B" OPERATE LEVEL SELECTOR SWITCH, SP-1B-MS1 WILL SELECT THE INPUT TO THE CONTROL BOARD INDICATOR. THE NON-SELECTED INPUT GOES TO THE COMPUTER POINT.
~
REFERENCES:
NNI DRAWINGS SENSING ELEMENT: VARIOUS NNI CONTACTS w
AR-503 Rev. 19 Page 53
. =
EBCLOSURE 1 (Page 52 of 93)
O
.ICS-K ANNUNCIATOR RESPONSE
-ICS-CY3-03-02 K-03-02 SASS MISMATCH EVENT POINT 0802 INDICATED CONDITION:
o LOOP "B" FEEDWATER TEMPERATURE INPUTS TO SASS MISMATCHED BY >15T.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O.
o LOOP "B" FEEDWATER TEMPERATURE INDICATOR, SP-58-TI.
o LOOP "B" FEFDWATER TEMPERATURE COMPUTER POINT, S-302.
OPERATOR ACTIONS FOR A' VALID ALARM:
o REFER TO OP-501 DISCUSSION:
THE NORMAL SASS SIGNAL SOURCE FOR LOOP "B" FEEDWATER TEMPERATURE IS THE TRANSMITTER SELCCTED ON SP-5B-SEL.
LOOP "B" FEEDWATER TEMPERATURE SELECOR SWITCH, SP-58-SEL WILL SELEG THE INPUT TO THE CONTROL BOARD INDICATOR. THE NON-SELECTED INPUT GOES TO THE COMPUTER POINT.
REFERENCES:
NNI DRAWINGS SENSING ELEMENT: VARIOUS NNI CONTACTS O
Ar
Rev. 19 Page 54
ENCLOSeki_l (Page 53 of 93)
ICS-K ANNUNCIATOR RESPONSE ICS-CY3-03-02 K-03-02 SASS MISMATCH 4
EVENT POINT 0805 INDICATED CONDITION:
o LOOP "B" FEEDWATER FLOW INPUTS TO SASS MISMATCHED BY >.18 PIILLON LBM/HR.
i REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
n/
I o LOOP "B" FEEDWATER FLOW INDICATOR, SP-008A-FIR 1. (PEN B)
N,_
o LOOP "B" FEEDWATER FL34 COMPUTER POINT, S-302.
OPERATOR AGIONS FOR A VALID ALARM:
o REFER TO OP-501 i
L 4
DISCUSSION:
THE NORMAL SASS SIGNAL SOURCE FOR LOOP "B" FEEDWATER FLOW IS THE TRANSMITTER SELEGED ON SP-88.
LOOP "B" FEEDWATER FLOW SELECTOR SWITCH, 51-8B WILL SELECT THE INPUT TO THE CONTROL BOARD INDICATOR. THE NON-SELECTED INPUT GOES TO THE COMPUTER POINT.
REFERENCES:
NNI DRAWINGS SENSING ELEMENT: VARIOUS NNI CONTACTS a
O n
AR-503 Rev. 19 Page 55
~...
- -... ~. _ _ _....
. - ~
..e ENCLOSURE 1
'(Page 54 of 93)
O i
i ICS-K ANNUNCIATOR RESPONSE ICS-CY3-03-02 K-03-02 L
sass 14ATCH i
i EVL4 POP i0806 INDICATED CONDITION:
i-o LOOP "B" FEEDWATER A.P INPUTS TO SASS MISMATCHED BY >3 PSID.-
F REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O
-o LOOP "B" FEEDWATER A P COMPUTER POINT A-302.
b o LOOP "B" FEEDWATER A P COMPUTER POINT A-303.
' OPERATOR ACTIONS FOR A VALID ALARM:
[
-o REFER TO OP-501 4
DISCUSSION:
THE NORMAL SASS SIGNAL SOURCE FOR LOOP "B" FEEDWATER A P IS THE
. TRANSMITTER SELECTED IN NNI' CABINET 5.
4
REFERENCES:
NNI DRAWINGS SENSING ELEMENT: VARIOUS NNI CONTACTS AR-503 Rev. 19 Page 56 1'
,, ',. - - A,,
w a..
,,.,--,--,v,---.
~.n
.n,,,..n.a-
~
+.
,.,--.a
- +,
- +., -,, - - -,
.__m...
ENCLOSURE 1 (Page 55 of 93) i-ICS-K ANNUNCIATOR RESPONSE ICS-CY3-03-02 K-03-02 4
SASS MISMATCH EVENT POINT 0807 INDICATED CONDITION:
o TURBINE HEADER PRESSURE "B" INPUTS TO SASS MISMATCHED BY >I8 PSIG.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
l o TURBINE HEADER PRESSURE "B" INDICATOR SP-10A-PIR1, (PEN B)
Q o TURBINE HEADER PRESSURE "B",
PT1-Y, COMPUTER POINT T-232.
V o TURBINE HEADER PRESSURE "B",
PT2-X, COMPUTER POINT T-234.
OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO OP-501 DISCUSSION:
4 THE NORMAL SASS SIGNAL SOURCE FOR LOOP "B" TURBINE HEADER PRESSURE IS THE TRANSMITTER SELECTED IN NNI CABINET 3.
TURBINE HEADER PRESSURE SELECTOR LOCATED IN NNI CABINET 3 WILL SELECT THE INPUT TO THE CONTROL BOARD INDICATOR. THE NON-SELECTED INPUT GOES TO THE COMPUTER POINT.
COMPUTER POINT T232 MONITORS TRANSMI'TER SP-10B-PT1 COMPUTER POINT T234 MONITORS TRANSMITTER SP-108-PT2
REFERENCES:
NNI DRAWINGS SENSING ELEMENT: VARIOUS NNI CONTACTS
\\
i AR-503 Rev. 19 Page 57--
i ENCLOSURE 1 (Page 56 of 93).
ICS-K ANNUNCIATOR RESPONSE ICS-CY3-03-02 K-03-02 1
1 SASS MISMATCH EVENT POINT 0808 INDICATED CONDITION:
o NEUTRON POWER INPUTS TO SASS MISMATCHED BY >3.8%.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o THE AVERAGE OF NI-5 AND NI-6 INDICATED POWER.
o THE AVERAGE OF NI-7 AND NI-8 INDICATED POWER.
OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO OP-501 DISCUSSION:
THE NORMAL SASS SIGNAL SOURCE FOR NEUTRON POWER IS NI-5/NI-6 OR NI-7/NI-8 SELECTED IN ICS CABINET 4.
REFERENCES:
NNI DRAWINGS SENSING ELEMENT: VARIOUS NNI CONTACTS AR-503 Rev. 19 Page 58
ENCLOSURE l'
-(Page 57.of 93)
ICS-K ANNUNCIATOR' RESPONSE ICS-CY3-03-02 K-03-02 I
SASS MISMATCH EVENT POINT 0845 INDICATED CONDITION:
o GENERATED MEGAWATTS INPUT TO SASS MISMATCHED BY >30 MEGAWATTS.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GENERATED MEGAWATTS COMPUTER POINT, E-210.
o GENERATED MEGAWATTS COMPUTER POINT, E-211.
OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO OP-501 DISCUSSION:
THE NORMAL SASS SIGNAL SOURCE FOR GENERATED MEGAWATTS IS THE TRANSMITTER SELECTED IN ICS CABINET 4.
REFERENCES:
NNI DRAWINGS SENSING ELEMENT: VARIOUS NNI CONTACTS AR-503 Rev. 19 Page 59
_ ~.
EELQSURE 1 (Page 58 of.93) j.;
t ICS-K ANNUNCIATOR RESPONSE ICS-CY3-03 K-03-02 SASS MISMATCH EVENT POINT 0846 INDICATED CONDITION:
o TOTAL CONDENSATE FLOW INPUT TO SASS MISMATCHED BY >0.3 MILLION LBM/HR.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o TOTAL CONDENSATE FLOW RECORDER CD-15-FIR.
o TOTAL CONDENSATE FLOW COMPUTER POINT, A-304.
OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO OP-501 DISCUSSION:
-THE NORMAL SASS SIGNAL SOURCE FOR TOTAL CONDENSATE FLOW IS THE TRANSMITTER SELECTED IN NN1 CABINET 7.
REFERENCES:
NNI DRAWINGS SENSING ELEMENT: VARIOUS NNI CONTACTS AR-503 Rev.-19 Page 60
ENCLOSURE 1 (Page 59 of 93)
ICS-K ANNUNCIATOR RESPONSE ICS-CY3-03 K-03 ;
SASS MISMATCH -
i I
EVENT POINT 0847 i
INDICATED CONDITION:
1 o DEAERATOR TANK LEVEL INPUT TO SASS MISMATCHED BY >0.42 FEET.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o DEAERATOR TANK LEVEL RECORDER CD-61-LIR.
o DEAERATOR TANK LEVEL COMPUTER POINT, S-240.
k OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO OP-501 J
DISCUSSION:
THE NORMAL SASS SIGNAL SOURCE FOR DEAERATOR TANK LEVEL IS THE TRANSMITTER SELECTED IN NNI CABINET 7.
DEAERATOR LEVEL INPUT SELECTOR LOCATED IN NNI CABINET 7 WILL SELECT THE INPUT TO THE CONTROL' BOARD RECORDER, CD-61-LIR, THE NON-SELECTED INPUT GOES TO THE' COMPUTER POINT.
REFERENCES:
NNI DRAWINGS SENSING ELEMENT: VARIOUS NNI CONTACTS O
AR-503~
Rev. 19 Page 61
. ~. -
ENCLO50RE'1 (Page 60 of 93)
ICS-K ANNUNCIATOR RESPONSE ICS-CY3-03-03 K-03-03 SASS TRANSFER EVENT POINT 0776 INDICATED CONDITION:
o SASS HAS AUTO SELECTED EITHER "A" OR "B" INPUT.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o RED SASS TRIPPED INDICATION ON FAILED SASS MODULE.
o SASS MISMATCH ALARM, OPERATOR ACTIONS FOR A VALID ALARM:
o ENSURE PLANT STABLE.
o REFER TO OP-501, DISCUSSION:
THIS ALARM DOES NOT NECESSARILY INDICATE THAT THE SASS SYSTEM HAS TRANSFERRED INPUTS TO A CONTROLLING MODULE IT ONLY INDICATES THAT ONE INPUT THAT FEEDS THAT SASS MODULE HAS FAILED.
REFERENCES:
NNI DRAWINGS SENSING ELEMENT: VARIOUS SASS NNI CONTACTS O
AR-503 Rev. 19 Page.62
ENCLOSURE 1
' age 61 of 93) g ICS-K ANNUNCIATOR RESPONSE ICS-CY3-04-01 K-04-01 l
l LOSS OF FW PP l
l RUNBACK l
l I
I EVENT POINT 1122 INDICATED CONDITION:
e o UNIT LOAD DEMAND >55% AND EITHER:
<2 MAIN FEED PUMPS CPERATING QB
<2 MAIN FEED BOOSTER PUMPS OPERATING REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
Ox o PLANT RUNS BACK TO 55% DEMAND AT 50% PER MINUTE.
o MAIN FEED PUMP OR MAIN FEED BOOSTER PUMP TRIP INDICATIONS.
OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO AP-545.
o REFER TO OP-605 FOR FEED PUMP LIMITATIONS AND RECOVERY.
DISCUSSION:
MAIN FEED PUMP TRIPPED IS SENSED BY <55 PSIG CONTROL OIL PRESSURE.
REFERENCES:
ICS DIGITAL AND ANALOG DRAWINGS SENSING ELEMENT:
ICS MODULE 2-9-9
(
AR-503 Rev. 19 Page 63
ENCLOSURE 1-(Page 62 of 93)
ICS-K ANNUNCIATOR RESPONSE ICS-CY3-04-02 K-04-02 ASYMMETRIC ROD RUNBACK EVENT POINT 1123 INDICATED CONDITION:
o ASYMMETRIC CONTROL ROD CONDITION EXISTS ULD DEMAND IS >60%.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o PLANT IS RUNNING BACK TO 60% DEMAND AT A RATE OF 30% PER MINUTE.
o ASYMMETRIC FAULT LIGHT IS ON LOCATED ON THE DIAMOND CONTROL PANEL.
OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO AP-545.
o REFER TO OP-502 FOR CRD RECOVERY.
DISCUSSION:
AN ASYMMETRIC ROD RUNBACK WILL OCCUR WHEN THE DIAMOND IS IN AUTOMATIC.
IllE ULD DEMA@_ IS >60% AND ANY ONE OF THE FOLLOWING OCCUR:
ANY SAFETY ROD GROUP AT IN-LIMIT.
SAFETY ROD GROUP NOT AT OUT-LIMIT &@ GROUP 5 IN-LIMIT.
CONTROL ROD >9" FAULT &@ ANY SAFETY GROUP NOT AT THE OUT-LIMIT.
CONTROL ROD >9" FAULT &@ CROUP 5 IN-LIMIT.
CONTROL ROD >9" FAULT &@ GROUP 6 IN-LIMIT AND GROUP S >80% WITHDRAWN.
CONTROL ROD >9" FAULT &@ GROUP 7 IN-LIMIT A@ GROUP 6 >80% WITHDRAWN.
REFER TO TS FOR ADMINISTRATIVE REQUIREMENTS.
REFERENCES:
ICS DIGITAL AND ANALOG DRAWINGS SENSING ELEMENT:
ICS MODULE 2-9-8 AR-503-Rev. 19 Page 64
ENCLOSURE l' (Page 63 of 93)
V ICS-K ANNUNCIATOR RESPONSE ICS-CY3-04-03 K-04-03 REACTOR LIMITED BY FEEDWATER I
EVENT POINT 1130 INC'.CATED CONDITION:
o FEEDWATER DEMAND EXCEEDS FEEDWATER FLOW BY MORE THAN 5%.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o UNIT MASTER IN TRACK ALARM.
A o REACTOR DEMAND IS DECREASING.
IU OPERATOR ACTIONS FOR A VALID ALARM:
o STABILIZE RCS PRESSURE AND TEMPERATURE USING PRESSC51IZER HEATERS, SPRAY l
VALVE, AND BALANCE FEED FLOW VS. REACTOR POWER.
o INVESTIGATE AND CORRECT THE CAUSE OF FFFDWATER MISMATCH.
DISCUSSION:
REACTOR LIMITED BY FEEDWATER CROSSLIMIT WILL DRIVE REACTOR DOWN TO l
WITHIN 5% OF INDICATED FEEDWATER FLOW.
REFER TO OP-103A FOR FEEDWATER FLOW VS. REACTOR POWER CURVE.
REFERENCES:
DRAWING ICS DIGITAL AND ANALOG DRAWINGS SENSING ELEMENT:
ICS MODULE 3-6-9
(%
V i
AR-503' Rev. 19
_Page 65
ENCLOSURE 1-(Page 64 of 93)
ICS-K' ANNUNCIATOR RESPONSE ICS-CY3-04-04 K-04-04 UNIT LOAD LIMIT -
HIGH EVENT POINT 1120 INDICATED CONDITION:
o UNIT LOAD DEMAND EXCEEDS THE OPERATOR SET HIGH LOAD LIMIT.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o UNIT MASTER IN TRACK ALARM.
o'ULD INDICATION IS GREATER THAN DIALED HIGH LOAD LIMIT SETPOINT.
OPERATOR ACTIONS FOR A VALID ALARM:
o REDUCE UNIT LOAD DEMAND OR INCREASE DIALED HIGH LOAD LIMIT SETPOINT.
o REFER TO OP-504 FOR NORMAL HIGH LOAD LIMIT SETPOINTS.
DISCUSSION:
IF THE HIGH LOAD LIMIT SETPOINT IS REDUCED BELOW THE CURRENT ULD SETTING, THE ULD WILL RUN DOWN TO THE HIGH LOAD SETPOINT AT OPERATOR DIALED IN RATE.
REFERENCES:
ICS' ANALOG AND DIGITAL DRAWINGS SENSING ELEMENT:
ICS MODULE 3-5-7 1 o AR-503 Rev. 19 Page 66
~
ENCLOSURE-1 (Page 65 of 93)
)
ICS-K ANNUNCIATOR RESPONSE ICS-CY3-04-05 K-04-05 UNIT LOAD LIMIT LOW EVENT POINT 1121 INDICATED CONDITION:
o UNIT LOAD DEMAND IS BELOW THE OPERATOR SET LOW LOAD LIMIT.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o UNIT MASTER IN TRACK ALARM.
o ULD INDICATION LESS THAN DIALED LOW LOAD LIMIT SETPOINT.
OPERATOR ACTIONS FOR A VALID ALARM:
o INCREASE UNIT LOAD DrMAND OR REDUCE DIALED LOW LOAD LIMIT SETPOINT.
o REFER TO OP-504 NORMAL LOW LOAD LIMIT SETPOINTS.
DISCUSSION:
IF THE-LOW LOAD LIMIT SETPOINT IS RAISED ABOVE THE CURRENT ULD SETTING, THE ULD WILL RUN UP TO THE LOW LOAD SETPOINT AT THE OPERATOR DIALED IN RATE.
REFERENCES:
-ICS ANALOG AND DIGITAL DRAWINGS-SENSING ELEMENT:
ICS MODULE 3-5-8
- O AR-503 Rev. 19 Page 67
= _.....
ENCLOSURE 1 (Page 66 of 93)
ICS-K ANNUNCIATOR RESPONSE ICS-CY3-05-01 K-05-01 i
l l
LOSS OF RC PP l
l RUNBACK I
I I
I EVENT POINT 1124' INDICATED CONDITION:
o UNIT LOAD DEMAND >75% DEMAND AND <4 RC PUMPS OPERATING.
o UNIT LOAD DEMAND >100% DEMAND AND 4 RC PUMPS OPERATING.
REDUNDANT INDICATION WrlICH WILL VERIFY ALARM:
o PLANT IS RUNNING BACK TO 75% DEMAND AT A RATE OF 50% PER MINUTE.
,.,/'
o RC PUMP TRIPS.
OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO AP-545.
DISCUSSION:
ICS USES RCP BREAKER POSITION TO DETERMINE REACTOR COOLANT PUMP STATUS.
REFERENCES:
ICS DIGITAL AND ANALOG DRAWINGS SENSING ELEMENT:
ICS MODULE 2-9-11 AR-503 Rev. 19 Page 68
I ENCLOSURE 1 (Page 67 of 93)
O-ICS-K ANNUNCIATOR RESPONSE ICS-CY3-05-03 K-05-03 FW LIMITED BY REACTOR
\\
~_
EVENT POINT 1135 INDICATED CONDITION:
o NI POWER AND REACTOR DEMAND ARE MISMATCHED BY MORE THAN 5%.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o NEUTRON ERROR >5% (POSITIVE OR NEGATIVE) IC-25-NEI.
o UNIT MASTER IN TRACK ALARM.
O OPERATOR ACTIONS FOR A VALID ALARM: ~
l o STABILIZE RCS PRESSURE AND TEMPERATURE USING PZR HEATERS, SPRAY, AND BALANCE FEED FLOW WITH REACTOR POWER.
o INVESTIGATE AND CORRECT THE CAUSE OF REACTOR DEMAND MISMATCH.
DISCUSSION:
THIS ALARM OCCURS WHENEVER REACTOR DEMAND AND NI POWER VARY BY MORE THAN 5%.
IF ONE OR BOTH FW LOOP MASTERS ARE IN AUTO THE FEEDWATER LIMITED BY REACTOR CROSS-LIMIT WILL INCREASE FEEDWATER DEMAND WHEN NEUTRON ERROR IS > +5%, AND DECREASE FEEDWATER DEMAND WHEN NEUTRON ERROR IS < -5%.
THIS MATCHES FEEDWATER TO WITHIN 5% OF NI POWER.
PLACING REACTOR A._N_ DIAMOND IN HAND WILL REMOVE ANY CROSS-LIMIT SIGNAL TO D
NEUTRON ERROR IS DEFINED AS HIGH SELECTED NI POWER MINUS RX DEMAND.
e
REFERENCES:
ICS DIGITAL AND ANALOG DRAWINGS SENSING ELEMENT:
ICS MODULE 3-7-5 4
AR-50h Rev. 19 Page 69
t.
ENCLOSURE 1 (Page 68 of 93)
ICS-K ANNUNCIATOR RESPONSE ICS-CY3-05-04 K-05-04 REACTOR DEMAND LIMITED HIGH EVENT POINT 1112 INDICATED CONDITION:
o REACTOR DEMAND > 102%.
4 REPUNDANT INDICATICN WHICH WILL VERIFY ALARM:
o REAGOR BAILEY DEMAND METER INDICATION.
o NUCLEAR INSTRUMENTS.
OPERATOR ACTIONS FOR A VALID ALARM:
o REDUCE ULD DEMAND TO s 100%.
o ENSURE REACTOR POWER IS LESS THAN 100% RTP PER TS.
DISCUSSION:
THIS ALARM INDICATES THE REACTOR (SUBSECTION) DEMAND IS LIMITED TO a
<102%.
IF ULD INCREASES ANY FURTHER A REACTOR TO FEEDWATER MISMATCH WILL DEVELOP.
THIS CONDITION CAN BE CAUSED BY A LOSS OF OVERALL PLANT EFFICIENCY.
REFERENCES:
ICS ANALOG AND DIGITAL DRAWINGS SENSING ELEMENT:
ICS LIMITER MODULE IC-3811-RC; SIGNAL MONITOR IC-3611-RC n
N 4
AR-503 Rev. 19 Page 70
.._..__ _ ~. _
ENCLOSURE 1 (Page 69 of 03)-
O ICS-K ANNUNCIATOR RESPONSE ICS-CY3-06-01 K-06-01 e
l l
RCS l
l A Tc -
l l
HIGH I
I EVENT POINT 1328 JUJICATED CONDITION:
o SELECTED LOOP "B" Tc EXCEEDS SELECTED LOOP "A" Tc BY MORE THAN ST.
AS SENSED BY RC-8-DTS.
REDUNDANT INDICAT!0N WHICH WILL VERIFY ALARM:
o A Tc INDICATOR.
O o INDIVIDUAL Tc INDICATION.
o FEEDWATER FLOW MISMATCH.
OPERATOR ACTIONS FOR A VALID ALARM:
o ENSURE A Tc SETPOINT CORRECT.
o MANUALLY ADJUST FEEDWATER FLOWS TO CORRECT A Tc MISMATCH.
o ENSURE QPT IS WITHIN LIMITS OF TS.
DISCUSSION:
THIS ALARM INDICATES "B" LOOP TC IS HOTTER THAN "A" LOOP Tc.
FEEDWATER MUST BE INCREASED TO THE "B" LOOP AND DECREASED TO THE "A" LOOP TO RESTORE ATc.
1 1
i
REFERENCES:
DRAWING 208-047 SHEET RC-027-SENSING ELEMENT: RC-8-DTS O
AR-503
_Rev -19 Page 71 c
.em-.
.or r
. - - - ~... -.
- r ENCLOSURE 1 (Page 70 of 93)
O ICS-K ANNUNCIATOR RESPON!.E' ICS-CY3-06-01 K-06-01 mammum 4
l RCS l-A Tc I
HIGH I
EVENT POINT 1370 INDICATED CONDITION:
- o SELECTED LOOP "A" 7 EXCEEDS SELECTED LOOP "B" Tc BY MORE THAN 5'F.
AS SENSED BY RC-8-DTS REDUNDANT INDICATION-WHICH WILL VERIFY ALARM:
o A Tc INDICATOR.
o INDIVIDUAL Tc INDICATION.
1 o FEEDWATER FLOW MISMATCH.
OPERATOR ACTIONS FOR A VALID ALARM:
o ENSURE A Tc SETPOINT CORP 2CT.
o MANUALLY AD]UST FEEDWATEF. FLOWS TO CORRECT A Tc MISMATCH.
o ENSURE QPT IS WITHIN LIMfTS OF TS.
DISCUSSION:
THIS ALARM INDICATES "A" LOOP TC IS HOTTER THAN "B" LOOP Tc.
FEEDWATER MUST BE INCREASED TO THE "A" LOOP AND DECREASED TO THE "B" LOOP TO RESTORE ATc.
REFERENCES:
DRAWING 208-047 SHEET RC-027 SENSING ELEMENT:
RC-8-DTS AR-503 Rev. 19 Page 72
i
~
ENCLOSURE 1 (Page 71 of 93)
O ICS-K ANNUNCIATOR RESPONSE ICS-CY3-06-02 K-06-02 UNIT MASTER IN TRACK EVENT POINT 1125 INDICATED CONDITION:
o THE FOLLOWING CONDITIONS WILL PLACE ICS IN " TRACK":
BOTH FEEDWATER LOOP DEMANDS IN HAND STM GEN /RX MASTER IN HAND TURBINE NOT IN ICS AUTO REACTOR DEMAND STATION IN HAND BOTH OUTPUT BREAKERS OPEN DIAMOND STATION IN MANUAL UNIT UNDER CROSS-LIMIT UNIT LOAD < LOW LOAD LIMIT PLANT RUNBACK UNIT LOAD > HIGH LOAD LIMIT REACTOR TRIP CONFIRM REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o RED AND WHITE LIGHTS ARE ON, LOCATED ON THE ULD STATION.
OPERATOR ACTIONS FOR A VALID ALARM:
o ENSURE STABLE PLANT CONDITIONS.
DISCUSSION:
WHILE IN TRACK ICS USES GENERATED MEGAWATTS AS FRONT END DEMAND, HOWEVER WHEN TRACKING IS DUE TO A LOW OR HIGH LOAD LIMIT, OR WHEN A PLANT RUNBACK IS IN PROGRESS, ICS TRACKS THE IMPOSED LOAD LIMIT.
REFERENCES:
ICS ANALOG AND DIGITAL DRAWINGS SENSING ELEMENT:
ICS MODULE 2-8-13 AR-503 Rev. 19
.Page 73
e
- ~
ENCLOSURE 1 (Page 72 of 93).
ICS-K ANNUNCIATOR RESPONSE-ICS-CY3-06-06 K-06-06 l
l ATMOSPHERIC l-DUMP VALVE NOT FULL CLSD EVENT POINT 0949 INDICATED CONDITION:
o ATMOSPHERIC DUMP VALVE, MSV-25, NOT FULL CLOSED.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o OTSG "A" STEAM PRESSURE >1025 PSIG.
o MSV-25 HAND / AUTO STATION DEMAND INDICATES >0.
OPERA TOR ACTIONS FOR A VALID ALARM:
o REDUCE OTSC "A" PRESSURE.
o VERIFY PROPER OPERATION OF TURBINE BYPASS VALVES.
o IF OTSG PRESSURE NORMAL AND MSV-25 IS OPEN THEN TAKE MANUAL CONTROL OF MSV-25 AND CLOSE VALVE.
DISCUSSION:
MSV-25 RECEIVES IT'S PRESSURE INPUT FROM EFIC OTSG PRESSURE INSTRUMENTS.
REFERENCES:
ORAWING 208-039 SHEET MS-014 4
SENSING ELEMEVr:
33-C, MSV-25 CLOSED CONTACT.
O AR-503 Rev. 19 Page 74
ENCLOSURE 1
-(Page 73 of 93) i g
V ICS-K ANNUNCIATOR RESPONSE ICS-CY3-06-06 K-06-06 I
I ATMOSPHERIC l
i l
DUMP VALVE NOT FULL CLSD EVENT POINT 0950 INDICATED CONDITION:
o ATMOSPHERIC DUMP VALVE MSV-26, NOT FULL CLOSED.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o OTSG "B" STEAM PRESSURE >IO25 PSIG.
o MSV-26 HAND / AUTO STATION DEMAND INDICATES >0.
OPERATOR ACTIONS FOR A VALID ALARM:
o REDUCE OTSG "B" PRESSURE.
o VERIFY PROPER OPERATION OF TURBINE BYPASS VALVES.
o IF OTSG PRESSURE NORMAL AND MSV-26 IS OPEN THEN TAKE MANUAL CONTROL OF MSV-26 AND CLOSE VALVE.
DISCUSSION:
MSV-26 RECEIVES IT'S PRESSURE INPUT FROM EFIC OTSG PRESSURE INSTRUMENTS.
REFERENCES:
' DRAWING 208-039 SHEET MS-014 SENSING ELEMENT:
33-C, MSV-26 CLOSED CONTACT.
O AR-503 Rev. 19.
Page 75
i ENCLOSURE 1 (Page 74 of 93) i ICS-K ANNUNCIATOR RESPONSE ICS-CY3-07-01 K-07-01 l
j STEAM GEN A l
l LEVEL l
l LOW-LOW I
I 4
EVENT POINT 0912 INDICATED CONDITION:
o STEAM GENERATOR "A" LEVEL <12" AS SENSED BY SP-1A-LS2.
4 REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o STEAM GENERATOR "A" LEVEL INDICATION.
O OPERATOR ACTIONS FOR A VALID ALARM:
a VERIFY PROPER FEEDWATER LINEUP.
o TAKE MANUAL CONTROL OF FEEDWATER VALVES AND/OR MAIN FEED PUMP AND INCREASE FEED RATE TO STEAM GENrRATOR "A".
o IF EMERGENCY FEEDWATER ACTUATES REFER TO EOP.
DISCUSSION:
IF ICS CONTROLS DOWNSTREAM OF THE LEVEL LIMITER ARE IN AUTO THE OTSG LEVELS SHOULD BE MAINTAINED AT THE LOW LIMIT OF APPROXIMATELY 30".
EMERGENCY FEED WATER WILL ACTUATE PRIOR TO REACHING 0" ON EFIC LOW RANGE LEVEL INSTRUMENTS.
SP-1A-LS2 INPUT IS FROM "A" STEAM GENERATOR STARTUP LEVEL.
REFERENCES:
DRAWING 208-039 SHEET MS-14 SENSING ELEMENT:
SP-1A-LS2 AR-503 Rev. 19 Page 76
ENCLOSURE 1 (Page 75 of 93)
ICS-K ANNUNCIATOR RESPONSE ICS-CY3-07-02 K-07-02 STEAM GEN A LEVEL HIGH/ LOW EVENT POINT 0943 INDICATED CONDITION:
o STEAM GENERATOR "A" LEVEL >93.5% AS SENSED BY SP-1A-LS1, REDUNDANT JNDICATION WHICH WILL VERIFY ALARM:
o STEAM GENERATOR "A" LEVEL INDICATION.
O OPERATOR ACTIONS FOR A VALID ALARM:
o DETERMINE CAUSE AND RESTORE STEAM GENERATOR LEVEL.
1 o TAKE MANUAL CONTROL OF FEEDWATER VALVES AND/OR MAIN FEED PUMP AND REDUCE FEED RATE TO STEAM GENERATOR "A".
o IF STEAM GENERATOR LEVEL CONTINUES TO INCREASE CONSIDERATION SHOULD BE CIVEN TO ISOLATE MAIN FEEDWATER TO STEAM GENERATOR "A" USING EFIC MAIN FEEDWATER ISOLATION PUSHBUTTONS, DISCUSSION:
IF ICS CONTROLS DOWNSTREAM OF THE LEVEL LIMITER ARE IN AUTO THE OTSG LEVELS Sil0VLD BE MAINTAINED AT THE HIGH-LIMIT OF APPROXIMATELY 95%.
VERY HIGH LEVELS IN A STEAM GENERATOR MAY CAUSE CARRYOVER AND DAMAGE THE MAIN TURBINE.
SP-1A-LSI INPUT IS FROM "A" STEAM GENERATOR OPERATE LEVEL.
THIS IS AN EXPECTED ALARM WHEN THE UNIT IS SHUTDOWN AND GENERATOR IS FILLED PER OP-209.
REFERENCES:
DRAWING 208-039 SHEET MS-14 r(
SENSING ELEMENT:
SP-1A-LS1 AR-503 Rev. 19 Page 77.
.~
ENCLOSURE 1-(Page 76 of 93)
ICS-K ANNUNCIATOR RESPONSE ICS-CY3-07 K-07-02 STEAM GEN A LEVEL-HIGH/ LOW EVENT POINT 0944 INDICATED CONDITIUl:
o STEAM GENERATOR "A" LEVEL <24" AS SENSED BY SP-1A-LS2.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o STEAM GENERATOR "A" LEVEL INDICATION.
O OPERATOR ACTIONS FOR A VALID ALARM:
o DETERMINE CAUSE AND RESTORE STEAM GENERATOR LEVEL.
o TAKE MANUAL CONTROL OF FEEDWATER VALVES AND/OR MAIN FEED PUMP AND INCREASE FEED RATE TO STEAM GENERATOR "A".
o IF EMERGENCY FEEDWATER ACTUATES 1 HEN REFER TO EOP.
DISCUSSION:
IF IN AUTO ICS SHOULD LIMIT OTSG LEVEL TO 30" ON 'THE START UP RANGE, THEREFORE A PROBLEM EXISTS WITH ICS LEVEL CONTROL OR OPERATOR ERROR.
SP-1A-LS2. INPUT IS FROM "A" STEAM GENERATOR STARTUP LEVEL.
REFERENCES:
DRAWING 208-039 SHEET MS-14 SENSING ELEMENT:
SP-1A-LS2 AR-503 Rev. 19 Page 78
ENCLOSURE 1 (Page 77 of 93)
ICS-K ANNUNCIATOR RESPONSE ICS-CY3-07-03 K-07-03 STEAM GEN A BTU CONDITION EVENT POINT 1126-INDICATED CONDITION:
o STEAM GENERATOR "A" FEEDWATER DEMAND IS > BTU LIMIT AS CALCULATED BY ICS.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o THE FOLLOWING PARAMETERS INPUT TO A BTU CONDITI0 t OTSG OUTLET PRESSURE HIGH FEEDWATER TEMPERATURE LOW RCS Th LOW RCS FLOW LOW OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE AND CORRECT CAUSE OF ALARM CONDITION.
o DURING REDUCED Tave OPERATIONS AT THE END OF FUEL CYCLE LIFE (EOL) THIS ALARM IS ACCEPTABLE PROVIDED > 44' MAINSTEAM SUPERHEAT IS MAINTAINED.
DISCUSSION:
THE BTU LIMIT ALARM INDICATES CONDITIONS WHERE EITHER, THE ENERGY INPUT TO THE OTSG IS NOT SUFFICIENT, OR FEEDWATER/0TSG TEMPERATURE / PRESSURE-ARE INADEQUATE TO MAINTAIN REQUIRED SUPERHEAT TO OPERATE-THE MAIN TURBINE.
- WITHOUT -SUFFICIENT SUPERHEAT THERE-IS A RISK OF CARRYOVER DAMAGE TO THE TURBINE BLADING.
REFERENCES:
ICS/NNI DRAWINGS SENSING ELEMENT:
ICS MODULE 3-7-3
/k)):
AR-503.-
Rev. 19 Page 79
ENCLOSURE 1 (Page 78 of 93)
ICS-K ANNUNCIATOR RESPONSE ICS-CY3-07-04 K-07-04 STEAM GEN A LOW l.EVEL LIMITED EVENT POINT 1128 INDICATED CONDITION:
o LOOP "A" FEEDWATER DEMAND IS ON LOW LEVEL LIMIT CONTROL.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
l o ICS MAINTAINS STEAM GENERATOR "A" AT APPROXIMATELY 32.5" ON THE START UP LEVEL INDICATOR.
OPERATOR ACTIONS FOR A VALID ALARM:
I o ENSURE ICS MAINTAINS OTSG LEVEL 2 32.5" ON THE START UP LEVEL INDICATOR.
o IF LEVEL IS NOT BEING MAINTAINED BY ICS THEN MANUALLY CONTROL OTSG LEVEL USING FEEDWATER CONTROL VALVES AND MAIN FEED PUMP SPEED FOR 80 PSID.
DISCUSSION:
THIS ALARM INDICATES THAT ICS IS TRYING TO CONTROL OTSG LEVEL AT THE LOW LEVEL LIMIT SETPOINT.
REFERENCES:
ICS AND NNI DRAWINGS SENSING ELEMENT:
ICS MODULE 3-7-5 AR-503 Rev. 19 Page 80
. -.. +,.,
m-,
e
ENCLOSURE l' (Page 79 of 93)-
s ICS-K ANNUNCIATOR RESPONSE ICS-CY3-07 K-07-05 VERIFY FWV 30 ON AUTO EVENT POINT 1227 INDICATED CONDITION:
o ICS FEEDWATER LOOP "A" DEMAND >50% AND FW-30 <15% FULL OPEN.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o FW-30 AUT0/ MANUAL TOGGLE SWITCH POSITION.
r~s o FW-30 POSITION INDICATION.
o LOOP "A" FEEDWATER MASTER DEMAND INDICATION.
OPERATOR ACTIONS FOR A VALID ALARM:
o VERIFY FW-30 AUT0/ MANUAL TOGGLE SWITCH IN AUTO.
o ENSURE FW-30 IS OPENING.
DISCUSSION:
THIS IS AN EXPECTED ALARM DURING A NORMAL POWER INCREASE.
'AT 50% FEEDWATER DEMAND ICS PULSES THE MAIN BLOCK VALVES TO 15% OPEN
.THEN RUNS THE VALVE OPEN THE REMAINING 85%.
WHEN THE MAIN BLOCK VALVE. LEAVES.IT'S' CLOSED SEAT FEED PUMP CONTROL TRANSFERS FROM AP CONTROL TO FLOW CONTROL,
REFERENCES:
ICS AND NNI DRAWINGS SENSING ELEMENT:
FW-30 POSITION SWITCHES
. OQ.
AR-503 Rev. 19 LPage 81 q
m
-.,e
l l
l ENCLOSURE 1 (Page 80 of 93) l O
t ICS-K ANNUNCIATOR RESPONSE ICS-CY3-07-06 K-07-06 l
I i
I l
AIR FAILURE EVENT POINT 0951 INDICATED CONDITION:
o TURBINE BYPASS VALVE, MSV-9 SUPPLY AIR PRESSURE <60 PSIG AS SENSED BY i
MSV 9-PS.
[
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o INSTRUMENT AIR LOW PRESSURE INDICATION.
I o TURBINE BYPASS VALVE WILL CLOSE.
OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE CAUSE OF LOW AIR PRESSURE.
o CONSIDERATION SHOULD BE GIVEN TO OPERATING MSV-9 LOCALLY USING INSTRUCTIONS GIVEN IN OP-608.
DISCUSSION:
TURBINE BYPASS VALVES ARE AIR TO OPEN AND AIR TO CLOSE THEY ARE DESIGNED TO FAIL CLOSED ON LOSS OF INSTRUMENT AIR.
AT = 60 PSIG DECREASING INSTRUMENT AIR PRESSURE, TRIP VALVE WILL CLOSE TURBINE BYPASS VALVE; AT = 72 PSIG INCREASING INSTRUMENT AIR PRESSURE THE TRIP VALVE WILL RESET AND THE TURBINE BYPASS VALVE WILL REOPEN.
REFERENCES:
DRAWING 208-039 SHEET MS-014 SENSING ELEMENT:
MSV-9-PS O
'AR-503 Rev. 19 Page 82
I B CLOSURE 1 (Page 81 of 93) i.
O ICS-K ANNUNCIATOR RESPONSE ICS-CY3-07-06 K-07-06 l
l l
l l
l l
TUR8 BVP VLV l
j AIR
]
FAILURE EVENT POINT 0952 INDICATED CONDITION:
l.
o TURBINE BYPASS VALVE, MSV-10 SUPPLY AIR PRESSURE <60 PSIG AS SENSED BY MSV-10-PS.
REDUNDANT INDICATION WHICH WIL'. VERIFY ALARM:
o INSTRUMENT AIR LOW PRESSUA. INDICATION.
o TURBINE BYPASS VALVE WILL CLOSE.
OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE CAUSE OF LOW AIR PRESSURE.
o CONSIDERATION SHOULD BE GIVEN TO OPERATING MSV-10 LOCALLY USING 3
INSTRUCTIONS GIVEN IN OP-608.
i DISCUSSION:
TURUINE BYPASS VALVES ARE AIR TO OPEN AND AIR TO CLOSE. THEY ARE DESIGNED TO FAIL CLOSED ON LOS5 0F INSTRUMENT AIR, AT = 60 PSIG DECREASING INSTRUMENT AIR PRESSURE, TRIP VALVE WILL CLOSE TURBINE BYPASS VALVE; AT = 72 PSIG INCREASING INSTRUMENT AIR PRESSURE THE TRIP VALVE WILL RESET AND THE TURBINE BYPASS VALVE WILL REOPEN.
REFERENCES:
DRAWING 208-039 SHEET MS-014 SENSING ELEMENT: MSV-10-PS O
AR'-503-Rev. 19 Page 83
., _.. _.-- _. _..~._
ENCLOSURfJ (Page 82 of 93)
ICS-K ANNUNCIATOR RESPONSE ICS-CY3-07-06 K-07-06 I
I l
l AIR ZZZZZ EVENT POINT 0953 INDICATED CONDITION:
o TURBINE BYPASS VALVE, MSV-11 SUPPLY AIR PRESSURE <60 PSIG AS SENSED BY MSV-11-PS.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o INSTRUMENT AIR LOW PRESSURE INDICATION.
o TURBINE BYPASS VALVE WILL CLOSE.
OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE CAUSE OF LOW AIR PRESSURE.
o CONSIDERATION SHOULD BE GIVEN TO OPERATING MSV-11 LOCALLY USING INSTRUCTIONS GIVEN IN OP-608.
DIECUSSION:
TURBINE BYPASS VALVES ARE AIR TO OPEN AND AIR TO CLOSE, THEY ARE DESIGNED TO FAIL CLOSED ON LOSS OF INSTRUMENT AIR.
AT = 60 PSIG DECREASING INSTRUMENT AIR PRESSURE, TRIP VALVE WILL CLOSE TURBINE BYPASS VALVE; AT = 72 PSIC INCREASING INSTRUMENT AIR PRESSURE THE TRIP VALVE h7LL RESET AND THE TURBINE BYPASS VALVE WILL REOPEN.
REFERENCES:
DRAWING 208-039 SHEET MS-014 SENSING ELEMENT:
MSV-11-PS 4
O t
AR-503-Rev. 19 Page 84
ENCLOSURE 1 f
(Page 83 of 93) l
/
t ICS-K ANNUNCIATOR RESPONSE IC5-CY3-07-06 K-07-06 r
l I
l l
l AIR FAILURE EVENT POINT 0954 INDICATED CONDITION:
o TURBINE BYPASS VALVE, MSV-14 SUPPLY AIR PRES 5URE <60 PSIG A5 SENSED BY MSV-14-PS.
.l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o INSTRU.'1ENT AIR LOW PRESSURE INDICATION.
o TURBINE BYPASS VALVE WILL CLOSE.
OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE CAUSE OF LOW AIR PRESSURE.
o CONSIDERATION SHOULD BE GIVEN TO OPERATING MSV-14 LOCALLY USING INSTRUCTIONS GIVEN IN OP-608.
DISCUSSION:
TURBINE BYPASS VALVES ARE AIR TO OPEN AND AIR TO CLOSE. THEY ARE DESIGNED TO FAIL CLOSED ON LOSS OF INSTRUMENT AIR.
AT = 60 PSIG DECREASING INSTRUMENT AIR PRESSURE, TRIP VALVE WILL CLOSE TURBINE BYPASS VALVE; AT = 72 PSIG INCREASING INSTRUPENT AIR PRES 5URE THE TRIP VALVE WILL RESET AND THE TURBINE BYPASS VALVE WILL REOPEN.
REFERENCES:
DRAWING.208-039 SHEET MS-014 SENSING ELEMENT: MSV-14-P5 O
AR-503 Rev. 19 Page 85
_.. - _ _ _ _ - - _ _ _. _ _ _ _. _. _ _. _ _. _ _... -~. _ _ _
fRCLOS.11&E_1 (Page 84 of 93)
O ICS-K ANNUNCIATOR RESPONSL ICS-CY3-08-01 K-08-01 l
I l
STEAM GEN B l
l LEVEL
~
l LOW LOW
~'
~
l EVENT POINT 0955 t
INDICATED CONDITION:
I o STEAM GENERATOR "B" LEVEL <12" AS SENSED BY SP-1B-LS2.
1 REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
f o STEAM GENERATOR "B" LEVEL INDICATION.
OPERATOR ACTIONS FOR A VALIO ALARM:
o VERIFY PROPER FEEDWATER LINEUP.
o TAKE MANUAL CONTROL OF FEEDWATER VALVES AND/OR MAIN FEED PUMP AND INCREASE FEED RATE TO STEAM GENERATOR "B".
o IF EMERGENCY FEEDWATER ACTUATES REFER TO EOP.
DISCUSSION:
IF ICS CONTROLS DOWNSTREAM OF THE LEVEL LIMITER ARE IN AUTO THE OTSG LEVELS SHOULD BE MAINTAINED AT THE LOW LIMIT OF APPR0XIMATELY 30".
EMERGENCY FEED WATER WILL ACTUATE PRIOR TO REACHING 0" ON EFIC LOW RANCE LEVEL INSTRUMENTS.
SP-IB-LS2 INPUT IS FROM "B" STEAM GENERATOR STARTUP LEVEL.
REFERENCES:
DRAWING 208-039 SHEET M3-14 SENSING ELEMENT:
SP-1B-LS2 AR-503 Rev. 19 Page 86
- ~.-
I l
ENCLOSURE 1 (Page 85 of 93)
O ICS-K ANNUNCIATOR RESPONSE ICS-CY3-08-02 K-08-02 STEAM GEN 8 LEVEL HIGH/ LOW EVENT POINT 0945 INDICATED CONDITION:
o STEAM GENERATOR "B" LEVEL >93.5% AS SENSED BY SP-18-LSI.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o STEAM GENERATOR "B" LEVEL INDICATION.
O OPERATOR ACTIONS FOR A VALID ALARM:
o DETERMINE CAUSE AND RESTORE STEAM GENERATOR LEVEL.
o TAKE MANUAL CONTROL Of FEEDWATER VALVES AND/OR MAIN FEED PUMP AND REDUCE FEED RATE TO STEAM GENERATOR "B".
o IF STEAM GENERATOR LEVEL CONTINUES TO INCREASE CONSIDERATION SHOULD BE GIVEN TO ISOLATE MAIN FEEDWATER TO STEAM GENERATOR "B" USING EFIC MAIN FEEDWATER ISOLATION PUSHBUTTONS.
DISCUSSION:
IF ICS CONTROLS DOWNSTREAM OF THE LEVEL LIMITER ARE IN AUTO THE OTSG LEVELS SHOULD BE MAINTAINED AT THE HIGH LIMIT OF APPROXIMATELY 95%
VERY HIGH LEVELS IN A STEAM GENERATOR MAY CAUSE CARRYOVER AND DAMAGE THE MAIN TURBINE.
SP-IB-LS1 INPUT IS FROM "B" STEAM GENERATOR OPERATE LEVEL.
THIS IS AN EXPECTED ALARM WHEN THE UNIT IS SHUTDOWN AND GENERATOR IS FILLED PER OP-209.
REFERENCES:
DRAWING 238-039 SHEET MS-14 SENSING ELEMENT:
SP-18-LS1 AR-503 Rev. 19-Page 87
ENCLOSURE _1 i
(Page 86 of 93)
O-ICS K ANNUNCIATOR RESPONSE-ICS-CY3-08-02 K-08-02 STEAM GEN 8 LEVEL HIGH/ LOW I
l EVENT POINT 0946 i
INDICATED CONDITION:
o STEAM CENERATOR "B" LEVEL <24" AS SENSED BY SP-1B-LS2.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o STEAM GENERATOR "B" LEVEL INDICATION.
t OPERATOR ACTIONS FOR A VALID ALARM:
o OETERMINE CAUSE AND RESTORE STEAM CENERATOR LEVEL.
o TAKE MANUAL CONTROL OF FEEDWATER VALVES AND/OR MAIN FEED PUMP AND INCREASE FEED RATE TO STEAM CENERATOR "B".
o IF EMERGENCY FEEDWATER ACTUATES THEN REFER TO E0P.
DISCUSSION:
IF IN AUTO ICS SHOULD LIMIT OTSG LEVEL TO 30" ON THE START UP RANGE.
THEREFORE A PROBLEM EXISTS WITH ICS *.EVEL CONTROL OR OPERATOR ERROR.
SP-18-LS2 INPUT IS FROM "B" STEAM GENERATOR STARTUP LEVEL.
REFERENCES:
DRAWING 208-039 SHEET MS-I4 SENSING ELEMENT: SP-1B-LS2 O
i
. AR-503 Rev. 19 Page 88
,37-=
n 4.
.em.,
y m e --
-ww
-g.m.
,. ~,.
~,--4
~.----.-.,.w.-,
.....or.,-,,,e.-.--._..
-.----m--.
.-v,w,
. -... -... - _ -.. -.. ~ - _. _. -....
i ENCLOSURE 1 (Page 87 of 03)
O-i ICS-K ANNUNCIATOR RESPONSE ICS-CY3-08-03 K-08-03 STEAM GEN B BTU CONDITION EVENT POINT 1127 INDICATED CONDITION:
o STEAM GENERATOR "B" FEEDWATER DEMAND-IS > BTU LIMIT AS CALCULATED BY ICS.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o IllLE.QLLOWING PARAMETERS INPUT TO A BTU CONDITION:
OTSG OUTLET PRESSURE HIGH FEEDWATER TEMPERATURE LOW RCS Th TEMPERATURE LOW RCS FLOW L N OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE AND CORRECT CAUSE OF ALARM CONDITION.
o DURING REDUCED Tave OPERATIONS AT THE END OF FUEL CYCLE LIFE (EOL) THIS 4
ALARM IS ACCEPTABLE PROVIDED > 44' MAINSTEAM SUPERHEAT IS MAINTAINED.
DISCUSSION:
THE BTU LIMIT ALARM INDICATES CONDITIONS WHERE EITHER, THE ENERGY INPUT TO THE OTSG IS NOT SUFFICIENT, OR FEEDWATER/0TSG TEMPERATURE / PRESSURE ARE INADEQUATE TO MAINTAIN REQUIRED SUPERHEAT TO OPERATE THE MAIN TURBINE.
WITHOUT SUFFICIENT SUPERHEAT THERE IS A RISK OF CARRYOVER DAMALE TO THE TURBINE BLADING.
REFERENCES:
-ICS/NNI DRAWINGS SENSING ELEMENT: ICS MODULE 3-7-4 AR-503 Rev. 19 Page 89
. ~ _ - -. _ _. _.._.. _.. __
ENCLOSURE 1 (Page 88 of 93)
O-ICS-K ANNUNCIATOR RESPONSE IC5-CY3-08-04 K-08-04 l
1 J
i STEAM OEN 8 i
LOW LEVEL LIMITED i
EVENT POINT 1129 r
INDICATED CONDITION:-
o LOOP "B" FEEDWATER DEMAND IS ON LOW LEVEL LIMIT CONTROL.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
l o ICS MAINTAINS STEAM GENERATOR "B" AT APPROXIMATELY 32.5" ON THE START UP LEVEL INDICATOR.
l OPERATOR ACTIONS FOR A VALID ALARM:
l o ENSURE ICS MAINTAINS OTSG LEVEL a 32.5" ON THE START UP LEVEL INDICATOR.
o IF LEVEL IS NOT BEING MAINTAINED BY ICS THEN MANUALLY CONTROL OTSG LEVEL USING FEEDWATER CONTROL VALVES AND MAIN FEED PUMP SPEED.
DISCUSSION:
THIS ALARM INDICATES THAT ICS IS TRYING TO CONTROL OTSG LEVEL AT THE LOW SETPOINT.
REFERENCES:
ICS AND NNI DRAWINGS SENSING ELEMENT:
ICS MODULE 3-7-6 O
AR-503 Rev. 19 Page 90
- .,-#..---..w.
,-w v.<
,y,-.-,
,..,.r
..m
,-w 3r.,
..,.,-,,,m,_m.
,.r..-..
....m...,-.__w-
~ - - _. - _ _.
-. ~... -.. _ - _.
I a
f QCLOSURE 1 (Page 89 of-93)
O-l ICS-K ANNUNCIATOR RESPONSE ICS-CY3-08-05 K-08-05 l
i VERIFY FWV 29 ON AUTO EVENT POINT 1228 i
INDICATED CONDITION:
o ICS FEEDWATER LOOP "B" DEMAND >50% AND FW-29 <15% FULL OPEN.
REDUNDANT INDICATION-WHICH WILL VERIFY ALARM:
o FW-29 AUT0/ MANUAL TOGGLE SWITCH POSITION.
i o FW-29 POSITION INDICATION.
1 o LOOP "B" FEEDWATER MASTER DEMAND INDICATION.
OPERATOR ACTIONS FOR A VALID ALARM:
o VERIFY FW-29 AUT0/ MANUAL TOGGLE SWITCH IN AUTO.
o ENSURE FW-29 IS OPENING.
DISCUSSION:
4 THIS IS AN EXPECTED ALARM DURING A NORMAL POWER INCREASE.
E AT $0% FEEDWATER DEMAND ICS PULSES THE MAIN BLOCK VALVES TO 15% OPEN THEN RUNS THE VALVE OPEN THE REMAINING 85%.
WHEN THE MAIN BLOCK VALVE LEAVES IT'S CLOSED SEAT FEED PUMP CONTROL TRANSFERS FROM AP CONTROL TO FLOW CONTROL.-
REFERENCES:
ICS AND NNI DRAWINGS SENSING ELEMENT:
FW-29 POSITION SWITCHES
[
t
-AR-503' Rev. 19 Page 91
ENCLOSME_1 l
(Page 90 of 93)
O ICS-K ANNUNCIATOR RESPONSE ICS-CY3-08-06 K-08-06
-l l
AIR l
FAILURE EVENT POINT 1430 INDICATED CONDITION:
o INSTRUMENT AIR PRESSURE TO FWV-37 IE < APPROXIMATELY 35 PSIG AS SENSED BY FWV-37-KS.
t REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o FW-37 AIR FAIL RESET PUSHBUTTON AMBER INDICATING LIGHTS ON.
O o FWV-37 BAILEY CONTROL STATION SHIFTS TO " HAND".
o FWV-37 WILL NOT MOVE IN RESPONSE TO MCB CONTROLS.
OPERATOR ACTIONS FOR A VALID ALARM:
o VERIFY PROPER INSTRUMENT AIR PRESSURE TO FWV-37.
o DEPRESS AIR FAIL RESET PUSHBUTTON WHEN AIR PPESSURE IS RESTORED.
DISCUSSION:
WITH <35 PSIG INSTRUMENT AIR TO FWV-37 A BELLOWS COLLAPSES, THIS MECHANICALLY LOCKS THE VALVE POSITIONER, OPENS A DIAPHRAGM B'rPASS VALVE AND ACTUATES THIS ALARM WHEN SUPPLY AIR PRESSURE DROPS TO <28 PSIG A SOLEN 0ID VALVE CLOSES AND ISOLATES AIR TO THE VALVE. THE AIR FAIL RESET PUSHBUTTON RE-OPENS THIS SOLENOID, BUT IF INSTRUMENT AIR IS BELOW 35 PSIG THE BELLOWS WILL NOT EXPAND AND REMOVE THE MECHANICAL LOCK INSIDE THE VALVE POSITIONER SO HOLDING THE AIR FAIL RESET PUSHBUTTON WILL NOT ALLOW THE OPERATOR TO POSITION THE VALVE UNLESS THE ALARM CLEARS AND THE AIR FAIL RESET PUSHBUTTON INDICATOR LIGHTS GO OUT.
REFERENCES:
DRAWING 208-032 SHEET FW-33 SENSING ELEMENT: 20X-FWV-37 AR-503 Rev. 19 Fage S2
1 EFLOSURE 1 (Page 91 of 93)
O 4
-ICS-K ANNUNCIATOR RESPONSE ICS-CY3-08-06 K-08 1 I
'l AIR l
l FAILURE EVENT POINT 1431 INDICATED CONDITION:
o INSTRUMENT AIR PRESSURE TO FW-38 IS < APPROXIMATELY 35 PSIG AS SENSED BY FWV-38-KS.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o FWV-38 AIR FAIL RESET PUSHBUTTON AMBER INDICATING LIGHTS ON.
o FW-38 BAILEY CONTROL STATION SHIFTS TO " HAND".
O o FW-38 WILL NOT MOVE IN RESPONSE TO MCB CONTROLS.
OPERATOR ACTIMS FOR A VALID ALARM:
o VERIFY PROPER INSTRUMENT AIR PRESSURE TO FWV-38.
> DEPRESS AIR FAIL RESET PUSHBUTTON WHEN AIR PRESSURE IS RESTORED.
DISCUSSION:
WITH <35 PSIG INSTRUMENT AIR TO FWV-38 A BELLOWS COLLAPSES, THIS MECHANICAL'.Y LOCKS THE VALVE POSITIONER, OPENS A DIAPHRAGM BYPASS VALVE AND ACTUATES THIS ALARM. WHEN SUPPLY AIR PRESSURE DROPS TO <28 PSIG A SULEN0ID VALVE CLOSES AND ISOLATES AIR TO THE VALVE. THE AIR FAIL RESET PUSHBU1 TON RE-OPENS THIS SOLEN 0ID, BUT IF INSTRUMENT AIR If BELOW 35 PSIG THE BELLOWS WILL NOT EXPAND AND PEMOVE THE MECHANICAL LOCK INSIDE THE VALVE POSITIONER SO HOLDING THE AIR FAIL RESET PUSHBUTTON WILL NOT ALLOW THE OPERATOR TO POSITION THE VALVE-UNLESS THE ALARM CLEARS AND THE AIR FAIL RESET PUSLBUTTON INDICATOR LIGHTS 'GO OUT. -
REFERENCES:
DRAWING 208-032 SHEET FW-33 SENSING ELEMENT:
20X-FWV-38 AR-503-Rev. 19 Page 93
s ENCLOSURE 1 (Fage 92 of 93)
ICS-K ANNUNCIATOR RESPONSE ICS-CY3 08-06 K-08-06 I
I I
I I
l l
l l
AIR l
l FAILURE EVENT POINT 1432 INDICATED CONDITION:
o INSTRUMENT AIR PRESSURE TO FW-39 VALVE POSITIONER <80 PSIG AS SENSED BY FW-39-PS1 OR o SUPPLY AIR PRESSURE TO FW-39 E/P CONVERTER <28 PSIG AS SENSED BY FW PS2.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o FWV-39 AIR FAIL RESET PUSHBUTTON AMBER INDICATING LIGHTS ON.
o FW-39 BAILEY CONTROL STATION SHIFTS TO " HAND".
o FW-39 WILL NOT MOVE IN RESPONSE TO MCB CONTROLS.
OPERATOR ACTIONS FOR A VALID ALARM:
o VERIFY PROPER INSTRUMENT AIR PRESSURE TO FWV-39.
o DEPRESS AIR FAIL RESET PUSHBUTTON WHEN AIR PRESSURE IS RESTORED.
DISCUSSION:
WITH LOW AIR PRESSURE PS-1 OR PS-2 WILL PICK UP. THIS WILL ENERGIZE A SOLENOID WHICH WILL ISOLATE AND BLEED AIR TO TWO DIAPHRAGM VALVES THAT i
SUPPLY-AIR TO THE VALVE ACTUATOR. WHEN AIR BLEEDS OFF THESE DIAPHRAGM VALVES THE VALVES CLOSE, THIS ISOLATES AIR TO THE TOP AND BOTTOM OF FW-39 ACTUATOR. THIS EFFECTIVELY LOCKS UP THE VALVE. THE AIR FAIL RESET PUSHBUTTON WILL RE-OPEN THIS SOLEN 0ID VALVE BUT IF PRESSURE IS
-NOT HIGH EN0 UGH THE-DIAPHRAGM VALVES WILL NOT OPEN TO ALLOW MOTIVE AIR
-TO GO TO THE VALVE ACTUATGR. 50, OPERATION OF THE VALVES WHILE AIR FAIL RESET ALARM IS IN USING-THE AIR FAIL RESET PUSHBUTTON IS NOT
?
CERTAIN.
REFEREN' ES:
DRAWING 208-032 SHEET FW-33, DRAWING 308-31; O\\
SENSING ELEMENT: 20X-FW-39 AR-503
-1
-Rev. 19.
Page 94
.~n
..~,--n=
F ENCLOSURE 1 (Page 93 of 93)
-~
ICS-K ANNUNCIATOR RESPONSE ICS-CY3-08-06 K-08-06 4
r.
FWf CONTROL VLV AIR FAILURE i
EVENT POINT 1433 INDICATED CONDITION:
o INSTRUMENT AIR PRESSURE TO FWV-40 VALVE POSITIONER <80 PSIG AS SENSED BY FWV-40-PS1 QB o SUPPLY AIR PRESSURE TO FWV-40 E/P CONVERTER <28 PSIG AS SENSED BY FWV-40-PS2.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
f3
(,j o FWV-40 AIR FAIL RESET PUSHBUTTON AMBER INDICATING LIGHTS ON.
o FWV-40 BAILEY CONTROL STATION SHIFTS TO " HAND".
o FWV-40 WILL NOT MOVE IN RESPONSE TO MCB CONTROLS.
OPERATOR ACTIONS FOR A VALID ALANM:
o VERIFY PROPER INSTRUMENT AIR PRESSURE TO FWV-40.
o DEPRESS AIR FAIL RESET PUSHEUTTON WHEN AIR PRESSURE IS RESTORED.
DISCUSSION:
WITH LOW AIR PRESSURE PS-1 OR PS-2 k&LL PICK UP. THIS WILL ENERGIZE A SOLEN 0ID WHICH WIll ISOLATE AND BLEED AIR TO TWO DIAPHRAGM VALVES THAT SUPPLY AIR TO THE VALVE ACTUATOR. WHEN AIR BLEEDS OFF THESE DIAPHRAGM VALVES THE VALVES CLOSE. THIS ISOLATES AIR TO THE TOP AND BOTTOM OF 1
FWV-40 ACTUATOR. THIS EFFECTIVELY LOCKS UP THE VALVE. THE AIR FAIL RESET PUSHBUTTON WILL RE-OPEN THIS SOLEN 0ID VALVE BUT IF PRESSURE IS NOT HIGH ENOUGH THE DIAPHRAGM VALVES WILL NOT OPEN TO ALLOW MOTIVE AIR TO C0 TO THE VALVE ACTUATOR. 50, OPERATION OF THE VAI.VES WHILE AIR FAIL RESET ALARM IS IN USING THE AIR FAIL RESET PUSHBUTTON IS i7T CERTAIN.
REFERENCES:
DRAWING 208-032 SHEET FW-33.
DRAWING 308-324
)
SENSING ELEMENT: 20X-FWV-40 t
AR-503 w Rev. 19 Page 95 (LAST PAGE)
._.