l ENCLOSURE 2
?
NOTICE OF DEVIATION Florida Power Corporation Docket No. 50-302 Crystal River Unit 3 License No. DPR-72 The following deviation was identified during a Nuclear Regulatory Commission (NRC) inspection conducted on April 16 - May 11,-1988.
Revision 8 of the Crystal River Unit 3 Final Safety Analysis Report (FSAR) specifies in paragraph 9.5.1 that the Nuclear Services and Decay (Heat Seawater (RW) system, the Nuclear Services Closed Cycle Cooling SW) system, and the Decay Heat Closed Cycle Cooling (DC) system are designed to the parameters'shown in Table 9-12.
Table 9-12 specifies that the design seawater cooling temperature for both.the SW and DC heat exchangers is 85 degrees Fahrenheit (F).
Contrary to the above, during the period of initial plant operation on March 13, 1977 through September 4,1987, the plant has operated at times with the seawater. cooling temperature in excess.of the 85 degrees F design limit. This temperature has been recorded as high as 90.5 degrees F.
1 Flease provide to the U.S. Nuclear Regulatory CommiWon, ATTN: Document Control Desk, Washington, DC 20555, with a copy to the Regional Administrator, Region II, and a copy to the NRC Resident Inspector, Crystal River 3, in writing within 30 days of the date of this Notice, the reasons for the deviation, the corrective steps which will be taken to avoid further deviations, and the date when your corrective action will be completed. Where good cause is shown, consideration will be given to extending the response time.
FOR THE NUCLEAR REGULATORY COMMISSION
/