Proposed Tech Specs Re ECCS Response Times
ML20155G067
Person / Time
Site: Fermi DTE Energy icon.png
Issue date: 10/07/1988
From:
DETROIT EDISON CO.
To:
Shared Package
ML20155G064 List:
References
NUDOCS 8810140069
Download: ML20155G067 (1)


Text

_ _ _

TABLE 3.3.3-3 EMERGENCY CORE C00L'ING SYSTEN RESPONSE TINES RESPONSE TIME (Seconds)

TRIP FUNCTION 4

1.

CORE SPRAY SYSTEN Reactor Vessel Low Water Level - Level 1.

<30 a.

730 b.

Drywell Pressure-High RA*

c.

Reactor Steam Dome Pressure-Low MA d.

Manual Initiation 2.

LOW PRESSURE COOLANT INJECTION 20E OF RHR SYSTEM Reactor Vessel Low Water Level - Level 1

< 41 a.

7 43 b.

Drywell Pressure - High c.

Reactor Steam Dome Pressure - Low NA*

d.

Reactor Vessel Low Water Level - Level 2 NA L

lj Reactor m an Dome Pressure - Low NA e.

trential Pressure - High NA f.

Riser g.

Reci m >1 on Pump Differential Pressure -

NA High h.

Manual

' ion NA I

3.

HIGH PRESSUkt C00LA.

INJECTION SYSTEN Reactor Vessel Low Water Level - Level 2

< 30 a.

14G NA b.

Drywell Pressure - High c.

Condensate Storage Tank Level-L w RA d.

Reactor Vessel Water Level-High, Level 8 NA j

Suppression Pool Water Level-High NA e.

l f

Manual Initiation NA 7

f 4.

AUTOMATIC DEPRESSURIZATION SYSTEM r

I a.

Reactor Vessel Low Water Level - Level 1 NA NA e

b.

Drywell Pressure-High

)

i NA c.

ADS Timer l

d.

Core Spray Pump Discharge Pressure-High NA RHR LPCI Mode Pump Discharge Pressure-High NA l

e.

Lj f.

Reactor Vessel Low Water Level - Level 3 NA NA g.

Manual Initiation i

5.

LOSS OF POWER l

4.16 kV Erargency Bus Undervoltage (Loss a.

NA ofVoltage) 4.16 kV caerpncy) Bus Undervoltage b.

NA (Degradsd Vo tage i

l l

"These are pemis'sTve signals only. They do not activate ECCS initiation.

I FERMI - Uh1T 2 3/4 3-29

{