ATTACHMENT B PROPOSED CHANGE TO APPENDIX A TECHNCIAL SPECIFICATION TO OPERATING LICENSES NPF-11 AND NPF-18 Revised Pages:

l NPF-11 NPF-18 3/4 3-75 3/4 3-75 3/4 3-77 3/4 3-77 (info only) 3/4 3-78 (info only) 3/4 3-78 (info only) 3/4 3-79 (info only) 3/4 3-80 (revised) i

%h33 g pg i

P 1449K

7-

=

Seune asavuhul INSTRUMENTATION sub usIh'I FIRE DETECTION INSTRUMENTATION s

LIMITING CCNDITION FOR OPERATION 3.3.7.9 As a minimum, the fire detection instrumentation for each fire detection zone of Unit 1 and Unit 2 shown in Tacle 3.3.7.9-1 shall be OPERABLE."

APPLICABILITY: Whenever equipment protected by the fire detection instrument is requirec co be OPERABLE.

ACTION:

With the num:er of OPERABLE fire detection instruments less than the Minimum Instruments GPERABLE requirement of Table 3.3.7.9-1:

Within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />, establish a fire watch patrol to inspect the zone (s) a.

with the inocerable instrument (s) at least once per hour, unless the instrument (s) is located inside the primary containment, then inspect the primary containment at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> or monitor the containment air temperature at least once per hour at the locations listed in Specification 4.6.1.7.

l l23 b.

Restore the minimum moer of instruments to OPERABLE status within 14 days or, prepare an submit a Special Report to the Commission pursuant to Specificatic 6.6.C within 30 days outlining the action taken, the cause of the in erability and the plans and schedule for restoring the instrument (s). OPERABLE status.

b.

,sa The provisions of Specifications 3.0.3 and 3.0.4 are not applicable.

SURVEILLANCE RECUIREMENTS 4.3.7.9.1 Each of the above required fire detection instruments which are accessible during unit operation shall be demonstratec OPERABLE at least once per 6 months by performance of a CHANNEL FUNCTIONAL TEST.

Fire detectors whicn are not accessible during unit coeration shall be demonstrated OPERABLE by the erformance of a CHANNEL FUNCTIONAL TEST during each COLD SHUTDOWN exceeding 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> unless performed in the previous 6 months.,

4.3.7.9.2 The NFPA standard 720 supervised circuits supervision associated with the detector alarms of each of the above required fire detection instruments shall be demonstrated OPERABLE at least once per 6 months. Super-vised circuits with detectors which are inassessible during unit operation shall be demonstrated OPERABLE during each COLD SHUT 00WN exceeding 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> unless performed in the previous 6 months.

"ine normal or emergency power source may be inocerable in OPERATICNAL CONDITION 4 or 5 or when defueled.

LA SALLE - UNIT 1 3/4 3-75 Amendment No. 23

\\

f Sawtearor,?each i

%bwoh l

,A TABLE 3.3.7.9-1 (Continued)

FIRE DETECTION INSTRUMENTATION MINIMUM INSTRUMENTS OPERABLE

  • INSTRUMENT LOCATION HEAT FLAME SMOKE Unit'l Fire Detection Instrumentation (Continued) 14.

Reactor Bldg./ Containment 6

Refuel Floor, Zone 1-26 a.

E1. 843'6", Fire Hazard Zone Area 1 11 b.

Reactor Bldg. East, Zone 1-24 El. 820'6", Fire Hazard Zone 2B1 9

c.

Reactor Bldg. West, Zone 1-23 El. 820'6", Fire Hazard Zone 2B2 18 d.

Reactor Bldg. South, Zone 1-36 j

El. 786'6", Fire Hazard Zone 20 l

17 Reactor Bldg. North, Zone 1-37 e.

E1. 786'6", Fire Hazard Zone 20 '

22 f.

Reactor Bldg. South, Zone 1-34 El. 761', Fire Hazard Zone 2E 18 g.

Reactor Bldg. North, Zone 1-35

.E1. 761', Fire Hazard Zone 2E 7

h.

Containment, Zone 1-16P E1. 761' and 777', Fire Hazard Zone 2J

-9 i.

Containment, Zone 1-16 E1. 74J' and 749', Fire Hazard Zone 2J 5

j.

Reactor Bldg., Zone 1-17 E1. 740', Fire Hazard Zone 2F 11 k.

Reactor Bldg. North, Zone 1-17P El. 740',. Fire Hazard Zone 2F 4

i 1.

Reactor Bldg. SW,. Zone 1-22 E1. 710'6", Fire Hazard Zone 2G 6

m.

Reactor Bldg. NW, Zone 1-22P E1. 710'6", Fire Hazard Zone 2G 17

' n.

Reactor Bldg. South, Zone 1-32 E1. 694', Fire Hazard Zones 2H1, 2H2, 2H3 20 Reactor Bldg. North, Zone 1-33 o.

El. 694', Fire Hazard Zones 2H1, 2H4, 2H5 19 p.

Reactor Bldg. South, Zone 1-30 E1. 673', Fire Hazard Zones 211, 2I2, 2I3 20 q.

Reactor Bldg. North, Zone 1-31 E1. 673', Fire Hazard Zones 211, 214, 215 r.

Ew.~ % g. ' rec, Ew l 4z j

j 6 !.

737 b ' Fire. h Aur5 hw.

1' i

i LA SALLE - UNIT 1 3/4 3-77

50 MC Q T on9 m cd 6kwAfcd TABLE 3.3.7.9-1 (Continued)

J FIRE DETECTION INSTRUMENTATION INSTRUMENT LOCATION MINIMUM INSTRUMENTS OPERABLE" HEAT FLAME SM0KE Unit 1 Fire Detection Instrumentation (Continued)

~

15.

Auxiliary Building / Turbine Bldg a.

Aux. Bldg. Vent Floor, Zone 1-1 2

El. 815', Fire Hazard Zone 4A b.

Aux. Bldg. Vent Floor, Zone 1-2 8

El. 786'6", Fire Hazard Zone 48 c.

Control Room, Zone 1-5 15 El. 768', Fire Hazard Zone 4C1 d.

Computer Room, Zone 1-6 8

E1. 768', Fire Hazard Zone 4C4 e.

Reactor Prot. M-G Set Room, Zone 1-12 12 El. 749', Fire Hazard Zone 403 f.

Cable Spreading Area, Zone 1-18 15 El. 749', Fire Hazard Zone 5A4 g.

Div. 2 SWGR Room, Zone 1-8 15 El. 731', Fire Hazard Zone 4E3 h.

Aux. Electric Equipment Room, Zone 1-27 13 El. 731', Fire Hazard Zone 4E1 1.

Aux. Bldg. Corridor, Zone 1-3 5

El. 731', Fire Hazard Zone 5813 j.

Aux. Bldg. Corridor, Zone 1-7 12 E1. 731',." ire Hazard Zone 5B13 k.

Div. 1 SWGR Room, Zone 1-9 17 El. 710'6", Fire Hazard Zone 4F1 1.

Aux. Bldg. Corridor, Zone 1-4 9

E1. 710'6", Fire Hazard Zone 5C11 m.

Div. 3 SWGR Room, Zone 1-10 5

g,.i-E1. 687', Fire Hazard Zone 501

      1. M 16.

DG Bldg./0G Bldg. Corridor a.

OG Bldg., Zone 1-29 17 E1. 736'6", Fire Hazard Zones 7A1, 7A2, 7A3 b.

DG Bldg. Corridor, Zone 1-25 3

E1. 710'6", Fire Hazard Zone SC11 c.

OG Bldg., Zone 1-28 15 E1. 674', Fire Hazard Zones 7C4, 7CS, 7C6 LA SALLE - UNIT 1 3/4 3-78 v

--,n.

-e

,,e,

.----,,<---,-.-.,-v.

n.

,-a-a---,-

r

INSEAT FcR PAG 5 3l1 3 -2 6 Sid I-3 N.

Aux.JGe'k.'2.,ue.

", Fire y ng.,J 2,ne yc2 39 El.

61d I-38 o.

Av1 643' g., zoue O, Fire \\4 agard 2ane fog 11.

A' a,#.

wwu 2

w-1Mhk/n

.fo wie aC 009:

$d mi NA}

l 4

I f

l

)()O ClhW W

  • 95 GA W TABLE 3.3.7.9-1(Continued)

FIRE DETECTION INSTRUMENTATION INSTRUMENT LOCATION MINIMUM INSTRUMENTS OPERABLE

  • HEAT Ft.AME SMOKE Unit 1 Fire Detection Instrumentation (Continued)
17. Off Gas Building a.

Off Gas Building, Zone 1-15P 3

E1. 710'6", Fire Hazard Zone 10A1 b.

Off Gas Building, Zone 1-15 6

E1. 690', Fire Hazard Zone 1081 B.

Unit 2 Fire Detection Instrumentation' Required For Unit 1 1.

Cable Spreading Room 15 (Dry Pipe Sprinkler System) 2.

Diesel Generator Corridor 9

(Dry Pipe Sprinkler System) 3.

Diesel Generator (2D601K) Room 2

(Cog Flooding System) 4.

Auxiliary Building / Turbine Bldg.

a.

Aux. B1dg. Vent Floor, Zone 2-1 5

E1. 815', Fire Hazard Zone 4A b.

Aux. Bldg. Vent Floor, Zone 2-2 9

E1. 786'6", Fire Hazard Zone 48 c.

Control Roos, Zone 2-5 17 E1. 768', Fire Hazard Zone 4C1 d.

Record Roos, Zone 2-6 3

i E1. 768', Fire Hazard Zone 4C5 e.

Reactor Prot. M-G Set Room, Zone 2-12 12 E1. 749', Fire Hazard Zone 404 f.

Cable Spreading Area, Zone 2-18 13 El 749', Fire Hazard Zone SA4 g.

Div. 2 SWGR Room, Zone 2-8 15 El. 731', Fire Hazard Zone 4E4 h.

Aux. Electric Equipment Room, Zone 2-27 12 E1. 731', Fire Hazard Zone 4E2 1.

Aux. Bldg. Corridor, Zone 2-3 5

E1. 731', Fire Hazard Zone 5813 j.

Aux. B1dg. Corridor, Zone 2-7 12 E1. 731', Fire Hazard Zone 5B13 LA SALLE - UNIT 1 3/4 3-79

NE ud TABLE 3.3.7.9-1 (Continued)

FIRE.0ETECTICN INSTRUMENTATION 4

INSTRUMENT LOCATION MINIMUM INSTRUMINTS OPERABLE

  • HEAT FLAME SMOKE Unit 2 Fire Detection Instrumentation Required for Unit 1 (Continued) k.

Div. SWGR Room, Zone 2-9 17 E1. 710'6", Fire Hazard Zone 4F2 1.

Aux. Bldg. Corridor, Icne 2-4 9

El. 710'6", Fire Hazard Zone SC11 l

5.

DG Bldg./DG Bldg. Corridor a.

DG Bldg., Zone 2-29 14 El. 736'6", Fire Hazard Zones 8A1, 8A2 b.

DG Bldg. Corridor, Zone 2-25 3

{

El. 710'6", Fire Hazard Zone SC11 c.

DG Bldg., Zone 2-28 11 E1. 674', Fire Hazard Zones 8C3, 8C4, 8C5

~

6.

Reactor Bldg.

a.

Refuel Floor, Zone 2-26 6

El. 843'6", Fire Hazard Zone Area 1 b.

Reactor Bldg. East, Zone 2-24 11 E1. 820'6", Fire Hazard Zone 381 f

C-Rea ckr-Bld. Weat, houe M - 40 7

Ll. 807',

Vice lanzard bn 3C-An.Olag., %e 3-h it. % 8 'o, F.'r e. 644 2a rd h N C 3 1

i j

l I

l i

"The fire detection instruments located within the primary containment are not required to be OPERABLE during t.9a cerformance of Ty;:e A Contair. ment Laakage Rata Tests.

o i

LA SALLE - UNIT 1 3/4 3-80

l...

Le as

  • Ofic; mcd sw(3rs; Uci 7

INSTRUMENTATION FIRE DETECTION INSTRUMENTATION 9

i LIMITING CONDITION FOR OPERATION 4

3.3.7.9 As a minimum, the fire detection instrumentation for each fire detection zone of Unit I and Unit 2 shown in Table 3.3.7.9-1 shall be OPERABLE.*

APPLICABILITY: Whenever equipment protected by the fire detection instrument is required to be OPERABLE.

ACTION:

with the numeer of OPERABLE fire detection instruments less than the Minimum Instruments OPERABLE requirement of Table 3.3.7.9-1:

a.

Within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />, establish a fire watch patrol to inspect the zone (s) with the inocerable instrument (s) at least once per hour, unless the instrument (s) is located inside the primary containment, then inspect the primary containment at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> or monitor the containment air temperature at least once per hour at the locations listed in Specification 4.6.1.7.

1 b.

Restore the minimum n car of instruments to OPERABLE status within 14 days or, prepare anc unmit a Special Eeport,to the Commission lM pursuant.to Specification 6.6.C within 30 days outlining the action U

i taken, the cause of the in erability and the plans and schedule for restoring the instrument (s)

OPERABLE status.

N*

l p

The provisions of Specifications 3.0.3 and 3.0.4 are not applicable.

SURVEILLANCE RECUIREMENTS i

4.3.7.9.1 Each of the above required fire detecti'on instruments wnich are j

accessible during unit operation shall be demonstrated OPERABLE at least once per 6 months by performance of a CHANNEL FUNCTIONAL TEST.

Fire detectors l

which are not accessible during unit operation shall be demonstrated CPERABLE by the performance of a CHANNEL FUNCTIONAL TEST during each COLD SHUTDOWN exceeding 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> unless performed in the previous 6 months.,

4.3 7.9.2 The NFPA Standard' 720 supervised circuits supervision associated with the detector alarms of each of the.above required fire detection instruments shall be demonstrated OPERA 8LE at least once per 6' months. Super-vised circuits witn detectors which are inaccessible during unit operation shall be demonstrated OPERABLE during each COLD SHUTDOWN exceeding 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> unless performed in the, previous 6 months.

i I

"The normal or emergency power source may be inoperable in OPERATIONAL CONDITION 4 or 5 or when defueled.

LA SALLE - UNIT 2 3/4 3-75 Amendment No.11

p c C ur%'L~&~S p(?

fAJ R & & T7C U 0*

l J

TABLE 3.3.7.9-1 (Continued)

FIRE DETECTICN INSTRUMENTATICN INSTRUMENT LCCATICN MINIMUM INSTRUNENTS OPERABLE" MEAT Ft.AME SMCAE Unit 2 Fire Detsetion Instrumentation (Continued)

14. Reactor 81dg./Contairment a.

Refuel Floor, Ione 2-25 6

El. 843'5", Fire Hazard Zone Area 1 b.

Reactor 81dg. East, Ione 2-24 11 E1. 820'6, Fire Hazard Zone 381 c.

Reactor Bldg. West, Zone 2-23 9

El. 320'6", Fire Hazard Zone 382 d.

Reactor Bldg. South, Zone 2-36 19 E1. 786'6", Fire Hazard Zone 30 -

e.

Reactor S1dg. North, Zone 2-37 17 E1. 786'6", Fire Hazard Zone 30 f.

' Reactor Bldg. South, Zone'2-34 23 E1. 761', Fire Hazard Zone 3E g.

Reactor Sidg. North, Zone 2-35 18 E1. 761', Fire Hazard Zone 3E h.

Containment, Zone 2-157 7

E1. 761' and 777', Fire Hazard Zone 3J l

1.

Cantainment, Zone 2-16 9

El. 740' and 749', Fire Hazard Zone 3J j.

Reactor Sidg., Zone 2-17 5

l El. 740', Fire Ha:ard Zone 3F k.

Reactor 31dg. North, Ione 2-177 11 E1. 740', Fire Hazard Zone 3F J

1.

Reactor 81dg. SW, Zone 2-22 4

E1. 710'6", Fire Hazard Zone 3G s.

Reactor Bldg. NW, Zone 2-22P 6

E1. 710'6", Fire Hazard Zone 3G n.

Reactor Bldg. South, Zone 2-32 17 E1. 694', Fire Hazard Zones 3H1, 3H2, 3H3 o.

Reactor 81dg. North, Zone 2-33 20 E1. 694', Fire Hazard Zones 3H1, 3H4, 3H5 p.

Reactor Bldg. South, Zone 2-30 19 E1. 673', Fire Hazard Zones 3II, 3I2, 3I3 I

q.

Reactor Bldg. North, Zone 2-31 20 E1. 673', Fire Hazard Zones 3II, 3I4, 3I5 m.

r.

Reactor B1dg. West, Zone 2-40 7

~

E1. 807', Fire Hazard Zone 3C LA SALLE - UNIT 2 3/4 3-77 4

00 CHMeS e.2 u m.u.arn-:

r CA

/

TABLE 3.3.7.9-1 (Continued)

FIRE DETECTICH INSTRUMENTATICN MINIMUM INSTRUMENTS CP5RABLES INSTRUMENT LCCATION MEAT FLAME SMOAE Unit 2 Fire Detection Instrumentation (Continued)

15. Auxiliary Building /Turtine Bldg 5

a.

Aux. 31dg. Vent Floor, Zone 2-1 El. 815', Fire Ha:ard Zone 4A 9

b.

Aux. 31dg. Vent Floor, Zone 2-2 E1. 786'6*, Fire Hazard Zone 48 17 c.

Control Room, Zone 2-5 E1. 768', Fire Hazard Zone 4C1 3

d.

Record Roca, Zone 2-6 E1. 768', Fire Hazard Zone 4C5 e.

Reactor Prot. M-G Set Room, Zone 2-12 12 E1. 749', Fire Hazarc Zone 404 f.

Cable Soreading Area, Zone 2-13 13 E1. 749', Fire Hazard Zone 5A4 g.

Div. 2 S'4R Room, Zone 2-8 15 E1. 731', Fire Hazard Zone 4E4 h.

Aux. Electric Equi;: ment Room Icne 2-27 12 E1. 731', Fire Hazard Icne 4E2 j

i.

Aux. 31dg. Corricor, Icne 2-3 5

El. 731', Fire Hazard Icne 5513 j.

Aux. Bldg. Corridor, Icne 2-7 12 E1. 731', Fire Hazarc Zone 5S13 k.

Div. 1 S'e,GR Room, Zone 2-9 17 E1. 710'6", Fire Hazard Zone 4F2 1.

Aux. Bldg. Corridor, Zone 2-4 9

E1. 710'6, Fire Hazard Zone SC11 j

s.

Div. 3 5'4R Room, Zone 2-10 5

El. 687', Fire Hazard Zone 502 n.

Aux. 81dg., Zone 2-39 10 E1. 768'0", Fire Hazard Zone 4C3 7

o.

Aux. B1dg., Zone 2-28 8

E1. 663'0a, Fire Hazard Zone SE

16. CG Bldg./CG Bldg. Corridor -

a.

CG Bldg., Zone 2-29 14 E1. 736'6', Fire Hazard Zones 8A1, 8A2 LA SALLS - UNIT 2 3/4 3-78

.y.,

.m..____v,-

j l

t ATTACHMENT C SIGNIFICANT HAZARDS CONSIDERATION l

Commonwealth Edison has evaluated the proposed Technical Specification Amendment and determined that it does not represent a significant hazards consideration. Based on the criteria for defining a significant hazards consideration estabished in 10 CFR 50.92, operation of LaSalle County Station Units 1 and 2 in accordance with the proposed amendment will not:

1) Involve a significant increase in the probability or consequences of an accident previously evaluated because the addition of fire detection in the areas specified enhances the likelihood of a fire being detected early.
2) Create the possibility of a new or different kind of accident from any accident previously evaluated because fire detection and protection has been previously evaluated in the FSAR and associated documents. The addition of these detectors is a result of those evaluations.
3) Involve a significant reduction in the margin of safety because the l

additional detectors increase the margin of safety in that the ability to detect and locate a fire is enhanced. The change in reporting requirements does not affect the ability of the fire protection program to detect a fire in a timely manner and take appropriate action. This change is an administrative change to make LaSalle Tech Specs correspond to the GE BWR Standard Tech Specs.

j Based on the preceding discussion, it is concluded that the proposed system change clearly falls within all acceptable criteria with respect to i

the system or component, the consequences of previously evaluated accidents will not be increased and the margin of safety will not be decreased.

Therefore, based on the guidance provided in the Federal Register and the criteria established in 10 CFR 50.92(c), the proposed change does not constitute a significant hazards consideration.

i l

j 1449K l

.--