ML20151Y050
| ML20151Y050 | |
| Person / Time | |
|---|---|
| Site: | 05000601 |
| Issue date: | 04/30/1988 |
| From: | WESTINGHOUSE ELECTRIC COMPANY, DIV OF CBS CORP. |
| To: | |
| Shared Package | |
| ML19302D540 | List: |
| References | |
| NUDOCS 8805040320 | |
| Download: ML20151Y050 (35) | |
Text
- . - - -. - - -.. - - - -.. - -.. -. -. - - - -. - - -
-. - ~. -.
j L, WESTINGH0'.4E CLASS '3 1
i-AMENDWENT 2 TO RESAR-SP/90 PDA N0DULE 13 i
1 i'
AUXILIARY SYSTEMS l
I i
i L
1 LG l
i i
i l
l l
i i
I o
ll'
!9 l
l i
i i
l 1
1 i
' S e
i O
WAPWR-As AMENDNENT 2 7388e:1d APRIL. 1988 I
8805040320 880420 PDR ADOCK 05000601 DCD K
AMENDMENT 2 TO RESAR-SP/90 PDA NODULE 13 AUXILIARY SYSTEMS O
INSTRUCTION SHEET O
Replace current page x with revised page x.
-Replace current pages 9.5-1 thru 9.5-18 with revised pages 9.5-1 thru 9.5-18.
Replace current page 9.5-20 with revised page 9.5-20.
Replace current page 9.5-22 with revised page 9.5-22.
Replace current page 9.5-29 with revised page 9.5-29.
Place remainder of package behind Amendment 1 in Module 13.
l O
O WAPWR-AS AMENDMENT 2 7388e:Id APRIL, 1988
~_
REQUEST FOR ADDITIONAL INFORMATION SECTION 9.5.1 FIRE PROTECTION WESTINGHOUSE ADVANCED PRESSURIZED WATER REACTOR DESIGN RESAR - SP/90 OCTOBER 1986 TASK COMPLETION NO. 141213 i
O 280.1 Section 9.5.1.1.d, pages 9.5-3. -4 The staff position reflecting fire protection for redundant safe shutdown trains in advanced reactor designs is that such O
redundant trains will be completely separated by 3-hour fire rated barriers, or completely separated by a 1-hour fire rated barrier with fire detection and automatic fire suppression throughout the area containing 1-hour fire rated barrier r
separation.
This protection is acceptable for redundant safe shutdown e:;Lipment located inside or outside primary contain-ment.
The staff does not recognize as acceptable for use in Advanced Reactor Design any methods which rely upon:
o Spatial separation, o Use only of automstic detection and suppression, or i
o Separation by radiant energy shields I
This is consistent with the guidance given in Section C.5 General Plant Guidelines. Subsection a.
Building Desion, of Standard Review Plan, MREG-0800, Branch Technical Position CHEB o.5-1.
Section 9.5.1.1.d of the SSAR is inconsistent with this position.
Provide clarification showing how RESAR SP/90 meets this position or provide justification for not doing so.
RESPONSE
Subsection 9.5.1.1(d) has been modified to clarify our intent to meet the guidelines provided in BTP CMEB 9.5-1.
Note that contrary to what is stated above, the use of spatial separation isconsideredacceptableperparagraphC.5.b(2)(b).
O i
L O
WAPWR-AS 280-1 AMENDMENT 2 7388e:1d APRIL, 1988
280.2 Section 9.5.1.1.e, page 9.5-4 The staff understands that one of the major goals of the APWR is to streamline the review process by eliminating requests for deviation and the subsequent need for staff review of such requests. The last sentence on page 9.5-4 reads, "The design basis fire approach will also be utilized as appropriate to determine if specific deviations (emphasis added) from the fire 2
protection features approach will provide an equivalent level of V
fire safety." This sentence is not consistent with the above stated goal.
Please clarify this issue.
(NOTE:
It is the staff position that PRA cannot provide the basis for exemptions torequirements).
RESPONSE
Subsection 9.5.1.1(e) has been moGified to remove the reference to "specific deviations"; deviations to the general separation philosophy are described in Subsection 9.5.1.3(a).
280.3 Section 9.5.1.3.a. page 9.5-7 The same concerns raised in Question 280.1 above apply here respecting spatial separation and use of one-hour fire rated O.
addition, we are confused by the wording in the second paragraph barriers and fire detection and automatic fire suppression.
In concerning the term "fire barriers."
The commonly accepted definition of a fire area is a volume in a building that is bounded by barriers of some known fire resistance rating given in terms of hours.
Please clarify the last sentence which
- reads, in part, "Similarly, fire barriers will be provided within a fire area to separate...."
RESPONSE
i Revisions to Subsection 9.5.1.1(d) and 9.5.1.3(a) are provided to provide conformance with the requirements, and to clarify the definition of a fire area.
- O
)
)
' O WAPWR-AS 280-2 AMENDMENT 2 7388e:1d APRIL, 1988 i
280.4 Section 9.5.1.3, pages 9.5-7,-8 The concerns raised in question 280.1 above reflecting spatial separation, and the concerns raised in question 280.3 above reflecting use of fire barriers within a fire area apply in Subsection a.
Separation of Safe Shutdown Equipment.
Please clarify this section.
RESPONSE
Subsection 9.5.1.3(b) has been revised to provide clarification.
280.5 Section 9.5.1.4.1, page 9.5-8 Please explain how the flame and heat resistant characteristics of the passive fire protection features will be determined, and 3
to what they will be compared.
RESPONSE
It is expected that the flame and heat characteristics of the passive fire protection features included in the SP-90 plant can be demonstrated using existing test data.
If not, additional tests will be performed during the Final Design Stage.
280.6 Section 9.5.1.4.1.a, page 9.5-9 Should the reference in the second line be to Subsection 9.5.1.3(a) rather than to 9.5.1.4(a) as shown?
RESPONSE
Yes!
The text has been revised to reflect Subsection 9.5.1.3(a) as the correct reference section.
I i
}
i O
WAPWR-AS 280-3 AMENDHENT 2 i
7388e:1d APRIL, 1988 i.
I
280.7 Section 9.5.1.4.1.b and e, page 9.5-11 o
See Question 280.1 above for comments on radiant energy O-
- shields, o
We have two questions concerning the last sentence in i
9.5.1.4.1.b which reads, "Each fire barrier component will be tested or analyzed to assure adequate fire resistance ratings."
i a.
We assume that "component" refers to such things as doors, dampers, penetration seals and cable wraps (we have already stated that radiant energy shields are not acceptable), and that such "components" will be tested in configurations like those to be used in this O
advanced reactor design.
The staff finds this concept acceptable.
If "component" refers to individual structural portions of total barriers (i.e. columns and beams or portions of concrete slabs used in the construction of fire wall or ceiling-floor assemblies),
then this concept is not acceptable. Clarify what is l
meant by "component."
.1 b.
The staff generally does not accept analysis in lieu of full scale testing for determining the adequacy of barrier fire resistance rating. How will such analysis be accomplished to assure that the results will be acceptable in place of actual full scale testing?
This position is consistent with Section C.S.a of BTP CHEB 9.5-1 of the Standard Review Plan, NUREG-0800, j
RESPONSE
l l
With regard to part
- a. of the question, the staff's assumption l
with regard to the definition of ' component' is correct.
In response to part b.,
it is the intent to utilize, where l
practical, proven components and materials (see also response to i
Question 280.5).
In scoe :ases, additional analysis may be i
required to determine the adequacy of barrier fire resistance ratirq.
If such analysis cannot be executed in an acceptable
- manner, additional testing will be performed during the Final Design stage.
1 WAPWR-AS 280-4 AMENDMINT 2 7388e:Id APRIL, 1988
280.8 Section 9.5.1.4.1.d, pages 9.5-11, -12 a.
The second paragraph ("Where door assemblies... devices.
l erdhardware.") appears to be an error.
Should this be i
d&leted? If not, clarify your position, b.
The first paragraph at the top of page 9.5-12 is not clear.
Specifically:
l o
What are the qualifications and responsibilities cf the
+
person who will review and evaluate each configuration?
o What code or standard does "analyzed" refer to?
,O o
Will the criteria used in these analyses be that in ASTM
- V E-152 and NFPA 80 or will other criteria be used?
RESPONSE
a.
The paragraph in question was in error and has been deleted, b.
Page 9.5-12 has been revised for clarification purposes.
280.9 Section 9.5.1.4.2.b, pages 9.5-13, -14 Will each fire pump be equipped for automatic and remote manual
- start, and manual stop only at the fire pump location (no remote stop capability), or automatic stop capability that conforms to the requirements of National Fire Protection Association i
Standard No. 20 "Standard for the Installation of Centrifugal l
Fire Pumps?"
Also, NFPA 20 is not referenced along with other NFPA standards at the end of this section.
Is this an oversight, or does Westinghouse not intend to follow this
]
standard with respect to their fire pump installations?
RESPONSE
Exclusion of NFPA 20 here was an error of omission (this standard is referenced throughoutSubsection9.5.1).
The SP/90 will conform to this standard with respect to fire pump installations.
0 4
I I
O WAPWR-AS 280 5 AMENDMENT 2 7388e:1d APRIL, 1988 I
w--
m,,
w---,,-----.-n-,.
r----_,
__--,y,,mr,__g,wn,e-
,rg.-
w,,---
---g
,=g
280.10 Section 9.5.1.4.3.e.2, pace 9.5-17 O-Why has self-contained breathing apparatus (SCBA) for control room personnel who r.ay(See Section C.3.c of BTP CNEBhave to leave th fire not been provided?
9.5-1 of Standard Review Plan, NUREG-0800.)
RESPONSE
O Subsection 9.5.1.4.3(c)2 has been modified to provide control personnel sufficient access to self-contained breathing apparatus for leaving the control room during a fire.
280.11 Section 9.5.1.6, page 9.5-20 Why are the words "suggested" rather than "required," and "recommendations" rather than "requirements" used when referring to National Fire Protection Association Standards 20 and 247
RESPONSE
Subsection-9.5.1.6 has been revised as suggetted.
O.
280.12 Section 9.5.1.7.a.2, pace 9.5-22 Should the second sente,ce read, "Upon completion of a task, and at the end of each work shif t...?"
This will assure clean up of a werk area immediately when a task is completed rather than waiting until the end of a shif t.
Also, if a task extends into other shifts, the work area will be cleaned up at least at the end of each shift. Please clarify.
RESPONSE
The word "and" has been added to clarify this issue.
280.13 Section 9.5.1.7.d.4, page 9.5-29 The third paragraph states that randomly selected unannounced O
drills will be critiqued by independent individuals. Who are these individuals and what are their qualifications?
O WAPWR AS 280 6 AMENDHENT 2 7388e:1d APRIL, 1986
RESPONSE
Ti:e "independent individuals" will be selected by each utility and will be independent of the licensee's staff.
Qualification will be based on each individual's knowledge, gained through training and experience, in the areas of fire protection, fire O
e t t4 #
e <4r
>4 O
~
5 O
O O
r O
WAPWR-AS 280-7 AMENDMENT 2 7388e:1d APRIL, 1988
TABLE OF CONTENTS (Continued)
O
,e<e,ence SAR Section l
Section Title h
Status 9.4.5.3 Codes and Standards 9.4-22 I
9.4.5.4 Safety Evatuation 9.4-22 I
i O
9.4.5.5 Inspection and Testing Requirements 9.4-23 1
9.4.5.6 Instrumentation Application 9.4-24 1
i 9.4.6 Containment Cooling and Ventilation System 9.4-24 1
9.4.6.1 Design Bases 9.4-25 I
9.4.6.1.1 Safety Design Bases 9.4-25 1
9.4.6.1.2 Power Generation Design Bases 9.4-26 I
9.4.6.2
System Description
9.4-26 1
9.4.6.2.1 General Description 9.4-26 I
9.4.6.2.2 Component Description 9.4-29 I
9.4.6.2.3 System Operation 9.4-30 1
9.4.6.3 Codes and Standards 9.4-31 1
9.4.6.4 Safety Evaluation 9.4-32 I
9.4.6.5 Inspection and Testing Requirements 9.4-32 I
9.4.6.6 Instrumentation Application 9.4-33 I
~
9.4.7 Diesel Generator Building Ventilation System 9.4-34 1
9.4.7.1 Design Bases 9.4-34 1
9.4.7.2
System Description
9.4-34 I
1
)
'.4.7.2.1 General Description 9.4-34 1
i 9.4.7.2.2 Component Description 9.4-35 I
9.4.7.2.3 System Operation 9.4-35 I
]
9.4.7.3 Codes and Standards 9.4-35 I
]
9.4.7.4 Safety Evaluation 9.4-36 I
9.4.7.5 Inspection and Requirements 9.4-37 I
9.4.7.6 Instrumentation Application 9.4-37 I
9.4.8 Essential Service Water Pump Structure 9.4-38 l
Ventilation System Design f.riteria l
i j
WAPWR-AS in OCTOBER, 1986 1
5539e:1d l
J m -
TABLE OF CONTENTS (Cont'd)
Reference SAR Section g,
Lan Status
- Section, Title a
9.4.9 Plant Heating System Design Criteria 9.4-38 9.4.9.1 General Descript hn 9.4-38 g
9.4.9.2 Design Criteria 9.4-39 9.4.10 Essential Chilled Water System 9.4-40 1
9.4.10.1 Design Bases 9.4-41 1
9.4.10.1.1 Safety Design Bases 9.4-41 1
9.4.10.2
System Description
9.4-41 1
9.4.10.2.1 General Description 9.4-41 1
9.4.10.2.2 Component Description 9.4-42 1
9.4.10.2.3 System Operation 9.4-42 1
9.4.10.3 Codes and Standards 9.4-43 I
9.4.10.4 Safety Evaluation 9.4-43 1
9.4.10.5 Inspection and Testing Require 4nts 9.4-44 I
9.4.10.6 Instrumentation Application 9.4-45 1
9.5 OTHER AUXILIARY SYSTEMS 9.5-1 fli 9.5.1 Fire Prote: tion System 9.5-1 Ill 9.5.1.1 Design Basis 9.5-1 9.5.1.2 Codes and Standards 9.5-4 2
9.5.1.3 Protection of Safe Shutdown Related 9.5-6 Equipment 9.5.1.4 Fire Protection System and Feature 9.5-8 g
Descriptions 9.5.1.4.1 Passive Fire Protection Features 9.5-8 9.5.1.4.2 Active Fire Protection Features 9.5-13 111 2 l 9.5.1.4.3 Support Systems 9.5-15 9.5.1.4.4 Curbs and Drains 9.5-17 Ill 2 l 9.5.1.4.5 Reactor Coolant Pump 011 Collection System 9.5-17 WAPWR-AS x
AMENDMENT 2 7388e:1d APRIL, 1988
9.5 OTHER AUXILIARY SYSTERS e
9.5.1 Fire Protection System 9.5.1.1 Design Basis I
The Fire Protection Program is developed to assure, through a defense-in-depth satrix, that fire will not affect redundant components required to achieve safe shutdown and to prevent an increased risk of radioactive releases to the In addition, the Fire Protection Program is intended to minimize O
environment.
property damage and protect personnel from injury due to fire.
The l
defense-in-depth protection matrix is based on recognition of potential fire hazards in safety-related areas and the need to protect redundant safe l
shutdown et;uipment from a comen mode fire-related failure.
l
)
a.
A Fire Hazards Analysis will be conducted to assess vulnerability of l
plant safety-related equipment to damage by fire.
The study will j
include an inventory of in situ flammable / combustible material and a t
review of anticipated plant activities such as storage areas, radwaste l
step-off pads, oil quantities in various pieces of equipment, and oil transport and handling methods to determine locations in which a serious fire may occur.
i i
Based on this information, the following features of plant general arrangement will be reviewed:
l l
o Access and egress routes o
Equipment locations
)
o Structural design faatures which separate or isolate redundant 1
safety-related systems.
i t
i j
e Floor drains l
I o
Ventilation
!O I
i WAPWR-AS 9.5-1 AMENDHENT 2 5405e:1d APRIL, ;,988 i
1 i
__.-...,.__,,l-
i o
Construction materials.
.\\
This review will assess potential for damage to safety-related h equipment and the effect of postulated fires relative to maintaining the ability to perform safe shutdown functions and minimize radioactive releases to the environmer.t.
b.
Active and passive fire protection features will be provided in cor.bination as a means for assuring defense-in-depth against fire.
In order to preclude a single fire resulting in an unacceptable release of radioactivity, passive fire protection features with apprcpriate fire resistance qualification will be provided to separate redundant systems and equipment required to achieve safe shutdown.
In areas where plant processes or presence of combustible material result in potential for fire ignition and significant fire propagation er personal injury, apprcpriate fixed fire suppression and detection systems will be installed to promptly notify plant personnel and provide fire suppression capabilities, g
Additional fire barriers, fire detection equipment, fire hose
- stations, and portable fire suppression equipment will be provided based on results of the Fire Hazards Analysis and professional judgment of an engineer experienced in fire protection.
c.
Fire protection concepts for the WAPWR consider fire concurrent with less of off-site power such that safe shutdown is achievable following g less of systems, equipment, and comronents in any one fire area without use of off-site power. Fire, is considered concurrently with other Design Basis Events or Accidents only when one may initiate the other. Examples are as follows:
o Fire induced by a Design Basis Accident (such as earthquake),
o Loss of Coolant Accident (LOCA) induced by fire.
WAPWR-AS 9.5-2 AMENDP.ENT 2 5405e:1d APRIL, 1968
i Where the possibility exists for fire to be induced by a Design Basis Accident, the hazard will be mitigated by system equipment design l
(such es a seismically qualified oil collection system for reactor coolantpumps). Where a loss of equipment function or malfunction due to fire may result in a LOCA, vulnerable equipment and components will be protected from the effects of a fire to preclude a LOCA.
]O If a fire is not initiated by or does not initiate another Design i
Basis Event or Accident, a fire is not considered to occur concurrent with and coincidental to Design Basis Events such as:
O o
o Ternado o
Flood j
o LOCA
)
d.
In Nuclear Power Block (NFB) areas outside containment separation of safety r31ated equipment will be achieved by three hour fire barriers.
1 i
Ins'ide containment, separation by three hour fire barriers is not practical because all compartments need to be in communication with l
each other in order to relieve pressure following a high energy line break.
For this reeson, fire protection is achieved by one or more of l
the following parameters:
i 2
o Separation by existing structural walls (note that these may be 3 l
hour fire barriers, but they do not fully enclose the equipment requiring separation),
i O 1
o Separation by horizontal distance of more than 20 feet with no intervening combustibles or fire hazards, coupled with fire il detection and automatic fire suppression.
10 Fire barriers will also be utilized to separate safety related areas
)
from non-safety related areas as dictated by the Fire Hazards i
nPWR A5 9.5-3 AMENDMENT 2 i
905e:1d APRIL, 1953 i
l
Analysis. Similarly, fire barriers will be provided within a fire area to separate components which present a fire hazard to other g
2 components or cable concentrations within the area. For example, each diesel generator is separated from the remainder of its associated safety related area.
e.
In order to determine appropriate combination of activo and passive fire protection features for property conservation and perser.nel safety considerations, the design basis fire approach will be used, employing professional judgment of engineers experienced in fire protection and use of validated analytical techniques existing in the public domain or developed specifically for the APWR.
2 f.
Fire protection fluid systems will be arranged by piping netwerk and provision of sectional isolation valves, such that a single failure or system impairment will not remove primary and secondary protection from service (i.e., fixed and manual suppression systems).
g.
The citimate objective of the WAPWR Fire Protection Program is to minimize uncontrolled release of radioactive material to meet requirements of 10CFR100, 9.5.1.2 Codes and Standards a.
Nuclear Regulatory Commission NUREG-0800, Standard Review Plan Section 9.5.1 of the Standard Revie. Plan refers to Branch Technical Position (BTP) CHEB 9.5.1 as the technical basis of the Nuclear Poaer Plant Fire Protection Program which is implemented for the WAPWR, BTP 9.5.1 addresses Fire Protection Programs for safety-related systems I
and equiprent and for other plant areas containing fire hazards that could adversely affect safety-related systems.
O WAPWR-AS 9.5-4 AMENDMENT 2 5405e:1d AFR1L, 1955
l il' r
Technical requirements of BTP CMEB 9.5.1 are u'tilized as the basis for the WAPWR Fire Protection Programs.
Specific features which deviate from technical requirements of BTP CHEB 9.5.1 will provide equivalent I
protection as determined by analysis as stated in Subsection 9.5.1.1(e).
b.
National Fire Codes O
National Fire Protection Association (NFPA)Codeeditionscurrentat the time of the PDA module submittal will be used as design standards for systems and features referenced in the codes. The following NFPA
' W s are utilized in development of the fire protection program for gAPWR:
i a 3 3
NFPA 10 - Portable Fire Extinguishers o
NFPA 12 - Carbon Dioside Extinguishing Syttems o
NFPA 12A - Halen 1301 +.. Extinguishing Systems o 'NFPA 13 - Installation of Sprinkler Systems o
NFPA 14 - Installation of Standpipe and Hose Systems i
e NFPA 15 - Water Spray Fixed Systems o
NFPA 20 - Installation of Centrifugal Fire Pumps i
I o
NFPA 22 - Water Tanks for Private Fire Protection i
O o
NFPA 24 - Installation of Private Fire Service Mains and Their j
Appurtenances i
e NFPA 30 - Fla mable and Combustible Liquid Code
[
WAFWR-AS 9.5-5 AMENDMENT 2 5405e:1d AFRIL, 1955 j
i I
~ - - -
o NFDA 37 - Installation and Use of Stationary Combustion Engines and Gas Turbines 9
o NFPA 50 - Bulk 0xygen Systems at Consumer Sites NFPA 50A - Gaseous Hydrogen Systems at Consumer Sites o
o NFPA 72D - Installation, Maintenance and Use of Proprietary Protective Signaling Systems o
NFPA 72E - Automatic Fire Detectors o
NFPA 78 - Lightning Protection Code o
NFPA 80 - Fire Doors and Windows NFPA 90A - Installation of Air Conditioning and Ventilation Systems o
NFPA 101 - Safety to Life from Fires in Buildings e,cd Structures.
o o
NFPA 232 - Records o
NFPA 803 - Light Water Nuclear Power Plants Where deviations from NFPA codes exist, the Fire Hazard Analysis will describe the deviation and determine that equivalent protection is provided.
9.5.1.3 Protection of Safe Shutdown Related Equipment g
Separation of Safe Shutdown Equipment a.
Safety related redundant components which may be required to function 2
to achieve safe shutdown will be protected as described in Subsection 9.5.1.1(d), with the exception of the Main Steam and Feedwater Tunnel WAPWR-AS 9.5-6 AMENDMENT 2 5405e:1d APRIL, 1988
and the Main Control Room outsido containment, and the pressurizer relief system inside containment.
V The Main Steam & Feedwater Tunnel contains the safety class portions of the main steam and feedwater lines outside containment in a single f-area.
The probability of fire initiation in this area is low because of the low density of cabling in this area.
In addition, the steam generator power operated relief valves, which may be required to achieve cold shutdown and which are located in the Main Steam and feedwater Tunnel are backed up by the relief valves of the Steam
/
Generator Overfill Protection System, which are located inside containment.
With regard to the Main Control
- Room, the probability of fire initiation is low because of the following features:
o The extensive use of multiplexed interconnection, which has 2
eliminated the need for cable spreading rooms.
'The use of l w voltage (24V) within the control boards.
o l
o The use of firs > retardant materials i
Moreover, fire detection and mitigation are enhanced by the continuous presence of plant operators in the Main Control Room by the incorporation of automatically actuated fire extinguishing systems, and by the availability of portable fire extinguishers.
Nevertheless, because a fire in the Main Control Room cannot be excluded, two emergency panel rooms are provided for in the SP-90 design.
Each of these two emergency panel rooms is located in one of I
the redundant safety related areas and includes the capability to j
bring the reactor to cold shuf.down using one of the redundant trains of engineered safety features.
O WAPWR-AS 9.5-7 AMENDMENT 2 5405e:1d APRIL, 1988
The pressurizer power operated relief valves (PORV's) are a safety grac'e means to depressurize the Reactor Coolant System (RCS) to allow injection of borated water by the High Head Safety Injection Pumps.
The redundant pressurizer PORV's, which are safety grade, are located in a single area above the pressurizer.
This exception is judged acceptable for the following reasons:
o The probability of a fire in this area is extremely remote due to 2
the absence of significant quantities of combustible material o
The charging pumps would normally be available to inject borated water into the RCS without the need for depressurization o
RCS depressurization is achievable without reliance on pressurizer PORV's (i.e.
using the safety grade hot leg letdown valves),
although this would be a less desirable mode of operation due to the complex operator action required.
b.
Protection of Safe Shutdown Power and Control Cables O
Redundant safe shutdown cables and associated circuits will be protected as described in 9.5.1.1(d), except as noted in 9.5.1.3.(a) 2 above.
c.
Fire Barrier Rating Barriers will be rated in accordance with criteria as stated in Subsection 9.5.1.1(d).
O 9.5.1.4 Fire Protection System and Feature Descriptiens 9.5.1.4.1 Passive Fire Protection Features Passive fire protection features are considered to be building assemblies and l
insulating materials which have fine and heat resistant characteristics.
l WAPWR-AS 9.5-8 AMENDMENT 2 5405e:1d APRIL, 1988
Passive fire protection features consist of fire rated structural assemblies, (i.e., walls,floorsorceilings),whichhave penetrations protected by fire rated devices (i.e.,
dampers, doors or firestops).
Insulating materials consist of cable wraps and heat resistant coatings.
The fire rating of these structural assemblies, penetration protection devices and insulating materials is determined by appropriate test procedures.
Passive fire protection features, henceforth referred to as fire barriers, are used to separate safety related systems from nonsafety related areas, redundant safety-related divisions or trains from each other and safety-related components which may present a fire hazard from other safety-related s
components. This separation will ensure that a single fire cannot cause loss of ability to achieve safe shutdown.
a.
Location of Fire Barriers Fire barriers will be provided on each elevation of safety-related areas to meet the criteria stated in Subsection 9.5.1.3(a).
The 2
following is an elevation-by-elevation list of redundant safety-rel'ated equipment which will be separated from its counterpart by three-hour fire rated barriers.
Elevation 72.0 Turbine-Driven Emergency Feedwater Pumps Motor-Driven Emergency Feedwater Pumps Residual Heat Removal Pumps High Head Safety Injection Pumps s
2 Elevation 77.4 l
Component Cooling Water Pumps l
Emergency Feedwater Storage Tanks Turbine-Driven Emergency Feedwater Pump Valves i
Motor-Driven Emergency Feedwater Pump Valves O
NAPWR-AS 9.5-9 AMENDMENT 2 3405e:1d APRIL, 1988
Elevation 84.8 Component Cooling Water Heat Exchangers Emergency Feedwater Storage Tanks Elevation 92.8 Diesel Generator Auxiliary Rooms Switchgear Rooms g
Battery Rooms Emergency Panel Rooms Elevation 100.0 Diesel Generator Rooms Diesel Generator Control Rooms Relay Rooms The following rooms, areas, and equipment will be separated from the remainder of the plant by three-hour fire ra~ted barriers.
Control Room Computer Room Control Rod Drive Mechanism Room Motor Control Center Room Fuel Storsge and Handling Area Nonsafety-Related Battery Rooms Stair Towers Elevator Shafts Duct Shafts l
Cable Shafts Containment Area The floors which sepcrate each elevation of safety-related areas will be constructed and maintained as three-hour fire rated barriers.
O WAPWR-AS 9.5-10 AF.ENDMENT 2 5405e:1d APRIL, 198S
The exterior walls of safety-related areas which are above grade level and are threatened by potential fire exposure from adjacent buildings, storage tanks, etc., will be constructed and maintained as three-hour s
fire rated barriers.
Walls, floors or ceilings which separate safety related systems from nonsafety related areas will also be constructed and maintained as three-hour fire barriers.
b.
Components of Fire Barriers Fire barriers are composed of structural assemblies (walls, floors and
%/
ceilings), materials which protect openings in structural assemblies (doors, dampers and penetration seals), and fire rated insulating materials (cable wraps, radiant energy shields).
Each fire barrier component will be tested or analyzed to assure adequate fire resistance ratings.
c.
Structura's Assemblies
- Wall, floor, and ceiling assemblies constructed as fire barrier units mee't the criteria established by ASTM E 119, "Fire Tests of Building and Construction Materials" for the hourly fire rating required.
d.
Door Assemblies Door assemblies installed in fire barriers meet the criteria established in ASTM E 152, "Fire Tests of Door Assemblies" and NFPA 80, "Fire Doors and Windows" for the hourly fire rating reeuired.
Door assemblies include door leafs, door frames, latching desices, closure devices, and hardware.
l 2
Where door assemblies in fire barriers must be modified for other design requirements, such as pressure differential or security requirements, each configuration will be analyzed or tested, in accordance with applicable codes and standards, to assure that door units will withstand potential fire exposure for the specific configuration.
WAPWR-AS 9.5-11 AMENDHENT 2 5405e:1d APRIL, 1988
e.
Dampers G,
HVAC fire dampers installed in fire barriers meet the criteria established in UL555, "Fire Dampers" and NFPA 90A, "Installation of Air Conditioning and Ventilation System" for the hourly fire rating required.
Maintenance access is provided to the installed fire dampers, as stated in NFPA 90A.
f.
Penetration Seals Mechanical and electrical penetration fire stop assemblies installed in fire barriers meet the criteria established in ASTM E 814, "Fire Tests of Through-Penetration Fire Steps." Mechanical and electrical penetrations include cable, cable trays, piping, and conduit.
Openings inside conduits larger than four inches will be sealed at the fire barrier assembly. Openings inside conduits less than four inches will be sealed at the fire barrier unless the conduit extends more than five feet on either side of the fire barrier, in which case the conduit will be either sealed at the fire barrier or at each end by a noncombustible material to prevent passage of smoke and hot gases.
g.
Fire Insulating Material Fire insulating materials may be of either a spray on application or a blanket type material. These insulating materials are used to protect components threatened by potential fire exposure.
Components protected by fire insulating materials may include structural
- steel, redundant safety-related cable trays, and pieces of safety-related equipment. Fire insulating materials meet the criteria of ASTM E 119, "Standard Tire and Temperature Curve" for the specific hourly rating required.
O Where protected by fire insulating material, electrical components will have ampere capacity derated accordingly.
WAPWR-AS 9.5-12 AMENDMENT 2 5405e:1d APRIL, 1988
9.5.1.4.2 Active Fire Protection Features 3(V a.
Fire Detection and Alarm Systems Automatic fire detectors will be provided over all significant hazards and over major safe shutdown components as dictated by the Fire J
Hazards Analysis.
The detection system will be designed and installed in accordance with current editions of National Fire Protection Association Standards 72-D and 72-E.
Detector coverage will include major cable concentrations, safe shutdown related major pumps, switchgear, motor corarol
- centers, battery and inverter areas, relay rooms, fuel
- areas, and all other areas containing appreciable
'n situ or potential transient combustibles.
Detector devices will be selected based on the type of fire anticipated and positioned considering ventilation, ceiling height, ambient conditions, and burning characteristics of the materials involved.
Detection system alarms will be annunciated in the Control Room and will sound locally in the fire area involved.
b.
Fire Protection Water Supply A dedicated fire protection water supply and distribution system will be provided to meet the anticipated needs for fixed water suppression systems and manual hose streams.
The water supply will consist of a 100 percent capacity electric motor-driven fire pump, powered by on-site emergency power buses and a 100 percent capacity diesel-driven fire pump.
Each pump will take suction from an assured water source with a minimum of 300,000 gallons.
(Ifgroundlevelsuction tanks are utilized, redundancy will be provided.)
The water distribution system will be sized to supply the largest fixed water suppression system demand, including a hose stream demand WAPWR-AS 9.5-13 AMENDMENT 2 5405e:1d APRIL, 1988
.- L
of 1000 GPM, with the shortest portion of the water distribution piping out of service. The system will be equipped with interier and exterior sectional control valves to meet single failure criteria as stated in Subsection 9.5.1.1(f).
The system will also be arranged such that yard fire hydrants may be repaired or serviced without loss of interim water suppression capability.
The water distribution system will be designed and installed in accordance with National Fire l
2 l Protection Association Standards 13, 14, 15, 20, and 24.
c.
Water Suppression Systems Fixed water suppression systems will be provided over major fire hazards where appropriate as dictated by the Fire Hazards Analysis.
These systems will be designed and installed in accordance with National Fire Protection Association Standards 13 and 15.
Water shields or buffers will be utilized as necessary to shield safety-related equipment requiring protection from water discharge.
d.
Gaseous S aression Systems Fixed Halen 1301 or carbon dioxide fire extinguishing systems will be installed to protect selected hazards which may not practically or effectively be protected by water suppression systems.
These systems will be provided as detailed by the Fire Hazards Analysis and will consider the characteristics of each extinguishing system with respect to effects on equipment and personnel. These systems will be designed and installed in accordance with National Fire Protection Association Standards 12 and 12A.
e.
Hydrants and Hose Standpipes Manual fire fighting capability utilizing hose streams will be provided through an arrangement of exterior fire hydrants and interior hose standpipes.
Fire hydrants will be provided in accordance with National Fire Codes or as dictated by the Fire Hazards Analysis.
O WAPWR-AS 9.5-140 AMENDHENT 2 5405e:1d APRIL, 1988
Exterior hose houses or hose cabinets will be provided and equipped in accordance with the recommendations of National Fire Protection Association Stcndard 24.
Interior 1 1/2" hose stations fed from standpipe systems will be provided in accordance with National Fire Codes or as dictated by the V
Fire Hazards Analysis. Each hose station will be equipped with a maximum of 100 feet of listed fire hose and anadjustablespray nozzle. Pressure reducing orifices will be used as necessary to assure that each hose has proper pressure. The standpipe systems will be designed and installed in accordance with the current edition of National Fire Protection Association Standard 14.
f.
Fire Extinguishers Portable fire extinguishers will be provided in areas which contain fixed or potential transient combustibles.
Extinguishers will be chosen considering the anticipated types of fire and the effect of the extinguishing agent on equipment.
Spacing, selection, and maintenance wiil be performed in accordance with the current edition of National Fire Protection Association Standard 10.
9.5.1.4.3 Support Systems Support systems include systems and equipment which are not directly involved in fire detection, suppression, or containment, but aid in fire fighting and plant operations during a fire incident.
a.
Fire Brigade Radios Portable radio communications will be provided for fire brigade and plant operations personnel during a fire incident. This communication O
> t iii 8 84 14 et e
<< 2
=>
c8 18 1 >>
t security force communications and actuation of protection relays are not affected.
The portable radio communication system will utilize r
WAPWR-AS 9.5-15 AMENDMENT 2 5405e:1d APRIL, 1988
fixed repeaters, as necessary, to assure communications capability g with any location in the station from the Control Room.
The fixed repeaters will be arranged and protected such that exposure to fire damage will not disable the entire system, b.
Emergency Lights g
Sealed-beam emergency lights with individual eight-hour battery supplies will be provided in areas which must be occupied for safe shutdown and routes used for access and egress to these locations, g The lighted areas will include areas where operator actions occur if the Control Room is evacuated.
In addition to the sealed-beam eight-hour emergency lights, portable sealed-beam battery powered hand lights will be provided for use by fire brigade and plant operations personnel during a fire incident.
c.
Fire Brigade Emergency Breathing Air Emergency breathing air will be provided for fire brigade and Control Room personnel.
The breathing air will be delivered by a self-contained apparatus or a
storage reservoir.
Full-face positive pressure masks approved by the National Institute for Occupational Safety and Health will be utilized by all personnel required to use emergency breathing air.
1.
Fire Brigade Personnel Equipment A minimum of ten self-contained breathing units will be provided for fire brigade use.
Each unit will be provided with two extra air bottles located on site.
Rated service life for the self-contained units will be a minimum of one half-hour.
In addition to the two extra bottles for each self-contained unit, compressors will be provided so that exhausted air bottles may be I
quickly replenished.
The compressors will operate in areas free of dust and contaminants and will be powered from a vital power bus so that breathing air is available if off-site power is lost.
I WAPWR-AS 9.5-16 AMENDHENT 2 5405e:Id APRIL, 1988
2.
Control Room Personnel Equipment Emergency breathing air will be provided for Control Room personnel by a manifold system piped from a storage reservoir.
The storage reservoir will have the capacity to supply emergency breathing air for six hours.
In addition, self-contained breathing apparatus (SCBA) is located in the control room 'to allow 2
personnel to leave this area during a fire.
9.5.1.4.4 Curbs and Drains Floor drains and curbs which are sized to remove expected fire fighting water flow will be provided in areas protected by fixed water fire suppression systems or hand-held hose lines if water accumulation will cause unacceptable damage to safety-related equipment.
Water drained from areas which may contain radioactivity will be properly collected, analyzed, and treated before being discharged to the environment.
In areas protected by gas suppression systems, either the floor drains will be O
designed with adequate liquid seals or the suppression agent supply will be sized to compensate for agent loss through the drainage system.
Floor drains located in areas containing combustible liquids will be designed such that these liquids cannot backflow into safety-related areas through the drainage system.
9.5.1.4.5 Reactor Coolant Pump Oil Collection System Seismically qualified oil collection systems will be provided for reactor coolant pump motor oil systems.
These oil collection systems will protect all potential pressurized and non pressurized leakage points in the pump lube oil A drain line will be provided to transport the largest potential oil O
system.
leak to a vented closed container.
The vent on the closed container will be provided with a flame arrestor if the oil flash point characteristics and proximity of het surfaces present a flashback hazard.
O WAPWR-AS 9.5-17 AMENDHENT 2 5405e:1d APRIL, 1988
The Reactor Coolant Pump 01 Collection System will be designed so that failure will not lead to a fire during normal or Design Basis Accident conditions.
The oil collection system will also be designed to withstand a safe shutdown earthquake.
9.5.1.4.6 Smoke Control Smoke will be removed from each fire area by ventilation systems.
The removal of smoke.by ventilation systems may be achieved either directly or via manual portable smoke venting devices. When using the manual smoke venting devices, smoke is removed from the iire-involved room or area and placed in an area where exhaust ventil tion is provided.
Release of smoke which may contain radioactive materials is monitored to ensure compliance with applicable guidelines.
9.5.1.4.7 Access / Egress Clearly marked fire exit routes will be provided for each fire area.
These routes will be designed to comply with applicable life safety codes and standards.
O O
O WAPWR-AS 9.5-18 AMENDHENT 2 5405e:Id APRIL, 1988 j
9.5.1.4.8 Construction Materials and Combustible Contents j
Noncorbustible materials having radiant energy heat flux of equal to or more 2
than 50 kW/CH will be used for interior wall and structural components, thermal insulation, radiation shielding, soundptcofing, interior finishes, and suspended ceilings.
Transformers located inside fire areas containing safety-related equipment will be of the dry type, insulated with noncombustible liquid or ceparated from safety-related equipment by three-hour fire rated construction.
9.5.1.5 Interaction with Other Systems a.
Water Spray on Safety Related Equipment Potential for water spray from fire protection water suppression system piping will be reviewed based on the Pipe Rupture Analysis Criteria. Where potential for water spray may result in damage to safety-related equipment, one of the following. options will be utilized to assure that equipment is not damaged:
o Rereuting of fire protection piping.
o Installation of water spray shields, o
Qualifying safety-related equipment to withstand effects of water spray.
b.
Flood Pipe rupture criteria will be used to assure that the flood inventory in fire protection piping will not cause damage to safety-related equipment.
Drains and sumps in the NPB will be sized to control maximum flood inventory of fire protection piping.
O WAPWR-AS 9.5-19 OCTOBER, 1986 5405e:1d
9.5.1.6 Preoperational Testing a.
Pumps 1.
Controls 2
Fire pump controls will be initially tested as required in National Fire Protection Association Standard 20.
2.
Capacity The fire pumps will be flow tested to assure that each pump is capable of pumping to 150 percent of rated capacity at appropriate 2 l pressures. The testing method will follow the requirements of National Fire Protection Association Standard 20.
b.
Piping Water distribution system piping will be flushed and hydrostatically tested to assure full operability.
These tests will follow the 2 l requireinents of the National Fire Protection Association Standard 24.
c.
Valves Each automatic and manual valve of the water distribution system will be cycled to verify proper operation.
d.
Detectors / Alarms Each fire detector and all related circuitry will be functionally testod to assure full system operability. Detector, alarm, and power supply functions will be tested in accordance with National Fire Protection Association Standards 72-D and 72-E.
O WAPWR-AS 9.5-20 AMENDMENT 2 5405e:1d APRIL, 1988
e.
Dampers Each fire rated damper will be inspected to verify proper installation and will be cycled to assure proper operation.
f.
Water Suppression Systems Each water suppression system will be tested in accordance with the applicable National Fire Protection Association Standard.
These tests will verify proper valve operation, local and Control Room alarm, and control functions.
All system piping will be flushed and hydrostatically tested to assure integrity.
Airflow tests will be performed on open head / nozzle systems to assure that all heads / nozzles are unobstructed.
g.
Gaseous Suppression Systems Each Halon 1301 and carbon dioxide system will be functionally tested in accordance with the applicable National Fire Protection Association Standards. This testing will include full discharge concentration tests.
h.
Radio System The portable radio system will be verified as fully operable through a functional test of the entire system. This testing will verify proper antenna placement and repeater operability to assure full coverage.
- i. Emergency Lights Self-contained eight-hour emergency lighting units will be inspected to verify proper aiming of beams and coverage for access and equipment manipulation.
Individual units will be load tested on a sampling basis to verify design duration.
WAPWR-AS 9.5-21 OCTOBER, 1986 5405e:1d
~
%..-m____-._,_.-,.-._,__,,_,_y
_._._m-
9.5.1.7 Administrative Controls, Quality Assurance, Personnel Qualification, and Training a.
Administrative Controls Administrative controls will be used to limit fire fuel and ignition g
sources inside safety-related areas.
These limits will be W
l accomplished by controlling the type, quantity, and length of presence of.corbustible materials inside safety reisted araas and establishing a hot work permit system.
1.
Control of Corbustible Materials The permanent bulk storage of combustible materials inside or adjacent to safety-related areas will be prohibited;
- however, to accomplish certain tasks the use of coebustible materials is unavoidable.
Administrative controls will be established to govern the handling and use of ordinary corbustibles such as:
o Combustible / flammable gases and liquids o
Flame ratardant wood o
plastic products o
dry ion exchange resins 2.
Transient Combustible Material Administrative controls will minimize the amount of transient corbustible material in safety-related areas during all phases of 2
plant operation.
Upon completion of a task and at the end of each work shif t, all waste corbustible material will be removed to a designated storage location.
An on-site staff organization will be designated to review l
proposed work activities. This review will identify potential WAPWR-AS 9.5-22 AMENDHENT 2 5405e:1d APRIL, 1988
4.
Fire Drills D
Fire drills will be performed in the plant at intervals not to exceed three months for the fire brigade for each shift.
A minimum of one drill per year for each fire brigade will be unannounced. Also one drill per year for each fire brigade will be perfor:ned on a back shift.
Local fire department partkipation will be provided at least once each year.
Each fire brigade member will be required to participate in a O
minimum of two drills per year, and records of each member's training will be maintained for a minimum of three years.
The drills will have preplanned training objectives and will be critiqued to determine if these objectives were met.
Unsatisfactory drill performance will be followed by a repeat drill within 30 days and by additional training. At intervals of 3 years, randomly selected unannounced drills will be critiqued-by qualified independent individuals, selected by the utility.
2 O
Drills, as a minimum, will assess the following:
o Fire alarm effectiveness.
o Time required to assemble the brigade.
o Selection, placement, and simulated use of equipment.
o Firo fighting strategies o
Knowledge of each brigade member of his/her role in the fire 1
fighting strategy.
O WAPWR-AS 9.5-29 AMENDHENT 2 5405e:1d APRIL, 1988 l
S o
Conformance of the brigade member with established fire fighting procedures and use of fire fighting equipment, to the extent practicable, o
Direction of the brigade leader of the fire fighting effort as to thoroughness, accuracy and effectiveness.
g e.
Fire Fighting Procedures g
Procedures will be developed that outline actions to be taken by the following:
o the individual discovering the fire o
control room personnel upon report of the fire or receipt of an alarm o
fire brigade personnel after notification of a fire o
plant manager after notification of a fire o
staff after notification of a fire The fire fighting procedures will also outline the actions to be taken to coordinate fire fighting activities with off-site fire departments.
l f.
Fire Fighting Strategies Strategies will be developed for fighting fires in all safety-related areas presenting hazards to safety-related equipment.
Specific strategies will include the following subjects for each plant zone:
o Identification of combustibles.
o Optimum methods for controlling a fire and the nearest location of these extinguishants.
WAPWR-AS 9.5-30 DCTOBER, 1986 5405e:1d
_