PY-CEI/NRR-2298L Page1of3 4
I l
TECHNICAL SPECIFICATION PAGE REVISIONS i
l L
)
t 9909150051 990903ADOCK 05000440v/
PDR P
popj L
~
Diesel Fuel Oil, Lube Oil, and Starting Air l
PY-CEI/NRR-2298L 3.8.3
(
Page 2 of 3 3.8 ELECTRICAL POWER SYSTEMS 1
l 1
l 3.8.3 Diesel Fuel Oil, Lube Oil, and Starting Air l
l LCO 3.8.3 The stored diesel fuel oil, lube oil, and starting air subsystem shall be within limits for each required diesel generator (DG).
j l
APPLICABILITY:
When associated DG is required to be OPERABLE.
l ACTIONS
NOTE-------------------------------------
Separate' Condition entry is allowed for each DG.
CONDITION REQUIRED ACTION COMPLETION TIME A.
One or more DGs with A.1 Restore fuel oil 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> fuel oil level:
level to within limits.
1.
For Div 1 and l
Div 2,
< 73,700 gal and l
2 65,100 gal; and f
2.
For Div
< 35,'^pl and
~3,(,' g l
_ ga 2 % gal.
g l
h_b B.
One or more DGs with B.1 Restore lu'be oil 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> lube oil inventory:
inventory to within limits.
1.
For Div 1 and Div 2, l
< 374 gal and i
2 350 gal; and 2.
For Div 3,
< 260 gal and-2 236 gal.
j PERRY - UNIT.1 3.8-21 Amendment No.
L
Diesel Fuel Oil, Lube Oil, and Starting Air PY-CEI/NRR-2293L 3.8.3 Page 3 of 3 SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.8.3.1 Verify each fuel oil storage tank contains:
31 days a.
2 73,700 gal of fuel for Div 1 DG and Div 2 DG; and
' b.
2 30,1^^ggal of fuel for Div 3 DG.
~34,7 00 5 SR 3.8.3.2 Verify lube oil inventory is:
31 days a.
2 374 gal for Div I DG and Div 2 DG; and b.
2 260 gal for Div 3 DG.
SR 3.8.3.3 Verify fuel oil properties of new and In accordance stored fuel oil are tested in accordance with the Diesel l.
with, and maintained within the limits of, Fuel Oil the Diesel Fuel Oil Testing Program.
Testing Program SR 3.8.3.4 Verify each required DG air start receiver 31 days pressure is 2 210 psig.
L SR 3.8.3.5 Check for and remove accumulated water from 92 days each fuel oil storage tank.
l.
SR 3.8.3.6 For each fuel oil storage tank:
10 years L
a.
Drain the fuel oil; b.
Remove the sediment; and c.
Clean the tank.
-PERRY - UNIT 1 3.8-23 Amendment No. [