ML20151N846

From kanterella
Jump to navigation Jump to search
Notice of Violation from Insp on 850823-0930
ML20151N846
Person / Time
Site: Comanche Peak  Luminant icon.png
Issue date: 12/24/1985
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
To:
Shared Package
ML20151N849 List:
References
50-445-85-13, 50-446-85-09, 50-446-85-9, NUDOCS 8601030161
Download: ML20151N846 (4)


See also: IR 05000823/2009030

Text

.

.

APPENDIX A

NOTICE OF VIOLATION

Texas Utilities Electric Company

Dockets: 50-445/85-13

Comanche Peak Steam Electric Station, Units 1 and 2

50-445/85-09

Permits:

CPPR-126

CPPR-127

During an NRC inspection conducted on August 23 through September 30, 1985,

five violations of NRC requirements were identified.

The violations involved

inspection failure to record a required pipe support dimension, inadequate

provisions for control of deleterious materials, inadequate protection of

installed components, incomplete and missing conduit identification, and

unauthorized breaking of an accepted flange joint.

In accordance with the

" General Statement of Policy and Procedure for NRC Enforcement Actions,"

10 CFR Part 2, Appendix C (1985), the violations are listed below:

A.

Criterion V of Appendix B to 10 CFR Part 50, as implemented by the TUGC0

. Quality Assurance Program (QAP), Section 5.0, Revision 2, dated May 21,

1981, requires that activities affecting quality shall be prescribed by

documented instructions, procedures, or drawings of a type appropriate to

the circumstances and shall be accomplished in accordance with these

instructions, procedures, or drawings.

Site Procedure QI-QAP-11.1-28 states that the Quality Control Inspector

shall assign a number to each dimensional attribute identified as a

specific dimension and shall record the actual measurements on this

inspection report.

Contrary to the above, no number was assigned and no measurement result

was recorded on the QC inspection report for the wall-to pipe centerline

dimension shown on pipe support drawing AF-2-006-412-533A.

When this

dimension was independently checked by NRC, it was found to be 13\\-inches

'

when the drawing showed it to be lik-inches.

This is a Severity Level V violation (Supplement II) (446/8509-V-01).

B.

Criterion XIII of Appendix B to 10 CFR Part 50, as implemented by the

TUGC0 QAP, Section 13.0, Revision 1, dated July 31, 1984, requires that

measures be established to control the handling, storage, shipping,

cleaning, and preservation of material and equipment in accordance with

work and inspection instructions to prevent damage or deterioration.

Section 2.17 of Gibbs and Hill Piping Erection Specification 2323-MS-100,

Revision 8, dated July 5, 1984, defines the actions to be taken to limit

contamination of reactor coolant equipment surfaces; e.g., prohibition of

low melting point metals and their compounds, prohibition of use of

oh050004

851RR4

5

PD

-

-

.

.

-

)

.

.

2

instruments containing mercury, and restriction of halide content of

products such as machining coolants, seals, and plug materials.

Contrary to the above, implementing site procedures do not address

prohibition of use of instruments containing mercury, do not provide

necessary craf t guidance for contamination control, or include provisions

to assure that procured consumables are in compilance with specification

requirements.

This is a Severity Level IV violation (Supplement II) (446/8509-V-02).

C.

Criterion V of Appendix B to 10 CFR Part 50, as implemented by the TUGC0

QAP, Section 5.0, Revision 2, dated May 21, 1981, requires that activities

affecting quality shall be prescribed by documented instructions,

procedures, or drawings of a type app,opriate to the circumstances and

shall be accomplished in accordance with these instructions, procedures,

or drawings.

Brown & Root Procedure MCP-10, paragraph 3.6, Revision 9, dated July 2,

1985, requires that items stored in place shall merit additional

protection if construction work threatens the-integrity of equipment and

includes a prohibition in regard to placing work platforms or scaffolds on

permanent plant installations, such as a pipe, tray hangers, etc., without

written engineering authorization.

Contrary to the above:

1.

On September 25, 1985, the NRC inspector observed in Room 16

(854 feet elevation) a wooden two by four which was laid across

3/4-inch pipe RC-2-095-501R-2 to serve as a work platform, but there

was no evidence to indicate that engineering had authorized this

temporary platform.

2.

On September 24, 1985, the NRC inspector observed at the 905 feet

elevation that welding had taken place above the reactor pressurizer

and associated piping without adequately protecting the equipment, as

evidenced by the presence of weld spatter on wold no. 42 in 6-inch

line RC-2-096-2501R-1.

This is a Severity Level IV violation (Supplement II)

(446/8509-V-03).

D.

Criterion V of Appendix B to 10 CFR Part 50, as implemented by the TUGC0

QAP,Sectir. 5.0, Revision 2 dated May 21, 1981, requires that activities

affecting, quality shall be prescribed by documented instructions,

procedures, or drawings of a type appropriate to the circumstances and

-

-

--

~

,

,

.

3

1

shall be accomplished S accordance with these instru::tions, procedures,

or drawings.

Paragraph 3.1.1, subparagraphs b and c, of TUGC0 Procedure QI-QP-11.3-8,

Revision 0, issue date July 7, 1978, " Identification and Color-Coding

Inspections," require that conduit designation shall be applied with black

ink or paint and that identification of conduit be verified at both sides

of all walls and slabs through which conduit passes.

Paragraph 3.1.1, subparagraph b, of TUGC0 Procedure QI-QP-11.2-23.7,

Revision 1, issue date January 5, 1980, " Verify Conduit Identifications,"

similarly requires that conduit be identified on both sides of all walls

and slabs through which conduit passes.

Subparagraph c. of this paragraph

states, in part, " Groups of embedded conduits which are flush with the

surface of walls, floors and manholes shall be identified on the surface

or the wall, floor, or manhole by attaching an identification template

<

near the conduit bank. . . ."

<

,

!

Contrary to the above, the following examples of incomplete and missing

'

conduit identifications were noted in the Unit I lower cable spread room,

i

auxiliary building, and safeguards building:

1.

Two conduits attached to embedded conduit wall sleeve TSW-A-020 were

not identified on the identification template and one conduit which

was identified on the template as being present did not, in fact,

exist.

,

2.

Two banks of embedded conduit wall sleeves below sleeve TSW-A-023 had

no form of identification.

3.

At tray section T14GC0H27, there were four floor sleeves which were

,

not identified by either identification template or ennduit marking.

'

4.

At tray section T24WAEF, there were two floor sleeves with an

'

incomplete identification template; i.e. , the template contained only

'

the letters TFS.

5.

Below battery pack CPI-ELOPSG-187 (Circuit ES07-11), there were two

floor sleeves which were not identified.

6.

At a tray section above junction box J01A-1332, the embedded conduit

wall sleeves were not identified by either identification template or

marking.

1

'

7.

Three of five floor sleeves at tray section T220ABA41 were unmarked.

8.

Four floor sleeves at tray section T120ABB23 were unmarked.

l

- -

. - -

-

-

. _ _ _ _ _ _

.____

_

___

__

_ ___ _ _ _ _ _ _ _ .

__

.

.

4

t

r

9.

Conduits attached to embedded conduit wall sleeve TSW-A-030 were not

identified on the identification template which was present.

This is a Severity Level IV violation (Supplement II) (445/8513-V-01).

E.

Criterion V of Appendix B to 10 CFR Part 50, as implemented by TUGC0 QAP,

Section 5.0, Revision 2, dated May 21, 1981, requires that activities

affecting quality shall be prescribed by documented instructions,

procedures or drawings of a type appropriatn to the circumstances and

shall be accomplished in accordance with the.e instructions, procedures,

or drawings.

Paragraph 3.5.2.1 in Revision 7 of Brown & Root Procedure CP-CPM 6.9E

states, in part, "When it becomes necessary to break an inspected flanged

joint for any reason, QA/QC Building Superintendent shall be notified by

the responsible craft foreman.

This notification will be by the foreman

completing an IRN (Item Removal Notice) in accordance with CPM 6.10. . . ."

Paragraph 3.11 states, in part, " Flanged pipe joints shall be tightened

sufficiently to prevent leakage."

Contrary to the above, flange no. 6 in Unit 2 piping system BRP-SW-2-018,

which was installed, inspected and accepted esing Construction Operation

l

Traveler No. MP-82-4117-0400 dated April 20, 1982, was observed in a

broken condition as evidenced by loose nuts on 4 of the 12 studs, thus

impairing its ability to sufficiently prevent leakage.

Further, there

'

were no available IRNs authorizing any activity which would require the

breaking of this flanged joint.

This is a Severity Level IV violation.

(Supplement II) (446/8509-V-04).

Pursuant to the provisions of 10 CFR 2.201, Texas Utilities Electric Company is

hereby required to submit to this office within 30 days of the date of the

letter transmitting this Notice, a written statement or explanation in reply,

including for each violation:

(1) the reason for the violations if admitted;

(2) the corrective steps which have been taken and thr. results achieved;

I

(3) corrective steps which will be taken to avoid further violations; and

(4) the date when full compliance will be achieved.

Where good cause is shown,

consideration will be given to extending the response time.

l,

!

.

Dated in Arlington, Texas,

this 24th day of December, 1985

l

l

-

-

-

-

-