ML20151L930

From kanterella
Jump to navigation Jump to search
Notice of Violation from Insp on 880521-0624.Violation Noted:Sys Operating Procedure for Diesel Generator Bldg Ventilation Sys Found to Be Inadequately Established & Implemented
ML20151L930
Person / Time
Site: Hatch  
Issue date: 07/21/1988
From: Brownlee V
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To:
Shared Package
ML20151L928 List:
References
50-321-88-17, 50-366-88-17, NUDOCS 8808040189
Download: ML20151L930 (3)


Text

_ _ _ _ _. _ _. _ _ _ _ _ _ -

ENCLOSURE 1 NOTICE OF VIOLATION Georgia Power Company Docket Nos. 50-321 and 50-366 Hatch Units 1 and 2 License Nos. DPR-57 and NPF-5 During the Nuclear Regulatory Commission (NRC) inspection conducted on May 21 -

June 24, 1988, violations of NRC requirements were identified.

In accordance with the "General Statement of Policy and Procedure for NRC Enforcement Actions," 10 CFR Part 2, Appendix C (1988), the violations are listed below:

A.

Technical Specification 6.8.1.a requires that written procedures be established, implemented, and maintained as recommended in Appendix A of Regulatory Guide 1.33, Revision 2, February 1978.

Appendix A of Regulatory Guide 1.33, Revision 2, recommends procedures for startup, operation, and shutdown of safety-related systems.

Contrary to the above, on June 8, 1988, the system operating procedure for the diesel generator building ventilation system was fcund to be inadequately established and implemented as follows:

1.

The Unit 1 procedure for the diesel generator building ventilation system, 3450-X41-001-1N, Revision 1, was not designated as a safety-related procedure nor approved by the appropriate member of plant management as required.

The Unit 2 procedure, 3450-X41-001-2, Revision 0, was designated as safety-related.

2.

The Unit 1 and Unit 2 diesel generator building ventilation system operating procedures were inadequate in that both procedures required verification of the IB (swing) diesel exhaust fan thermostats operation to different temperature settings.

The Unit 2 procedure required the exhaust fan thermostats to operate at 87*F for X41-N004B and 85 F for X41-N0058, but the Unit 1 procedure required both X41-N004B and X41-N005B to operate at 55*F.

In addition, further evaluation of the procedure found all the thermostat settings for all of the Unit 1 diesel generator room's exhaust fans, V-1 and V-2, and two heater thermostats, H-1 and H-2, to be incorrect and not in agreement with plant design data referenced on system Piping and Instrumentation Diagram H-12619, Revision 5.

3.

The 18 and 2C diesel generator oil storage room exhaust fans were not aligned per procedure which required one fan switch to be in the RUN position and the other fan switch to be in the STt.NDBY position.

Both of the 1B fans were found in RUN and both of the 2C fans were found in STANDBY.

The 20 battery room exhaust fans switches were both found in the PRIMARY position instead of one in PRIMARY and the other in STANDBY as designated in the procedures.

This is a Severity Level IV Violation (Supplement I).

8808040189 080721 PDR ADOCK 05000 1

l Georgia Power Company 2

Docket Nos 50-321 and 50-366 Hatch Units 1 and 2 License Nos. DPR-57 and NPF-5 B.

Technical Specification 6.8.1.a requires that written procedures be established, implemented, and maintained for the applicable activities in Appendix A of Regulatory Guide 1.33, Revision 2, February 1978.

Appendix A of Regulatory Guide 1.33, Revision 2 recommends procedures for operation of the condensate system and for plant startup.

Procedure 34S0-N21-007-2S, "Condensate and Feedwater System," provides written instructions for operation of the Unit 2 condensate and feedwater c.ys tem.

Procedure 34G0-0PS-001 15, "Plant Startup," providos written instructions for the startup of Unit 1.

Contrary to the above, these two procedures were inadequate as noted below:

1.

On May 27, 1988, operations personnel attempted to fill and vent Unit 2 condensate pump 2N21-C001B with the unit operating at power.

This particular operation was not covered in Procedure 34S0-N21-007-2S.

In the absence of instructions in this procedure, air was inadvertently introduced into the condensate and feedwater system. This resu'ted in trips of the condensate booster and reactor feed pumps and ultimately resulted in the automatic scram of Unit 2.

2.

On May 20, 1988, operations personnel improperly swapped the Unit 1 drywell pneumatic supply from instrument air to nitrogen.

Procedure 34G0-0PS-001-1S did not specifically require this operation to be done in accordance with Data Package 5 of Procedure 34S0-P70-001-1S, "Drywell Pneumatic System."

In the absence of clear instructions, an improper valve lineup was established.

This resulted in the inadvertent closing of several main steam isolation valves and ultimately in the automatic scram of Unit 1.

This is a Severity Level IV violation (Supplement I).

Pursuant to the provisions of 10 CFR 2.201, Georgia Power Company is hereby l

required to submit a written statement or explanation to the Nuclear Regulatory i

Commission, ATTN:

Document Control Desk, Washington, D.C.

20555, with a copy to the Regional Administrator, Region II, and a copy to the NRC Resident Inspector, Hatch Nuclear Plant, within 30 days of the date of the letter transmitting this Notice. This reply should be clearly marked as a "Reply to a Notice of Violation" and should include for each violation:

(1) admission or denial of the violation, (2) the reasons for the violation if admitted,

Georgia Power Company 3

Docket Nos. 50-321 and 50-366 Hatch Units 1 and 2 License Nos. DPR-57 and NPF-5 (3) the corrective steps which have b.en taken and the results achieved, (4) corrective steps which will be taken to avoid further violations, and (5) the date when full compliance will

. achieved.

Where good cause is shown, consideration will be given to extending the response time.

If an adequate reply is not received within the time specified in this Notice, an order may be issued to show cause why the license should not be modified, suspended, or revoked or why such other action as may be proper should not be taken.

FOR THE NUCLEAR REGULATORY COMMISSION YM Virgi Brown ee, Chief Reactor Projects Branch 3 Division of Reactor Projects Dated at Atlanta, Georgia this & i day of July 1988 l

1