ML20151G287
| ML20151G287 | |
| Person / Time | |
|---|---|
| Site: | Oyster Creek |
| Issue date: | 04/05/1988 |
| From: | Fiedler P GENERAL PUBLIC UTILITIES CORP. |
| To: | NRC OFFICE OF ADMINISTRATION & RESOURCES MANAGEMENT (ARM) |
| Shared Package | |
| ML20151G229 | List: |
| References | |
| NUDOCS 8804190317 | |
| Download: ML20151G287 (3) | |
Text
p
./
- ~
.)
GPU Nuclear Corporation arsippany, New Je sey 07o54 201-316-7000 TELEX 136-482 Writer's Direct Oial Number:
April 5, 1988 U.S. Nuclear Regulatory Commission Attention: Document Control Desk Washington, D.C.
20555 Gentlemen:
Subject:
Oyster Creek Nuclear Generating Station Docket No. 50-219 Technical Specification Change Request (TSCR) No.148, Rev.1 In accordance with 10CFR50.59,10CFR50.90 and 10CFR50.91, GPU Nuclear Corporation, operator of the Oyster Creek Nuclear Generating Station, Provisional Operating License No. DPR-16, requests changes to Appendix A of that license.
TSCR No.148 concerning reactor coolant system (RCS) iodine activity limits and surveillance requirements was previously submitted on October 23, 1986 to the NRC staff for their review and approval.
During our meeting of June 30, 1987, the Staff requested re-submittal of the proposed changes with the following revisions:
1.
Delete words "if inhaled by an adult" from the definition of DOSE EQUIVALENT (D.E.) I-131 (Section 1.39).
2.
Incorporate provisions for performing additional analyses at least once per 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> until the specific activity of the primary coolant is restored to within its limit when the coclant activity exceeds 0.2 uCi/ gram D.E. I-131 (Section 3.6. A).
3.
Eliminate provisions for allowing a second sample, and place the reactor in hot shutdown within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> when the coolant activity exceeds 4 uCi/ gram D.E. I-131 (Section 3.6. A) 4.
Add sampling and analysis requirements for f odino following changes in thennal power or offgas level (Section 3.6. A).
The above revisions were requested by the Staff to be consistent with Standard Technical Specification', for General Electric Boiling Water Reactors (NUREG-0123).
fo 8804190317 880405
\\
PDR ADOCK 05000219 P
IED GPU Ntr,; ear Corpaation is a subsdary of General Public Utttres Corporatton
)
As for non-iodine activity, Section 3.6.E.1 of Oyster Creek Technical Specifications limits the release rate of gross activity in noble gases discharged from the main condenser air ejector not to exceed 0.21/E Ci/sec where E is the average gama energy.
The staff agreed in our June 30, 1987 meeting that this existing Tech. Spec. provision is adequate for non-iodine activity.
All specifications proposed in the TSCR No.148, Rev.1 can be implemented at Oyster Creek within two months of issuance by NRC.
This time is necessary in order for new procedures to be put in rUace and to allow for personnel training on these changes to be effected.
This Technical Specification Change Request has been reviewed in accordance with Section 6.5 of the Oyster Creek Technical Specifications.
Pursuant to 10CFR50.91(b)(1), a copy of this Technical Specification Request has been sent to the State of New Jersey Department of Environmental Protection.
Very truly yours, P.
edler Vice President and Director Oyster Creek PBF/YN/pa(5354f) cc: Mr. William T. Russell, Administrator Region I U.S. Nuclear Regulatory Comission 631 Park Avenue King of Prussia, PA.
19406 NRC Resident Inspector Oyster Creek Nuclear Generating Station Forked River, N.J.
08731 Mr. Alex Dromerick, Jr.
U.S. Nuclear Regulatory Comissicn Washington, D.C. 20555
UNITED STATES OF AMERICA NUCLEAR REGULATORY C0tHISSION IN THE MATTER OF
)
)
DOCKET NO. 50-219 GPU NUCLEAR CORPORATION
)
CERTIFICATE OF SERVICE This is to certify that a copy of Technical Specification Change Request No.148, Rev.1 for the Oyster Creek Nuclear Generating Station Technical Specifications filed with the United States Nuclear Regulatory Comission on April 5
,1988, has this day of April 5
,1988, been served on the Mayor of Lacey Township, Ocean County, New Jersey by deposit in the United States mail, addressed as follows:
Mayor of Lacey Township 818 West Lacey Road Forked River, NJ 08731 By:
2 Peter 8. Fiedler Vice Pre',ident and Director Oyster Creek DATED:
April 5, 1988 PBF/YN/pa
. - - - - -