Insp Rept 50-425/88-32 on 880523-26.Deviation Noted.Major Areas Inspected:Const Fire Protection Program,Administrative Controls,Fire Protection Water Supply Loop,Fire Protection Sys Insp & Actions on Previous Insp Findings
ML20151C705
Person / Time
Site: Vogtle Southern Nuclear icon.png
Issue date: 06/21/1988
From: Conlon T, Wiseman G
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To:
Shared Package
ML20151C697 List:
References
50-425-88-32, NUDOCS 8807220126
Download: ML20151C705 (7)


See also: IR 05000425/1988032

Text

. . . . , .

..

.

. .

. -

- - - - - - - - - - . - -

' '

,.

,

~f

UNITED STATES

- -

pftou4

,

'

'

A

-NUCLEAR REGULATORY COMMISSION

- [

- * ,

-o

,"

h

REGION 11

t

O

101 MARIETTA STREET,N.W.

5

I f.

ATLANTA, GEORGIA 30323

'

-

% .. /

.

...

_

-

F. port No.:

50-425/88-32

cicensee: Georgia Power Company

P. O. Box 4545

Atlanta, GA 30302

'

Docket No.:

50-425

License No.:

CPPR-109

Facility Name:

Vogtle 2

Inspection Conducted:

May 23-26, 1988

Inspector:

.k-

z4I m

h/[f8

G. R. Wisemari

Date $1gned

>

Approved by: d If A f# A /s

/p////#9

T. E. C6rro6,J,tfef

Da'te Signed

Plant Systems' 5ection

Division of Reactor Safety

SUMMARY

Scope:

This routine, unan.nounced inspection was conducted in the areas of

Unit 2 construction fire protection program, administrative controls,

fire protection water supply loop, fire protection system inspection,

actions on previous inspection findings, review of NRC commitments

associated with the reactor coolant pump oil collection system; and

review of the status of NRC commitments proposed for removal of the

temporary fire wall between Unit 1 and Unit 2 control room.

Results:

In the areas inspected, violations were not identified.

l

However, one deviation was identified - Failure to Maintain Maoual

Fire Hose Suppression Capability For The Unit 2 Control Room

'

Paragraph 3.d.

f

8807220126 G80629

PDR

ADOCK 05000425

PDC

0

,

'

.

-

--.----

_ _ _ _ _ _ . _ _ _ _ _ - _ _ _ . _ _ _ _ _ _

-

-

.

.

.

-

-

?

. .

.

,

.

'

.

t

1

RLFORT DETAILS ~

1.

Persons Contacted

. Licensee Employees

  • J. A. Bailey, Project' Licensing

'*C, Belflower,7QA Assessment Manager

  • A.' Gallant, Quality Control
  • S. Haltom, QA Engineering Support Supervisor

'*W.:Ramsey, Manager, Project Engineering

  • P. Rice, Vice President / Project Director

~

H. Williams,. Construction Fire Protection Supervisor

Other licensee employees contacted during this inspection included

engineers, technicians, and administrative personnel.

Other Organizations

'C. Foster, Mechanical Engineer, Bechtel

R. Gardner, Field Enginec'

Walsh Construction

  • R. Cross,-Project Enginee

bechtel

.M. Larson,' Fire Protection Group Leader, Bechtel-

  • J. Maddry, Fire Protecticn Manager, Southern Company' Services

A. TauFigue, Senior Mechanical Engineer, Southern Company Services

i

  • Attended exit interview

2.

Fire Protection / Prevention Program (640518)

a.

Fire Prevention / Protection Control Procedures

The inspector reviewed the following Fire Prevention / Administrative

Procedures from the Vogtie Field Procedure Manual:

Procedure No.

Title

GD-T-15, (Rev. 6)

Welding and Cutling

GD-T-17, (Rev. 6)

Housekeeping

SD-T-02, (Rev. 3)

Impaired Fire Protection

SD-T-05, (Rev. 7)

Fire Protection Equipment

Inspection and Testing

GD-A-30, (Rev. C)

Receipt, Receipt Inspection

Storage and Handling

.

MD-T-22, (Rev. 0)

NFPA Piping Installation

"

MD-T-23, (Rev. 1)

Testing of NFPA Piping Systems

GD-T-45, (Rev. 0)

Cable Tray / Conduit Fire

Protection Material Installation

and Repair

,

-

-

,

,

o

, .

,

.

'

.-

.

2

-

.

CD-T-16, (Rev. 9)

Installation and Inspection of

Category 1

Miscellaneous

Elec-

trical' Systems

CD-T-16,-(Rev. 10)

Structural Steel and Q-Decking

Based on this review, it appears that the above procedures meet the

licensee's commitments in Section 9B of the Vogtle FSAR and the Unit

Fire Protection Quality Assurance Program Evaluation Report dated

March 1,1988, (File X4BJ01, Log: 7323). This report evaluated the

existing ~ QA program applied to design, construction, installation,

and testing of the fire protection features provided for Vogtle

'.

Unit 2.

Included in this report is a description of the Fire

Protection Finalization Program, FP-3, which is intended to verify

specific fire protection features by a combination of design reviews

and walkdowns. The fire protection features which are to be verified

are:

Underground Utilities

Fire Detection System

Sprinkler System

Fire Hose Cabinets

Fire Door Assemblies

Emergency Lighting

afe Shutdown Conduit

The rr sults of this program will be reviewed during a future NRC

-

inspection.

Additionally, the inspector reviewed the following test records for

l

the dates indicated. The test data and frequency associated with the

i

construction fire protection systems inspecticas were found to be

satisfactory with regard to meeting the requirements of procedure

i

SD-T-05.

(1)

File X7BA01-C11Q - Monthly Fire Extinguisher Inspection Report:

The construction Fire extinguishers were inspected each month

between January 1988, and April 1988, except not all extin-

guishers located outside the power block were inspected during

February 1988, s'ue to manpower shortage to conduct inspections.

The inspector ve. ified that all extinguishers inside the power

block safety related plant areas were inspected during this

period.

(2)

File X7BA01-C3A - Monthly Hose House Inspection Report: The

inspector verified that the plant Hose Houses and Hose boxes

were inspected between October 1987, and April 1988, except

records for the February 1988, inspection was not located in the

QA ' records vault.

During the inspection the licensee satis-

factorily located copies of these records which were to be

placed in the appropriate file in the records vault.

-

___

.

_ _ - _ .

-

_-

.

7

.

. ~ .

s

,

3

-

,

,'

3.

Permanent-Plant Fire Protection Features

The= status of the construction and installation of the permanent plant

features for Unit 2 is a follows:

a.

Fire Pumps, Storage Tanks, Yard Mains, Hydrants, Fire Hose Houses

(Module 640538)

The fire water supply and distribution system is essentially 100%

installed and under operational control of Unit 1.

Some lead-in

water supply piping to Unit 2 sprinkler systems has not yet been

flushed.

Test blanks have been installed between the system

isolation valves and Unit 2 preaction sprinkler valves prior to

system installation.

The test blanks will be removed after the

header piping is verified clean.

For Unit 2, this provides reesonable

assurance that foreign materials have been removed from the

-undergrovri lead-in piping system and that sprinkler systems are free.

from foretgn material. Georgia Power Company requested NRC approval

by letter dated July 7,1987, for this alternate flushing technique.

SER approval was provided by letter dated October 26, 1987, from the

NRC that concluded the proposed change was acceptable. The inspector

reviewed sprinkler system detail and tagging chart Drawing 2X4DF00290

(Revision 1), and flushing Procedure VEGP-2 (Revision 0), Attachment

10.3, Temporary Flushing Modifications, which indicate the instal-

lation of the test blanks and the lead-in piping flushing procedure.

. Based on this review, it appears that the installation and removal of

the test blanks are adequately controlled through the use of drawings

and the procedures for Vogtle Unit 2.

b.

Automatic Sprinkler Systems

The installation of 124 Unit 2 sprinkler systems is nearing 70%

completion. Design is completed fc

all sprinkler systems. A review

was made of the QC inspection and hydrostatic tests for the below

listed systems:

System No.

Drawing

Location

Hydrostatic Test Date

41

2X4DF3A257

Auxiliary Building,

7/1/87

Level 1 Elevation 220;

Fire Zone 17

47

2X4DF3A261

Auxiliary Building,

9/30/87

Level 1A Elevation 195;

l

Fire Zone 37, CCW Pump

Rcom, Train B

48

2X4DF3A262

Auxiliary Building,

11/24/87

level A Elevation 195;

Fire Zone 36, CCW Pump

Room Train A

m

t

+

-

$+

s

w

.

..

'

4

.

1

These tests appeared to meet the 200 psi test pressure for two hour s

duration testing requirements of NFPA-13, Sprinkler Systems and are

satisfactory.

A .walkdown of these systems was conducted ar.d it appeared that the

sprinkle. coverage was in general, provided at the ceilir.g level. It

was noted that criteria for placement of in-tray spray systems was

deleted for these and other plant areas, except the cable spreading

>

rooms.

Also it was noted that sprinkler piping supports in these

areas utilize NFPA-13 hanger and sway bracing designs rather that

rigid type supports which were used on Unit 1.

These sprinkler

'

design changes were accepted by the NRC in a SER dated October 26,

1987.

Based upon the inspectors review it appeared that the

-

installed systems reviewed met the licensee's design criteria as

approved by the SER.

c.

. Fire Door

Fire door installation is proceeding with approximately 60%

completed. An inspection was made of the following fire doors to -

verify that the appropriate QA inspection records were provided as

designated in the Vogtle Unit 2 Fire Protection Quality Assurance

Program Evaluation Report.

No discrepancies were noted.

Ocor No.

Location

General Inspection

Checklist (CD-T-16)

Inspection Date

V22111L1264

Control Building,

3/31/88

Room 270

V22111LIA16

Control Building,

4/25/88

Room A13

V22111LIA19

Control IBuilding,

4/21/88

Room A16

V22108LIC25

Auxiliary Building,

3/3/88

Room C36

V2210821161

Auxiliary Building,

2/11/88

Room 156

V2219821153

Auxiliary Building,

3/7/88

Room 47

d.

Control Room Temporary Fire Barrier Wall

For a period of Unit 1 operation and Unit 2 construction, the Unit 1

and Unit 2 centrol rooms were separated by a gypsum board three hour

fire barrier wall on the Unit 2 side between the two control rooms.

By letter dated December 21, 1987, Georgia Power notified the NRC of

the proposed removal of this fire barrier prior to completion of

Unit 2.

The inspector reviewed the licensees commitments to provide

interim fire protection features denoted in the above letter to

,

.

.

~

5

.

.

verify their implementation to preclude the remaining Unit 2 control

room construction activities from compromising the safety of the

Unit 1 control room.

The inspector reviewed the Unit 2 fire watch

log and verified that appropriate fire watches had been established

since January 1988. Other features including structural steel fire

proofing, portable fire extinguishers, welding permit controls

l

'

appeared to be in place, except it was observed during the

walkthrough that the committed Unit 2 fire hose cabinet immediately

adjacent to the control room entrance (labeled Station No.

2-23-01-R4-197) was not maintained available for fire brigade use due

to construction related obstructions in the areas consisting of a

construction workstation, stacked five gallon cans of construction

,

materials, ladders and crew boxes weich restricted accessibility to

'

!

the cabinet.

In addition, the fir 2 hose cabinet door latch was

inoperable and construction electrical power cords were being stored

i

inside the cabinet. The failure to maintain this fire hose cabinet

'

capable of spraying all Unit 2 control room areas is a failure to

meet a commitment made to the NRC and is identified as Deviation

(425/88-32-01), Failure to Maintain Manual Fire Hose Suppression

!

Capability for the Unit 2 Control Room.

Except as noted above,

within the areas examined, no additional violations or deviations

were identified.

!

4.

Oil Collection System (64100)

The Vogtle FSAR Section 9BC.7.a states that an oil collection system is

provided for the reactor coolant pump.. Each Uni: 2 reactor coolant pump

is provided with an oil collection systcm arranged to collect oil from

potent?al leakage points and drain this oil into a drain tank.

Potential oil leakage points for each pump have been provided with an oil

containment system consisting of a lower bearing oil pot drip pan, upper

oil level detection drip pan, oil cooler drip pan, and oil lif t system

enclosure.

These enclosures are connected to oil collection piping headers which are

designed in accordance with the Bechtel Nuclear Project Classification

List (414) denoted as Nuclear Safety Class 4 (Quality Group D) as defined

by Regulatory Guide 1.26. and are supported to Nuclear Seismic Category 1

to withstand a design basis seismic event. A separate tank of 300 gallons

capacity is provided for each pump's lubrication system oil collection

piping headers. Each collection tank is verted and provided with a flame

arrestor.

Each tank's capacity is sufficient to hold the full volume of

oil from the reactor coolant pump.

The inspector reviewed the following documentation of the oil collection system

and it was verified that the system was being installed under a QA/QC program.

.

.

- _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

__

_ _ _ _ _

. _ _ _ _ - _ _

- _ _ _ .

_-___

_-

w

,

,

.

'

.6

-

,

Drawing Nos.

Title

'

System Drawing:

2X4DB112 (Re'v. 17)

P&I Diagram Reactor Coolant System

(System No. 1201)

Bechtel/ Georgia Power

Reactor Coolant System - Fabrication-

Company drawings

Isometrics

2J4-1201-210-01,02;

2J4-1201-215-01,02;

2J4-1201-220-01,02,03;

2J4-1201-225-01,02,03

A_ walkdown inspection was made of the oil collection systems for the

Unit 2 reactor ' coolant pumps.

These systems appear to meet the FSAR

commitments

Within the areas examined, no violations or deviations were identified.

5.

Action on Previous Inspection Findings (92701)

(Closed) IFI (425-84-34-01). Removal of All Combustible Scaffolding,

Planking and Temporary Construction Structures Required Prior to

Licensing.

The licensee stated that all

combustible construction

material, scaffolding and temporary structures were removed from the plant

areas before these areas were turned over to operations as denoted in a

memo to all contractors dated October 21,1986, (File No. CPS-316). Any

new combustible materials which enter these areas must be approved by

Procedure 92015, Control of Transient Combustibles.

Furthermore, weekly

inspection conducted using Procedure 92010-C, Weekly fire Inspections,

will identi fy any new combustibles and should implement the necessary

action to remove these combustibles or authorize these materials by

permit.

During the plant tours, the inspector did not identify any

unauthorized combustible materials in Unit 2 areas that were under

operations turnover control.

This item is closed.

6.

Exit Interview

The inspection scope and results were summarized on May 26, 1988, with

those persons indicated in paragraph 1.

The inspector described the

,

areas inspected and discussed in detail the inspection results listed

below.

Proprietary information is not contained in this report.

Dissentir.g comments were not received from the licensee.

Deviation (425/88-32-01), Failure to Maintain Manual Fire Hose Suppression

Capability for the Unit 2 Control Room.

.

I

I