j ENCLOSURE 1 NOTICE OF DEVIATION Georgia Power Company Docket No. 50-425 Vogtle Unit 2 License No. CPPR-109 The following deviation was identified during a f'ucle.ar Regulatory Commission (NRC) inspection condteted on May 23-26, 1988.

Georgia Power Company letter to the NRC dated December 21,1987,(File-X7BC35) concerning removal of the control room temporary gypsum board fire wall states that a fire hose cabinet immediately adjacent to the control room entrance with 150 feet of hose would be available to protect all areas of the control room.

Contrary to the above, the Unit 2 hose cabinet (labeled No. 2-23 R4-197) was not sauintained available for fire brigade use due to construction related obstructions in the area of the cabinet front which restricted accessibility to the cabinet.

In addition, the fire hose cabinet door latch was inoperable and construction electrical cords were stored inside the cabinet.

Please provide to the U.S. Nuclear Regulatory Comission, ATTN:

Document Control Desk, Washington, DC 20555, with a copy to the Regional Administrator, Region II, and a copy to the NRC Resident Inspector, Vogtle, in writing within 30 days of the date of this Notice, the reasons for the deviation, the I

corrective steps which have been taken and the results achieved, the corrective I

steps which will be taken to avoid further deviations, and the date when your corrective action will be completed. Where good cause is shown, consideration will be given to extending the response time.

FOR THE NUCLEAR REGULATORY COMMISSION

/

Alan R. Herdt, Chief Engineering Branch Division of Reactor Safety Dated at Atlanta, Georgia this day of 1988 eso7220124 880629 DR ADOCK 0500 5