Requests Approval of Encl Proposed Changes Re Control Room Design Improvements and Installation of SPDS Monitor,Per NUREG-0737,Suppl 1,by 880404.Quantity & Category of Human Engineering Discrepancies Also Addressed
ML20149F607
Person / Time
Site: Fort Saint Vrain 
Issue date: 02/10/1988
From: Warembourg D
PUBLIC SERVICE CO. OF COLORADO
To:
NRC OFFICE OF ADMINISTRATION & RESOURCES MANAGEMENT (ARM)
References
RTR-NUREG-0737, RTR-NUREG-737 P-88066, TAC-56125, NUDOCS 8802170277
Download: ML20149F607 (13)


Text

-

g OPublic Service ~

Company of Colorado 16805 WCR 19 1/2, Platteville, Colorado 80651 February 10, 1988 Fort St. Vrain Unit No. 1 P-88066 U.S. Nuclear Regulatory Commission ATTN:

Document Control Desk Washington, DC 20555 Docket No. 50-267

SUBJECT:

Staff Review of the Fort St. Vrain Control Room Design Review Summary Report

REFERENCE:

NRC Letter (G-85363)

Hunter to Lee Dated 8/27/85 Gentlemen:

Public Service Company of Colorado (PSC) requests the approval of the implementation of five changes relative to the requirements of NUREG-

0737, Supplement 1,

during the Spring of 1988.

Four of these are control room design improvements and the fifth will install the Safety Parameter Display System (SPDS) Monitor. Attachment 1 to this letter lists these five control room changes and the related design package submitted in response to the above referenced letter. provides a discussion of these changes relative to the design package submitted and the review activities to date. provides an accounting of the quantity and category of Human Engineering Discrepancies (HED's) to be addressed by the listed changes.

l This approval is needed in order to make a final determination relative to the amount and nature of work to be scheduled.

PSC requests the NRC's approval by April 4,

1988, so that the construction activities can effectively be integrated into the overall schedule for the helium circulator outage which is to begin l

May 2, 1988.

8802170277 080210 l

DR ADOCK 050 7

5

[

P-88066-.Februaryjl0, 1988-

'-If :you have any questions, please contact M..H. Holmes at (303) 480-6960.

Very truly yours, Nb

( der.

D. W. Warembourg Manager, Nuclear Engineering Division DWW:DJG/jbl Attachments cc:

Regional Administrator, Region IV ATTN:

Mr. T. F. Westerman, Chief Project Section 8 Mr. Robert Farrell.

Senior Resident Inspector Fort St. Vrain J

9 f

L 1.-,--,a n

e.-

I P-88066' Page 1 of 1 ITEM DESCRIPTION TRANSMITTAL ATTACHMENT TITLE OF LETTER TO THE OF PROPOSED

SUMMARY

ATTACHMENT CHANGE REPORT 1

CN-1764 Warembourg to 6b-21 Summary of the Control Room Relocation Berkow Dated Improvement Design Process

.of Manometer 06/16/86 As Applicable to I-09.

& Barometer (P-86407) 2 CN-2109 Warembourg to 6b-26 Summary of the Control Room Deletion of Berkow Dated Improvement Design Process Spurious &

08/18/86 As Applicable to the Annun-Nuisance (P-86505) ciator System (Alarm Alarms Initiating Circuits).

3

.CN-1878 Warembourg to 6b-7 Summary of the Control Room I-09 Berkow Dated Improvement Design Process Modification 12/03/85 As Applicable '.o I-09 For Recorder (P-85454)

Recorder Move.

Relocations 4

CN-1895 Warembourg to 6b-8 Summary of the Control Room Location Berkow Dated Improvement Design Process

Aids, 05/16/86 As Applicable to I-10
Labeling, (P-86366)

Control Board.

Demarcation

& Minor Component Changes 5

  • See Note 1 Warembourg to 6b-5 Summary of the Control Room CN-1395 Berkow Dated Improvement Design Process Installation 12/03/85 As Applicable to I-03/04.

of the (P-85454)

SPDS Monitor

  • Note 1 - The SPOS monitor installation package was not submitted as a part of the Control Room Design Review Summary Report or as an attachment to that report.

This installation does, however, affect our previous design submittal for main control boards I-03/04.

The SPOS Safety Analysis Report and Program Plan was transmitted by letter (P-84487) Warembourg to Johnson, dated November 11, 1984.

PSC received the staff's Safety Evaluation Report on the SPDS in a letter (G-86384) Heitner to Williams, dated July 14, 1986.

.X 4

P-88066 Page 1 of 4 t*

PROPOSED CHANGES RELATIVE TO PREVIOUS DESIGN PACKAGE SUBMITTALS CN-1764 Manometer.& Barometer Replacement / Relocation

- b-21 transmitted by letter (P-86407)

Warembourg to Berkow, dated June 16, 1986, listed a disposition for the Manometer discrapancies as

' Relocate, Rescale & Relabel' by CN-1881.

CN-1764 has been assigned to install (relocate) a new Manometer and Barometer on the East wall of the Control Room.

This new equipment purchase will address the scaling (rescale) issues cited by HED-0802.

Proper labeling will be provided by CN-1764.

There were no review questions addressed to the disposition of HEO-0802.

CN-2109 was originally assigned to implement the de-CN-2109 sign intent of Attachment 6b-26, submitted by letter, (P-86505) Warembourg to Berkow, dated August 18, 1986.

The new basis of this change notice will accomplish 28 alarm deletions and/or minor modifications in support of a black board concept.

These activities address items 5 & 6 of Attachment 6b-12 transmitted by letter (P-86088) Warembourg to Berkow, dated March 18, 1986, which were originally assigned to CN-1880.

A subsequent reissue of CN-2109 will address the issues described by Attachment 6b-26.

CN-2109 will delete alarm FAHL-4671 (HED-340) which was addressed by PSC's response [ Letter (P-87357),

Warembourg to Calvo, October 20,1987] to Science Applications International Corporation (SAIC) review comments.

This alarm deletion is :ensistent with PSC's explanation and the disposition of HED-0340.

CN-1895 This CN will address minor component & labeling changes described by Attachment 6b-18, transmitted by letter (P-86366) Warembourg to Ber(ow, dated May 16, 1986, with the following exception:

P-88066~

Page 2 of 4

.gn

- CN-1895 (Cont.)

Labeling of the "No fail" lights (HED 364) will be done in conjunction with the work on Control Board I-13 and Instrument Rack I-14.

This is a

-consistency consideration, since a similar problem exists on these two structures.

There were several review questions relative to the disposition of HED's generated on Instrument Rack 1-9310.

Generally, these questions were directed toward PSC's intent to not address vertical positioning, labeling and meter scaling problems on electronic modules not reautred by control room operators in plant operations.

PSC's responses on page 73 & 92 of the Attachment to letter (P-87357),

Warembourg to Calvo, dated October 20,

1987, provides an explanation and PSC's justification for not taking add'tional action.

The intent of CN-1895 is consistent with PSC's design-package -submittal and PSC's response to the technical reviewers questions.

CN-1878 This change makes structural modifications to I-09 in order to accommodate the relocation of various recorders.

This change will-implement the design intent of Attachment 6b-7 of letter (P-85454),

Warembourg to Berkow dated December 3,

1985, with the exception that TR-2227 and.TR-2255 will be temporarily locateo on the West end of I-09 pending installation of the Steam Generator / Core Graphics display on I-04. The Steam Generator / Core Graphics

display, once operational will display the information currently provided by

.TR-2227 and TR-2255 in a more directly useable form. Until the Steam Generator / Core Graphics installation is complated, TR-2227 and TR-2255 will be maintained in this more accessible interim location.

There are six (6) HED's to be resolved or partially resolved by CN-1878 which were addressed by PSC's response [ Letter (P-86528), Warembourg to Berkow, dated August 19,1986], to SAIC review comments.

I.

Four (4) of these HED's will be partially resolved as follows:

HED-653 - NR-1133-2 will be relocated to I-09 and rescaled in accordance with PSC's response i

l to item 7, page 20.

l

'P-88066 Page 3 of 4 HED-654 - TR-4637 & TR-4638 will be relocated.to I-09 and the chart ' paper' rescaled in accordance with PSC's response to items 8 and 9, pages 22 and 24 respectively.

HED-655 - TR-4637 & TR-4638 will be relocated to I-09 and the chart paper rescaled in accordance with PSC's response to items 8 and 9, pages 22 and 24 respectively.

HED-764 - TR-2232 and FR-2222 will be relocated to I-09 in accordance with PSC's response to item 12, page 29.

TR-2227 and TR-2255 will be temporary located on the West end of I-09 until the Steam Generator Temperature and Flow display.is available on I-04.

The remaining two (2) HED's will be completely resolved as follows:

HED-695 - TR-4637 and TR-4638 will be relocated to I-09 and the chart paper will be rescaled in accordance with PSC's response to item 11, page 28.

HED-786 - TR-2321 will be relocated to the refueling floor and TR-2322 will be relocated to I-09 in accordance with PSC's response to item 13, page 30.

CN-1395 This CN was reserved to provide for the installation of the SPDS monitor and the required control switches.

This CN was not part of a CRDR Submittal (The general intent was included as part of the SPDS Program Plan submittal.)

The location originally selected for the SPDS monitor was above the vertical board section of Main Control Board I-04.

This original location would have resulted in a minimal reconfiguring of I-04.

1 4'

g

a u

P-88066 Page 4 of 4 CN-1395(Cont.) Attachment 6b-5 transmitted by -letter (P-85454),

Warembourg to Berkow, dated December 3, 1985, shows the proposed I-04 configuration without -respect to the SPOS monitor positioning. A subsequent review of the required viewing distances, graphics software availability, and the resolution of available Cathode Ray Tubes, dictated a different (lower) elevation for this monitor.

A simultaneous evaluation of the existing I-04 core graphics panel showed that the addition of a Core Graphics display to the proposed Steam Generator Temperature & Flow Display monitor would provide the operator with the required information in a more useable form than the existing display.

PSC's response to the SAIC comment on HED-0656 tran-smitted by letter (P-87357) Warembourg to Calvo, dated October 20, 1987, provided a description of this display.

The implementation of CN-1395 will provide for eliminating certain existing digital indicators, and locating the SPOS monitor in the upper vertical section of I-04, CN-1887 (scheduled for later implementation) proposes to further reconfigure I-04 by placing the Steam Generator / Core Graphics display in the location occupied by the existing Core Graphics panel.

There were no questions or requests for additional information (letter G-86316, Heitner to Walker, dated June 13, 1986), made on the I-04 design submittal.

l l

P-88066 Page 1 of 6-HUMAN ENGINEERING DISCREPANCIES (HEDs)TO BE ADDRESSED BY CN-1764, CN-2109, CN-1878, CN-1895 and CN-1395

. [ CATEGORY 1l CATEGORY 2l CATEGORY 3l CATEGORY 4l CN l

HEDs l

HEOs l

HEDs l

HECs l

REMARKS I

I I

l l

I I

I I

i 1764 1 802 l 802 l

l HED will be completely re-l l

l l

l solved.

I I

I I

I I

I I

I I

l l

l l

l l

l 1

I l

l l

i l

2109 l 460, 827 l 421 1 441 1 340, 401 1 HED will be completely re-l 830 l

l l

l solved.

I I

I I

I I

I I

I i

l l

l 336 l HED will be partially re-l l

l l

l solved.

Discrepancy l

l l

l l cleared on Liquid Waste i

l l

l Cooling Water Mixing Flow l

l l

l l Low alarm.

I I

I I

I l

l l

1 l

l l

l 411 l

l HED will be partially re-l l

l 1

i solved. Discrepancies l

l l

l 1 cleared on alarm windows l

l l

l l 1060, 4-11 and 1060, 5-11.

I I

I I

I I

I I

I I

l l 418 l

l l HED will be partially re-l 1

l l

l solved. Discrepancy I

l l

l l cleared on alarm window I

I I

I I IO6A, 2-5.

I I

I I

I I

I I

I i

l

! 419 l

l l HED will be partially re-l 1

l l

l solved.

Discrepancy l

l 1

l 1 cleared on alarm window I

l I

i l 106A, 2-5.

I I

I I

I I

I I

i 1

l l

l 426 l

l HED will be partially re-I I

l l

l solved.

Discrepancy 1

1 l

l l cleared on alarm window I

l i

I i 106E, 5-8.

I I

I l

l l

1 I

I l

l 1

l 438 l

l HED will be partially re-I l

l l

l solved. Discrepancy I

l l

l cleared on alarm window I

l l

l l 106H, 4-3.

I I

I I

I L

'~

P-88066 Page 2 of 6 HUMAN ENGINEERING DISCREPANCIES (HEDs)TO BE ADDRESSED BY-CN-1764, CN-2109, CN-1878, CN-1895 and CN-1395-

.lCATEGORY 1l CATEGORY 2l CATEGORY 3l CATEGORY 4l CN ' l HEDs l

HEDs l

HEDs l

HEDs i

REMARKS l

l I

I I

I I

I I

l

~2109 l.531 l

l l

.I HED will be partially re-l l

l l

l solved.

Discrepancy

'l l

l l'

I cleared on alarm window

.]

l-l l

l 113C, 5-5.

I I

I l

l-1 I

l l

l 1878 l 168, 252 l l 695, 786 l l HED will be completely re-l 517 l

l l

l solved.

l l

1 l

I I

I I

I l

l 25 l

l l

l HED will be partially re-l l

l l

l solved.

NR-1199/XR-11262/

'l l

l l

l FR-11262 will be labeled.

I I

I I

I I

I I

I l

l 269 l

l l

l HED will be partially re-l l

l l

l solved TR-2322, FR-2222 l

l l

l l & TR-2321 will be labeled.

l l

1 I

I l

1 I

I i

l l

l 384 1

i HED will be partially re-l l

l l

l solved.

Discrepancies l

l l

l l will be cleared on:

l l

l l

l POR-73335, POR-73440, l

l l

l 1

POR-73441, POR-73442, l

l l

l l

PDR-73449, POR-73450, l

l l

l l

PDR-73451, POR-73452, l

l l

l l

TR-73445, TR-73446, l

l l

l l

TR-73447, TR-73448, I

l l

I I

TR-73449, TR-73450, l

l l

l l

TR-73451, TR-73452, I

I i

l l

I l

l l

l l

l 384 l

l l HED will be partially re-l l

l l

l solved.

Discrepancies i

l l

l l will be cleared on:

l l

l l

l TR-4637, TR-4638, I

l l

l l

TR-5156, and TR-92105.

i l

l l

l l

l l

l 1

l l

l l 496 i HED will be partially re-l l

l l

l solved.

NR-1199/XR-11262/

l l

l l

l FR-11262 will be relocated I

l l

l l

l P-88066 Page 3 of 6 HUMAN ENGINEERING DISCREPANCIES (HEDs)TO BE ADDRESSED BY CN-1764, CN-2109, CN-1878, CN-1895 and CN-1395 l CATEGORY llCATEGORY 2l CATEGORY 3l CATEGORY 4l CN I HEOs l

HEDs i

HEDs I

HEDs l

REMARKS I

I I

I I

I I

I I

I 1878 l 544 l

l l

l HED will be partially re-I l

l I

I solved.

TR-2321 & TR-2322 l

l l

l l will be labeled.

I I

i l

l I

I l

l'.

I l 652 I

l l

l HED will b partially re-l l

l l

l solved.

Charts will be l

I l

l l revised for:

l l

l l

l TR-4637, TR-4638, PR-1108, l

l l

l l TR-2256, NR-1199/XR-11262/

l l

i l

l FR-11262, NR-1133-2, I

l l

l l POR-73335, TR-73335, I

I i

l l FR-2222, TR-31115, I

l l

l l TR-3118, TR-2322, I

l l

l l TR-2321, TR-92105, I

i l

l l TR-5156 and GR-5154.

I I

I I

l l

l l

l l 653 l

l l

l HED will be partially re-l l

l l

l solved.

Discrepancies l

l l

l l cleared on:

I l

l l

l PR-1108, NR-1133-2, I

l l

l l

TR-31115, GR-5154, l

l l

l l

TR-92105, TR-4637, l

l l

l l

TR-4638, POR-73448, l

l l

l l

and FR-2222.

I I

l l

l 1

l l

1 l

l 654 l

l 1

l Hd0 will be partially re-l l

l l

l solved.

Discrepancies l

l l

l 1 cleared on TR-4637 and l

l l

l l TR-4638.

l i

l i

I I

l t

I l

l 655 l

i l

l HED will be partially re-l l

l l

l solved.

01screpancies l

l l

l l cleared on:

1 I

l l

l TR-2256, GR-5154, l

l l

l l

TR-4637, TR-4638, I

l l

l l

and POR-73348.

l l

l l

l

P-88066 Page 4 of 6 HUMAN ENGINEERING DISCREPANCIES (HEDs)TO BE ADDRESSED BY CN-1764, CN-2109, CN-1878, CN-1895 and CN-1395

-l CATEGORY 1l CATEGORY 2l CATEGORY 3] CATEGORY 41 CN l

'HEDs l

HEDs' l

HEDs l

HEDs l

REMARKS l

l i

l I

i l

i l

1878 l l 656 1

I l HED will be partially re-l l

l l

l solved.

Discrepancies l

l l

l l cleared on:

l l

l l

l NR-1133-2, TR-31115, I

l' l

l l

GR-5154, TR-5156, 1

I l

l i

TR-92105, TR-2322, I

I l

l 1

and TR-2321.

l I

I I

I I

l 1

l l

1 657 l

l l

l HED will be partially re-l l

l l

l solved.

Discrepancies l

I l

l l cleared.on:

l l

l l

l GR-5154, TR-5156, l

l l

1 l

TR-92105, PDR-73448, I

l l

l l

and TR-2321.

I l

I l

l I

I I

l 1

l l

l 659 l

l HED will be partially re-I l

l l

l solved.

Discrepancies l

l l

l l

l cleared on:

l l

l l

1 l

GR-5154, TR-5156, l

l l

l l

snd TR-2321.

l I

i l

l l

l l

l 1

l l

l 746 l

l HED will be partially re-1 l

l l

l solved.

Discrepancy i

I l

i I cleared on FR-2222.

I I

I l

l l

l l

l 1

1895 1 241, 318 l l

l 359 l HED will be completely re-1 320, 323 l l

l 1 solved.

l 324, 325 I I

I l

l 326, 327 l l

l l

1 362, I

l l

l

[ 365-1, I

l l

1 I 521, 542 l l

1 I

I 545, 597 l l

1 l

l 627, 782 l l

l l

I 784. 785 l l

l l

l 792 l

I I

l l

1 l

l l

1 l

l 1

I i 14 l

l l

l HED will be partially re-l l

l l

l solved.

Discrepancy I

l l

l l cleared on I-10.

P-08066 Page 5 of 6 HUMAN ENGINEERING DISCREPANCIES (HEOs)TO BE ADDRESSED BY

-CN-1764, CN-2109, CN-1878, CN-1895 and CN-1395 l CATEGORY 1l CATEGORY 2l CATEGORY 3] CATEGORY 4l CN j.

HEOs l

HEOs l

HEOs l

HEOs l

REMARKS I

I I

l l

1895 l l

.I l

l

~

l l

_l 384 l

l HED will be partially re-l l

l l

l solved. Discrepancy l

l l

l l cleared on CS22 A & B, I

l l

l l XCR BIN Modules, RIS-93250 l

l l

l l -10 and -11 thru RIS-93252 l

l l

l 1 -10 and -11, XI-93235 thru l

l l

l l XI-93237, XI-93181 thru l

l l

l 1 XI-93183, TSH-22136 thru l

l l

l l TSH-22137 and RWP LOGIC.

l I

l 1

l l 488 l

l l

l HED will be partially re-l l

l l

l sovled.

Discrepancy i

I l

l l cleared on Bins 104, 204,-

l l

l l

l 304, 704 P10 & 11, 904, l

l l

l l P10 & 11, 405 P6, 7 & 8, I

l l

l l 505 P6, 7 & 8, 605 P6, 7 &

l l

l l

l 8, 1005 P6, 7 & 8, 406 P4, I

l l

l l 8 & 10, 506 P4, 8 & 10, l

l l

l l 1006 P4, 8 & 10, 1206 P4, I

I I

I I 8 & 10.

I l

l 1

l 1

l 1

l l

1395 1 33, 34 l

l l

l MED will be completely re-1 43, 97 l

l l

l solved.

I 98, 99 l

1 l

l l 100, 506 l l

l l

l 644 l

l l

l 1

l l

1 l

l 14 l

l l

l HED will be partially re-1 I

I I

I solved.

I-04 will be l

l l

l l labeled.

I l

l l

1 I

l 1

l 1

l 96 l

l l

l HED will be partially re-1 I

l l

l solved. HS-22147-1 thru 6 l

l l

l l and HS-22148-1 thru 6 will l

l l

l l be deleted.

l I

l l

l 1

l l

l l

l l 503 l

l l HED will be partially re-l l

l l

l solved.

XI-11142/3/4 will l

l l

l l be deleted.

I l

l 1

I I

I I

I I

l 591 l

l l HED will be partially re-1 l

l l

l solved.

XI-22147 will be l

l l

l l deleted.

n

P-88066 Page-6 of 6-

SUMMARY

OF HEDs TO BE ADDRESSED BY CN-1764, CN-2109, CN-1878, CN-1895 and CN-1395 HEDs TO BE COMPLETELY RESOLVED l CATEGORY 1l CATEGORY 2l CATEGORY 3l CATEGORY 41 CN l HEDs

.I HEDs l

HEDs l

HEDs l

l I

i l

l l

l l

l l

1764 l 1

l 1

l l

l 2109 l 3

l 1

l 1.

I I

l l

l l

2 l

1 1

I I

I 1878 l 3

l l

2 l

l 1

l I

l

.I 1895 l 19 l

l l

1 l

l l

1 i

l 1395 l 9

l l

l l

Mi 35 2

l 3

1 3

l NOTE:

Totals may include HEOs assigned to two categories.

HEDs TO BE PARTIALLY RESOLVED l CATEGORY llCATEGORY 2l CATEGORY 3l CATEGORY 41 CN l HEDs l

HEOs l

HEDs l

HEOs l

I I

I l

1 l

1 1

I l

2109 l 1

1 2

1 4

l l

l l

l l

l 1878 l 8

1 2

1 3

l 1

l l

l l

l I

1 1895 l 2

l l

1 l

l 1

l l

1 l

1395 l 2

l 2

i i

i l

l l

I I

l TOTAL l 13 1

6 l

8 l

1 l

l I

l i

l i