DEC 2 31985 Docket No. 50-219 Mr. P. B. Fiedler Vice President and Director Oyster Creek Nuclear Generating Station Post Office Box 388
\\A O
Forked River, New Jersey 08731 p
Dear Mr. Fiedler:
SUBJECT:
IE BULLETIN 80-11, MASONRY WALL DESIGN Re:
Oyster Creek Nuclear Generating Station The enclosed safety e' valuation provides the results of the staff's review of your submittals on the seismic reevaluation of reinforced concrete masonry walls at Oyster Creek. These submittals were provided in response to IE Bulletin 80-11. The staff's evaluation is based on the results of reviews performed by Franklin Research Center, which are presented in the enclosed Technical Evaluation Report.
As presented in the staff's safety evaluation, Enclosure 1, the staff concludes that IE Bulletin 80-11 has been fully resolved for Oyster Creek and that there is a reasonable assurance that the safety-related masonry walls at Oyster Creek will withstand the specified design load conditions without impairment of wall integrity or the performance of the required safety functions.
You are presently connitted to complete the remaining modifications of the masonry walls in the Cycle 11 Refueling outage; however, you requested by letter dated July 26, 1985, to defer the modifications for 13 masonry walls to Operating Cycle 11. This request is.still under review by the staff and will be the subject of a separate letter.
Sincerely, Orc asi e b od by John A. Zwolinski, Director BWR Project Directorate #1 Division of BWR Licensing
Enclosure:
Safety Evaluation cc w/ enclosure:
8601020349 851223 See next page PDR ADOCK 05000219 G
' DISTRIBUTION E'NHR"TDs m EJordan ACRS(10)
NRC PDR^~~~""
BGrimes NChokshi Local PDR JPartlow DVassallo BWD#1 Reading JDonohew GHolahan RBernero CJamerson OELD wc linski DBL:PD#1 DB DBL:PD#1 CJamerson-JD ew:tm JZwolinski 4/%/85 g g/
85 g/g/85 I
t
pa nag'o f
UNITED STATES g
E NUCLEAR REGULATORY COMMISSION n
WASHINGTON, D. C. 20555
%,...../
December 23, 1985 Docket No. 50-219 Mr. P. B. Fiedler Vice President and Director Oyster Creek Nuclear Generating Station Post Office Box 388 Forked River, New Jersey- 08731
Dear Mr. Fiedler:
SUBJECT:
IE BULLETIN 80-11, MASONRY WALL DESIGN Re:
Oyster Creek Nuclear Generating Station The enclosed safety evaluation provides the results of the staff's review of your submittals on the seismic reevaluation of reinforced concrete masonry walls at Oyster Creek. These submittals were provided in response to IE Bulletin 80-11. The staff's evaluation is based on the results of reviews performed by Franklin Research Center, which are presented in the enclosed Technical Evaluation Report.
As presented in the staff's safety evaluation, Enclosure 1, the staff concludes that IE Bulletin 80-11 has been fully resolved for Oyster Creek and that there is a reasonable assurance that the safety-related masonry walls at Oyster Creek will withstand the specified design load conditions without impairment of wall integrity or the performance of the required safety functions.
You are presently committed to complete the remaining modifications of the masonry walls in the Cycle 11 Refueling outage; however, you requested by letter dated July 26, 1985, to defer the modifications for 13 masonry walls to Operating Cycle 11. This request is still under review by the staff and will be the subject of a separate letter.
Sincerely,
[
(,
s John
. Zwolinski, Director BWR Pr ject Directorate il Division of BWR Licensing
Enclosure:
Safety Eve uation cc w/ enclosure:
See next page
~
Mr. P. B. Fiedler Oyster Creek Nuclear Oyster Creek Nuclear Generating Station Generating Station cc:
G. F. Trowbridge, Esquire Resident Inspector Shaw, Pittran, Potts and Trowbridge c/o U.S. NRC 1800 M Street, N.W.
Post Office Box 445 Washington, D.C.
20036 Forked Riv?r, New Jersey 08731 J.B. Liberman, Esquire Com..iss,' u.w Bishop, Liberman, Cook, et al.
New Jersey Department of Energy 1155 Avenue of the Americas 101 Comerce Street New York, New York 10036 Newark, New Jersey 07102 Eugene Fisher, Assistant Director Regional Administrator, Region I Division of Environmental Quality U.S. Nuclear Regulatory Comission Department of Environmental 631 Park Avenue Protection King of Prussia, Pennsylvania 19406 380 Scotch Road Trenton, New Jersey 08628 BWR Licensing Manager GPU Nuclear 100 Interpace Parkway Parsippany, New Jersey 07054 Deputy Attorney General State of New Jersey Department of Law and Public Safety 36 West State Street - CN 112 Trenton, New Jersey 08625 Mayor Lacey Township 818 West Lacey Road Forked River, New Jersey 08731 D. G.. Holland Licensing Manager Oyster Creek Nuclear Generating Station Post Office Box 388 Forked River, New Jersey 08731 I
l
. _ _..