Amend 4 to License NPF-29,revising Tech Specs to Be Consistent W/Planned Equipment Mods & Temporarily Making Railroad Bay Area Part of Secondary Containment
ML20135H872
Person / Time
Site: Grand Gulf 
Issue date: 09/18/1985
From: Thompson H
Office of Nuclear Reactor Regulation
To:
Shared Package
ML20135H873 List:
References
TAC-59184, TAC-59185, TAC-59186, TAC-59187, NUDOCS 8509240334
Download: ML20135H872 (15)


Text

_ _ _ _ _ - _ - _ _ -

[

UNITED STATES E

e NUCLEAR REGULATORY COMMISSION g

E WASHINGTON, D. C. 20555

%,..... s o

MISSISSIPPI POWER & LIGHT COMPANY MIDDLE SOUTH ENERGY, INC.

SOUTH MISSISSIPPI ELECTRIC POWER ASSOCIATION DOCKET NO. 50-416 l

GRAND GULF NUCLEAR STATION, UNIT 1 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No.4 License No. NPF-29 1.

The Nuclear Regulatory Comission (the Comission) has found that:

A.

The application for amendment to the Grand Gulf Nuclear Station, Unit-i 1 (the facility) Facility Operating license No. NPF-29 filed by the Mississippi Power and Light Company acting for itself, Middle South Energy, Inc...and South Mississippi Electric Power Association '(the licensees), dated July 3, 1985, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act) l and the Commission's regulations as set forth in 10 CFR Chapter I; B.

The facility will operate in conformity with the application, as amended, the provisions of the Act, and the regulations of the Comission; C.

There is reasonable assurance; (1) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in ccmpliance with the Cer;nission's regulations set forth in 10 CFR Chapter I; D.

The issuance of this license amendment will not be inimical to the common defense and security or to the health and safety of the public; f

E.

The issuance of this license amendment is in accordance with 10 CFR Part 51 of the Comission's regulations and all applicable _ requirements have been satisfied.

2.

Accordingly, Facility Operating License NPF-29 is amended as follows:

A.

Add paragraph 2.C.(39) to read as follows:

(39) Temporary Secondary Containment Boundary Change l

For a period ~of time not to exceed 144 cumulative hours, the 8509240334 850918 PDR ADOCK 05000416 P

PDR

provisions of Specification 3/4.6.6.1 may be applied to the rail-road bay area including the exterior railroad bay door on the 4

auxiliary building in lieu of the present secondary containment l

boundaries that isolate the railroad bay area. While the railroad bay area is being used as a secondary containment bounda'ry, the railroad bay door may be opened for the purpose of moving trucks in and out provided the four hour limitation in ACTION a of Tech-nical Specification 3.6.6.1 is reduced to one hour. A fire watch shall be established in the railroad bay area while the door is being used as a secondary containment boundary.

3.

The license is further amended by page changes to the Technical Specifications i

as indicated in the attachment to this license amendment.

Paragraph 2.C.(21 l

of Facility Operating license NPF-29-is hereby amended to read as follows:

(2) The Technical Specifications contained in Appendix A, as revised through l

Amendment No. 4 and the Environmental Protection Plan contained in i

Appendix B are hereby incorporated into this license. Mississippi Power & l.ight Company shall operate the facility in accordance with the Technical Specifications and the Environmental Protection Plan.

4.

I.icense Condition 2.C.(39) is effective upon issuance of this amendment and the Technical Specification changes are effective when the equipment necessitating the Technical Specification changes is installed and made operable.

FOR THE NUCLEAR REGULATORY COMMISSION P

l.. Thompso rector D

sion of licensin Office of Nuclear Re tor Regulation

Enclosure:

Technical Specification Changes Date of Issuance:

September 18, 1985 9

ATTACHMENTT0(ICENSEAMENDMENTNO.4 FACILITY OPERATING LICENSE NO. NPF-29 DOCKET NO. 50-416 Replace the following pages of the Appendix "A" Technical Specifications with the enclosed pages. The revised pages are identified by Amendment number and contain vertical lines indicating the areas of change. The corresponding over-leaf pages are also provided to maintain document completeness.

Amended Overleaf Page Page 3/4 3-87 3/4 3-88 3/4 6-31 3/4 6-32 3/4 6-35 3/4 6-36 3/4 6-39 3/4 6-40 3/4 6-43 3/4 6 3/4 8-26 3/4 8-25 e

o e

O e

e O

O 9

e

TABLE 3.3.7.9-1 (Continued)

FIRE DETECTION INSTRUMENTATION MINIMUM INSTRUMENTS OPERABLE

  • ROOM ELEV ROOM NAME HEAT FLAME (1)

SMOKE (1).

@)

M M

12. Zone 2-17 16/0 1A101 93'

~ Passage 1A109 93' HPCS Pump Rm.

1A111 93' Piping Penetration Rm.

1A114 93' Fan Coil Area (Partial) 1A117 93' Misc. Equip. Area (Partial) 1A121 103' East Corridor 1A122 103 South Corridor (Partial) 1A123 103' North Corridor (Partial)

~13. Zone 2-18 20/0 1A201 119' East Corridor 1A211 119' North Corridor (Partial) 1A215 119' South Corridor (Partial)

14. Zone 2-19 13/0

~

1A314 139' South Corridor (Partial) 1A316 139' North Corridor (Partial) 1A321 139' MCC Area 1A322 139' Centrifugal Chiller Area 1A323 139' SGTS Area 1A324 139' HVAC Equip. Area 1A326 139' SGTS Area

15. Zone 2-20 2/0 1A305 139' Steam Tunnel
16. Zone 2-21 4/0 1A12

'185' Stairwell 1A12 20'8' Stairwell 1A12 245'

. Stairwell d.

DIESEL GENERATOR BUILDING 1.

Zone 2-10 9/0 i

1D301 133' Corridor 0/3 (Deluge) 1D304 133' Day Tank Area 1D306 133'

Div. III Diesel Gen. Room 10401 158' Div. III Diesel Gen.

Room 0/7 (Deluge) 2.

2-11 6/0 1D303 133' Day-Tank Area 1D308 133' Div. II Diesel Gen. Room 10402 158' Div. II Diesel Gen.

Room 0/7 (Deluge)

GRAND GULF-UNIT 1 3/4 3-87 Amendment No. 4 Effective Date:

4 TABLE 3.3.7.9-1 (Continued)

FIRE DETECTION-INSTRUMENTATION

(

MINIMUM INSTRUMENTS OPERABLE

  • ROOM ELEV ROOM NAME HEAT FLAME (1)

SM0KE(1)

U77)

(x/Y)

U7?T 3.

Zone 2-12 6/0 10302 133' Day Tank Area 1D310 133' Div. I Diesel Gen. Room 10403 158' Div. I Diesel Gen. Room 0/7 (Deluge) e.

STANDBY SERVICE WATER PUMP HOUSE 1.

Zone 2-1 4/0 1M110 133' SSW Pump Rm. A 1M112 133' SSW Valve Rm. A 2M110 133' SSW Pump Rm. B 2M112 133' SSW Valve Rm. B f.

CHARC0AL FILTER TRAINS 1.

Standby Gas Treatment System Filter Trains A & B 2/0 (Allison Thermistor Wire)

Auxiliary Building E1. 139'

(

2.

Control Room Standby Fresh Air System Filter Trains A & B 2/0 (Allison Thermistor Wire)

Control Building El. 133'

~

g.

CONTROL BUILDING (PGCC HALON SYSTEMS)

OC503 166' Control Room (Unit 1

~

side)

Module /Halon Panel 1H13-U700/1H13-P900

.0/10 10/0 1H13-U701/1H13-P901 0/10 15/0 1H13-U702/1H13-P902 0/9 14/0 1H13-U703/1H13-P903 0/11 17/0

1H13-U720/1H13-P920 0/7 13/0 SH13-U730/1H13-P930 0/11 12/0

-1H13-U738/1H13-P9S8 0/10 12/0 SH13-U739/SH13-P939 0/5 14/0

(

GRAND GULF-UNIT 1 3/4 3-88

TABLE 3.6.4-1 (Continued)

CONTAINMENT AND DRYWELL ISOLATION VALVES MAXIMUM

~

SYSTEM AND PENETRATION ISOLATION TIME VALVE NUMBER NUMBER VALVE GROUP (a)

(Seconds)

Containment (Continued)

Main Steam Line B21-F016-B 19(I) 1 20 Drains RHR Heat Exchanger E12-F028A-A 20(I) 5 90 "A" to LPCI RHR Heat Exchanger E12-F037A-A 20(I) 3 74 "A" to LPCI RHR Heat Exchanger E12-F0288-B 21(I) 5 90 "B" to LPCI RHR Heat Exchanger E12-F0378-B 21(I) 3 74 "B" to LPCI RHR "A" Test Line E12-F024A-A 23(0)(d) 5 90 to Supp. Pool RHR "A" Test Line-E12-F011A-A 23(0)(d) 5 36 to Supp. Pool

,RHR "C" Test Line E12-F021-B 24(0)(d) 5 144 l

^

to Supp. Pool HPCS Test Line E22-F023-C 27(0)(d) 6B 75 RCIC Pump Suction E51-F031-A 28(0)(d) 4 56 RCIC Turbine E51-F077-A 29(0)(c) 9 26 Exhaust LPCS Test Line E21-F012-A 32(0)(d) 5 144 l

Cont. Purge and M41-F011-(A) 34(0) 7 4

Vent Air Supply Cont. Purge and M41-F012-(B) 34(I) 7 4

Vent Air Supply Cont. Purge and M41-F034-(B) 35(I) 7 4

Vent Air Exh.

Cont. Purge and M41-F035-(A) 35(0) 7 4

Vent Air Exh.

Plant Service P44-F070-8 36(I) 6A 33 Water Return Plant Service P44-F069-A 36(0) 6A 33 Water Return Plant Service P44-F053-A 37(0) 6A 33 Water Supply Chilled Water P71-F150-(A) '38(0) 6A 12 Supply GRAND GULF-UNIT 1 3/4 6-31 Amendment No. 4 Effective Date:

l e

TABLE 3.6.4-1 (Continuc;d)

CONTAINMENT AND ORYWELL ISOLATION VALVES MAXIMUM SYSTEM AND PtNETRATION ISOLATION TIME VALVE NUMBER NUMBER VALVE GROUP (a)

(Seconds) t Containment (Continued)

Chilled Water P71-F148-(A) 39(0) 6A 12 Return

-Chilled Water P71-F149-(B) 39(I) 6A 12 Return Service Air P52-F105-(A) 41(0) 6A 6

Supply Inst. Air Supply P53-F001-( A) 42(0) 6A 6

RWCU to Main G33-F034-A 43(0) 8 35 Condenser RWCU to Main G33-F028-8 43(I) 8 35 Condenser RWCU Backwash to

. G36-F106-(B) 49(I) 6A 11 C/U Phase Sep. Tank RWCW Backwash to G36-F101-(A) 49(0) 6A 11 C/U Phase Sep. Tank Drywell & Cont.

P45-F067-(B) 50(I) 6A

  • 7 Equip. Drain

(

Sump Disch.

~

Drywell & Cont.

P45-F068-(A) 50(0) 6A 7

Equip. Drain Sump Disch.

Drywell & Cont.

P45-F061-(B) 51(I) 6A 7

Floor Drain Sump Disch.

Drywell & Cont.

P45-F062-(A) 51(0) 6A 7

Floor Drain

~

Sump Disch.

Condensate Supply Pll-F075-(A) 56(0) 6A 10 FPC & CU to Upper G41-F028-A 57(0) 6A 51 Cont. Pool Upper Cont. Pool G41-F029-A 58(0) 6A 51 to Fuel Pool

~

Drain Tank Upper Cont. Pool G41-F044-8 58(I) 6A 40 to Fuel Pool Drain Tank Aux. Bldg. Fir.

P45-F273-A 60(0) 6A 32 and Equip. Drn.

Tks. to Supp. Pool Aux. Bldg. Fir.

P45-F274-8 60(0) 6A 32 and Equip. Drn.

Tks. to Supp. Pool GRAND GULF-UNIT 1 3/4 6-32

TABLE 3.6.4-1 (Continued)

CONTAINMENT AND DRYWELL ISOLATION VALVES SYSTEM AND PENETRATION VALVE NUMBER

~

NUMBER 2.

Manual Isolation Valves (9)#

a.

Containment Main Steam Lines E32-F001A-A 5(0)

Main Steam Lines E32-F001E-A 6(0)

Main Steam Lines E32-F001J-A 7(0)

Main Steam Lines E32-F001N-A 8(0)

Feedwater Inlet 821-F065A-A 9(0)

Feedwa~ter Inlet B21-F0658-A 10(0)(d)

RHR Pump "A" E12-F004A-A 11(0)

Suction

'RHR Pump "B" E12-F004B-B 12(0)(d)

Suction RHR Pump "C" E12-F004C-B 13(0)(d)

. Suction RHR Heat Exchanger E12-F042A-A 20(I)

"A" to LPCI

.RHR Heat Ex. "A" E12-F027A-A 20(0) to LPCI RHR Heat Exchanger E12-F0428-B 21(I)

"B" to LPCI RHR Heat Ex. "B" E12-F0278-8 21(0) to LPCI RHR Pump "C" to E12-F042C-B 22(0)

LPCI RHR "A" Test Line E12-F064A-A 23(0)(d)

To Suppr. Pool RHR "C" Test Line E12-F064C-B 24(0)(d)

~

To Suppr. Pool HPCS Suction E22-F015-C 25(0)(d)

~

HPCS Discharge E22-F004-C 26(0)(d)

HPCS Test Line-E22-F012-C 27(0)(c)

RCIC Turbine Exh.

E51-F068-A 29(0)

LPCS Pump Suction E21-F001-A 30(0)( )

LPCS Pump E21-F005-A 31(0)

Discharge LPCS Min. Flow E21-F011-A 32(0)(d) :

l CRD Pump C11-F083-A 3,3(0)

Discharge CCW Supply

. ' P42-F066-A 44(0)

CCW Return P42-F067-A 45(0)

CCW Return P42-F068-B

,45(I)(d)

RCIC Pump E51-F019-A 46(0)

Discharge Min. Flow Reactor Recire.

B33-F128-B 47(I)

Post Accident Sampling GRAND GULF-UNIT 1 3/4 6-35

- Amendment No. 4 Effective Date:

TABLE 3.6.4-1 (Continued)

CONTAINMENT AND DRYWELL ISOLATION VALVES SYSTEM AND PENETRATION VALVE NUMBER

' NUMBER Containment (Continued)

Reactor Recirc.

B33-F127-A 47(0)

Post Accident Sampling Vent Header to E12-F0738-8 48(0)(d)

Supp. Pool RHR Pump "B" E12-F0648-B 67(0)(d)

Test Line RHR "C" Relief E12-F346-8 71B(0)(c)

Viv. Vent Hdr.

to Suppr. Pool

& Post-Acc.

Sample Ret.

RHR Heat Ex. "A" E12-F073A-A 77(0)(d)

Relief Reactor Recire.

B33-F126-B 81(I)

Accident Sampling Reactor Recire.

B33-F125-A 81(0)

Accident Sampling 89(0)((c) c SSW Supply "A" P41-F159A-A 90(I)(c))

(

SSW Return "A" P41-F168A-A SSW Return "A"

. P41-F160A-A 90(0)(c)

SSW Return "B" P41-F1688-B.

91(I)(c)

SSW Return "B" P41-F1608-B 91(0)

SSW Supply "B" P41-F1598-B 92(0)(c)

Drywell Press.

M71-F593-A 101C(0)

Inst.

Drywell Press.

M71-F591A-A 101F(0)

Inst.

Dryvell Press.

M71-F5918-B 102D(0)

Inst.

Ctat. Press. Inst.

M71-F592A-A 103D(0)

Ctat. Press. Inst.

M71-F5928-8 1040(0)

Drywell H2 E61-F595C-(A) 106A(0)

Analyzer Sample Drywell H2 E61-F5950-(B) 106A(I)

Analyzer Sample Drywell H2 Ana-E61-F597C-(A) 106B(0)

~

.lyzer Sample Ret..

106B(I)

Drywell H2 Ana-

.- E61-F5970-(B) lyzer Sample Ret.

Ctat. H E61-F596C-(A) 105A(0) 2 Analyzer Sample Ctat.-H -

E61-F596D-(B) 105A(I) 2 Analyzer Sample Ctmt. H2 Analyzer E61-F598C-(A) 106E(0)

Sample Ret.'

(

L Ctat. H2 Analyzer E61-F5980-(B) 106E(I) l Sample Ret.

GRAND GULF-UNIT 1 3/4 6-36

TABLE 3.6.4-1 (Continued)

CONTAINMENT AND 0RYWELL ISOLATION VALVES SYSTEM AND PENETRATION

. VALVE NUMBER NUMBER Containment (Continued)

RHR Pump "A" Test E12-F227 23(0)(')

Line to Suppr.

Pool RHR Pump "A" Test E12-F262 23(0)(*)

Line to Suppr.

Pool RHR Pump "A" Test E12-F228 23(0)(*)

Line to Suppr.

Pool RHR "A" Test Line E12-F290A-A 23(0)(d) to Supp'. Pool RHR Pump "A" Test E12-F338 23(0)(c)

Line to Suppr.

Pool RHR Pump "A" Test E12-F339 23(0)(c)

Line to Suppr.

Pool RHR Pump "A" Test E12-F260 23(0)(*)

Line to Suppr.

Pool 24(0)(d)-

RHR Pump "C" Test E12-F280 Line to Suppr.

Pool RHR Pump "C" Test E12-F281 24(0)(d)

Line to Suppr.

~

_ Pool HPCS Suction E22-F014 25(0)(d)

HPCS Discharge E22-F005-(C) 26(I)

HPCS Discharge.

E22-F218 26(I)

HPCS Discharge E22-F201 26(I)(d)

HPCS Test Line E22-F035' 27(0)

~

HPCS Test Line E22-F302 27(0)(,)-

27(0)((')

HPCS Test Line E22-F301

)

LPCS Pump Suction E21-F031 30(0)

LPCS Discharge E21-F006-(A) 31(I)

LPCS Discharge E21-F200 31(I)

LPCS Discharge ',

E21-F207 31(I)(d)~

LPCS Test Line E21-F217 32(0)(d)

LPCS Test Line E21-F218 32(0)

CRD Pump C11-F122

'33(I)

Discharge PSW Supply P44-F043 37(I)

Plant Chilled P71-F151 38(I)

Water Supply Service Air PS2-F122 41(I)

Supply GRAND GULF-UNIT 1 3/4 6-39 Amendment No. 4 Effective Date:

TABLE 3.6.4-1 (Ccntinuid)

CONTAINMENT AND ORYWELL ISOLATION VALVES SYSTEM AND

' PENETRATION VALVE NUMBER NUMBER Containment (Continued)

Instr. Air Supply P53-F002 42(I)

CCW Supply P42-F035 44(I)(c)

RCIC Disch.

E51-F251 46(0)

Min. Flow RCIC Disch.

E51-F252 46(0)(c)

Min. Flow RHR Heat Ex. "B" E12-F0558 48(0)(d)

Relief Vent Header RHR Heat Ex. "B" E12-F1038 48(0)(d)

Relief Vent Header RHR Heat Ex. "B" E12-F1048 48(0)(d) i Relief Vent Header Refueling Wtr.

G41-F053 54(0)

J

-Stg. Tk. to Upper Ctat. Pool

}y Refueling Wtr.

G41-F201 54(I)

}

Stg. Tk. to Upper Ctat. Pool

(

Condensate Supply P11-F004 56(I)

FPC & CU to Upper G41-F040 57(I)

Cont Pool Stby. Liquid C41-F151 61(I)

Control Sys.

Mix. Tk.

(future use)

Stby. Liquid C41-F150 61(0)

Control Sys.

Mix. Tk.

~

(future use)

RHR Pump "B" Test E12-F276 67(0)(*)

Line RHR Pump "B" Test E12-F277 67(0)(')

Line RHR Pump "B" Test. E12-F212 67(0)(*)

RH mp "B" Test '512-F213 67(0)(')

Line RHR Pump "B" Test E12-F249 67(0)(')

Line RHR Pump "B" Test E12-F250 67(0)(')

Line RHR Pump "B" Test E12-F334 67(0)(c)

Line t

.A GRAND GULF-UNIT 1 3/4 6-40

I i.

TABLE 3.6.4-1 (Continued)

CONTAINMENT AND DRYWELL ISOLATION VALVES SYSTEM AND PENETRATION

{

VALVE NUMBER NUMBER 4.

Test Connections (9) t a.

Containment Main Steam T/C B21-F025A 5(0) l Main Steam T/C B21-F025B 6(0) l Main Steam T/C B21-F025C 7(0)

Main Steam T/C B21-F0250 8(0)

Feedwater T/C B21-F030A 9(0)

~

Feedwater T/C B21-F063A 9(0) i Feedwater T/C B21-F063B 10(0)

Feedwater T/C B21-F0308 10(0)

RHR Shutdown Cool.

E12-F002 14(0)

Suction T/C i

.#CIC Steam Line E51-F072 17(0)

I T/C RHR to Head E12-F342 18(0)

Spray T/C RHR to Head E12-F061 18(0)

Spray T/C LPCI "C" T/C E12-F056C 22(0)

RHR "A" Pump E12-F322 23(0)(c)

Test Line T/C RHR "A" Pump E12-F336 23(0)(c) l Test Line T/C RHR "A" Pump E12-F349 23(0)(c)

L Test Line T/C l

RHR "A" Pump E12-F303 23(0)(c)

Test Line T/C 1

I RHR "A" Pump -

E12-F310 23(0)(C)

Test Line T/C RHR "A" Pump E12-F348 23(0)(c)

Test Line T/C

~

RHR"C" Pump E12-F311 24(0)(c)

Test Line T/C RHR"C" Pump E12-F304 24(0)(c) i i

Test Line T/C HPCS Discharge T K E22-F021 26(0)

HPCS Test Line T/C E22-F303 27(0)(c)

,27(0)((c) c HPCS Test Line T/C E22-F304

)

i RCIC Turbine E51-F258 29(0)

Exhaust T/C RCIC Turbine E51-F257 29(0)(c)

Exhaust T/C LPCS T/C E21-F013 31(0)

LPCS Test Line E21-F222 32(0)(c)

T/C LPCS Test Line E21-F221 32(0)(c)

T/C i

GRAND GULF-UNIT 1 3/4 6-43

- Amendment No. 4 Effective Date:

--,,n,--

.,.-,,+n,-----,


+~-----,,,--,,-n,m.,mn,-,--

.,,,,a-.

,,-,----,.m,-,----.

,---,,,,n----w--

-.n

-en,-

TABLE 3.6.4-1 (C:ntinued)

CONTAINMENT AND DRYWELL ISOLATION VALVES i

SYSTEM AND PENETRATION VALVE NUMBER NUMBER Containment (Continued)

CRD T/C C11-F128 33(0)

Cont. Purge M41-F042 34(0)

Supply T/C Cont. Purge M41-F051~

35(0)

Exhaust T/C PSW Supply T/C P44-F333 37(0)

Plant Chilled P71-F232 38(0)

Water T/C Plant Chilled P71-F246 39(0)

Water T/C 1

Ctat. Leak Rate M61-F009 40(I)

T/C l

Service Air T/C PS2-F258 41(0)

Inst. Air T/C P53-F036 42(0)

'5 RWCU T/C, G33-F070 43(0)

'CCW Supply T/C P42-F161 44(0)

CCW Return T/C.

P42-F162 45(I)

Condensate Supply P11-F095 56(0) 1 i

T/C FPC & CU To G41-F340 57(I)

(

i Upper Cont. Pool T/C Aux. B1dg. Fir.

P45-F275 60(0)

& Equip. Drain Tk. to Suppr.

Pool T/C Aux. Bldg. Fir.

P45-F290 60(0)

& Equip. Drain Tk. to Suppr..

Pool T/C Stby. Liquid C41-F152 61(0)

Control Sys.

Mix. Tk. T/C (future use)

Combustible Gas E61-F017 65(0)

Control T/C Purge Radiation M41-F054 66(0)

Detector T/C RHR "B" Test Line E12-F321 67(0)(C)

T/C RHR "B" Test Line E12-F351 67(0)(c)

T/C RHR "B" Test Line E12-F331 67(0)(c)

T/C k

GRAND GULF-UNIT 1 3/4 6-44

TABLE 3.8.4.1-1 (Continu:d)

PRIMARY CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES c.

480 VAC Circuit Breakers (Continued)

Molded Case, Type NZM' TRIP

RESPONSE

BREAKER SETPOINT TIME SYSTEM / COMPONENT NUMBER (Amperes)

(Seconds)

AFFECTED 52-1222-04 800 0.100 CNTMT CLR FAN COIL UNIT FAN (N1M41B001B-N) 52-1222-05 240 0.100 CNTMT COOLING SYS CHAR TRAIN FAN (N1M4100028-N) 52-1222-09 1200 0.100 LIGHTING XFMR 1X104 (N1R185204-E) 52-1222-11 800 0.100 480 V RECEPTACLES 52-1222-18 500 0.100 REAC. RECIRC. PUMP SPACE NEATER (TB1B33C0018) 52-1222-19 75 0.100 MOV - RWCU RETURN TO REACTOR (N1G33F042-N) 52-1222-20 32 0.100 MOV - VESSEL DRAIN LINE RECIRC.

(Q1G33F101-N)

~

~

52-1222-21 75 0.100 HOV - CLEANUP LINE SUCT. IN DRYWELL (Q1G33F102-N) 52-1222-22 32 0.100 HOV - CLEANUP LINE RECIRC LOOP B (Q1G33F106-N) 52-1251-01 175 0.100 STEAM TUNNEL CLR INSIDE CNTMT (N1M41C004B-N) 52-1251-07 60 0.100 CNTMT CHEM WASTE SUMP PUMP i

(N1P45C027A-N)

GRAND GULF-UNIT 1 3/4 8-25

TABLE 3.8.4.1-1 (Continued)

PRIMARY CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES c.

480 VAC Circuit Breakers (Continued)

Molded Case, Type NZM TRIP

RESPONSE

BREAKER SETPOINT TIME SYSTEM / COMPONENT

~~

NUMBER (Amperes)

(Seconds)

AFFECTED 52-1251-13 800 0.100 CNTMT CLR FAN COIL UNIT FAN (N1M418001C-N) 52-1251-15 32 0.100 MOV - RWCS HX INL ISOL VLV (N1G33F256-N) 52-1251-18 38 0.100 MOV - REGEN HEAT EXCHANGER BYPASS (Q1G33F107-N) 52-1251-19 38 0.100 MOV - RWCU DRAIN FLOW ORIFICE BYP (N1G33F031-N) 52-1251-20 320 0.100 CNTMT EQUIP DRAIN PUMP (N1P45C0048-N) 52-1251-22 32 0.100 MOV - RWCU TO FLT "S" ISOL VLV (N1G33F255-N) 52-1251-26 1200 0.100 LIGHTING XFMR 1X112 (N1R18S112-D) 52-1251-28 5

0.100 MOV - STM TUNNEL COOLER INLET (N1P44F1058-N) 52-1252-23 60 '

O.100 DRYWELL FLOOR DRAIN SUMP PUMP (N1P45C0018-N) 52-1252-27 500 0.100 FUEL TRANSFER SYS MN CONSOLE (N1F11E015-MC) 52-1411-01 38 0.100 MOV - VESSEL HEAD VENTILATION (Q1821F002-N)

GRAND GULF-UNIT 1 3/4 8-26 Amendment No.

4 Effective Date: