i Docket No. 50-461
~ Mr. Frank A. Spangenberg Director of Nuclear Licensing &
Configuration Management Clinton Power Station
'P.O. Box 306 Mail Code V920 Clinton, Illinois 61727 i
Dear.Mr. Spangenberg:
SUBJECT:
C0! TENTS ON THE PROPOSED OFFSITE DOSE CALCULATION MANUAL FOR CLINTON The staff has completed its review of the Clinton Offsite Dose Calculation Manual (CDCM),-Revision 0, submitted in a letter from Illinois Power Company to W. R. Butler dated June 12, 1985. Our specific coments on the CDCM are contained in the enclosure. You should submit for a final review a revised ODCM that resolves the cements contained in the enclosure within 30 days of receipt of this letter.
If you have any questions concerning these coments or schedule l
for subnittal of revised ODCM contact the licensing project manager for your l
application.
l Sincerely, Ortstaal alamed by t.
~
Walter R.. Butler, Chief Licensing Branch No. 2 Division of Licensing l
Enclosure:
j As stated j
i cc: See next page DISTRIBUTION: 'DEdkit'Filel NRC PDR Local PDR PRC System USIC l
Lbt2 Reading EHyltoii~~'
BSiegel Goddard,0 ELD ACRS (16)
JPartlow l
BGrimes EJordan FCongel MWangler JLee JLevine B/f/ /PM LB#2/DL/BC BSieg>1.lb UButler 08/TV85 08/g/85
@"Mii!!8886 PDR
((
'o UNITED STATES y
g g
NUCLEAR REGULATORY COMMISSION 5,
a E WASHINGTON, D. C. 20555 2
/
AUG 2 8' 1985 Docket No. 50-461 Mr. Frank A. Spangenberg Director of Nuclear Licensing &
Configuration Management
'Clinton Power Station P.O. Box 306 Mail Code V920 Clinton, Illinois 61727
Dear Mr. Spangenberg:
SUBJECT:
C012 TENTS ON THE PROPOSED OFFSITE DOSE CALCULATION MANUAL FOR CLINTON The staff has completed its review of the Clinton Offsite Dose Calculation Manual (ODCM), Revision 0, submitted in a letter from Illinois Power Company to W. R. Butler dated June 12, 1985. Our specific comments on the ODCI'. are contained in the enclosure. You should subnit for a final review a reviseo CDCM that resolves the coments centained in the enclosure within 30 days of receipt of this letter.
If you have any questions concerning these corrrer.ts or schedule for submittal of revised ODCM contact the licensir.g project manager for your applicaticr..
Sincerely, Walter R. Butler, Chief Licensing Branch No. 2 Division of Licensing
Enclosure:
As stated cc: See next page
.=
fir.: Frank A Spangenberg Clinter Pc+.er Station
-~
Illinois Fcs.er Ccepeny Unit 1 CC*
- hr. Allen Sauuelsen, Escrire Jean Foy, Esquire ALsistant Attorney Generci 511 Li. Nevoda l
Envircrmertal. Control Division Urbar.a, Illinois 61601
'Scuthern Region 500 South Second Street Richard C. Hubborc
~
1 Springfield. _ Illir.ois 62706 Vice Presicer.t Technical Associates Mr. D. PL Ual1 1723 Hamilton Ave. - Suite L
~
'Vice President San Jose, CA 95125 Clinton Power Staticr.
P. O. Go>. 67E-Clinton,_ Illinois, 61727 I
lir.1;. R.jictor Manager-Nuclear Stctier. Ercireering Dpt.
C11nten Power Station F. L. Scx'678 Clir ten, Ill1nois 61727 L
Sheldon 7abel, Esquire Schiff; har011. L t.eitt 7200 Sears Tower 233 Wacker Crise Chicago, Illineis-CCClt I
kesident Inspectc U. S. l.uclear Fettletory Cornission l-Rh 3, Etx 229 A Clinton, Illinois 617E7 l
l Mr. R. C. Heiner l
Project Manager Sargent a Lu.c'y Engineers 55 East Monree Street-Chicago, Illinois 6Cf03 Mr. L. Larscn Project Manager General Electric. Ccrpany 175 Curtner Avenue,' N/C 395 -
Sun Jose, California 95125 Regional Administrater, Regicr.111 799 Eccsevelt Road l
Glen Ellyn, Iilinois. 60137 s
s l
6 t
u
Enclosure COMMENTS ON THE CLINTON ODCM 1.
Section 2.3, page 2-Iff The instrumentation for each alarm and trip set point, including radiation monitoring and sampling systems and effluent control features, should be referenced to the Clinton FSAR (Section 11.5).
2.
Section 2.4', page 2-11 The value for U, of 10 liters /yr is not acceptable. Regulatory Guide (R.G.) 1.109 in. Table E-5 specifies a value of 730 liters / year for the maximum-exposed individual.
3.
Table 2.4-1, page 2-11 This table must be recalculated and reconstructed based on comment 2.
4.
Table 2.6-1, page 2-24 This table is incomplete. The complete table must be submitted.
5.
Table 3.4-2, page 3-9ff For the purposes of 10 CFR Part 20 calculations, the child is considered the critical receptor. Therefore, the pathway dose factors, P, must be j
recalculated. Additionally, only the factors for the inhalation pathway need to be calculated.
6.
Section 3.5.2.1.2, page 3-19 The exposure time, t, is specified as 15 years, which is the midpoint of a 30 year operating license. Since it is our understanding that you will request Clinton ODCM Review 1
08/22/85
4 k
a 40 year license, the appropriate new value of 20 years for t must be used in
. your calculations.
7.
Section 3.5.2.1.3, page 3-20 C
Pathway factors, R, are calculated differently for H-3 and C-14.
You have correctly indicated the equation for H-3.
YoumustalsocalculateaRh for C-14.
Equation C-8, page 1.109-26 of R.G. 1.109 provides the appropriate method for performing this calculation.
8.
Section 3.5.2.1.4, page 3 -That the exponential in line 2 of equation (11) is a raultiplicative factor of line 1 should be clarified.
9.
Section 3.5.2.1.4, page 3-22 See coment 7.
An equation for pathway factor, R", must be used.
- 10. Section 3.5.2.1.4, page 3-23 V
See comment 7.
An equation for pathway factor, R, must be used.
- 11. Table 3.5-10, page 3-58 The value for t is specified as 90 days. Table E-15 of R.G. 1.109 h
specifies a value of 0 days for cattle ingestion of pasture grass. You must justify the of use the longer time period.
If you choose hot to justify your current values, the factors in Tables 3.5-13 through 3.5-16 must be recalculated.
Clinton ODCM Review h
08/22/85 i
o
- 12. Table 3.5-11, page 3-59 See coment 9. for t.
In addition, parameter, t,,
in your table is h
identified as t in Table E-15 of R.G. 1.109. This correction should be made.
s
- 13. Table 3.5-12, page 3-60
.The reference for parameter, f, is incorrectly indicated as Table E-5 of L
R.G.-1.109.
The correct' reference is Table E-15.
Additionally, the reference for parameter, f,'is indicated as page 28 (sic). The correct reference should g
be provided.
- 14. Figures 5.0-1 through 5.0-3, pages 5-9 through 5-11 These figures must depict the locations of the sampling points in the Radiological Environmental Monitoring Program (REMP). The present figures (maps) are too vague and small for this' purpose. These maps must be revised to show clearly, inter alia, the site boundary for Clinton and all monitoring locations. An enlarged, annotated map will facilitate review of the REMP locations.
- 15. Table 5.0-1, page 5-2 Technical Specification 3.12.1 and its Table 3.12-1 require that the REMP include the following samples, which do not appear in Table 5.0-1:
1.
Control sample for drinking water.
2.
I sample of each recreationally important species of fish in the vicinity of the plant discharge area.
Additionally, the locations for milk sampling are indicated "as detennined by Annual Census" in the Table 5.0-1.
The locations for these samples must also Clinton ODCM Review 3
08/22/85
s be specified in the ODCM. The ODCM may be updated annually to reflect the current Annual Census. Table 5.0-1 should be corrected accordingly.
I
- 16. (No Reference)
A new section describing the atmospheric dispersion models used to determine the relative concentration, X/Q, and relative deposition, D/Q, values must be provided. Additionally, the type of release, ground or mixed mode, continuous or periodic, used to calculate these values must be discussed.
- 17. (No Reference)
Technical Specification 3/4.12.3 requires that the applicant participate in an Interlaboratory Comparison Program. This participation must be described in the ODCM.
l Clinton ODCM Review 4
08/22/85