U-602657, Application for Amend to License NPF-62 to Revise Table 3.3.8.1-1, Loss of Power Instrumentation, by Dividing Function, Degraded Voltage - 4.16 Kv Basis, Into Two Separate Items

From kanterella
(Redirected from ML20134M307)
Jump to navigation Jump to search
Application for Amend to License NPF-62 to Revise Table 3.3.8.1-1, Loss of Power Instrumentation, by Dividing Function, Degraded Voltage - 4.16 Kv Basis, Into Two Separate Items
ML20134M307
Person / Time
Site: Clinton 
Issue date: 11/19/1996
From: Connell W
ILLINOIS POWER CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
Shared Package
ML20134M310 List:
References
L47-96(11-19)LP, U-602657, WC-352-96, NUDOCS 9611250020
Download: ML20134M307 (7)


Text

-.. _ _ _ _ _ _. _ _,

'D

M lilinois Power Company Clinton Power Station P.O. Box 678 Clinton,IL 61727 Tel 217 935-5623 Fax 217 935-4632 Wilfred Connell Vice President ILLINSIS-1 P6MR u 6o2657 L47-%(11-19 )LP l

8E.100a November 19, 1996 WC-352-96 l

Docket No. 50-461 10CFR50.90

. Document Control Desk Nuclear Regulatory Commission Washington, D.C. 20555

Subject:

Clinton Power Station Additional Revision to Proposed Amendment of Facility Operating License No. NPF-62 (LS-94-013)

Dear Madam or Sir:

By letter dated February 22,1996 (letter number U-602554), Illinois Power (IP)

Company proposed an amendment to the Clinton Power Station Technical Specifications (TS) to revise the setpoint for the 4.16 kV safety bus degraded voltage relays, and to revise or delete other Loss of Power instrumentation TS requirements, due to planned modifications to replace the degraded voltage relays at CPS. For related reasons, IP also proposed to change the minimum required diesel generator voltage specified in certain diesel generator surveillance requirements within the Technical Specifications. Upon initial review ofIP's submittal, the NRC issued a Request for Additional Information (RAI), to which IP responded via IP letter U-602613 dated July 24,1996. Following discussion with the NRC subsequent to IP's response to the RAI, IP determined that the proposed amendment should be revised. Consequently, by letter dated October 4,1996 (letter number U-602635), IP submitted a revision to the proposed amendment.

Following recent discussion with the NRC (Mssrs. Pickett and Lazcynick) during the NRC's continued review ofIP's proposed TS change (as revised by IP's October 22, 1996 letter), IP has decided to further revise the proposed amendment. The changes to the proposed amendment would revise Table 3.3.8.1-1, " Loss of Power Instrumentation,"

i by (1) dividing the Function, " Degraded Voltage - 4.16 kV basis," into two separate items,

" Degraded Voltage Reset - 4.16 kV basis" and " Degraded Voltage Dropout - 4.16 kV basis," (2) re-numbering the items in the table, and (3) revising the associated notes. The l

l proposed TS changes are discussed in detailin Attachment 2. Within Attachment 3 please l

find marked-up pages of the proposed TS changes including marked-up pages of proposed

(-

TS changes that were previously submitted. The overall proposed changes are encircled, and the proposed changes being submitted for the first time with this letter are additionally i

indicated by triple revision bars in the right hand margin.

t,l I

l' 9611250020 961119 hSi,,

DR ADOCK 0 g1

I 6

h.

1 U-602657.

Page 2 l

~

Also, please find Attachment 5 which contains marked-up pages of the TS Bases reflecting additional changes to the affected TS Bases pages. In a manner similar to the j

proposed TS changes in Attachment 3, the proposed changes for the TS Bases, includmg those previously submitted, are marked such that the changes are encircled and the proposed changes being submitted for the first time with this letter are additionally j

indicated by triple revision bars in the right hand margin. An affidavit supporting the facts l

set forth in this letter and its attachments is provided in Attachment 1.

)

It should be noted that IP Calculation 19-AN-19, "Calcs for Functional

)

Requirements for 1st & 2nd Level Undervoltage Relays at 4kV 1 A1, IB1, & IC1,"

Revision 2 Volume C was included as Attachment 2 with IP's response (IP letter U-602613) to the NRC RAL IP then revised IP Calculation 19-AN-19 and provided the

' NRC with Revision 2 Volume D as Attachment 5 to IP letter U-602635. IP has further revised the calculation to revise the nominal setpoint for the Degraded Voltage Dropout -

' Function. The changes to the calculation are discussed in detail in Attachment 2 and IP Calculation 19-AN-19 (Revision 2 Volume E) is attached (as Attachment 4) to this letter.

The changes contained in this revision ofIP's proposed amendment do not alter IP's determination that the proposed Technical Specification c;.anges meet the criteria given in 10CFR50.22(c)(9) for a categorical exclusion from the requirement for an Environmental Impact Statement. In addition, IP has also concluded that the Basis for No Significant i

Hazards Consideration, as provided in IP's Febniary 22,1996 submittal, remains unchanged.

1 i

As noted in IP's February 22,1996 submittal, the implementation schedule for the j

degraded voltage relay modifications calls for installing new relays fer the Division 2 4.16 kV safety bus during the current outage (RF-6) at CPS. Implementation of the modifications is part of corrective action committed to the NRC for Licensee Event Report (LER)94-005.

l IP is therefore requesting that the application for amendment, as supponed by this letter, continue to be reviewed on a schedule sufficient to suppon planned work actisities scheduled to begin November 27,1996.

1 i

Sincerely yours, i

Y & bwW Wilfred Connell Vice President AJP/csm Attachments

4

.a.

i e

4.

j U-602657 Page 3 cc:

NRC Clinton Licensing Project Manager NRC Resident Office, V-690 Regional Administrator, Region III, USNRC Illinois Department of Nuclear Safety Y

+

r a

b i

l I

t

s l

to U-602657 l

Wilfred Connell, being first duly sworn, deposes and says: That he is Vice President of l

Illinois Power; that this revision to the proposed amendment ofFacility Operating License No. NPF-62 (LS-94-013) has been prepared under his supervision and direction; that he l

l knows the contents thereof; and that to the best of his knowledge and belief said letter and 1

the facts contained therein are true and correct.

Date: This /f day ofNovember 1996.

1 Signed: //[/ M d & #

hilfred Connell STATE OF ILLINOIS l SS.

'N MAL

  • b ps.mses y

Notsy Nes,Suas of muk dtwM COUNTY j

{ MyCommissionEgires112457......

Subscribed and sworn to before me this /9 day ofNovember 1996.

&/4-J V

/p(Notary Publicj l

s 2;

to U-602657 LS-94-013 Page1 of3 Discussion and Description of Chan-By letter dated February 22,1996, Illinois Power (IP) submitted a proposed License Amendment to change Technical Specification (TS) 3.3.8.1, " Loss of Power -

Instrumentation," and TS 3.8.1, "AC Sources - Operating.". The changes originally-proposed in IP's February 22,1996 submittal would delete Surveillance Requirement (SR) 3.3.8.1.1 which requires performance of a channel check for the Loss of Power instrumentation, revise TS Table 3.3.8.1-1 to change the Allowable Value for the Degraded Voltage Function (items 1.c and 2.c) from "23762 V and $3832 V" to "23876

.V" and to change the required number of channels for the Division 3 degraded voltage protection (item 2.c) from 3 to 2, and revise SR 3.8.1.2, SR 3.8.1.7, SR 3.8.1.11, SR

~ 3.8.1.12, SR 3.8.1.15, SR 3.8.1.19 and SR 3.8.1.20 to change the minimum steady-state voltage identified in these SRs from "23740 V" to "23870 V."

During the NRC's review ofIP's proposed License Amendment, several questions posed by the NRC reviewer regarding the proposed amendment were discussed. The NRC issued a Request for Additional Information (RAI) to docket the identified questions, and IP responded via IP letter U-602613 dated July 24,1996. Following review ofIP's response to the RAI there was additional discussion of the proposed amendment. As a result of that additional discussion with the NRC, IP revised its submittal via IP letter U-602635 dated October 4,1996, with respect to some of the proposed changes to Technical Specification 3.3.8.1. Ongoing review of the revised submittal, including recent discussions between the NRC and IP regarding the proposed changes, has prompted IP to further revise the proposed License Amendment.

Within letter U-602635 dated October 4,1996, and consistent with IP's initial position that only the reset (pickup) function associated with the degraded voltage protection relays should be addressed in the Technical Specifications, IP had proposed to add the word " reset" to the degraded voltage Function description, for items 1.c and 2.c in Table 3.3.8.1-1, " Loss of Power Instrumentation." However, in response to a comment from the NRC reviewer, IP has determined that the dropout and reset functions associated with the degraded voltage protection relays should both (but separately) be addressed in the Technical Specifications. IP therefore proposes dividing the Function, " Degraded Voltage

- 4.16 kV basis" into two line items within TS Table 3.3.8.1-1. For each line item, the Function, the required number of channels per division, the associated surveillance requirements, and a range for the associated Allowable Value (AV) would be specified under the respective headings of Table 3.3.8-1. To incorporate these changes, IP proposes to revise Table 3.3.8.1-1 such that the addition cf the Function, " Degraded Voltage Reset - 4.16 kV basis" would replace item 1.c. The present item 1.c Function,

" Degraded Voltage - 4.16 kV basis" would replace item 1.d and would be revised to read

" Degraded Voltage Dropout - 4.16 kV basis." The present item 1.d Function, " Degraded Voltage - Time Delay" would be changed to be new item 1.e. Similarly, IP proposes to revise Table 3.3.8.1-1 such that the addition of the Function, " Degraded Voltage Reset -

i

=--

O.

p 1

i l

l to U-602657 l

[

LS-94-013 j

Page 2 of 3

~

4.

4 l

4.16 kV basis" would replace item 2.c. The present item 2.c Function, " Degraded Voltage Dropout - 4.16 kV basis" would replace item 2.d and would be revised to read " Degraded l

l Voltage Dropout - 4.16 kV basis." The present item 2.d Function, " Degraded Voltage -

[

i Time Delay" would be changed to be new item 2.e.

l 4

[

The additional revision to IP's proposed TS changes also includes adding a note applicable I

to the new Degraded Voltage Reset Function as well as revising and re-numbering the r

i notes. The purpose of note "(a)" is to provide an explanation that the Degraded Voltage i

l Reset Functions specified for items 1.c and 2.c are not applicable until after the release for l

operations (RFO) of the corresponding plant modification. Similarly, the purpose of note 4

"(b)" is to provide explanation that the values specified for the Degraded Voltage Dropout i

j are applicable only after RFO of the corresponding plant modification. Prior to RFO, note j

(b) explains that current values are to be used. Lastly, note "(c)" has a similar purpose to l

provide explanation that the number of required channels specified for the Division 3 i

Degraded Voltage Reset is applicable after RFO of the corresponding plant modification.'

Note (c) explains that, prior to RFO, the present number is to be used (for the current relay configuration corresponding to the " Degraded Voltage - 4.16 kV" Function on Table 3.3.8.1-1).

1 p

Because of the additional TS changes, additional TS Bases changes are being proposed.

IP_ has revised the proposed changes to the TS Bases to discuss the addition of the new Function item to Table 3.3.8.1-1 and to reflect revision of other items and item numbers 1

within Table 3.3.8.1-1; Additional changes are proposed to discuss both the Degraded

- Voltage Reset and the Degraded Voltage Dropout Functions corresponding to Table 3.3.8.1-1 items 1.c,1.d,2.c, and 2.d.

Included as Attachment 4 to this submittal is IP Calculation 19-AN-19, Revision 2, Volume E. As noted within the cover letter, IP had previously transmitted IP Calculation 19-AN-19 Revision 2,> Volume C when IP responded to the NRC Request for Additional Information (RAI) via IP letter U-602613 dated July 24,1996. After further discussion with the NRC, IP subsequently transmitted Revision 2, Volume D of the calculation in IP letter U-602635 dated October 4,1996. As further explained below, Revision 2,

- Volume E reflects changes made to the calculations to support the Allowable Values specified for the Degraded Voltage Dropout function. A complete copy of Revision 2, j

Volume E of the calculation (and its attachments) is provided in Attachment 4. This revision supersedes all previously provided revisions to the calculation (and its attachments).

- IP initiated the most recent revision ofIP Calculation 19-AN-19 (Revision 2, Volume E) to address the NRC reviewer's comment that the separation (voltage difference) from the drop-out calibration lower limit to the drop-out minimum AV (as originally proposed) would have been much smaller than the separation from the reset calibration lower limit to the reset minimum AV. The reviewer considered this to be an issue wherein it may be

e

o to U-602657 LS-94-013 Page 3 of3 conjectured that an instrument bias or degradation could cause the setpoint to change.

identically for the reset and the drop-out.- This could result in the reset setpoint being less than the calibration lower limit but within the reset AV lower limit, while the drop-out could be at a value less than the calibration lower limit and less than the drop-out AV lower limit. Therefore, the dropout setpoint has been revised to provide similar separation for the dropout and the reset between their respective calibration lower limits and AV-lower limits.

l 1

l l

1 l

l

l to U-602657, LS-94-013 Page 2 of 50 l

CALCULATION COVER SHEET.

SHEET 1 OF 1i TITLE / DESCRIPTION:

DElrT/DIV CALCULATION NO.

i ElEPED 19 AN 19 CALCS FOR FUNCTIONAL REQUIREMENTS FOR 1st & 2nd LEVEL 1

UNDERVOLTAGE RELAYS AT 4kV 1 A1,1B1, & 101 QUALITY SYSTEM CODE TOPIC BLDG /ELEV/ AREA

=

l RELATED (or NA)

(or NA) i (Q or N)

.I Q

AP E90 NIA i

APPROVALS - NAME/ SIGNATURE /DATE 4

i CORP PREPARING REVISION VOLUME READY FOR INCORPORATION:

PREPARED BY A. R. Ha----

WIS REV.

YES

/

NO N/A mwr IP 2

E Id 4# f4 d

/ /

oAn somwRs CONFIRMATION REQUIRED M CROFCHE ATTACHE 0 5

YES NO PAGE NO(s)

YES

/

NO j

CHECKED BY mwr VOL INCORP ASSGNMNT.

Engmeenne DAM SmMAwRs MOD.

AP 28 ECN CR 4

l A u Gk., des COMMENTS:

MWR REVIEWED BY Y

l THIS VOLUME IS TO SUPPORT THE TECH SPEC CHANGE. It adds mergin to the pickup setting i

lL.aav 3

0 ** * ""

4 CORP PREPARING REVISION VOLUME READV FOR INCORPORATION:

)

PREPARED BY

'DUS REV.

YES NO N/A 9

PRINT i

/ /

4 oAn CONFIRMATION REQUIRED MICROFICHE ATTACHED:

YES U NO PAGE NO(s)

YES NO CHECKED BY f

mwr VOL INCORP. ASSGNMNT.

dAu#

MOD.

ECN CR COMMENTS MWR REVIEWED BY 4

MM n

DATs smNATURE O

CORP PREPARING REVISION VOLUME READY POR INCORPORA'nON:

i PREPARED BY WIS REY.

YES NO N/A j

mwr j

/ /

j DATs somwRe CONFIRMATION REQUIRED ~

MICROFICHE ATTACHED:

YES NO PAGE NO(s) l YES NO CHECKED BY mwr VOL INCORP. ASSGNMNT.

i

/ /

DATE SomwRe MOD.

ECN CR l

COMMENTS:

MWR REVIEWED BY 1

PRINT

{

/ /

DATE

$80 NATURE l

i i

Q(PDMUlLWD k1D mm i

i

. to U-602657, LS-94-013 Page 3 of 50 REVISION HISTORY Page 2 oI/1 l

Dept./Div. E1EPED Calc. # 1HAN 19 j

1 Revision 2 Volume (if applicable)

E Objective: Iba purpasa of this volume _Calculatian in in addinarginhatwaan the pekup nattingandjinpickuplowethwahla Emit _

)

i 2

Reason: This volume is required in incorporata NRC TFCH SPFC reviewer comments and adds more margin hetwaan the relay allowahla_ drop _nu.t_

limit and the drapetja'aala' l

l List of Affected Pages: Paaa+'5 thranah R This wahuna --=%-% D A

Revision Volume (if applicable)

Objective:

Reason:

4 i

t i

i List of Affected Pages:

j i

Revision Volume (if applicable) j Objective:

1 4

Reason-List of Affected Pages:

NF-303 (10/95)

CALCULATION 19-AN-19 REV. 2 VOL. E Page 4 of 50 PAGE J of /i

. iDeptJDiv. E/EPED)

=

TABLE OF CONTENTS PAGE i

COVER SHEET 1

. REVISION HISTORY 2

TABLE OF CONTENTS 3

PURPOSE 4

DISCUSSION 4

INPUTS 5

ASSUMPTIONS 8

METHODOLOGY 8

EVALUATION 15 3

REFERENCE LIST 19 l

ATTACHMENTS 8

Probability table 1page ABB instruction IB 7.4.1.7-7 issue D 12 pages ABB Descriptive Bulletin 41-233S September 2 pages 1990 l

ABB Type Test Certificate Number RC-6004 6 pages Revision 0 dated 2/10/89.

i HP 3458A Multimeter Data Sheet dated May 7 pages 1991 & Test and Measurement Catalog 1994.

i Copies ofselected pages Westinghouse Electric Corporation Product 2 pages j

bulletin 44-215 D WE A dated July 15,1976 for type PCO-60 Voltage transformers 4

VOL_E_1.MCD

. - - - ~. _ -

-. -.. -. ~. -

1 to U-602657, LS-94-013

CALCULATION 19-AN-19 REV. 2 VOL. E Page 5 of 50 PAGE f of /1

,a

[ Dept /Div. E/EPEDI PURPOSE The purpose of this Calculation is i

To evaluate the use of an' ABB 27N undervoltage relay in the Second Level Under-Voltage (also called degraded voltage) protection scheme.

Determine the relay trip (drop-out) and reset (pick-up) bands based on the loop accuracy methods described in CI-01.00 Instrument Set-point Calculation i

Methodology (Reference 10).

The analytical limits (AL) for the second level under-voltage relay. pick-up are as follows:

1

1. The maximum pick-up voltage is equal to the minimum 4KV ESF bus i

voltage under steady-state LOCA loading with the off-site voltage at the I

minimum expected value.

2. The minimum pick-up voltage is equal to the minimum 4KV ESF bus i

voltage required to start and run the LOCA required equipment.

The allowable value (AV) will also be established by this volume and this i

number will be used in the Tech Spec revision which is being prepared to support the new relay settings.

DISCUSSION i

The second level under voltage relay scheme has a two-fold function. It 8

i must ensure that there is adequate voltage following the LOCA block start j

initiation for the ESF required equipment to start and run. It must also prevent the i

ESF buses from transferring to the on-site source'if there is adequate voltage from the off-site source to operate the ESF equipment. Therefore the second level a

under voltage relay pick-up voltage (accounting for the various instrumentation l

errors) must fall between these values. In addition, we want to prevent spurious transferring of the ESF buses to the onsite source and allow for minor changes to j

the off-site grid with out impacting the degraded voltage relay aeninaa. We have j

therefore based on engineering judgment chosen to limit the maximum relay pick-i up to 0.75% below the 4160 volt bus 1A1 voltage found in Calculation 19-AQ-02 g

Rev. 3 =*achment 10.2. This setting will pmvide a degree of margin below the i

minimum expected 4KV Bus voltage under steady state LOCA conditions with the 345 Ky switch-yard at the uinimum expected value. Calculation 19-AQ-02 l

Rev. 3 Attachment 10.2 lists the steady state minimum voltage at the Bus 1 A1 as l

3938 volts. 100%-0.75% of 3938 equals 3908 volts. The minimum reset point will be the minimrm voltage at the 4KV bus which will ensure that all the ESF equipment required for LOCA will start and run. The minimum voltage required by the ESF equipment will be taken from 19-AQ-02 Rev. 3 volume P Attachment i

8.1 (3870 volts). The nominal second level under-voltage relay pick-up point has j

therefore been chosen to be mid way between the maximum and minimum reset-j points or 3889. We will call this nominal value NTSP. This calculation will i

assure that there is adequate margin for NTSP between the maximum and l

minimum allowable values when the total relay loop error is considered.

1

}

VOL E 1.MCD to U-602657 LS-)4-013 CALCULATION 19-AN-19 REV. 2 VOL. E Page 6 of 50 PAGE o of I$

[DepUDiv. E/EPED]

1 INPUTS II.

The relays utilized in the Second Level Under-Voltage scheme will be ABB type 27N catalog number 41IT6375-HF (or 410T6375-HF which has the same characteristics). The relay pickup range is from 70 to 120 volts, the dropout range is 70% to 99.5%, the pickup time delay is instantaneous. The drop out time delay will be set at minimum (= 0.1 sec)

The relay requires a 125 volt nominal DC source to operate. The relay will include the harmonic distortion filter. The published relay tolerances from Reference 3,4 and 5 EXPRESSED AS A PERCENT OF SE'ITING are as follows:

a)

Pickup and dropout setting repeatability with respect to temperature with a constant control voltage and the relay operating in an environment where the ambient temperature could vary A

between +10 to +40*C is *0.4%. We will call this 28 value ATE

^ " 'I b)

Pickup and dropout setting repeatability at a constant temperature and constant control voltage is i 0.1%. We will call this 26 value VA.

c)

Pickup and dropout setting, repeatability over " allowable" de control power range is i 0.1%. The allowable de control power range for a 125 volt nominal relay is 100 to 140 V DC. The Tech Spec requires that when AC power is available to supply the 1

battery charger the DC buses must operate between 121 and 139 yot s volts. The published DC supply error is considered linear over the operating range per Reference 10, Engineering standard CI 01.00.

Therefore, the published error of*0.1% can be divided by 40 volt allowable range. In addition, data in the ABB type test Certificate PSE :=.045 %

i Reference 5 shows that this is conservative. The variation then equals *0.0025%/ volt.

We willcallthis 25 error PSE and consider it to be *0.045% for our operating range.

.' d)

The radiation and humidity effects are considered negligible i

because the relays are not subjected to an environment with humidity or radiation above normal atmospheric conditions, e)

The 27N relay has been subjected to 6g ZPA either axis biaxial broad band multifrequency vibration without malfunction or

[

damage per ANSI /IEE C37.98 (reference 4). Therefore there is no V.L E seismic impact to the relay accuracy.

f)

ABB tests indicate that there is no RFI interference effect associated with the relay. Therefore it is not considered a factor in this calculation (Reference 5).

VOL_,E_.1.MCD

- - ~ ~ -

Attachmant 4 to U-602657, LS-94-013 CALCULATION 19-AN-19 REV. 2 VOL E Page 7 of 50 PAGE I of Ii

[DeptJDiv. E/EPEDI 4

I2.

The relay calibration setup will consist of a low noise variable AC power supply, the ABB 27N relay and a Hewlett Packard Model HP3458A Digital Multimeter.

L

~

e

\\

0 0 7

e i

Varable AC HP3458A Power Supply ABB 27 N Relay Multimeter Relay test set-up figure 1 The HP 3458A Specification and accuracy from Reference 6 are as follows:

a)

Minimum resolution at 100 volt range is 10 micro volts b)

The Accuracy coefficient in %/de' gree C is 0.001% ofreading plus 0.0001% ofrange (with the meter set on the 100V range). We will ~

callthis 35 value CIATE c)

The AC accuracy with the meter set on the 100 V range is (a 36 value) 0.02% ofreading plus 0.004% ofrange and will be called CIVA.

t d)

The meter is calibrated using a 10 voh DC test cell traceable to US NIST with an added error of 2 ppm or 0.0002%. We will call this 3 S value ClSTD.

i l

k i

VOL_E_1.MCD

..~_

CM.CULATION 19-AN 19 REV. 2 VOL E Page 8 of 50 PAGE

~7 of Ii

[DeptJDiv. E/EPED]

, ~.

13 The detection loop consists of the 4KV bus which we wish to measure, a potential transformer (PT) to convert 4KV to 120 volts and the ABB 27N relay.

The pts for DIV. I & II are Westinghouse PC-60 and, for DIV. III, GE

, type JVM-3. Both PT models have a ratio of 4200 - 120 volts and are class IE. They conform to ANSI C57.13-1%8 metering accuracy class for.03 i

class standard burdens W, X, M, & Y. The pts were purchased to l

' Westinghouse drawing EN005, and GE data sheet 317A6131, and S&L d

form 1815-L (Reference 1). The PT burden was established using E02-l 1 AP12 SH 11 R/W, E02-1 AP99 SH 36 R/D, E02-1 AP99 SH 38 R/U i

E02-1AP12 SH 13 R/V, E02-1 AP12 SH 15 R/f, and E02-1HP99 SH 107 i

R/L (Reference 7), and the load data from the vendor manuals (Reference l

1). The PT burden consists of a CV2 relay, the 27N relay, a voltage j

j transducer, a lamp and a voltmeter (Note: the EMTs shown on E02-1 AP12 SH 13 R/V are being disconnected from the pts by mods AP-l~

027,28, & 29). The total burden on the PT is 7.5VA with a possible l

change in burden (caused by switching the voltmeter between phases) of 1 4

1 VA. From.the performance curve found in reference 9, we can see that for a change in burden of 12.5 VA the tums ratio correction changes 0.1%.

f Therefore, if the actual change is'1 VA the change in PT tums ratio (EPT) would be.008% ofrating. The curve also shows that the PT ratio correction factor should be.997.

EFT :=.008%

.I4.

Two relays will be installed in DIV. I & II (one between phase AB and le

)

NE one between phase BC). The relay trip functions are wired in series so i

' that both relays must trip in order for the protective action to be initiated.

Only one relay must reset for the timer to reset, preventing transferring of load to the diesel. Reference E02-1 AP12 sheets 11 & 13 (Reference 7).

15.

Two relays will replace the present single three phase relay in Div. III.

The new single phase relays will monitor phase AB and. BC. The trip contacts are wired in series. All the elements must sense a degraded voltage for the protective function to be iwtiated. Only one relay must reset for the timer to reset, preventing transferring ofload to the diesel.

Reference E02-1HP99-sheets 107,103, & 102A (Reference 8).

VOL_E_1.MCD

.. ~ _....

Attachm:nt 4 to U-602657, LS94-013 CALCULATION 19-AN-19 REV. 2 VOL. E Page 9 of 50 PAGE F of'/f (Dept 3Div. E/EPED] -

i ASSUMPTIONS i

A1.

The accuracy's published by the instrument manufactures are considered as a 95% probability value, equal to two standard deviations (20). This assumption does not require verification based on engineering judgment and direction given in Engineering Standard CI 01.00 Instrument Set-point Calculation Methodology i

(Reference 10).

~

j 1

A2 All accuracy data is considered to be a normal distribution.

A3 The ABB 27N relay drift for 6 months is assumed to be equal to relay -

accuracy of.1%. For an 18 month surveillance period the drift err'or (VD) is equalto the following.

l Ifl81 2

VD := l7 l 0.1 VD = 0.1732

% Error it 4 This assumption does not require verification based on i

engineering judgment and direction given in Engineering Standard CI 01.00 Instrument Set-point Calculation Methodology (Reference 10) l

, METHODOLOGY M.I. The accuracy for the ABB27N relay (A27N) will be calculated by -

the square root of the sum of the squares method.

M.2 The nominal relay pick-up point will be calculated by taking the nominal relay pick-up voltage at the 4KV bus and reflecting it to the low voltage side of the PT VOL_E_1.MCD

Attachmtnt 4 to U-602657, LS-4-013 l

  • - ' CALCULATION 19-AN-19 REV. 2 VOL. E Page 10 of 50 PAGE of /f

[ Dept /Div. E/EPED) 1 i

l nrimarv ratin enrracelan inwalda matana mitmas sano as; -

n on7 -

111 dann TABLE 1 I

M3 The loop calibration error will be calculated as follows:

a) First the calibration instrument error Cl must be determined a.1) The HP3485A accuracy error CIVA from the inputs above at 111.44V can be expressed as

' Va L G 111.44.0002 + 100.00004 ClVA :=

-100 CIVA =0.0236

% error

,g g a.2) The temperature error contribution Cl ATE can be expressed as follows, noting that the Calibration lab temperature is kept at 72* F

  • 2'F or within 1.l*C. The temperature of the test j

instrument can be read directly by the HP3485A and the requirement that the test instrument be calibrated and used at 72' F

  • 2*F will be controlled by the relay calibration procedure. The j

input data for the temperature error would then be expressed as yLE l

Cl AE := 1.1-100 Cl AE = 0.0012

% error 3g a.3) 'Ihe calitration instrument error Cl then becomes Cl :=]CIVA + CI ATE 2

2 C1 = 0.0236

% error VOL_E_1.MCD

- ~ ~.

Attachmsnt 4 to U-602657, LS-94-013 CALCULATION 19-AN-19 REV. 2 VOL. E Page 11 of 50 PAGE /0 of'/i

[ Dept /Div. E/EPED]

b) The next step is the calibration of the relay using the set-up shown above in figure 1. The calibration loop error (CL) is determined as follows:

1 b.1) Based on conversation with the Waterford plants, and tests at 4

Clinton P.S., the ABB 27N relay can be set to a resolution of.005 volts AC. This will be considered the calibration resolution for the calibration. Therefore the resolution error R will be determined as follows:

1 R :=,gg,5

.00 4

-100 R = 0.0045

% error 44 e

4 b.2) The new ABB 27N relay calibration procedure will allow for j

an acceptance band of *0.04 volts. Therefore the calibration as-left tolerance error (ALT) will be determined as follows:

}

.04

  • 111,44 s.

4 ALT = 0.0359

% error i

l b.3) The calibration instrument error Cl is taken from a) above b.4) the calibration loop error then becomes vel E 1

fALTt

  • fRt' fCit 2 ct -0.02ss

% error cL:=2. \\ 3 ] + (Tl * (Tl 5

This is considered to be 2 a 4

i i

J VOL_E 1.MCD

-l

_- to U-602657, LS-94-013 -

CALCULATION 19-AN-19 REV. 2 VOL. E Page 12 of 50 PAGE

//

of. / I

. [ Dept /Div. E/EPED]

3 j

I c) The next step is to determine the channelinstrument accuracy (AI). This will take into consideration the various errors associated with operating temperature, DC voltage etc. From the inputs section above the errors are restated ar..I the instrument accuracy j

determined:

i a

i 2

2 l

/VA\\

/ATEi' fPSEt' fVD\\

Al := 2-AI -0.4495

% error 7;+

2 2

l+ T) j This is considered to be 2 e d) The loop accuracy AL can now be determined. The inputs are as follows:

d.1) From b) above the calibration loop error ct -0.02:s wta d.2) From c) above the channel instrument error AI = 0.4495 d.3) From input 13 above the PT error or EPT = 0.008 (CL)' fAI,2y- + y +1 fEPT '

~

]

AL :=

AL -0.2252 2

This is considered to be 1 o M. 4 Illinois Power uses the GE methodology (Engineering Standard CI 01.00 -

Reference # 10) for deterrnining critical set points based on instrument errors.

This methodology is statistically based. 'Ihe desired probability for relay actuation

-is 95% (per Reg. Guide 1.105 -Reference # 11). In order to determine the 95%

probabihty ofeither 2 relays actuating together or 1 of 2 relays resetting, the table Attachment I was set up. 'lhe table was established by plotting the probability distribution that one relay would actuate assuming a normal distribution curve (see Assumption # A2). The equation for that plot was:

1 f(x) = Jii *e2 i

V VOL_E_1.MCD

-~

CALCULATION 19-AN-19 REV. 2 VOL. E Page 13 of 50 PAGE /1 of / i

' [DeptJDiv. E/EPED]

4 The probability that two will actuate together was determined by muhiplying the j

probability ofeach of them together and plotting that curve accordingly. In this case that meant squaring the probability ofone relay (since the probability for both i

relays is the same). The point on the Table in attachment I which equaled.95 was then found. This came out to be 1.96.-

5 To determine the same a multiplier for when only one of the two relays needed to change state, the probability that the relays would fail to actuate was considered.

To do this, I minus the probability squared was tabulated (attachment 1). From this table the value for 95% confidence was found. This corresponds to a value of

.76.

2 4

j Therefore, the 1.96 6 is to be used for a 95% probability that two relays will actuate together and 0.76 8 that one of the two will reset.

i M.4a Two 27N relay contacts (in series) are required to initiate the time delay relay and the subsequent protective action. We have, therefore, I

determined that for a 1.% 6 deviation about the set point the relay loop

)

will activate with 95% confidence level. We will call this Accuracy drop

. out (Ado). It can be expressed as:

Ado := 1.96 AL Ado = 0.4415

% of setting '

M.4b Only one of the two 27N relay contacts (in series) are required to reset the time delay relay and subsequently prevent the buses from transferring to the diesels. We have, therefore, determined that for a 0.76 deviation about the reset point the relay loop will activate with 95% confidence level.

l VOL_E_1.MCD

CALCULATION 19-AN-19 REV. 2 VOL. E kADh8I h Ii

[DeptJDiv. E/EPED]

Page 14 of 50 i

5 j

We will call this " Accuracy pick-up" (Apu). It can be' expressed 4

Apu := 0.76 AL Apu = 0.1712

% of setting 1

1 i

MS - The loop Allowable will provide the limits on the as found which will j

provide confidence that the relay would have responded within the proper range disregarding the drift error. This error will be calculated as foL E follows:

a).The calibration loop error will be the same as above

' f ALTj + (fR1Tl+(T) 2 2

2 fCl\\

cL = 0.02ss

% ermr CL := 2-3j 5(

l This is considered to be 2 e i

b) The next step is b determine the channel instrument Allowable Accuracy (AV) without the drift error. This will tr.ke into Yol E i

consideration the various errors associated with operating temperature, DC voltage etc. From the inputs section above the j

errors are restated and the instrument accuracy determined:

i f VA1 2 2

2

/A'IE1 fPSE1 AV.:= 2-l

+

'*j i

AV = 0.4148

% error 2

2 j

g j

l This is considered to be 2 a 4

c) The Loop Allowable Accuracy (ALV) can now be detennined, as above. The inputs are as follows:

vu a c.1) From b) above the calibration loop error ct = 0.0288 e

l c.2) From c) above the channel instrument error AV = 0.4148

)

c.3) From Input 13 above the PT error or EFT = 0.008 i

'i VOL_E_1.MCD J

-...~.

Attachmant 4 to U-602657, LS-94-013 CALCULATION 19-AN-19 REV. 2 VOL E Page 15 of 50 PAGE /4 of / f

[ Dept 3Div. E/EPED]

e i

AVt EFT 1 CL 2 2

2 ALV :=

+

+

i ALV = 0.2079 2

j This is considered to be 1 a j

j

{

- M. 6 Using the same methodology as above (Engineering Standard CI 01.00 -

j Reference # 10) for determining critical set points based on instrument errors, the probability that at least one of the relays will reset is 0.76 6 e

l l

We have, therefore, determined that for a 0.76 6 deviation about the reset point the relay loop will activrte with 95% confidence level We will call j

the Allowable Value pick-up (AVpu). It can be expressed as i

2 i

j AVpu := 0.76 ALV AVpu = 0.158

% of setting

}

~

M.7 _ Using the same methodology as above (Engineering Standard CI 01.00 -

i Reference # 10) for determining critical set points based on instrument errors, we can also calculate the allowable for relay drop-out. The probability that two of the relays will drop-out (trip) is 1.96 6.

Ae We have, therefore, determined that for a 1.96 6 deviation about the trip point the relay loop will activate with 95% confidence level. We will call the Allowable Value drop-out (AVdo). It can be expressed as AVdo := 1.96 ALV AVdo = 0.4075

% ofsetting i

i 4

VOL_E_1.MCD i

l

CALCULATION 19-AN-19 REV. 2 VOL. E Pege 16 of 50 PAGE /I of If

[ Dept /Div. E/EPED)

EVALUATION The results can now be represented by a graph sinular to the following:

i RELAY ERRORRECION minimum off-site minus.75% =3908 -

~

VOLTAG E 4

PUUV 2

.3901 3809V-rel ck-up setting PULV RELAY ERROR RECION 3870 volts 95% confidence

- probabillty The PICK-UP SETTING ACCEPTABLE In other words we will show that by setting the degraded voltage relay pick-up at 3889 the total loop error will not cause (with a 95%

probability) the relay to pick up below 3870 nor above the minimum off-site vohage as seen by the 4KV ESF buses. This can be represented by the

' following expressions:

We will call the upper limit of the permissible relay pick-up settings PUU and the lower limit PUL. The calculation of these values is PUU := 3908 - 3908-PUU = 3901.3104 Volts at the 4 KV level 1 0 = H l.8014 Voh at 6e N bel PUU120 := (.

5)

PUL := 3870 + 3870-PUL = 3876.6245 Volts at the 4 KV level U

PUL120 := (. 35)

PUL<3889<PUU 3877<3889<3901 VOL E_,1.MCD l

~_.- _._..

Attachmsnt 4 to U-602657' E R of_/7 LS-94-013 CALCULATION 19-AN-19 REV. 2 VOL. E Page 17 of 50 PAG i

[ Dept /Div. E/EPED) i 1

1 THE AS-FOUND ALLOWABLE (TECH. SPEC. ALLOWABLE)

We will next evaluate the upper (PUUV) and lower limit (PULV) of the I

j as-found allowable (Tech. Spec Allowable) relay pick-up settings. This is of concern when recording the as-found relay and confirms that it would l

i vet c have performed its function when considering all the errors except 4

i additional drift. The calculation of these values is 1

PULV := 3870 + 3870 1 PULV = 3876.1153 Volts at the 4 KV level PULV

}

PULV 120 := (.997 35)

PULV 120 = 111.0794 Volts at the 120V level A,V P

m := 3908 - 3908

,0 PUUV = 3901.8247 Volts at the 4 KV level PUUV N120 := (.997 35)

PUUV120 = 111.8162 Volts at the 120V level i

i THE DROP-OUT SETTING ACCEPTABLE j.

The lower limit of the Degraded voltage relay drop-out is dependent on the j

minimum voltage required to keep ESF equipment running. From

]

calculation 19-AQ-02 we can show that the ESF equipment will run at 3832 volts. We will call the relay drop-out limit DOL. There is no upper

]

limit for the drop-out except the physical restraints of the relay which will l

allow it to pick up in the range described above. The drop out can be r

{

adjusted between 70% and 99.5 % of the pick-up. We want to provide the j

maximum voltage to our equipment and still keep the relay pick-up as j

described above. Therefore we have chosen to set the drop-out at 99.3%

I of the pick-up or 3862 volts.

VoL E i

i i

I i

1 VOL_E_1.MCD

4-013 I

Attachmsnt 4 to U-602657, LS-f7 of /1 CALCULATION 19-AN-19 REV. 2 VOL E Page 18 of 50 PAGE IDept/Div. E/EPED]

DOL := 3832 + 3832-DOL = 3848.9166 Volts at the 4'KV level DOL 120 :=

DOL 120 = 110.2999 Volts at the 120V level g

The Allowable drop-out value (DOLV) then is calculated by same method used for the pick-up above.

^

DOLV := 3832 + 3832-DOLV = 3847.6161 Volts at the 4 KV level DOLV120 i DOLV120 = 110.2627 Volts at the 120V level 3

The drop-out allowable (3847.62) limit and the setting limit (3848.92) are both below the drop-out setting of 3862.

gg The critical requirement, from a plant safety standpoint, is that all the equipment required to support the LOCA block start receive sufBeient voltage to start and run. Therefore the critical degraded voltage relay parameter is that the relay must reset at or above 3870 volts. This'is equivalent to the relay minimum reset accounting for the appropriate relay errors.

The following table listing settings and analytical limits will be used as inputs for a Tech. Spec. change and the procedure for calibration of the relays. The vohage at the 120 vok level reflects the required voltage at the 4KV bus as scaled (transformed) by the PotentialTransformer. The ratio of the 4KV voltage to the 120 vok levelis 34.895:1. The Degraded Vohage relay senses and is calibrated for voltage at the 120 Voh level.

'Ibe calibration limits are established by drawing E02-1 AP04 sheet 001 and in the CPS calibration procedure. 'Ihey are used as inputs to this calculation. The calibration limits are *0.04 vohs. They are taken from section M3b.2 and are added and subtracted from the relay set-point at the 120 voh level. The 4 KV level value is equal to the 120 vok value times the PT ratio (35*0.997).

VOL_E_1.MCD l

]

CALCULATION 19-AN-19 REV. 2 VOL E Page 19 of 50 PAGE of /9

[ Dept /Div. E/EPED) i summery oflimits PICK-UP j

4kylevel 120v level nominal setpoint 3889 111.45 Min PICK-UP Max PICK-UP 4kv level 120v level 4ky level 120v level calibration limits 3887.60 111.41 3890.40 111.49 techspec limits 3876.12 111.08 3901.81 111.82 l

summery oflimits DROP-OUT 4kylevel 120v level i

nominal setpoint lHi2-110.67 Min DROP-OUT Max DROP-OUT 4kVlevel 120v level 4ky level 120v level i

calibration limits 3860.38 110.63 3863.17 110.71 allowable 3847.62 110.26

~

Vol E The second level undervoltage relay minimum pick-up and minimum drop-out voltages, at 4KV buses, which will be used by other calculations are 3870 volts l

and 3832 respectively.

r VOL E 1.MCD

CALCULATION 19-AN-19 REV. 2 VOL E Page 20 of 50 PAGE

/ I of /9-

[ Dept /Div. E/EPED]

Reference 1 Westinghouse drawing EN005-6A REV 5, and GE data sheet 317A6131 REV. 2. The PT were all purchased per S&L form 1815-L. These documents are found in the purchase specifications and vendor manuals for K-2801 and K-2968.

2 Reference 2 E02-1 AP12 sheets 11 R/W& 13 R/V.

1 Reference 3 ABB instruction IB 7.4.1.7-7 issue D l

Reference 4 ABB Descriptive Bulletin 41-233S September.1990 2

Reference 5 ABB Type Test Certificate Number RC-6004 Revision 0 dated 2/10/89.

4 i

i Reference 6 HP 3458A Multimeter Data Sheet dated May 1991 i'

Reference 7 E02-1 AP12 SH 11 R/W, E02-1 AP99 SH 36 R/D, E02-1 AP99 SH 38 R/U E02-1 AP12 SH 13 R/V, E02-1 AP12 SH 15 R/f, and 4

E02-1HP99 SH 107 R/L.

Reference 8 E02-lHP99-SH 107R/L,103 R/H, & 102A R/H.

l Reference 9 Westinghouse Electric Corporation Product bulletin 44-215 D WE i

A dated July 15,1976 for type PCO-60 Voltage transformers.

i Reference 10 Engineering Standard CI 01.00 Instrument Setpoint Calculation 1

Methodology REV 0 l

Reference 11 Reg. Guide 1.105 INSTRUMENT SETPOINTS REV.1.

i I

4 i

a s

VOL_E_.1.MCD l

j. ~. __ _ _ _ _ _ ____

- to U-602657, LS-94-013' Page 21 of 50 M'*** I - CAILULNIlON 19-AN-19 REV2 VOLUMB E

' DEFT /DIV. B/BPED 1

PROS THAT PRN THAT PROB THAT-

[/-

82D DEVS IIORMAL 1 RETAY 2 RBIAYS 1 OF 2 RLYS FROM CURVE GEIS STATE G83 STATE CHG STA7E jl SETPT f(x)

F(x)

F(x) *2 1-F (x) *2

}

-4 0.00013 3.14Es05 9.8904E-10 1

l

-3.8 0.00029 7.195-05 5.1678E-09 0.99999999*-

}

-3.6 0.00061 0.000158 2.5025E-08 0.99999997

-3.4 0.00123 0.000335 1.1235E-07 0.999'99989

.j

-3.2 0.00238 0.000684 4.6781E-07 0.99939953 j'

-3 0.00443 0.001344 1.8073E-06 0.99999819 4

-2.8 0.00792 0.002546 6.4817E-06 0.99999352 l

-2.6 0.013:i2 0.004646 2.*159E-05 0.99997841.

-2.4 0.02239 0.008175 6.6833E-05 0.99993317 j

-2.2 0.03547 0.013871 0.0001924 0.9998076 j

-2 0.05399 0.022705 0.00051552 0.99948448 j

j

-1.98 0.05618 0.0238 0.00056644 0.99943356

-1.96 0.05444 0.024946 0.00062231 0.99937769 I

-1.94 0.06077 0.*026138 0.0006832 0.9993168 I

-1.8 0.07895 0.035871 0.00128674 0.99871326 l

-1.6 0.11092 0.05,4725 0.00299486 0.99700514

)

-1.4 0.14973 0.080669 0.00650753 0.99349247 I

-1.2 0.19419 0.114973 0.01321868 0.98678132

-1 0.24197 0.158554 0.02513949 0.97486051

-0.8 0.28969 0.211759 0.04484178 0.95515822 i

l 0.76 l0.29887 0.223535 0.04996784 10.95003216 l l

-0.74 0.30339 0.229558 0i05269709' O.94730291 l

-0.6 0.33322 0.27417 0.07516905 0.92483095 f

-0.4 0.36827 0.344517 0.11869185 0.88130815 l

-0.2 0.39104 0.420708 0.17699495 0.82300505 l

-1E-10 0.39894 0.5

'O.25 0.75 0.2 0.39104 0 579292 0.3355796 0.6644204 i

0'. 4 0.36827 0.655483 0.42965819 0.57034181 j

0.6 0.33322 0.72583 0.52682956 0.47317044 0.74 0.30339 0.770442 0.59358017 0.40641983 l

0.76 0.29887 0.776465 0.6028981 0.3971019 l

0.8 0.28969 0.788241 0.62132424 0.37867576 l

1 0.24197 0.841446 0.70803074 0.29196926 l

1.2 0.19419 0.885027 0.78337362 0.21672638 1.4 0.14973 0.919331' O.84516895 0.15483105 1.6 0.11092 0.945275 0.89354419 0.10645581 l

1.8 0.07895 0.964129 0.92954452 0.07045548 1.94 0.06077 0.973862 0.94840715 0.65159285 1

l 1.96 10.05844 0.975054 1 0.95073005 1 0.04926995 h

1.98 O.05618 0.9762 0.95296634 0.04703366 2

0.05399 0.977295 0.955'10522 0.04489478 1

i 2.2 0.03547 0.986129 0.97245051 0.02754949 l

2.4 0.02239 0.991825 0.98371651 0.01628349 1

2.6 0.01358 0.995354 0.99072861 0.00927139 2.8 0.00792 0.997454

'O.99491466 0.00508534 3

0.00443 0.998656 0.99731307 0.00268693 4

3.2 0.00238 0.999316 0.99863254 0.00136746

)

3.4 0.00123 0.999665 0.99932974 0.00067026 3.6 0.00061 0.999842 0.99968364 0.00031636 3.8 0.00029 0.999928 0.99985623 0.00014377 4'

O.00013 0.999969 0.9999371 6.2897E-05 i

a l

ProbiHty table i.

rm-w-t e-

. _.. to U-602657, LS-94-013 j -

Page 22 of 50 j

l Rogsp_p fle.omi-

+44-70 9 -01of

!~

N EEEE AL ER ER IB 7.4.1.7-7 i

. Attachment 2 CALCULA*I1ON 19-AN-19. REV 2 VOr,UME E Issue D

j AscAm mn' DEPTJDIV. E/EPED i

INSTRLJCTIONS

, (~';

i I

Single Phas'e Voltage Relays i

I Type 27N HIGH ACCURACY UNDERVOLTAGE RELAY I'

l Type' 59N HIGH ACCURACY OVERVOLTAGE RELAY Type 27N Catalog Series 211T Standard Case Type 27N Catalog Series 411T Test Case Type S9N Catalog Series 211U Standard Case l

Type 59N Catalog Series 411U Test Case i

h f

l

(,d uw aur I

.g-i i

i l

i i

i i

1 i

i ARFA RROWN BOVERI t

i

' ' to U-602657, 1.S-94-013 CAIAXXEI1DN 19 Af(e 23 of SR_tWB E Pag

-19 REV2 vu A88-6

  • 2 DEPTJDIV. B/EPSD j

}

187.4.1'.77 Single-enese voltage eessays j

Page t TABLE OF '00NTEN115 Introduction..................Page 2

{

Precautions....'..............Page 2

a Placing Relay into Servloe....Page 2

~

{

Appl ication Data.............Page 4 Testing.......................Page to 4

i i

INTRODUCTION These instructions contain the information required to properly install, operate, and-test certain single-phase undervoltage relays type 27N. catalog series 211T and 411T; and overvoltage relays, type EgN. catalog series 211U and 411U.

i The relay is housed in a case suitable for conventional. semiflush panel mounting.

A11 connections to the relay are made at the rear of the case and are clearly numbered.. Relays of the 4117, and 411U catalog series are sinflar to relays of the 211T, and 211U series.

Both series provide the same basic functions and are of 4

totally drawout constewotion; however,.the 411T and 411U series relays provide integral test facilities.

Also, seguenced disconnects on the 410 earles prevent nuisance operation during withdrawal or insertion of the relay if' the norpally-open i

contacts are used in the application.

Basic settings are made on the front panel of the relay, behind a resovable. clear plastic cover.

Additional adjustment is provided by means of calibration potentfo-meters inside the relay on the circuit board.

The target is reset by means of a i

pushbutton extending through the relay cover.

PRECAUTIONS The following precautions should be taken when applying 'these relays:

1. Incorrect wiring may result in~ damage. Be sure wiring agrees with the connection diagram.for the particular relay befotu energizing.

2.

Apply only the rated control voltage marked on the relay front panel. The proper polarity must be observed uhen the dc. control power connections are made.

case and

3. For relays with dual-rated control voltage, withdraw the relay from the check that the movable link on the printed circuit board is in the correct position for the system control voltage.
4. High voltage insulation tests are not recommended.

See the section on testing l

for additional information.

l 5.

The entire circuit assembly,of the relay is removable.

The unit should insert emoothly. Do not use excessive force.

I

6. Follow test instructions to, verify that the relay is in proper working order.

should CAUTION: einoe troubiechootthe entaiis Norking with energized equfpment, cere be taken to avoid personal shock. Only competent technicians familiar with good safety practices should service these devices.

PLACING THE RELAY INTO SERVICE

1. RECEIVING. HANDLING. STORAGE Upon receipt of the relay (when not included as part of a switchboard) examine for shipping damage.

If damage or loss is evident, file a claim at once and promptly notify Asea Brown Boveri.

Use normal care in handling to avoid mechanical damage.

(

Keep clean and dry.

j

-Attachment 4 to U-602657, LS-94-013 4

Page 24 of 50

}

Annamaar 2 cat 4UIE!10N 19 AN-19 RBV2 VOLUMB E I

DEPT /DIV. B/BPED i

singie-Phase voltage Relays I.e 7.4.t.7 7 l

Page 3

2. INSTALLATION

. f' J

Mounting:

The outline' dimensions and panel drilling and outout information is'given in' Fig. 1.

j E

Connections:

~

Typtoal external connections are shown in Figure 2.

. Inter'nal connections and 1

contact logic are shown in Figure 3.

Control power must be connected in the proper polarity.

l J

For relays with dual-rated control power:, before energiring, withdraw the relay from its case and inspect that the movable Tink on the lower printed circuit board is in the correct position for the system control voltage.

(For units rated 110vdc. the i

i link should be placed in the posit.fon mat-kod 125vdc.)

l-These relays h' ave an external resistor wired to terminals 1 and 9 which must be in place for normal operation.

The resistrr is supplied mounted on the relay.

i These relays have metal front panels witach are connected.through printed circuit.

j board runs and connector wiring to a terminal at the rear of the relay case. The terminal is marked *G".

'In all applications this terminal should be wired to ground.

l i

3. SETTINGS 1

PICKUP The pickup voltage taps identify the voltage level which the relay will cause the i

j output contacts to transfer.

OROPOUT i

The dropout voltage taps are identified as a percentage of.the pickup voltage.

Taps are provided for.70s, 80%, 90%, and 99K of pickup, or, 30s, 40%. 505-, and 60X of pickup.

~

1 Note:

operating voltage values other.than the spectffc values provided by the taps 8

can be obtained by means of an internal adjustment potentiometer. See section on j

testing for setting procedure.

6 TIME DIAL j

The time dial taps are identified as 1,2,3,4,5,6.

Refer to the time-voltage charac-j teristic curves in the Application section.

Time dial selection is not provided on l

relays with an Instantaneous operating characteristic. The time delay may also be i

varied from that provided by the fixed tap by using the internal calibration adjust-j ment.

l'

4. OPERATION IMOICATORS 1

i The types 27N and 59N provide a target indicator that is electronically actuated at the time the output contacts transfer to the trip condition.

The target must be manually reset.

The target can be reset only if control power is available, AND if the input voltage to the relay returns to the ' normal

  • condition.

An led indicator is provided for convenience in testing and calibrating the relay and to give operating personnel information on the status of trhe relay. See Figure 4 for the operation of this indicator.

Units with a *-L" suffix on the catalog number provide a green led to indicate the presence of control power and internal power supply voltage.

1 1

.___ _ ~.. _ _ _._ _ _ _.. _.

~. _.. _ _ _. _ _ _

4 to U-602657, LS-94-013 4.

.L_.

Page 25 of 50 l

CAI4UI A'!10N Ap.AN-19 REV2 VOLUMB F_

l An.,4.===r 2 DEPTJDIV. E/BPSD l'

Single-Phase Voltage Relays i

IB 7.4.1.7-9

}

Page 4 APPt.ICATION DATA overvoltage relays are used to provide a wide Single-phase undervoltage relays and range of protective functions, including the protection of anotors and generators i

to initiate bus transfer.

repeatabilf t,y, relay are dos,1gned for those applications where exceptional accuracy, j

i and long-term stability are required.

Remember that the given in the Ratings section.

accuracy of the pickup and dropout settings with reispect to the prin Tolerances and repeatability are l

2 At the time of field cal-tain the particular operating values for the application.the instrumente used to set the relays is the im J

l the scouracy of means for accurate ibration, Multiturn internal calibration potentiometers provideand allow the difference between pickup j

factor.

adjustment of the relay operating points, and dropout to be set.as low as 0.6E.

operating time, or with definite-time Therelaysaresupplied.wNhinstantaneousThe definite-time units are offered in two time de i

J delay characteristic.

1-10 seconds, or 0.1-1 second.

Harmonia; distort' ion in An accurate peak detector is used in the types 27N and.69N.noticible effect on the relay operat..; p j.

set the twlay.

An internal' harmonic filter is l

the AC waveform cart have a measuring instevnents used tofor those applications where waveform distortion is a factor.

I available as an option The relay then The harmonic filter attenuates all hacinonics of the 60/60 Hr. input. fundamental compone j

add i

be,sica11y operates on the To specify the harmonic filter i

figure 6 for the typical filter response curve. Note in the section on ratings that the

" HF" to the catalog number.

the relay addition of the harmonic filter does reduce somewhat the repeatability ofIn applicatio the suffix l

l vs. temperature variation.

In these cases, the harinonic filter may be desirable to operate on the peak voltage.

would not be used.

I CHARACTERISTICS OF COMMON UNITS i

Catalog Numbers i

Time Delay Type Pickup Range Oropout Range Pickup Oropout Std Case Test Case 1

i 27N 60 - 110 v 70% - 99%

Inst Inst 211T01x6 411T01x6 l

Inst 1 - to sec 211T41x6 411T41x6 1

Inst 0.1 - 1 sec 211T61x6 411T6fx6 l

70 - 110 v 70E - Set feat Ynat tttTaevs a11Taews j

Inst 1 - 10 sec 211T43x6 411T48x6 0.1 - 1 seo. 211T63x6 411T63x6 l

Inst 411T02x6 l

60 - 110 v 305 - 60%

Inst Inst 211T02x6 Inst 1 - 10 sec 211T42x6 411T42x6 Inst 0.1 - t sec 211762x6 411T62x6

^

411UO1x6 SSN 100 - 150 v 7'0% - 99%

Inst Inst 211UO1x6 1 - 10 s Inst 211U41x6 411U41x6 0.1 - 1 s Inst' 211U61x6 411061x6 j

l J,

b EMMTANT NOTES:1. Each of the listed catalog numbers for the types 27N and 69N To contains an *x* for the control voltage designation.

complete the catalog tuseber, replace the *x" with the proper i

control voltage code digit:

48/125 vde..... 7 i

}

250 vde...... S 220 vde..... 2

<j 48/110 vdc..... 0 1

2. To specify the addition' of the harmonic filter module, add

(

For example: 411T4176-HF.

Harmonic the suffix "-HF".

filter not available on type 27N with instantaneous delay timing characteristic.

4

.n

. _ _ _ to U-602657, LS-94-013 Page 26 of 50

  • An=4-ar 2 CAIXXKATION19.AN-19 REV2 VOLUME E.

DEPTJDIV. B/EPSD Single-Phase Voltage Relays IB 7.4.1.7 7 Page 6

)

SPECIFICATIONS 150v maximus' continuous.

i j

f' Input Cirwuit: Rating: -type 17N type 59N 160v maximum continuous.

i Burden: less than 0.5 VA at 120 vac.

1, 1

Frequency: 50/60 Hz.

4 Taps:

available models include:

Type 17N: pickup - 60. 70 80 90, 100 110 volts.

70. 80. 90 100, 110 120 volts.

dropout-60, 70. 80 90, 99 percent of pickup.

l 30,40.50,60 percent of pickup.

4 -

Type SSN: pickup - 100, 110 120 130 140, 150 volts.

dropout-

60. 70. 80. 90. 99 percent of pickup.

Operating Time:

See Time-Voltage characteristic curves that follow.

1 Instantaneous models: 3 cycles or less.

Roset Time: 27N: less than 2 cycles; 59N: less than 3 cycles.

(Type 27N resets when input voltage goes above pickup setting.)

(Type 59N resets when input voltage goes below dropout setting.)

f

% i.Out Circuit:

Each contact e 120 vac e 125 vdc e 250 vdc 30 amps.

30 amps.

30 amps.

tripping duty.

5 amps.

5 amps.

5 amps.

continuous.

3 amps.

. 1 amp.

0.3 amp.

break, resistive.

2 amps.

0.3 amp.

0.1 amo.

break, inductive.

Operating Temperature Range:

-30 to +70 deg. C.

Control Power: Models available for Allowable variation:

48/125 vdc e 0.05 A max.

48 vdc nominal 36-58 v*c d

48/110 vdc e 0.05 A max.

110 ydc

$8-125 Vdc 220 vdc e 0.05 A max.

125 vdc 100-140 vdc 250 vdc e 0.05 A max.

220 vdc 176-246 vdc.

250 vde-200-280 vde Tolerances:

(without harmonic filter option, after 10 minute warm-up)

+

Pickup and dropout settings with respect to printed dial markings (factory calibration) s +/- 25.

t, Pickup and dropout settings. repeatability at constant temperature and constant control voltage s +/- 0.15. (see note below)

Pickup and dropout settings, repeatability over " allowable" do control power range: +/- 0.15.

(see note below)

Pickup and dropout settings, repeatablility over temperature range:

-20 to +55'C

+/- 0.4%

-20 to +70eC

+/-0.7%

0'to +40eC +/- 0.25 (see note below) the three tolerances shown should be considered independent and Note: may be cumulative. Tolerances assume pure sine wave input signal.

Time Delay:

Instantaneous models: 3 cycles or less.

Definite time models: +/- 10 percent or +/-20 millisecs.

whichever is greater.

Harmonic Filter:

All ratings are the same except:

(optional)

Pickup and dropout settings, repeatability over temperature range:

' 0 to +55'C

+/- 0.755

-20 to +70*C

+/.1.5%

+10 to +40*C

+/- 0.40%

Dielectric Strength: 2000 vac. 50/60 Hz., 60 seconds, all circuits to ground.

I Seismic capability: Hore than 6g ZPA biaxial broadband multifrequency vibration without damage or malfunction. ( ANSI C37.98-1978 )

.j

Attachmsnt 4 to U-602657, LS-94-013 Pag 2 27 of 50 Attaciunent 2 CALCULATION 19-AN.19 REV2 VOLUME E oserav. wra, IS 7.4.1.7 7 Single-Phase Voltage Relays Page 7 INTERNAL CONNECTION DIAGRAN AND OUTPUT CONTACT LOGIU Figure 3:

table and diagram define the output contact states under all possible i

supply.

"AS SHOWN" The following conditions of the measured input voltage and the control power i

means that the contacts are in the state shown on the internal connection.d agram for the opposite

" TRANSFERRED

  • means the contacts are *ln

~

the relay being considered.

state to that shown on the internal connection diagram.

--a.-----

Contact State Condition Type 27N Type SSN Normal Control Power Transferred As Shown AC Input Voltaeg Below Setting Normal Contral Power As Shown Transferred AC Input Voltage Above Setting As Shown As Shown No Control Voltage


~~~-~~--

16DELLH Std. or Test Case,

8 1 OE os 3. ot 1

o g

r 036 15 11 13 12 11 10 1 8

cmanet assisvua surruce um acuw.

Pickup Voltage Level Off On On Off Oropout Voltage Level W

on input put Voltage Off Voltage On Decreasing increasing Start Sthrt figure hb: ITE-59H Operation of figure I.a ITE-27N Operation of Pickup indicating Light Oropout indicating Light Operation of Pickup / Dropout Light-Emitt.ing-Otode Indicator f

A l'igure 4 :

I l

f l

l

\\

\\

l I

A"achaear 2 AL4ULKI1ON 19M-19 2

5 DEPT /DIV. B/EPED 18 7.4.1.7=7 single-Phase Voltage Relays Page 6 s t,,

. i so m amar sms t

J iMas m as g-1 r -- - - - - -,i d$

}

i j

4 i

e n

L_

Y J

l8_

sooE VIOt j

encerrveEw HigtjtotAHotes

< W

<r h t

oms.

=

k s

~*

_e e

i I

j Stim efuldBEft$

g euxvon i

OsteEedssoses AA4 @

l

.l Figure 1: Relay outline and Panel Ortiling I

i 1

l 1

l' 52 W

A 1 v e

t

^ +

11 CONTROL CONTftOL POWER 12 PGHEg GDURCE 8

k u

i Figure 2:

Typical External Connections a

(

.. ~ _ _ _. -.. -.. _

.. _.... _._ to U-602657, LS-94-013 d

Page 29 of 50 Attersawar 2 CAIXXJLA't10N 194-19 REV2 VOUUMB E.

DEPr/DIV. B/EPED 18 7.4.1.7-7 etngle-enase Voltage Relays i

Fage 8 j

l 1 M #08TAGECW AACIEN8E8 TesaE WOI.TAGE CHARACTEMSTICS w swa - - emar tws so som mesams.es asev eersess tes J

eereess ess

]

as I

)

nas.

en es 1

IM 4A C

e e

, ed 0= M

^

8 d

i I.,

1 3*

u u

t t

~

  • 4 w

u is is u

t' a

u em in u

e usus.ineersseenies *

.n,mme.,

,,,, eseien.

1 M e.es eine== ew 44m==

e eserese e een es,s d e.,

e.

marase*=

e saun as oe-enum,tet sortes escueens esd ettueen am tes seedbser4e $4tedemur ased ettfeens j

.gques pgsg sams earms emar a== ev w resa emme ese = w a me==awam asu.

~

e m sees 1 I suses as

,,,,,,,,,,g l vos

  • '-****'~

1

..w.e s.

a 5

too

\\

T-.

\\

80

\\

I se t

5 se 0

1 Ee l 4e

\\

so

(

h k 30 40 120 100 300 reesseener - Hertz Figure 5: Normalized Frequency ' Response - Optional Harmonic Filter Module i

-- ~-- ~ ~-~

^

^ ~ ~ ' "

~ ~ ~ ~ ~ ~ ~ ^ to U-602657, LS-94-013 f

Paoe 30 of 50 l

And-e 2 CALCULKnOH 19 AN-19 REV2 VOLAJt2B R l

, DEIT/DIV. B/ SPED 13 7.4 Single-Phase Voltage Relays

__u________________________.,____________


~~-

Control Voltage Selector P1og I

I c % < **'=>," v

(

.... b' uye Oe

.l,f s Eli 9

3 r4. '. '

r 't

.I

. L piouu.

sw I' f3 Voltage ese Calibration s

g Pot.

- ;g i(t gg i

_s*_

J*t.

27N: CCW to Incr.

slal

'3[I l lz Ve, i

b l

^

ssN: cw to iner.

8

'g g

,,1; 5,

, v._,l-l, wy4 l+ #-

p,_

2

~ :

-0.0 g

i-p 4. :i, ' e.* 1 pTc(u;kfih

-i ea c 2e jm y

I Calibration i

sE fi elf

  • wr1
  • 5. j _,,
  • ' 3"*"-

l I

Ic Typical Circuit Board Layouts, types 27N and 59N Figure 6:

aug 9 Cif4

" "g dh ]h eue l

cas

[i 3aC l

E%

Il jdgi '

_l t g

l ocI lii

!ll >

1

_8-i

- Q,iw-

,.c Typical Circuit Boa'rd Layout - Harmonic Filter Hodule Figure 7:

i to U-602657, LS-94-013 I

Page 31 of 50 Atta4= war 2 CA!4ULA*t10N 19.AN-19 REV2 VOLUME E DEPTJDIV. B/BPED Is 7.4.t.7-7 single-Phase Voltage Relays Page 10 t

TESTING

1. HAINTENANCE AND RG4EWA1. PARTS Ho routine amintenance is required on these relays.

Follow test instructions to verify that the relay is in proper working order.

We recommend that an inoperative relay be returned to the factory for repair; however, a circuit descriptiop booklet COT.4.1.7-7 which includes schematic diagrams,'can be provided on request.

Renewal parts will be quoted by the factory on request.

211 Series Units Crawout circuit boards of the same catalog number are interchangible.

A unit is identified by the catalog number stamped on the front panel and a serial number stamped on the bottom side of the drawout circuit board.

The board is removed by using the metal putt knobs on the front panel. Removing the board with the unit in service may cause an undesired operation.

An 18 point extender board (cat 200X0018) is available for use in troubleshooting and calibration of the relay.

411 Series Units Metal handles provide leverage to withdraw the relay assembly from the case. Removing the unit in an application that' uses a normally closed contact will cause an operation. The assembly is identified by the catalog number stamped on the front panel and a serial number stamped on the bottom of the circuit board.

Test' connections are readily made to the drawout relay unit by using standard banana plug Isads at the rear vertical circuit board.

This rear board.is marked for easier identification of the connection points, s

Important: these relays have an' external resistor mounted 'on rear terminals 1 and 9.

In order to test the drawout unit an equiv11ent resistor must be connected to p-terminals 1 & 9 on 'the rear vertical circuit board of the drawout unit. The i

resistance value must be the same as the resistor used on the relay. A 25 or 50 watt resistor will be sufficient for testing. If no resistor is available, the resistor assembly mounted on the relay case could be removed and used. If the resistor from the case,is used, be sure to remount it on the case at the conclusion of testing.

Test Plug:

A test plug assembly, catalog number.400X0002 is available for use witly. the 410 ceries units. This device plugs into the relay case *on the switchboard and allows access to all external circuits wired to the case. See Instruction Book 18 7.7.1.7-8 for dotatis on the use of this device.

2. HIGH POTENTIAL TESTS High potential tests are not recommended. A hi-pot test was performed at the factory before shipping. If a control wiring insulation test is required, partially withdraw the relay unit from its case sufficient to break the rear connections before applying the test voltage.
3. BUILT-IN TEST FUNCTION 8e sure to take all necessary precautions if the tests are run with the main circuit i

energized.

The built-in test is provided as a convenient functional test of the relay and assoc-lated circuit.

When you depress the button labelled TRIP, the measuring and timing circuits of the relay are actuated.

When the relay times out, the output contacts transfer to trip the circuit breaker or other associated circuitry, and the target is

(

displayed.

The test button must be held down continuously until operation is obtained.

Attachmeng4toU-602657,LS-94-013 f

CA14ULATION 19-AN-19 REMOLUME DEPT /DIV. FAPED 10.7.4.t 7 7 Single-Phase Voltage Relays Page 11 i

4. ACCEPTANCE TESTS 4

Follow the test procedures under paragraph 5.

For definite-time units.

  • select Time the voltage to 50% of the For the type 27H, check timing by dropping 1

Dial 83.

(or to zero volts if preferred for simplification of the test).

dropout voltage set

.105% of pickup,(do not For the type 59N check timing by switching the voltage to exceed max. input voltage rating.) Tolerances should be within those shown on page 5.

If the settings required for the parttoular application are known" use the l

i

. procedures in paragraph 5 to make the final adjustments.

5. CALIBRATION TESTS Test connections and Test sources:

8.

Connect the relay to a Typical test circuit connections are shown in Figure (and internal plug proper source of dc control voltage to match 1'ts nameplate ratingGenerally the types 27N and S setting for dual-rated units).

The ac test source must be stable and f ree of 4

tions where high accuracy is required.

a "line-A test source with less than 0.3% harmonic distortion, such as

?

harmonics.

Do not use a voltage source that employs a ferroresonant is recommended.

corrector" as these usually have high transformer as the stabilizing'and regulating device,The accuracy of the voltage measuring instruments l

l harmonic content in their. output.

used must also be considered when calibrating these relays.

s If the resolution of the ac test source adjustment means is not adequate, the I

arrangement using two variable transformers shown in Figure 9 to give " coarse" and

  • fine" adjustments is recommended.

rating of When adjusting the ac test source do not exceed the maximum input voltage the relay.

LED Indicator:

det-emining A light emitting diode is provided on the front panel for convenience inThe action of the ind the pickup and dropout voltages.

and is best explained by referring to level and the direction of voltage change, Figure 4.

s The calibration potentiometers mentioned in the following procedures are of the For catalog series 211 multi-turn type for excellent resolution and ease of setting.

units, the 18 point extender board provides easier access to the calibration pots. If desired, the calibration potentiometers can be resealed with a drop of nait polish at the completion of the calibration procedure.

Settina pickuo and Drocout Voltanes:

fixed taps by adjusting the pickup calibration between the Pickup may be varied (60%

Pickup should be set first, with the dropout tap set at 99%

potentiometer R27.

the pickup tap to the nearest value to the desired units").

Set dropout on " low The calibration potentiometer has approximately a

+/-5%

range.

Decrease Re-setting.

until dropout occurs, then check pickup by increasing the voltage.

the voltage adjust and repeat until pickup occurs at precisely the desired voltage.

Set the dropout tap to the next Potentiometer R16 is provided to adjust dropout. Increase the input voltage to above pickup,and then lower tap to the desired value.

Readjust R16 and repeat until the required lower the voltage until dropout occurs.

setting has been made.

Settina Time Delay:

values shown on Similarly, the time delay may be adjusted higher or lower than thethe time-voltag On above the pickup the type 27N, time delay is initiated when the voltage drops fromis initiated when the va?ue to below the dropout value. On the type 59N, timing Referring to' Fig.

4, voltage increases from below dropout to above the pickup value.

relay is " timing out" when the led indicator is I f ghted.

the The following resistor values may be used when testing dit External Resistor Values:

series units.

Connect to rear connection points t & 9.

(-HF models with harmonic filter 4000 ohms)

(

Relays rated 48/125 vdc: 5000 ohms;

(-HF models with harmonic filter 3200 ohms) 48/110 vdc: 4000 ohms;

(-HF models with harmonic filter'9000 ohms) 250 vdc: 10000 ohms; 220 vdc: 10000 ohms; ( -HF models with harmonic filter 9000 ohms) to U-602657, LS-94-013 Page 33 of 50

~

  • p.A.~at 2 CALCULATION 19.AN-19 REV2 VOLUME E.

M WI DEPT /DJV. E/EPED ASEA BROWN 80 VERI i

ABS Power Transmission Inc.

Protective Relay Division 35 N. Snowdrift Rd.

2 Issue D (2/89)

Allentown, Pa. 18106 Supersedes Issue C 218-395-7333

- Z i

X To AC Test Source See Fig. 9 DC Control Source y

t-i (+:

Timer START Input 08Or05O5((4 p Or9

_f hM d! E GNO Ot6 ISOt4Ot3OttOttOt0h9 O.

s T

To Timer STOP Input p

Figure 8: Typical Test Connections T1, T2 Variable Autotransformers (1.5 amp rating)

T3 Filament. Transformer (t amp secondary)

V Accurate AC Voltmeter

~

--- + X l

i 3

s

?Y 4- --

4 l

V

~

UNE 120V;,

I;G.3V (20 VAC CORRECTOR 120 M ;

I UNE (LKVA)

.r

.r

.r

-Z 4 -.-

Tl T2 T3 COARSE FtNE l

Figure 9: AC Test source Arrangement These instructions do not purport to cover all detatis or variations in equipment, nor to provide for every possible contingency to be met I.,

Should in conjunction with insta11ation, operation, or maintenance.

particular problems arise which are not covered sufficiently for the purchaser's purposes, the matter should be referred to Asea Brown Goveri.

_ __ _ _. _. _. _ _ _ _... _. _ _ _ _ _ _ _ _ _. _. _ _ _ _. to U-602657, LS-94-013 1

ll

4 Page 34 of 50

)

l Desertpave swean Aos Power T&o company sac.41-233s a

a a

(Hsion R

E E

Sprinos, R.

Page 1 g g ARenlown,PA

?

y y

IW Ontarlo. Canada h

ASEABROWNBOVERt CAIEULNITON 19-AN-19.REV2 VOLUMB Ei-s An.,+==t 3 orr.to1V. FRPED sepanen ieso Higte scours" CIRQUIT WSHIELO

  • Devloe Number:27 Underwitage Type 27N and 59N '

1 supersedes ouseen 7A.s-tc.

a ** "a=*

5' o=="aa*

ga,5,;2ggf;g=

Undervoltage and l

Overvoltage Relay 4

Application l

The Type 27N and Type 59N Voltage Retsys provide a wide range of proledve funclions,

.c...

Induding underwetage proledian d motors, j

.L overvomage protecton, and autoensee bus i

-~ '

~.

transfer. The Type 27N and Type 59N solays i

. (.-

ase pitnersy designed for those aprw~w

)

cn:; m t. d.i-z..g;.gle ~.

whece esoepsonas accuracy, encepconer q ;-

h

[: k h h Y

$ggy.hE l' a$

W

tent,

..m c. g*:-

M@.

sessys in genwanna seasons or -d'=*=a~w in ienemouany.sowenveewewee i

a.. c y v.;>? S ;n.*

whae en paionnance W electomechanical

. - m.. g. - -

e 1.

F =. u.m ic.4..fC,9.6_J a ;4'), ; :.

or eene types of stase seters is maginst.

j m,

Nm.

3Mhf. 75:i.iN,2 seen types han a dual nominal frequency

[gg1..:..h

'9'iO i

i.

i.

rating of 50 or 60 HL fo uw unique at sw output ekouit dom not seqdre contads, asowing simper sonof txm4ransferachemes.opwaaon i(,

toes, twwowr. are provided as standard j

features on as types.

~

.q Harmonic dissortionin the Ac wawform can 1

/

w wa effect on the reteyoperaGng

Features,

/

have a no point and on enessuring instruments used to l

set sw relay. Aa innemsi hannonic Ser module e Seismic capabRy to 6g ZPA is avaEable for tiose applice5ons where wave-i e oesnha anw orhigh speed

  • Transientimmunity formdistortionis alador.
  • Higt# stable, accurate and sepeataide charaderts6m e orawoutconstudion i
  • tarburden
  • 2yearwananty
1)
  • TT A

,e a p"

'5 C a

m,,i e es 4,i 4

C b u "' 1" Gainc

/

\\

- sj

~

s2 I CONTROr.r L,,_ J o

Gaestnad c : A mi g

mu.v J,eowcn

.u

g,,,,,,r.,ane,
6. es

- 2 4

to E6 le u

4 <j e

5 ye sected 6er e,tey se epovaes.Rakte' t

4 o oa TC I

        • "'"d*"**"'"-

racoucucy m na g

_1 f.-

Typical Se(smic Test Results Typical Ctreult Shleid Voltage ne(sy 4 puestion

_ ___ _ _..._ _. _. _. _ _ _ _. _ _ _ _ - _. _. _. _. _ _ _ to U-602657, LS-94-013 Page 35 of 50 kkk 4

CA14ULA*110N 19.AN-19 REV2 VOf.UME E.

DEPTlDIV. B/BPED

%gg l

se 2 ASEA BROWN BOVERI f

j (~th

~i

s,.

i t

j spe0lfications HowTo Spe0lfy i

taput Circun Rating: Type 27N 160 Vac Maximum Conanuous Votage Relay shsE be Ases Gnmn Sowd t

Type 6ON 160 Vac Mamimum Consnuous Tyos 27N. Type EON or appawed equad draw-l Sunden:

Laes tien 0.5 VA d 120 Vac out case, capable of othstanding to to 6g 2PA s

esimmic stess wthout damage or malfunceon.

i Frequency:

5040 Hz.

Output Cirouk:

Each conted at 125 Vde:

at minknum voRage and amo seeings. A ma0-1 30ATsipping Duty nede operadon incRoelor shal be pnWided whkh setnins $belEen on has of control power.

5A Consnuous i

1A 8 teak. RealqEve Bugt4 means shes be pnneded to aAow oper.

j 03A Break, inducdwe.

adonal tests atticut addisonsi equipment centrol Power:

Rated at 48/125,250 Vdc at 0.05 ampere medmum.

,,.m..

j T_- ; m:

ANSt range -20'C to +5S'C

=

Mustoperase -30'C to +70c Picia, and dmpow esten0s wah vesped to l

Telerances:

hannonic pdnied disi sneddngs (Inctory cagbradonl l_.

l_

==

enodule, ener

- *2%.

i se minute wemm4 Picia, and dropow essenOs. espeessbety at u~

a-h=

constant tenpasswo and constam conerot l

weeGe = *0.1%(See Note)

[r E-i Piday and dropout soldn0s. mpestabsty over 3_

occonerot powwran0 eor 100140 was 2

3

=

= 20.1E(See Note)

Pielay and dropout setangs, sepassahny owr

  • i u

g44u 44u u

l

'__;+ "re

(See Note)

=

~S 70'C $$

"n h ""

"E*::' "'/s*.'.'l"t' i

0'C to +40'C 20.2%

  • * - - ruumm

. arrrma Note:The twee tolerances shown should be conddaedindependait and may be meie: Time semps esadams mui se see esos er i

oumuladw. Tolerances assume pure sine waw sw Tppe SIN Ovenetape Retey as idendosi is tese of tw Type 27N Undervoeage Relay.

input d0nal.

    • 8" dd'r ***** ** *'d'*: 88 ***

'nme oday

" '#" Ed** *'

. Instantaneous model: 3 cydes or less opersfing me.

i Desnlie Tnnw models (see appmpdate ourw).

How To Ostler.

L s10% or eso menseconds, whidwwris gmaler.

For a compista Isdng et avaEable versions of 1

Toserences:

AE raenes me the some escept. Pkfag and single and thee prce vota0e miays see TD

' (Wilk hermonic fluer dmpout esten0s. sepeatsbRty owr lengerature 41 025.

snodule) sange:

E O'C to +ss'C 20.7s%

Models are avansbie sor 4e to 250 Vdc conbot

+10'C to +40'C 20A0%

poew, and 120 Vac potenssi trancionners. For y

j

-20'C to +70'C *1.50%

ogier control totages contact tw nearest J

Reest Time:

Less tien 2 cydes (Type 27N).

District OIEce.

taes tien 3 oydos (Type 50N).

l (The retey resets when se input waa0e Goes To place an onsor, or for surther informason.

abow the pidag seteng -27N.below #w cordact tw nearest Distrid Onios.

i

. dmpout setung -s0N.)

j

. seemic capabliny: More than 6g zPA eNher AXIS bladel FurtherInfofmation broadband muerequency vibreson wahout damage or malfuncelon ANSI /IEEE C37.08.

Det Pdoes: PL 41420 Transient immunity: More egen 2500V,1MHz bursts at 400 Hz Todinical Data:TD 41025 l

repouuan raie, conunuous (ANSI C37.00.1 Instruelson Soolc 18 7A.1.7 78 SWC); Fast transient test.EMI test Otier Puoisceve Relays:

i j

Otelectric:

2000 Vac RMS 60 seconds as drausts to Appeceson haarear GtAde. TD 41416 e amassue seen seguem.ee e*= Maes== Met r

ground AB8 Power T&D Compa'ny enc.

ABB Power T&D Compahy Inc.

j A88 Power T&D Company Inc.

miay oMelon Resey DMenon Rday & Relay Systems oMsion m0 Corsi Rid e orive 35 N. Snowdr#t Road 606 Abenleen Avenue 0

7 il Springs. FL 33065 Asensown. PA 18106 Hambton. Ontario L8P 2Tt Canada 416.s2s4et1

(

752 4700 2:s 39s.7333 t

I

- to U-602657, Ls-94-013 CAIEULATIO'N 19-AN-19 ikBV 2 EdLtM{E E I

AMment 4 DEPT /DIV. FJEPED.

RC-Go04 Ascreau, am s

~

Number:

RC-6004 ASEA BROWN BOVERI Protectivo Relay Division 1YPE TEST Page:. 1.of S 35 N. Snowdrift Road CE1TIFICATE Issue Date: 2/10/ss Allentown Pa. 18166 Revision:

0 Revised:

215-395-7333 Type. Test for ty' e 27N High Accuracy Undervoltage Relays,

Title:

p Catalog Series 211T and 411T.

t Relay Tested:

see individual tests.

211T 411T Relay catalog series 612239 Printed circuit board (lower) 612745 Printed circuit board (backplane)

Printed circuit board 612272 (optional harmonic filter) 611996 Schematic diagram 611798 Schemtic diagram (hatinonic filter)

IB 7.4.1.7-7 Instruction book Hodelo covered by Theco Tooto:

All type 27N, cat series 211T, 411T.

'l h

Related Standards:

ANSI C37.90-1978, IEC 255.

Internal Connections:

(See instruction book for outputi contact logic) j st.wnee veztwo stetmes i

3.sor.ian I

sw. oc rese cese e ---

((#

h*

05 0*

i os s

at a

s onum.www mvua.

e

Title:

Product Hanager Approved by:

M This is the property of Asea Brown Boveri, Inc. and contains proprie-information which must not be duplicated or dis-tary and confidential closed other than as expressly authorized by Asea Brown Bovari, Inc.

a m o m,4 >r m a n m v23taim!9

-~ '

_ _ _ _, _ _ _ _ _ _ _ _ _, _ Attachment 4 to U-602657, LS-94-013 i

Page 37 of 50 q

)

IsnderHowember 21,199610:1T -- Ffwa '6103951055' ~ Pese 41 1

'G103951055 A B B P OI E Ali s m X M F-931 T-632 6% 21 '9412:11 -

i

!

  • ht 4 CA!4ULATION 19-AN-19 REV2 VOLUME E*.

DEPT /DIV. E/EPED Report Number:

RC-6004 Reviai.pn:

0 Phge 2 of 6

)

l Set Point Accuracy Tests:

1 Dropout Voltaae:

Pickup. Tap Dropout Tap Ooeratina Voltaae l

Settin9 Setting Expected Actual i

l 100 V

$9%

99.0v 98.8v 110 v 70%

77.0v 77.1v 90 v 80%

72.0V 72.1v 1

i 80 v 90%

72.0v 72.0v l

70 v 99%

69.3v 69.2v 60 v 99%

69.4v 59.3v Time Delay:

settings 110v pickup, 99% dropout, voltage switched from 120v to Ov.

Time Tap Operating Times,

Setting Expected Actual i

6 1.0 sec 1.0 sec 5

0.70 0.69 4

0.60 0.49 3

0.30 0.29 2

0.20 0.20 1

0.10 O.095 Results of Test:

Relay set point accuracy is within published limits of +/- 2% for dropout voltage and +/-10%

for time delay.

Relay Tested:

211T6176 Date of Test: 8/25/88

.S/N 1568 Tester: Production Line Test Ooeratina Time - Instm.Laneous Units:

(6) trials, relay pickup setting 110v, voltage switched from 120vac to ov:

0.043, 0.030, 0.041, 0.034, 0.038 seconds.

Results of Test: relay meets published requirement of~ operating time less than 0.05 sec.

Relay Tested:

211T017S Date of Test: 6/3/88 S/H 1554 Production Line Test i

- - - - - - - - - - - - - -~ -

- - - - to U-602657, LS-94-013 Page 38 of 50 e

Asea!*=~it 4 CAIEULNITON 19 AN-19 RBV2 V0tEMB G.

j

- DEPT /DIV. B/BPED,

4 j

Report Number:

RC 6004 Revision: o Page 3 of 6 fs Dielectric Tests (ANSI C87.90 IEC 255-5):

f between 2000 vac RNS, 60 Hz, applied for 60 seconds each test, '

^

i terminals as shown: '

3+4+7+8+10+11+12+13+14+15 G

(all ters kals to Ground) l' 3+4 7+8 (ac voltage input to control power. input) 4 9

{

3+4 10+11+12+13+14+15 (ad' voltage input to output contacts) i 10+11+12+13+14+15 746 (outout contacts to control power input) 10+11+12 13+14+15 (output contact sets to.each other) i i

Results of' test: ' No breakdown, no leakage, relay undamaged and operating properly after test.

l

, Relay tested:

211T4175 Date of. test:

11/2/82 i

Teater:

W.C. Martin

{

t Surge Withstand Tests (ANSI C2'7.90a, IEC 255):

1 Mhz. oscillatory wave, 2.5kV peak open cin:uit, 50 and 450 Hertz

()

repetition rates, applied for 2 seconds each test, tietween terminals v

'as shown.

Relay settings: pickup.100v, dropout 99%, input voltage j

l 101 vac.

i+8

> _ G (control voltage input, common mode) i t

3+4

> 'G (AC voltage input, common mode) i 10+11+12

> G (Output contacts, common mode)

~

i 1S+14+15

'G (Output contacts, common mode) 7 8

(Control voltage input, transverse mode)

?

3 4

  • ( AC voltage input, transverse mode) i 10+11 12 (Trip contact, transverse mode)

)

13+14 15 (Trip contact. transverse mode)

Results of test:

No in<iorrect operation or targets.

No damage, relay operated properly after test.

Relay tested: 211T0175 Date: 11/8/82 Tester: Mc Hartin 1

211T6175-HF Oate:

5/8/84 Tester: B Laskowski i

- - - -. - -.. ~.. ~,.

. ~,

w,- m,

agg

_. ~ _ _. _ _ _ - -. _. _. _

_.. _ _.. _ _. -._ __.- _ _.~._ -

~,

- to U-602657 LS-94-013 Page 39 of 50

. :. a,;,..

s esdw -

'= 21,199410:17 -- Fme e6hr,ione -- = g F-931 T-G32 P-GS987 MN 21 '94 12:11' 6103951835 ABB RIE (f.1RMIM-MW4 CALCULAT10N 19-AN 19 REV2 VOLUME E DEPT /DIV. E/BPED Report Number: RC 6004 Revision:

O Page 4 of 6

b..

l Fast Transient Test:

HFA51 auxiliary relay,12Sydc coil.' Triansients Transient source:

impressed on dc control power bus, mlny teminals 7 and '8.

Relay settings: pickup 100v, dropout 99%,.tisee dial.81/ Input voltage 101vac.

Auxiliary relay coil energized and de-energized 30 times.

Results of test:

No incorrect operations or targets.

No damage.

Relay tested:

211T6175 Date: 10/29/82 Tester.: WC Martin 211T4175-41F Date:

5/8/84 Tester: 8 Laskowski Radio Frequency Interference Test:

Hand-held 5 watt walkie--talkie, 464 Nhz operating frequency keyed with relay settin9s at 10Q pu, 99% do, time dial #1 and the input Walkie talkie antenna held within 24 inchet of signal at 106vac.

l the relay case on All sides.

No incorrect operation o'f relay, Results of test:

Teater: WC Nartin Relay Teated:

2iiT4175 Date: 10/21/87 ~

Tester: 8 Laskowski

~

211T4176-44F Date:

5/8/84 control Voltiage Variation Test:

pickup = 100v, dropout as shown:

Relay settings:

Voltane Selector Plua e 48vde Voltaae Selector plu'a = 125vdc Control Voltage Drupout=70%

Control Voltage Ortpout=90%

125 Vdc 89.92 vac 48 Vdc 69.94 vac 143 Vdc 89.93 vac 56 vdc 69.97 vac 39 Vdo 69.94 vac 100 vdc 89.92 vac

'AC operating point remains stable over do' control Results of Test:

vo1tage range.

Date of Test: 11/9/82 Relay Tested: catalog 211T0176 Tester: W.C. Hartin Control Drain:

at 12Sydc -

211T0175, S/N 1554, production line test, 8/3/88:

standby: 0.018A, operate: 0.034A l

211T6175-HF, test 3/10/86 by R.Schildt:

f standby: 0.027A, operate:.0.043A M

_ ~ - - -. - -

'---~~

i to U-602657, LS-94-013 i

Page 40 of 50 a

=.. e =^-- - - 4 CA'NTION194N-19 REV2 VO(AJMB E DEPT /DIV.. B/EPED l

Page 5'of G Report Number:

RC 6004 Revision:

O 4

o j ()

Output Contact Rating and Durability Test:

2500 operations at 125 vdo, 30 ampere resistive load, duty. cycle 4

l per ANSI CS7.go.

Contact wear and end-point conta't resistance c

l Results of Test:

acceptable.

Teater: H. Hinch l

Date of Test:

July 1977 e

Impulse Test (IEC 255-6):

1.2 x 50 us impulse 3 positive and 3 negative Sky open circuit, polarity shots between terminals as shown.

3+4

>G (ac voltage input to ground) 7+8

.9 G

(contrti power input to ground) 10+11+12

-)

G (output contact set to ground)

(output contact set to getund) t3+14+15 G

3 G

(acrvss ao vo'1tage input)

(across control voltage input) 7 a

10+11 <-----> 12 (across contact output)

, actsss contact output)

(

13+14 <-> 15 relay was undamaged and operated properly after Results of Test:

test.

Date of Test:

11/1/82 Rel'ay tested:

catalog 211T6175 Tester: WC Martin

~

4 m

w#wTrH erF0d 88U 990195mT9

-- *