| | | Reporting criterion |
|---|
| 05000251/LER-1985-001, :on 850102,containment Isolation Valve SV-2819 Failed to Close at 100% Power Upon Receiving Containment Ventilation Isolation Signal.Caused by Dirt Buildup on Contacts in Lockout Relay.Contacts Cycled |
- on 850102,containment Isolation Valve SV-2819 Failed to Close at 100% Power Upon Receiving Containment Ventilation Isolation Signal.Caused by Dirt Buildup on Contacts in Lockout Relay.Contacts Cycled
| |
| 05000251/LER-1985-002-01, :on 850129,malfunction Caused Emergency Diesel Generator a to Be Out of Svc So Vital Buses 3A & 4A Did Not Have Access to Onsite Emergency Power.Caused by Short in Panel Light Socket.Plant Change/Mod Initiated |
- on 850129,malfunction Caused Emergency Diesel Generator a to Be Out of Svc So Vital Buses 3A & 4A Did Not Have Access to Onsite Emergency Power.Caused by Short in Panel Light Socket.Plant Change/Mod Initiated
| |
| 05000251/LER-1985-002, :on 850129,emergency Diesel Generator a Out of Svc,Leaving Vital Buses 3A & 4A W/O Access to on-site Emergency Power.Caused by Short in Diesel Local Panel Light Socket |
- on 850129,emergency Diesel Generator a Out of Svc,Leaving Vital Buses 3A & 4A W/O Access to on-site Emergency Power.Caused by Short in Diesel Local Panel Light Socket
| |
| 05000250/LER-1985-003, :on 840119,turbine Manually Tripped Following Permissive P-7 Disarming to Prevent Tave from Decreasing Enough to Cause Safety Injection signal.P-7 Rearmed Prior to Turbine Trip.Caused by Personnel Error |
- on 840119,turbine Manually Tripped Following Permissive P-7 Disarming to Prevent Tave from Decreasing Enough to Cause Safety Injection signal.P-7 Rearmed Prior to Turbine Trip.Caused by Personnel Error
| |
| 05000251/LER-1985-003-01, :on 850206,reactor Tripped Due to Reactor Protection Logic of Steam Flow Greater than Feed Flow.Caused by Steam Flow/Feed Mismatch Alarm & Decrease in Steam Generator Level |
- on 850206,reactor Tripped Due to Reactor Protection Logic of Steam Flow Greater than Feed Flow.Caused by Steam Flow/Feed Mismatch Alarm & Decrease in Steam Generator Level
| |
| 05000250/LER-1985-004, :on 850129,reactor Tripped.Caused by ESF Actuation Due to Nonlicensed Operations Personnel Removing Unit 3 Motor Generator Sets a & B from Svc Rather than Unit 4 Sets.Personnel Counseled |
- on 850129,reactor Tripped.Caused by ESF Actuation Due to Nonlicensed Operations Personnel Removing Unit 3 Motor Generator Sets a & B from Svc Rather than Unit 4 Sets.Personnel Counseled
| |
| 05000251/LER-1985-004-01, :on 850207,high Voltage Flashover Occurred on Insulating Support of 240-kV Circuit Switcher.Caused by Gradual Buildup of Dirt & Salt Deposits on Insulating Supports.Electrical Insulators Cleaned |
- on 850207,high Voltage Flashover Occurred on Insulating Support of 240-kV Circuit Switcher.Caused by Gradual Buildup of Dirt & Salt Deposits on Insulating Supports.Electrical Insulators Cleaned
| |
| 05000250/LER-1985-005-01, :on 850205,during Work Order to Clean Four Batteries for Diesel Driven Fire Protection Pump,Battery Acid Fluid Noticed Forced Out of Four Batteries.Caused by Standby Charging Sys Overcharging |
- on 850205,during Work Order to Clean Four Batteries for Diesel Driven Fire Protection Pump,Battery Acid Fluid Noticed Forced Out of Four Batteries.Caused by Standby Charging Sys Overcharging
| |
| 05000251/LER-1985-005, :on 850207,spurious Safety Injection Signal Generated in ESF Sys W/No Resultant Safety Injection Flow. Caused by Blown Fuse on Flow Comparator of Steam Generator B Coincident W/Electrical Spike.Fuse Replaced |
- on 850207,spurious Safety Injection Signal Generated in ESF Sys W/No Resultant Safety Injection Flow. Caused by Blown Fuse on Flow Comparator of Steam Generator B Coincident W/Electrical Spike.Fuse Replaced
| |
| 05000250/LER-1985-006, :Redundant Raw Water Tank II Installed,Which Holds 300,000 Gallons of Water Dedicated to Fire Suppression.New Raw Water Tank II Meets App R Iii.A Requirements Approved by NRC on 811109 |
- Redundant Raw Water Tank II Installed,Which Holds 300,000 Gallons of Water Dedicated to Fire Suppression.New Raw Water Tank II Meets App R Iii.A Requirements Approved by NRC on 811109
| |
| 05000251/LER-1985-006-01, :on 850207,auxiliary Feedwater Sys Actuated Automatically.Caused by Incorrect Setting of Relay on 4,160- Volt Bus C.Auxiliary Feedwater Pumps Reset & Affected Relay Rewired |
- on 850207,auxiliary Feedwater Sys Actuated Automatically.Caused by Incorrect Setting of Relay on 4,160- Volt Bus C.Auxiliary Feedwater Pumps Reset & Affected Relay Rewired
| |
| 05000250/LER-1985-007-01, :on 850221,discovered Plant Procedures Did Not Include All Flowpath Valves Which Should Be Visually Verified Periodically for Position & Functionally Cycled,Per Tech Specs Re Fire Protection Sys |
- on 850221,discovered Plant Procedures Did Not Include All Flowpath Valves Which Should Be Visually Verified Periodically for Position & Functionally Cycled,Per Tech Specs Re Fire Protection Sys
| |
| 05000251/LER-1985-007, :on 850218,containment Spray Pump Power 4A Supply Breaker Inoperable.Caused by Closing Spring Charging Motor Being Off During Test,Resulting in Closing Springs Discharging.Charging Power Restored |
- on 850218,containment Spray Pump Power 4A Supply Breaker Inoperable.Caused by Closing Spring Charging Motor Being Off During Test,Resulting in Closing Springs Discharging.Charging Power Restored
| |
| 05000250/LER-1985-008, :on 850312,check Source Operability Verification of Two Sys Level Particulate,Iodine & Noble Gaseous Effluent Monitors Not Performed.Caused by Miscommunication Between Technicians |
- on 850312,check Source Operability Verification of Two Sys Level Particulate,Iodine & Noble Gaseous Effluent Monitors Not Performed.Caused by Miscommunication Between Technicians
| |
| 05000251/LER-1985-008-01, :on 850411,small Leak Discovered at Fitting on Test Connection Between Containment & Containment Isolation Valve.Caused by Test Connection Leakage & Malfunction of Valve CV-4-951 |
- on 850411,small Leak Discovered at Fitting on Test Connection Between Containment & Containment Isolation Valve.Caused by Test Connection Leakage & Malfunction of Valve CV-4-951
| |
| 05000250/LER-1985-009, :on 850401,evaluation Required for Inoperable Mechanical Shock Arrestor (Snubbers) Not Completed within Allowable Time Limits.Caused by Snubbers Inadequately Evaluated |
- on 850401,evaluation Required for Inoperable Mechanical Shock Arrestor (Snubbers) Not Completed within Allowable Time Limits.Caused by Snubbers Inadequately Evaluated
| |
| 05000251/LER-1985-009-01, :on 850425,emergency Diesel Generator a Taken Out of Svc Coincident W/High Head Safety Injection Pump. Caused by Personnel Error.Generator a Returned to Svc, Personnel Counseled & Procedures Revised |
- on 850425,emergency Diesel Generator a Taken Out of Svc Coincident W/High Head Safety Injection Pump. Caused by Personnel Error.Generator a Returned to Svc, Personnel Counseled & Procedures Revised
| |
| 05000250/LER-1985-010, :on 850330,subcooling Margin Monitors Considered Inoperable Per Tech Specs & Plant Shutdown.Caused by Failure of RCS Temp Elements to Meet Environ Acceptance Criteria.Elements Will Be Replaced |
- on 850330,subcooling Margin Monitors Considered Inoperable Per Tech Specs & Plant Shutdown.Caused by Failure of RCS Temp Elements to Meet Environ Acceptance Criteria.Elements Will Be Replaced
| |
| 05000251/LER-1985-010-01, :on 850515,turbine & Reactor Trip Occurred. Caused by Actuation of ESF Relay Inadvertently Bumped by Const Worker While Performing App R Mods.Const Halted. Post-trip Review Found No Abnormal Conditions |
- on 850515,turbine & Reactor Trip Occurred. Caused by Actuation of ESF Relay Inadvertently Bumped by Const Worker While Performing App R Mods.Const Halted. Post-trip Review Found No Abnormal Conditions
| |
| 05000251/LER-1985-011-01, :on 850517,reactor Trip Occurred When off-site Power Lost Due to Multiple Faults on High Voltage Power Sys. Caused by Multiple Intense Brush Fires.Natural Circulation Cooling Established |
- on 850517,reactor Trip Occurred When off-site Power Lost Due to Multiple Faults on High Voltage Power Sys. Caused by Multiple Intense Brush Fires.Natural Circulation Cooling Established
| |
| 05000250/LER-1985-011, :on 850406,while in Refueling Shutdown,Two safety-related Snubbers Inside Containment on RCS Pressurizer Spray & Relief Line Removed Before Inservice Insp Could Be Performed |
- on 850406,while in Refueling Shutdown,Two safety-related Snubbers Inside Containment on RCS Pressurizer Spray & Relief Line Removed Before Inservice Insp Could Be Performed
| |
| 05000251/LER-1985-012-01, :on 850530,reactor Trip Occurred Due to Loss of Power from as Inverter to 120-volt Ac Vital Instrument Bus for Panel 4P07.Caused by Blown Fuse on Spare as Inverter. Power Restored & Inverter Successfully Tested |
- on 850530,reactor Trip Occurred Due to Loss of Power from as Inverter to 120-volt Ac Vital Instrument Bus for Panel 4P07.Caused by Blown Fuse on Spare as Inverter. Power Restored & Inverter Successfully Tested
| |
| 05000250/LER-1985-012, :on 850429,during shutdown,generator-main Transformer Lockout Relay Tripped,Resulting in Actuation of ESF Equipment.Caused by Personnel Error.Personnel Counseled. Transformer turn-ratio Tested |
- on 850429,during shutdown,generator-main Transformer Lockout Relay Tripped,Resulting in Actuation of ESF Equipment.Caused by Personnel Error.Personnel Counseled. Transformer turn-ratio Tested
| |
| 05000250/LER-1985-013, :on 850502,during Scheduled Refueling Outage, Emergency Diesel Generator a Automatically Started.Caused by Incorrect Step in Procedure 3-OP-005 Used to Deenergize 4,160-volt Bus 3A.Procedures Changed |
- on 850502,during Scheduled Refueling Outage, Emergency Diesel Generator a Automatically Started.Caused by Incorrect Step in Procedure 3-OP-005 Used to Deenergize 4,160-volt Bus 3A.Procedures Changed
| |
| 05000251/LER-1985-013-01, :on 850606,reactor Tripped as Result of Turbine Trip.Caused by Inverter Trip Originating in Input Filters on Supply Side of Power Fuses.Fuse on Inverter & Input Filters Replaced.Inverters Replaced W/New Model |
- on 850606,reactor Tripped as Result of Turbine Trip.Caused by Inverter Trip Originating in Input Filters on Supply Side of Power Fuses.Fuse on Inverter & Input Filters Replaced.Inverters Replaced W/New Model
| |
| 05000250/LER-1985-014, :on 850520,refueling Cavity,Spent Fuel Pool & Fuel Transfer Canal Levels Lowered Below Tech Spec Min. Caused by Personnel Oversight During Repair of Fuel Transfer Carriage Drive Motor Chain.Level Raised |
- on 850520,refueling Cavity,Spent Fuel Pool & Fuel Transfer Canal Levels Lowered Below Tech Spec Min. Caused by Personnel Oversight During Repair of Fuel Transfer Carriage Drive Motor Chain.Level Raised
| |
| 05000251/LER-1985-014-01, :on 850608,containment & Control Room Ventilation Isolation Occurred When Pressurizer Relief Tank Drained.Caused by Leakage from Pressure Control Valve.Block Valve Closed.Faulty Valve Repaired |
- on 850608,containment & Control Room Ventilation Isolation Occurred When Pressurizer Relief Tank Drained.Caused by Leakage from Pressure Control Valve.Block Valve Closed.Faulty Valve Repaired
| |
| 05000251/LER-1985-015, :on 850610,while Emergency Diesel Generator B Out of Svc,Generator a Declared Out of Svc.Caused by Personnel Allowing Water Into Motor Control Ctr Where Bus Shorted Out.Generator Cleaned & Reenergized |
- on 850610,while Emergency Diesel Generator B Out of Svc,Generator a Declared Out of Svc.Caused by Personnel Allowing Water Into Motor Control Ctr Where Bus Shorted Out.Generator Cleaned & Reenergized
| |
| 05000250/LER-1985-015-01, :on 850626,voluntary Unit Cooldown Initiated Using Guidance of Tech Spec 3.0.1 Due to Detection of RCS Leak.Cause of 850625 Reactor Vessel O-ring Leakage Still Under Investigation |
- on 850626,voluntary Unit Cooldown Initiated Using Guidance of Tech Spec 3.0.1 Due to Detection of RCS Leak.Cause of 850625 Reactor Vessel O-ring Leakage Still Under Investigation
| |
| 05000251/LER-1985-016-01, :on 850618,motor Control Ctr 4A Taken Out of Svc,Requiring Cooldown of Unit.Caused by out-of-adjustment Breaker Trip Latch on Vital to Nonvital Tie Breaker 40535 Associated w/4A 480-volt Ac Motor Control Ctr |
- on 850618,motor Control Ctr 4A Taken Out of Svc,Requiring Cooldown of Unit.Caused by out-of-adjustment Breaker Trip Latch on Vital to Nonvital Tie Breaker 40535 Associated w/4A 480-volt Ac Motor Control Ctr
| |
| 05000250/LER-1985-016, :on 850613,automatic Start of Emergency Diesel Generator a Occurred.Caused by Personnel Error.Generator Stopped & Returned to Normal Standby Condition,Per Operating Procedure 0-OP-023 |
- on 850613,automatic Start of Emergency Diesel Generator a Occurred.Caused by Personnel Error.Generator Stopped & Returned to Normal Standby Condition,Per Operating Procedure 0-OP-023
| |
| 05000250/LER-1985-017, :on 850617,Train B Safeguards Equipment Actuated by Spurious Safety Injection Signal Generated in ESF Sys.Caused by Operator Error.Operator Counseled on Correct Use of Procedures |
- on 850617,Train B Safeguards Equipment Actuated by Spurious Safety Injection Signal Generated in ESF Sys.Caused by Operator Error.Operator Counseled on Correct Use of Procedures
| |
| 05000250/LER-1985-018-01, :on 850716,inverter 3C Supplying Power to 120-volt Vital Instrument Panel 3P06 Tripped.Cause Not Determined.Inverter Removed from Svc on 850719 for Replacement W/Different Model |
- on 850716,inverter 3C Supplying Power to 120-volt Vital Instrument Panel 3P06 Tripped.Cause Not Determined.Inverter Removed from Svc on 850719 for Replacement W/Different Model
| |
| 05000251/LER-1985-018, :on 850623,critical Heat Tracing Circuits 8A & 8B Declared Out of Svc.Caused by Heat Tracing Circuit 9 Inadvertently Coming in Contact W/Heat Tracing Circuit 8. Circuits 8A & 8B Repaired & Returned to Svc |
- on 850623,critical Heat Tracing Circuits 8A & 8B Declared Out of Svc.Caused by Heat Tracing Circuit 9 Inadvertently Coming in Contact W/Heat Tracing Circuit 8. Circuits 8A & 8B Repaired & Returned to Svc
| |
| 05000250/LER-1985-019, On 850721,reactor Protection Sys Actuated, Turbine Tripped & Auxiliary Feedwater Initiated Due to Spurious Low Pressure Signal.Probably Caused by Lightning. Periodic Operability Test Performed | On 850721,reactor Protection Sys Actuated, Turbine Tripped & Auxiliary Feedwater Initiated Due to Spurious Low Pressure Signal.Probably Caused by Lightning. Periodic Operability Test Performed | |
| 05000251/LER-1985-020-01, :on 850626,agastat in Closing Circuitry for Bypass Valve Failed Causing Closure Due to Interlock Between Valves CV-4-6275C & CV-4-6275C-1.On 850808,steam Generator 4C Blowdown Isolation Valve Inoperable |
- on 850626,agastat in Closing Circuitry for Bypass Valve Failed Causing Closure Due to Interlock Between Valves CV-4-6275C & CV-4-6275C-1.On 850808,steam Generator 4C Blowdown Isolation Valve Inoperable
| |
| 05000250/LER-1985-020, :on 850723,possible Inability of MSIVs to Close During Uncontrolled Steam Release Discovered.Caused by Deficiency in MSIVs Built by Ametek,Inc & Designed by Bechtel.Design Will Be Modified Per FSAR |
- on 850723,possible Inability of MSIVs to Close During Uncontrolled Steam Release Discovered.Caused by Deficiency in MSIVs Built by Ametek,Inc & Designed by Bechtel.Design Will Be Modified Per FSAR
| |
| 05000251/LER-1985-021, :on 840920,turbine Runback & Reactor Trip Occurred Upon Nis Rod Drop Signal.Caused by Failure of Inverter 4A to Provide Power to Vital 120-volt Instrument Bus,Panel 4P07,due to Blown Fuse |
- on 840920,turbine Runback & Reactor Trip Occurred Upon Nis Rod Drop Signal.Caused by Failure of Inverter 4A to Provide Power to Vital 120-volt Instrument Bus,Panel 4P07,due to Blown Fuse
| |
| 05000250/LER-1985-021-01, :on 850722,two Automatic Initiations of Auxiliary Feedwater Sys Occurred Due to Bypass Feedwater Control Valves Malfunctioning.Caused by Moisture in Instrument Air.Actuators Inspected & Cleaned |
- on 850722,two Automatic Initiations of Auxiliary Feedwater Sys Occurred Due to Bypass Feedwater Control Valves Malfunctioning.Caused by Moisture in Instrument Air.Actuators Inspected & Cleaned
| |
| 05000250/LER-1985-021, :on 850722,two Automatic Initiations of Auxiliary Feedwater Sys Occurred Due to Valve Malfunction. Caused by Quality of Instrument Air Supplied to Valve Actuators.Actuators Inspected & Cleaned |
- on 850722,two Automatic Initiations of Auxiliary Feedwater Sys Occurred Due to Valve Malfunction. Caused by Quality of Instrument Air Supplied to Valve Actuators.Actuators Inspected & Cleaned
| |
| 05000251/LER-1985-021-01, :on 850820,turbine Runback & Reactor Trip Occurred Due to Reactor Protection Sys Actuation.Caused by Rod Drops Resulting from Electrical Malfunctions.Gripper Coil on CRD Mechanism Replaced |
- on 850820,turbine Runback & Reactor Trip Occurred Due to Reactor Protection Sys Actuation.Caused by Rod Drops Resulting from Electrical Malfunctions.Gripper Coil on CRD Mechanism Replaced
| |
| 05000250/LER-1985-022, :on 850729,reactor Trip Occurred.Caused by Dirty Contacts on One Nuclear Instrumentation Sys Channel. Power Range Trip Relays Removed,Cleaned & Reinstalled |
- on 850729,reactor Trip Occurred.Caused by Dirty Contacts on One Nuclear Instrumentation Sys Channel. Power Range Trip Relays Removed,Cleaned & Reinstalled
| |
| 05000251/LER-1985-022-01, :on 851016,4A 4160-volt Breaker 4AA8 Tripped, Deenergizing Load Ctr.Cause of Trip Unknown.Breaker Replaced |
- on 851016,4A 4160-volt Breaker 4AA8 Tripped, Deenergizing Load Ctr.Cause of Trip Unknown.Breaker Replaced
| |
| 05000250/LER-1985-023, :on 850801,safety Injection Sys Actuation Occurred Following Reactor Trip Resulting from Trip of Bs Inverter.Caused by Failure of Oscillator & Logic Power Supply Module.Power Restored |
- on 850801,safety Injection Sys Actuation Occurred Following Reactor Trip Resulting from Trip of Bs Inverter.Caused by Failure of Oscillator & Logic Power Supply Module.Power Restored
| |
| 05000251/LER-1985-023-01, :on 850824,discovered That Containment Isolation Valve CV-4-956A Not Tested on Quarterly Cycle,Per Tech Spec 3.3.3.Caused by Failure to Note Previous Testing Problems on Valve Clearance.Valve Tested |
- on 850824,discovered That Containment Isolation Valve CV-4-956A Not Tested on Quarterly Cycle,Per Tech Spec 3.3.3.Caused by Failure to Note Previous Testing Problems on Valve Clearance.Valve Tested
| |
| 05000250/LER-1985-024, :on 850726,during Operability Test of Auxiliary Feedwater Pump C,Discharge Control Valve CV-3-2817 Failed to Fully Stroke Closed.Caused by Misadjusted Positioner.Valve Positioner Reset |
- on 850726,during Operability Test of Auxiliary Feedwater Pump C,Discharge Control Valve CV-3-2817 Failed to Fully Stroke Closed.Caused by Misadjusted Positioner.Valve Positioner Reset
| |
| 05000251/LER-1985-024-01, :on 851102,automatic Initiation of Standby Component Cooling Water Pump 4A Occurred.Caused by Maint & post-maint Testing Performed on auto-start Circuitry PC-611. Auto-start Circuitry Returned to Svc |
- on 851102,automatic Initiation of Standby Component Cooling Water Pump 4A Occurred.Caused by Maint & post-maint Testing Performed on auto-start Circuitry PC-611. Auto-start Circuitry Returned to Svc
| |
| 05000250/LER-1985-025, :on 850827 & 30,during App R Safe Shutdown Review,Addl Circuits That May Require Protection,Rerouting or Circuit Mods Identified.Caused by Addl NRC Guidance.Fire Watch Expanded |
- on 850827 & 30,during App R Safe Shutdown Review,Addl Circuits That May Require Protection,Rerouting or Circuit Mods Identified.Caused by Addl NRC Guidance.Fire Watch Expanded
| |
| 05000251/LER-1985-025-01, :on 851123,reactor Trip Occurred at Hot Standby Conditions.Caused by Intermediate Range Detectors Overcompensated Due to Voltage Setpoint Drift.Compensation Voltage Adjusted |
- on 851123,reactor Trip Occurred at Hot Standby Conditions.Caused by Intermediate Range Detectors Overcompensated Due to Voltage Setpoint Drift.Compensation Voltage Adjusted
| |
| 05000251/LER-1985-026-01, :on 851224,480-volt Power Supply Breaker to Backup Group 4A Pressurizer Heaters Discovered to Have No Light Indication.Caused by Backing Off Action by Arcing Contacts.Breaker Manually Tripped |
- on 851224,480-volt Power Supply Breaker to Backup Group 4A Pressurizer Heaters Discovered to Have No Light Indication.Caused by Backing Off Action by Arcing Contacts.Breaker Manually Tripped
| |