NS-96-004 Page 1 of 3 SLs 2.0 2.0 SAFETY LIMITS (SLs) 2.1 SLs 2.1.1 Reactor Core SLs I

2.1.1.1 With the reactor steam do;ae pressure < 785 psig or core flow < 10% rated core flaw:

THERMAL POWER sha'11 be s 25% RTP.

2.1.1.2 With the reactor steam dome pressure d 785 psig and core flow a 10% rat flow:

f. o9 ll MCPR 1 be 4,07 or two recirculation loop operation or he& for s g e. recirculation loop operation.

j.lo 2.1.1.3 Reac or vessel water level shall be greater than the top of active irradiated fuel.

2.1.2 ' Reactor Coolant System Pressure SL Reactor steam dome pressure shall be s 1325 psig'.

2.2 SL Violations i

l With any SL violation, the following actions shall be completed:

2.2.1. Within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />, notify the NRC Operations Center, in accordance with 10'CFR 50.72.

I 2.2.2 Within 2 hour2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />s:

Restore comp}i' nce with all SLs; and i

2.2.2.1 a

2.2.2.2 Insert all insertable control rods.

i 2.2.3 Within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, notify the plant manager and the corporate executive responsible for overall plant nuclear safety.

(continued) 4

-- - - - - - - - - N O T E - - -

Only applicable for cycle 7 operation.

CLINTON 2.0-1 Amendment No. 4 9701140105 970107 PDR ADOCK 05000461 P

PDR

Attachment' 2 to'U-602680 l

~

No changes. Provideci

[S-96;0 3

{or continuity only.

RepoftingRequireme 5.6 Reporting Requirements 5.6.2 Annual Radioloaical Environmental Operatina Report (continued) report shall be submitted noting and explaining the reasons for the missing results. The missing data shall be submitted in a-supplementary report as soon as possible.

5.6.3 Radioactive Effluent Release Report The Radioactive Effluent Release Report covering the operation of the unit during the previous calendar year shall be submitted by May 1 of each year. The report shall include a summary of the quantities of radioactive liquid and gaseous effluents and solid waste released from the unit. The material provided shall be '

consistent with the objectives outlined in the ODCM and process control program and in conformance with 10 CFR 50.36a and 10 CFR 50, Appendix I, Section IV.B.I.

5.6.4 Monthly Operatina Reports Routine reports of operating statistics and shutdown experience, including documentation of all challenges to the main steam safety / relief valves, shall be submitted on a monthly basis no later than the 15th of each month following the calendar month covered by the report.

5.6.5 COREOPERATINGLI51TSREPORT(C0lR) a.

Core operating limits shall be established prior to each reload cycle, or prior to any remaining portion of a reload cycle, and shall be documented in the COLR for the following:

1.

LC0 3.2.1, Average Planar Linear Heat Generation Rate (APLHGR),

2.

LCO 3.2.2, Minimum Critical Power Ratio (MCPR),

3.

LCO 3.2.3, Linear Heat Generation Rate (LHGR), and 4.

LC0 3.3.1.1, RPS Instrumentation (SR 3.3.1.1.14).

(continued)

CLINTON 5.0-18 Amendment No.

Attachtment 2 to B-#@Fs9A NS-96-004 Page 3 of 3 Reporting Requirements 5.6 5.6 Repor, ting Requirements 5.6.5 CORE OPERATING LIMITS REPORT (COLR)

(continued) b.

The analytical methods used to determine the core operating limits shall be those previously reviewed and approved by the NRC in General Electric Standard Application for Reactor Fuel (GESTAR), NEDE-24011-P-A,g:tst.;;r:';;d cr;i=$

ll The core operating limits shall be determined such that all c.

applicable limits (e.g., fuel thermal mechanical limits, core thermal hydraulic limits, Emergency Core Co'oling Systems (ECCS) limits, nuclear limits such as SON, transient analysis limits, and accident analysis limits) of the safety analysis are met.

d.

The COLR, including any midcycle revisions or supplements, shall be provided upon issuance for each reload cycle to the NRC.

l except that the MCPR Sa(cfy Limits

{or Operating Cycle 7 shall be determined as described in Illinois Power leHers (io the NRC) U-602624 dated August 15, 1996; U-G0ZG51 dated October 28,1996 ; and U-602662 dated November 15, 1996.

1 CLINTON 5.0-19 Amendment No. 1 O