J a

ENCLOSURE 1-NOTICE OF VIOLATION 2

Florida !'ower Corporation Docket No. 50-302 Crystal River Unit 3 License No. DPR-72 The following violation was identified during an inspection conducted on November 10 - December 20, 1984. The Severity Levels were assigned in accordance with the NRC Enforcement Policy (10 CFR Part 2, Appendix C).

I Technical Specification (TS) 3.7.13.5 requires the oxygen concentration in any waste gas decay tank (WGDT) to be less than 2% by volume whenever the concentration of hydrogen in that WGDT is greater than or equal to 4% by volume.

Action statement b for this TS requires whenever both the concentration of hydrogen and oxygen are each greater than or equal to 4% by volume in a WGDT, that waste gas additions to this tank be suspended and that the oxygen concentration be reduced to within its limit.

Contrary to the above, during the period from 3:30 a.m. on December 13, 1984, through 8:25 a.m. on December 14, 1984, WGDTs B, C and A exceeded the 4% hydrogen and oxygen limits and waste gas additions to these tanks were not suspended.

This is a Severity Level IV violation (Supplement I).

Pursuant to 10 CFR 2.201, you are required to submit to this office within 30 days of the date of this Notice, a written statement or explanation in reply, including:

(1) admission or denial of the alleged violation; (2) the reasons for the violation if admitted; (3) the corrective steps which have been taken and the results achieved; (4) corrective steps which will be taken to avoid further violations; and (5) the date when full compliance will be achieved.