ML20128J555

From kanterella
Jump to navigation Jump to search
Integrated Inspection Report 05000445/2020001 and 05000446/2020001
ML20128J555
Person / Time
Site: Comanche Peak  
(NPF-087, NPF-089)
Issue date: 05/07/2020
From: O'Keefe N
NRC/RGN-IV/DRP/RPB-B
To: Peters K
Vistra Operations Company
References
IR 2020001
Download: ML20128J555 (24)


See also: IR 05000445/2020001

Text

May 7, 2020

Mr. Ken Peters

Senior Vice President and Chief Nuclear Officer

VISTRA Operations Company, LLC

P.O. Box 1002

Glen Rose, TX 76043

SUBJECT:

COMANCHE PEAK NUCLEAR POWER PLANT, UNITS 1 AND 2 -

INTEGRATED INSPECTION REPORT 05000445/2020001 AND

05000446/2020001

Dear Mr. Peters:

On March 31, 2020, the U.S. Nuclear Regulatory Commission (NRC) completed an inspection

at Comanche Peak Nuclear Power Plant, Units 1 and 2. On April 2, 2020, the NRC inspectors

discussed the results of this inspection with Mr. T. McCool, Site Vice President, and other

members of your staff. The results of this inspection are documented in the enclosed report.

One finding of very low safety significance (Green) is documented in this report. This finding

involved a violation of NRC requirements. We are treating this violation as a non-cited

violation (NCV) consistent with Section 2.3.2 of the Enforcement Policy.

If you contest the violation or the significance or severity of the violation documented in this

inspection report, you should provide a response within 30 days of the date of this inspection

report, with the basis for your denial, to the U.S. Nuclear Regulatory Commission,

ATTN: Document Control Desk, Washington, DC 20555-0001; with copies to the Regional

Administrator, Region IV; the Director, Office of Enforcement; and the NRC Resident Inspector

at Comanche Peak Nuclear Power Plant, Units 1 and 2.

If you disagree with a cross-cutting aspect assignment in this report, you should provide a

response within 30 days of the date of this inspection report, with the basis for your

disagreement, to the U.S. Nuclear Regulatory Commission, ATTN: Document Control Desk,

Washington, DC 20555-0001; with copies to the Regional Administrator, Region IV; and the

NRC Resident Inspector at Comanche Peak Nuclear Power Plant, Units 1 and 2.

K. Peters

2

This letter, its enclosure, and your response (if any) will be made available for public inspection

and copying at http://www.nrc.gov/reading-rm/adams.html and at the NRC Public Document

Room in accordance with Title 10 of the Code of Federal Regulations 2.390, Public

Inspections, Exemptions, Requests for Withholding.

Sincerely,

Neil F. O'Keefe, Chief

Reactor Projects Branch B

Division of Reactor Projects

Docket Nos. 05000445 and 05000446

License Nos. NPF-87 and NPF-89

Enclosure:

As stated

cc w/ encl: Distribution via LISTSERV

Cornelius

F. O'Keefe

Digitally signed by

Cornelius F. O'Keefe

Date: 2020.05.07

14:50:23 -05'00'

ML20128J555

SUNSI Review

Non-Sensitive

Sensitive

Publicly Available

Non-Publicly Available

OFFICE SRI:DRP/B

RI:DRP/B

DRS/IPAT

DRS/EB1

NAME

JEllegood

NDay

AAgrawal

VGaddy

DATE

05/01/2020

05/04/2020

05/01/2020

05/04/2020

OFFICE DRS/EB2

DRS/OB

DRS/RCB

DNMS/RxIB

NAME

NTaylor

GWerner

MHaire

GWarnick

DATE

05/04/2020

05/04/2020

05/01/2020

05/04/2020

OFFICE SPE/DRP/B

BC:DRP/B

NAME

DProulx

NOKeefe

DATE

05/04/2020

05/07/2020

Enclosure

U.S. NUCLEAR REGULATORY COMMISSION

Inspection Report

Docket Numbers:

05000445 and 05000446

License Numbers:

NPF-87 and NPF-89

Report Numbers:

05000445/2020001 and 05000446/2020001

Enterprise Identifier: I-2020-001-0010

Licensee:

VISTRA Operations Company, LLC

Facility:

Comanche Peak Nuclear Power Plant, Units 1 and 2

Location:

Glen Rose, TX 76043

Inspection Dates:

January 1 to March 31, 2020

Inspectors:

J. Ellegood, Senior Resident Inspector

D. Antonangeli, Health Physicist

B. Baca, Health Physicist

N. Day, Resident Inspector

N. Greene, Senior Health Physicist

J. Melfi, Project Engineer

J. O'Donnell, Senior Health Physicist

Approved By:

Neil F. O'Keefe, Chief

Reactor Projects Branch B

Division of Reactor Projects

2

SUMMARY

The U.S. Nuclear Regulatory Commission (NRC) continued monitoring the licensees

performance by conducting an integrated inspection at Comanche Peak Nuclear Power Plant,

Units 1 and 2, in accordance with the Reactor Oversight Process. The Reactor Oversight

Process is the NRCs program for overseeing the safe operation of commercial nuclear power

reactors. Refer to https://www.nrc.gov/reactors/operating/oversight.html for more information.

List of Findings and Violations

Manual Reactor Trip Due to Loss of both Main Feed Pumps

Cornerstone

Significance

Cross-Cutting

Aspect

Report

Section

Initiating Events

Green

NCV 05000446/2020001-01

Open/Closed

[H.12] - Avoid

Complacency

71153

A self-revealed finding and associated non-cited violation (NCV) of very low safety

significance occurred when the licensee failed to implement procedures for operation of the

feed and condensate system as required by Technical Specification 5.4.1.a. Specifically,

while adjusting flow to the auxiliary condensers for the Unit 2 main feed pumps, the operators

isolated circulating water flow to the condensers, causing a loss of both Unit 2 main feedwater

pumps. Control room operators manually insert a plant trip in response to the loss of

feedwater.

Additional Tracking Items

Type

Issue Number

Title

Report Section

Status

LER 05000446/2018-002-01

LER 2018-002-01 for

Comanche Peak, Unit 2,

Automatic Actuation of

Auxiliary Feedwater System.

71153

Closed

LER 05000446/2019-002-00

LER 2019-002-00 for

Comanche Peak Nuclear

Power Plant, Unit 2,

Automatic Actuation of

Auxiliary Feedwater System.

71153

Closed

3

PLANT STATUS

Unit 1 began the inspection period at rated thermal power and remained there throughout the

inspection period.

Unit 2 began the inspection period at rated thermal power. On January 1, 2020, the licensee

inserted a manual trip in response to a loss of both main feed pumps while adjusting circulating

water flow to the auxiliary condensers. The licensee took the reactor critical and synchronized

to the grid on January 3, 2020. The licensee reached 100 percent power on January 4, 2020,

and remained at or near rated thermal power for the remainder of the inspection period.

INSPECTION SCOPES

Inspections were conducted using the appropriate portions of the inspection procedures (IPs) in

effect at the beginning of the inspection unless otherwise noted. Currently approved IPs with

their attached revision histories are located on the public website at http://www.nrc.gov/reading-

rm/doc-collections/insp-manual/inspection-procedure/index.html. Samples were declared

complete when the IP requirements most appropriate to the inspection activity were met

consistent with Inspection Manual Chapter (IMC) 2515, Light-Water Reactor Inspection

Program - Operations Phase. From January 1 - March 19, 2020, the inspectors performed

plant status activities described in IMC 2515, Appendix D, Plant Status, and conducted routine

reviews using IP 71152, Problem Identification and Resolution. The inspectors reviewed

selected procedures and records, observed activities, and interviewed personnel to assess

licensee performance and compliance with Commission rules and regulations, license

conditions, site procedures, and standards.

Starting on March 20, 2020, in response to the National Emergency declared by the President

of the United States on the public health risks of the coronavirus (COVID-19), resident

inspectors were directed to begin telework and to remotely access licensee information using

available technology. During this time the resident inspectors performed periodic site visits

each week and during that time conducted plant status activities as described in IMC 2515,

Appendix D; and observed risk-significant activities when warranted. In addition, resident and

regional baseline inspections were evaluated to determine if all or portions of the objectives and

requirements stated in the IP could be performed remotely. If the inspections could be

performed remotely, they were conducted per the applicable IP. In the cases where it was

determined the objectives and requirements could not be performed remotely, management

elected to postpone and reschedule the inspection to a later date.

REACTOR SAFETY

71111.01 - Adverse Weather Protection

Impending Severe Weather Sample (IP Section 03.02) (1 Sample)

(1)

The inspectors evaluated the adequacy of the overall preparations to protect

risk-significant systems from forecasted thunderstorms on January 10, 2020

4

71111.04 - Equipment Alignment

Partial Walkdown Sample (IP Section 03.01) (1 Sample)

The inspectors evaluated system configurations during partial walkdowns of the following

systems/trains:

(1)

Unit 2, chemical and volume control system on February 6, 2020

71111.05 - Fire Protection

Fire Area Walkdown and Inspection Sample (IP Section 03.01) (4 Samples)

The inspectors evaluated the implementation of the fire protection program by conducting a

walkdown and performing a review to verify program compliance, equipment functionality,

material condition, and operational readiness of the following fire areas:

(1)

Unit 1, turbine building basement on January 17, 2020

(2)

Unit 2, turbine building basement on January 17, 2020

(3)

Unit 2, emergency diesel generator A room on January 23, 2020

(4)

Service water intake structure building on March 26, 2020

Fire Brigade Drill Performance Sample (IP Section 03.02) (1 Sample)

(1)

The inspectors evaluated the onsite fire brigade training and performance during an

unannounced fire drill on March 3, 2020

71111.11Q - Licensed Operator Requalification Program and Licensed Operator Performance

Licensed Operator Performance in the Actual Plant/Main Control Room (IP Section 03.01) (1

Sample)

(1)

The inspectors observed and evaluated licensed operator performance in the control

room during turbine start and synchronization to the grid on January 3, 2020

Licensed Operator Requalification Training/Examinations (IP Section 03.02) (1 Sample)

(1)

The inspectors observed and evaluated licensed operators for just in time training for

a reactor startup on January 2, 2020

71111.12 - Maintenance Effectiveness

Maintenance Effectiveness (IP Section 03.01) (1 Sample)

The inspectors evaluated the effectiveness of maintenance to ensure the following

structures, systems, and components (SSCs) remain capable of performing their intended

function:

(1)

Unit 2, auxiliary feedwater system on February 25, 2020

5

71111.13 - Maintenance Risk Assessments and Emergent Work Control

Risk Assessment and Management Sample (IP Section 03.01) (4 Samples)

The inspectors evaluated the accuracy and completeness of risk assessments for the

following planned and emergent work activities to ensure configuration changes and

appropriate work controls were addressed;

(1)

Realignment of the Units 1 and 2 circulating water system on January 15, 2020

(2)

Planned yellow risk for Unit 1 auxiliary feedwater valve strokes concurrent with

emergent work to restore the Unit 1 emergency diesel generator A to operable status

on February 14, 2020

(3)

Risk associated with switchyard work and troubleshooting of Unit 2 circulating water

pump on February 7, 2020

(4)

Risk associated with starting the Unit 2 circulating water pump 2 on March 5, 2020

71111.15 - Operability Determinations and Functionality Assessments

Operability Determination or Functionality Assessment (IP Section 03.01) (4 Samples)

The inspectors evaluated the licensee's justifications and actions associated with the

following operability determinations and functionality assessments:

(1)

Unit 1, residual heat removal systems A and B, due to increasing pressures as

described in condition report CR-2019-009779 on January 9, 2020

(2)

Unit 2, emergency diesel generator A, due to a degraded time delay device as

described in condition report CR-2020-001295 on February 24, 2020

(3)

Unit 2, safety chiller 2-06, tripping due to a shorting bulb socket assembly as

described in condition report CR 2020-001502 on March 2, 2020

(4)

Unit 2, control rods from potential thermal sleeve cracking as described in Part 21

report LTR-NRC-19-79, and corrective action document TR 2020-1247

71111.19 - Post-Maintenance Testing

Post-Maintenance Test Sample (IP Section 03.01) (4 Samples)

The inspectors evaluated the following post maintenance test activities to verify system

operability and functionality:

(1)

Repair of disconnected wires and replacement of components in the Unit 2 safeguard

sequencer system per Work Order 5840776 on February 20, 2020

(2)

Replacement of cell 22 on battery 1DT4 per Work Order 5848383 on January 31,

2020

(3)

Repair of failed switch on neutron flux power ranch channel N-42 per Work

Order 5866789 on February 28, 2020

(4)

As found testing, calibration, and installation of Unit 2 safeguard sequencer B

undervoltage relays per Work Order 5666818 on March 4, 2020.

6

71111.22 - Surveillance Testing

The inspectors evaluated the following surveillance tests:

Surveillance Tests (other) (IP Section 03.01) (4 Samples)

(1) Unit 2, emergency diesel generator monthly load test per Procedure OPT 214B, Diesel

Generator Operability Test, Revision 16, on January 22, 2020

(2) Unit 2, at power end of core life reactivity test per Work Order 5659452 on February 10,

2020

(3) Unit 1, monthly control rod exercise surveillance per Work Order 5829754 on

January 24, 2020

(4) Unit 1, train A slave relay K609 actuation test per Work Order 5656218 on March 11,

2020

71114.06 - Drill Evaluation

Select Emergency Preparedness Drills and/or Training for Observation (IP Section 03.01)

(1 Sample)

(1)

The blue team emergency preparedness drill on February 19, 2020.

RADIATION SAFETY

71124.05 - Radiation Monitoring Instrumentation

Walk Downs and Observations (IP Section 02.01) (1 Sample)

The inspectors evaluated the following radiation detection instrumentation during plant

walkdowns:

(1)

Portable Survey Instruments

RM-177, HP-1461

RM-177, HP-1113

RM-177, HP-1145

RM-177, HP-2400

RM-177, HP-1464

RM-177, HP-1081

RM-177, HP-1026

AMS-4, HP-2166

3030E, HP-3270

Source Check Demonstration

Rad Eye G, HP-3112

Telepole, HP-1906

Rad Eye GX, HP-4045

Ludlum Model 3000, HP-3166

Area Radiation Monitors and Continuous Air Monitors

2-RE-6253

7

2-RE-6259A

2-RE-6297

X-RE-5896A

X-RE-5895B

1-RE-6256

1-RE-6295

Personnel Contamination Monitors, Portal Monitors and Small Article Monitors

SAM, HP-0063

GEM-5, HP-0075

SAM, HP-0055

GEM-5, HP-0076

Calibration and Testing Program (IP Section 02.02) (1 Sample)

The inspectors evaluated the calibration and testing of the following radiation detection

instruments:

(1)

Alarm Setpoint and Calibration Method Check of Personnel Contamination Monitors,

Portal Monitors and Small Article Monitors

GEM-5, HP-0075

SAM, HP-0063

Failure to Meet Calibration or Source Check Acceptance Criteria

Telepole, HP-1907

ARGOS, HP-0065

RO-20AA, HP-4123

AMS-4, HP-2166

71124.06 - Radioactive Gaseous and Liquid Effluent Treatment

Walk Downs and Observations (IP Section 02.01) (1 Sample)

The inspectors walked down the following gaseous and liquid radioactive effluent monitoring

and filtered ventilation systems to assess the material condition and verify proper alignment

according to plant design:

(1)

Plant Vent Stack Radiation Monitoring System

Liquid Waste Processing Radiation Monitoring System

Turbine Sump Radiation Monitoring System

Station Service Water to Discharge Canal Radiation Monitoring System

Calibration and Testing Program (Process & Effluent Monitors) (IP Section 02.02) (1 Sample)

The inspectors reviewed the following gaseous and liquid effluent monitor instrument

calibrations and tests:

(1)

WO 5360001, X-RE-5567A, South Plant Vent Stack Radiation Monitor

Calibration, 07/30/2018

8

WO 5590739, X-RE-5570B, North Plant Vent Stack WRGM Radiation Monitor

Calibration, 10/01/2019

WO 5585319, X-RE-5253, Liquid Waste Processing Discharge Radiation

Monitor Calibration, 10/28/2019

WO 5556086, 2-RE-5100, Turbine Sump 2-04 Radiation Monitor Calibration,

06/12/2019

WO 5421935, 1-RE-4269, Unit 1 Station Service Water Train A to Discharge

Canal Radiation Monitor Calibration, 10/24/2018

WO 5631300, 1-RE-4270, Unit 1 Station Service Water Train B to Discharge

Canal Radiation Monitor Calibration, 01/14/2020

WO 5576336, 2-RE-4269, Unit 2 Station Service Water Train A to Discharge

Canal Radiation Monitor Calibration, 09/25/2019

WO 5447947, X-FT-5288, LWPS LHMT X-01/X-02 Discharge to VD System

Flow Transmitter Calibration, 09/27/2018

Sampling and Analysis (IP Section 02.03) (1 Sample)

The inspectors reviewed the following:

(1)

Radioactive Effluent Sampling and Analysis Activities

Plant Ventilation Weekly Sampling, 01/27/2020

Containment Ventilation Sampling, 01/30/2020

Effluent Discharge Permits

G2018-034, Unit 1 Containment Vent, 02/27/2018

G2018-208, Plant Vent Stack B, 12/09/2018

G2018-210, Non-Routine Gas Normal, 12/10/2018

G2019-046, Plant Vent Stack B, 03/12/2019

G2019-193, Unit 2 Containment Vent, 11/24/2019

G2019-216, Plant Vent Stack A, 12/31/2019

L2018-023, Plant Effluent Tank 1, 07/05/2018

L2018-040, Plant Effluent Tank 2, 10/24/2018

L2018-051, Low Volume Waste Pond (LVWP), 12/01/2018

L2019-016, Plant Effluent Tank 1, 02/14/2019

L2019-055, Squaw Creek Reservoir, 08/01/2019

L2019-072, Plant Effluent Tank 2, 12/12/2019

Instrumentation and Equipment (IP Section 02.04) (1 Sample)

The inspectors reviewed the following radioactive effluent discharge system surveillance test

results:

(1)

WO 5319196, Primary Plant Ventilation Exhaust Filter Unit X-16 - Carbon

Analysis B Train, 01/13/2018

WO 5377734, Primary Plant Ventilation Exhaust Filter Unit X-01 - ESF Filter

Test A Train, 10/31/2018

WO 5431297, Primary Plant Ventilation Exhaust Filter Unit X-02 - ESF Filter

Test B Train, 11/07/2018

9

WO 5558463, Primary Plant Ventilation Exhaust Filter Unit X-02 - Carbon

Analysis B Train, 09/18/2019

Dose Calculations (IP Section 02.05) (1 Sample)

The inspectors reviewed the following to asses public dose:

(1)

Liquid and Gaseous Discharge Permits

G2018-034, Unit 1 Containment Vent, 02/27/2018

G2018-208, Plant Vent Stack B, 12/09/2018

G2018-210, Non-Routine Gas Normal, 12/10/2018

G2019-046, Plant Vent Stack B, 03/12/2019

G2019-193, Unit 2 Containment Vent, 11/24/2019

G2019-216, Plant Vent Stack A, 12/31/2019

L2018-023, Plant Effluent Tank 1, 07/05/2018

L2018-040, Plant Effluent Tank 2, 10/24/2018

L2018-051, Low Volume Waste Pond (LVWP), 12/01/2018

L2019-016, Plant Effluent Tank 1, 02/14/2019

L2019-055, Squaw Creek Reservoir, 08/01/2019

L2019-072, Plant Effluent Tank 2, 12/12/2019

Annual Radiological Effluent Release Reports

2017 Annual Radioactive Effluent Release Report, 03/12/2018

2018 Annual Radioactive Effluent Release Report, 04/20/2019

Abnormal Gaseous or Liquid Tank Discharges

None were available for review during this inspection

71124.07 - Radiological Environmental Monitoring Program

Site Inspection (IP Section 02.01) (1 Sample)

The inspectors evaluated the radiological environmental monitoring program

implementation.

(1)

The inspectors reviewed the following:

Walkdowns, Calibrations, and Maintenance Record Review

Air sampling stations: A1, A2, A3, A4, A5, A6, A7, A8

Thermoluminescent dosimeter (TLD) monitoring stations: R1, R4, R11, R13,

R22, R25, R27, R29, R30, R36

Calibrations of selected air sample pumps: 2178, 2196B, 2214, and 2224

Environmental Sample Collections and Preparation Observation

Air particulate (A1, A2, A3, A4, A5, A6, A7, A8)

Air charcoal (A1, A2, A3, A4, A5, A6, A7, A8)

Broad leaf (BL1, BL2, BL3)

Surface water (SW1, SW2, SW3, SW4, SW5)

10

Licensee Actions in Response to Missed Sample, Inoperable Sampler, Lost

Thermoluminescent Dosimeter (TLD) or Anomalous Measurement

The inspectors reviewed the licensee's response to 13 missing or anomalous TLD

results. The inspectors reviewed 6 inoperable samplers as noted in corrective action

documents since May 2017 and noted in the 2017 and 2018 Annual Environmental

Operating Reports. The majority of inoperable samplers were attributed to loss of

power due to external events, such as weather and power line work.

Sampling Program for the Potential of Licensed Material Entering Groundwater

Groundwater Monitoring Wells: 9, 10, 11, 12, 14, 15, 16, 19, 25, CP-A, CP-B,

CP-C

Groundwater Protection Initiative (GPI) Implementation (IP Section 02.02) (1 Sample)

(1)

The inspectors evaluated the licensee's voluntary groundwater protection initiative.

A few observations were as follows:

The general maintenance and material condition of the groundwater

monitoring wells was adequate with the general area around the well was

kept clear of any obstructions.

Most monitoring wells had enough water for samples to be taken.

Monitoring well locations 11 and CP-A had results of 835 and 1700 pCi/L,

respectively, which are both below their lower limit of detection (LLD)

requirements. The remaining well location samples all tested below the

minimum detectable activity.

The licensee implemented additional surface water sampling of the drainage

flow catch basin to track the potential impact of a water treatment filtered

water storage tank leak. The licensee has corrective actions in progress to

address the identified leak.

OTHER ACTIVITIES - BASELINE

71151 - Performance Indicator Verification

The inspectors verified licensee performance indicators submittals listed below:

IE01: Unplanned Scrams per 7000 Critical Hours Sample (IP Section 02.01) (2 Samples)

(1)

Unit 1 January 1, 2019, to December 31, 2019

(2)

Unit 2 January 1, 2019, to December 31 2019

IE03: Unplanned Power Changes per 7000 Critical Hours Sample (IP Section 02.02)

(2 Samples)

(1)

Unit 1 January 1, 2019, to December 31, 2019

(2)

Unit 2 January 1, 2019, to December 31, 2019

11

IE04: Unplanned Scrams with Complications (USwC) Sample (IP Section 02.03) (2 Samples)

(1)

Unit 1 January 1, 2019, to December 31, 2019

(2)

Unit 2 January 1, 2019, to December 31, 2019

71153 - Follow-up of Events and Notices of Enforcement Discretion

Event Follow-up (IP Section 03.01) (1 Sample)

(1)

The inspectors evaluated licensee response to a Unit 2 reactor trip on January 1,

2020.

Event Report (IP Section 03.02) (2 Samples)

The inspectors evaluated the following licensee event reports (LERs):

(1)

LER 05000446/2019-002-00, Automatic Actuation of Auxiliary Feedwater System

(ADAMS Accession No. ML19199A033). The inspectors determined that it was not

reasonable to foresee or correct the cause discussed in the LER; therefore, no

performance deficiency was identified. The inspectors did not identify a violation of

NRC requirements.

(2)

LER 05000446/2018-002-01, Automatic Actuation of Auxiliary Feedwater System

(ADAMS Accession No. ML 19199A032). The inspectors determined that it was not

reasonable to foresee or correct the cause discussed in the LER; therefore, no

performance deficiency was identified. The inspectors did not identify a violation of

NRC requirements.

INSPECTION RESULTS

Manual Reactor Trip Due to Loss of both Main Feed Pumps

Cornerstone

Significance

Cross-Cutting

Aspect

Report

Section

Initiating Events

Green

NCV 05000446/2020001-01

Open/Closed

[H.12] - Avoid

Complacency

71153

A self-revealed finding and associated non-cited violation (NCV) of very low safety

significance occurred when the licensee failed to implement procedures for operation of the

feed and condensate system as required by Technical Specification 5.4.1a. Specifically,

while adjusting flow to the auxiliary condensers for the Unit 2 main feed pumps, the licensee

isolated circulating water flow to the condensers, causing a loss of both Unit 2 main

feedwater pumps. Control room operators manually insert a plant trip in response to the loss

of feedwater.

Description: On January 1, 2020, the Comanche Peak on-shift operations crew decided to

secure a running circulating water pump for Unit 2. Although securing the pump was not on

the plan of the day schedule, the shift manager added the activity into the shift's work

activities to support planned work the following week. The inspectors noted that the activity

would use normal circulating water system operating Procedure SOP-310B, Circulating

Water, Revision 18, and the work schedule provided enough time to prepare for and conduct

the evolution. The procedure was structured to secure one circulating water pump, adjust

12

flow as needed to the main condenser, and then to adjust flow to the two main feedwater

pump auxiliary condensers. There are two steam driven main feedwater pumps.

The auxiliary condensers support operation of the two main feedwater pumps by condensing

the steam used by the feedwater pump turbines. Flow was being adjusted to optimize plant

thermal efficiency.

The crew successfully secured the circulating water pump and adjusted main condenser flow.

The crew then proceeded to the auxiliary condensers to adjust circulating water flow. A field

operator was stationed at each of the two auxiliary condenser outlet valves and a third field

operator was communicating with the main control room staff. In addition, a senior reactor

operator provided local oversight of the evolution. The crew intended to adjust the throttle

position of the circulating water with a final position directed by the reactor operator in the

control room. The reactor operator directed the valve operators to slowly close their

respective valves (simultaneously) to his mark while he monitored water box outlet

temperature. The valves were initially in a throttled position at the start and they reached the

fully closed position shortly after starting. Without any flow to the auxiliary condensers, both

main feedwater pumps automatically tripped on low vacuum to protect the pumps. Control

room staff immediately inserted a manual trip from 100 percent power. The control room

operators stabilized the plant in mode 3 using Emergency Procedure E-0, Reactor Trip and

Safety Injection, and normal operating procedures without further issue.

Personnel directly involved in the task failed to recognize that condenser vacuum would

respond quickly to reduced cooling water flow, but there would be delays before condensate

temperature would be reduced as the circulating water was adjusted due to mixing. In

addition, the personnel directly involved in the task did not recognize that the auxiliary

condenser outlet valves were two turns from full closed at the start of the evolution. These

factors led the field operators to erroneously fully close the valves prior to control room

direction to stop throttling the valves. The inspectors noted that the auxiliary condenser outlet

valves had large valve position indicators to provided system configuration information to the

local operators.

Comanche Peak performed a root cause evaluation to understand the event. The review

identified several weaknesses in crew performance that contributed to the event. Weakness

identified as the root cause were an over-reliance on process (i.e., procedures) coupled with

a failure to address gaps in behaviors and standards. This resulted in a lack of critical

thinking by plant staff as well as a failure to understand and address risks associated with the

proposed activities. During this evolution, operators failed to recognize the potential to lose

vacuum for the feed pumps due to a lack in understanding system operation and

fundamentals. The crew considered the throttling of cooling water flow to be a routine activity

and, therefore, the task preparations did not trigger a focused brief to discuss the evolution.

However, changing the circulating water pump configuration only occurs during winter months

to allow for maintenance on the pumps. The operators assigned to the task had a lack of

proficiency as none of the operators directly involved with adjusting flow on the auxiliary

condensers had secured a circulating water pump before. Furthermore, the operations shift

included three operators that had performed this evolution previously, but none were directly

involved in adjusting flow to the auxiliary condensers. The inspectors noted that their direct

involvement could have reduced the likelihood of an error during the evolution. In addition,

periodic throttling of the auxiliary condenser outlet valve flow occurred with regularity;

however, the adjustments were normally made in small increments with time between valve

movements to allow the system to equilibrate.

13

The inspectors performed walkdowns of the evolution after the event, interviewed the

personnel involved, reviewed plant operating procedures, and reviewed the root cause

evaluation. The inspectors noted that although Comanche Peak used the correct procedure

and the procedure had been used successfully previously, weaknesses in preparation for the

activity and oversight led to the loss of the feed pumps. Weaknesses included a failure to

recognize the risks associated with throttling auxiliary condenser circulating water flow,

adjusting flow to two condensers simultaneously, giving a non-standard order (throttle slowly

closed to my mark), not understanding the throttling characteristics of a butterfly valve, not

establishing the initial valve positions and closely monitoring the position as it was adjusted,

not monitoring the most applicable system parameters for the expected changes, and failure

to recognize and compensate for a lack of proficiency of the operators in performing this

evolution.

Corrective Actions: As an immediate corrective action, Comanche Peak operators tripped the

Unit 2 reactor and stabilized the plant in mode 3. Personnel involved were removed from

on-shift duties pending remedial training. Longer term actions included additional oversite of

operations activities. Additional actions are discussed on AR 2020-00008.

Corrective Action References: CR-2020-00008

Performance Assessment:

Performance Deficiency: The failure to adequately supervise component manipulations and

control system parameters within procedure limits while adjusting circulating water flow

through the auxiliary condensers was a performance deficiency. Specifically, operators failed

to adequately prepare for adjusting circulating water flow to the Unit 2 main feedwater pump

auxiliary condenser outlet valves, which caused inappropriate valve manipulation during the

evolution and created a condition that required a Unit 2 reactor trip.

Screening: The inspectors determined the performance deficiency was more than minor

because it was associated with the human performance attribute of the Initiating Events

Cornerstone and adversely affected the cornerstone objective to limit the likelihood of events

that upset plant stability and challenge critical safety functions during shutdown as well as

power operations. Specifically, the failure to adequately supervise component manipulations

and maintain system parameters within procedural limits led to the loss of both running main

feedwater pumps and a plant trip.

Significance: The inspectors assessed the significance of the finding using Appendix A, The

Significance Determination Process (SDP) for Findings At-Power. In accordance with

IMC 0609, Appendix A, Exhibit 1, the inspectors determined that the finding required a

detailed risk evaluation because the loss of feedwater caused operators to manually trip the

reactor and the loss of main feedwater constituted a loss of mitigation equipment used to

transition the plant to a stable shutdown condition.

The senior reactor analyst performed a detailed risk evaluation by treating the finding as an

initiating event and using the conditional core damage probability for a loss of main feedwater

as called for in Section 8.0, Initiating Event Analyses, of the Risk Assessment of Operational

Events Handbook. The analyst used Comanche Peak SPAR model version 8.58, run on

SAPHIRE, software version 8.2.1, for the evaluation.

The model was modified to reflect probabilistic recovery of a main feedwater pump. To

accomplish this, the analyst adjusted Basic Event MFW-XHE-XL-TRIP, Operator Fails to

14

Restart Main Feedwater Flow, used in Fault Tree MFW, Main Feedwater System, from

TRUE to a SPAR-H human reliability model derived value of 4.40E-2. In this human reliability

analysis, the analyst assigned high stress to both diagnosis and action and moderate

complexity to both diagnosis and action for the recovery. All other performance shaping

factors were set to nominal. Also, the analyst credited the use of the licensees diverse and

flexible coping strategies (FLEX) equipment. Performance of the initiating event analysis with

these modifications yielded an estimate of the increase in core damage frequency of 7.8E-7

per year from internal events. Loss of main feedwater events were the dominant sequences

and were mitigated by the auxiliary feedwater system.

The analyst noted that this detailed risk assessment evaluates an actual event in which no

external events occurred. Additionally, the period that the events impacted plant equipment

was small enough that the probability of an external initiator occurring during this time would

be negligible. Therefore, the analyst assumed that the risk from external events, given the

subject performance deficiency, was essentially zero. This resulted a total estimate in the

increase of core damage frequency of 7.8E-7 per year, making the finding of very low safety

significance (Green).

The increase in large early release frequency from this finding was determined to be of very

low safety significance using IMC 0609, Appendix H, Containment Integrity Significance

Determination Process, because loss of main feedwater sequences screen as having low

safety significance in pressurized water reactors with large dry containments.

Cross-Cutting Aspect: H.12 - Avoid Complacency: Individuals recognize and plan for the

possibility of mistakes, latent issues, and inherent risk, even while expecting successful

outcomes. Individuals implement appropriate error reduction tools. The licensee identified in

their root cause analysis that operations did not recognize nor understand the risks

associated with the evolution. The inspectors concluded that as a result, operators did not

plan for the possibility of mistakes or implement appropriate error reduction tools.

Enforcement:

Violation: Technical Specification Section 5.4.1.a requires, in part, that written procedures

shall be established, implemented, and maintained covering the applicable procedures

recommended in Regulatory Guide 1.33, Revision 2, Appendix A, February 1978.

NRC Regulatory Guide 1.33, Revision 2, Appendix A, Section 3, addresses Procedures for

Startup, Operation, and Shutdown or Safety-Related PWR Systems and Section 3.K,

addresses Feedwater System. The licensee established Procedure SOP-310B, Circulating

Water, Revision 18, to address operation of the circulating water system, including adjusting

flow to the auxiliary condensers which support operation of main feedwater system.

Procedure SOP-310B, Revision 18, step 5.3.7, requires operators to slowly adjust the

auxiliary condenser differential pressure to between 1- and 10 feet H2O. Contrary to the

above, on January 1, 2020, the licensee failed to slowly adjust the auxiliary condenser

differential pressure and maintain it between 1- and 10 feet H2O when operators fully closed

the valves, causing a condition (dual feedwater pump trips on low vacuum) that required a

reactor trip.

Enforcement Action: This violation is being treated as a non-cited violation, consistent with

Section 2.3.2 of the Enforcement Policy.

15

EXIT MEETINGS AND DEBRIEFS

The inspectors verified no proprietary information was retained or documented in this report.

On January 31, 2020, the inspectors presented the radiation safety exit meeting

inspection results to Mr. T. McCool, Site Vice President, and other members of the

licensee staff.

On April 2, 2020, the inspectors presented the integrated inspection results to

Mr. T. McCool and other members of the licensee staff.

16

DOCUMENTS REVIEWED

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

71111.04

Procedures

SOP-103B

Chemical and Volume Control System

13

71111.05

Fire Plans

FPI-105B

U-2, train B Diesel generator and Equipment Elevation, 810'

2

Miscellaneous

Fire Hazard Analysis Report Sections 5.9.7 and 5.6

32

Drill 20-15-01

Fire Drill Scenario for EDG 2-02 810' Fuel Oil Transfer Pit

March 3,

2020

71111.12

Corrective Action

Documents

TR-YYYY-NNNN

2016-008019

Miscellaneous

Maintence Rule Summary Report for Unit 1 and Unit 2

Auxillary Feedwater

02/18/2020

Auxiliary Feedwater System Status

2nd Quarter

FY19

71111.13

Drawings

E2-0026

6.9KV Three Line Diagram Normal Buses

13

Miscellaneous

STI-600.01-1

Guarded Equipment Management Posting Log

February 12,

2020

Procedures

SOP-310B

Circulating water System

18

Work Orders

5835726

Auxiliary Feedwater Pump Turbine 2-01Govenor Stroke

02/13/2020

71111.15

Corrective Action

Documents

CR

2019-9530

12/13/2019

TR

2020-1247

February 19,

2020

Drawings

M2-2760

Diesel Engine Start/Stop Logic

15

Operability

Evaluations

FSAR Table 8.3-1, Loading Requirements for Loss of

Coolant Accident Coincident with Loss of Offsite Power

104

CR-

2020-001295

71111.19

Corrective Action

Documents

CR-YYYY-NNNN

2019-009453

IR-2020-001597

Multiple Relays Out of Tolerance on Unit 2 Train B

Sequencer

Procedures

INC-7393A

CH Cal Neutron Flux Power Range ION Current Gain and

Summing Level Amplifier

6

MSE-S2-0673B

Unit 2 Train B Sequencer Under Voltage Relay Surveillance

5

Work Orders

WO 5666818

Perform MSE-S2-0673B, TR B Sequencer UV Relay

WO 5840776

Troubleshoot and Repair Sequence Alarm Circuit as

documented in IR-2019-009453

17

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

WO 5848383

Replace Cell 22 on BT1D4 at Power

WO 5866715

Perform CCAL IAW INC-7393A

WO 5866789

Troubleshoot test signal going to zero described in CR 2020-

001447

71111.20

Miscellaneous

BEACON 3D Reactivity Projection for Unit 2 Forced Outage

Startup

01/01/2020

71111.22

Procedures

ETP-106

Monthly RCCA Repositioning

1

OPT-106A

Control Rod Exercise

12

OPT-467A

Train A Safeguards Slave realy K609 Actuation Test

Revision 5

Work Orders

WO 5656218

Solid State Protection System Slave Relay Test

March 11,

2020

WO 5659452

Perform NUC 202 AT-Power MTC Measurement

WO 5829754

OPT-106A, Control Rod Exercise Test

WO 5846000

Monthly RCCA Reposit ETP-106

WO 5852752

IR-2020-000542 Troubleshoot 2-01 EDG Volt Reg TRBL

71114.06

Miscellaneous

ERO team Exercise

February 9,

2020

71124.05

Calibration

Records

3443188

X-RE-5700 ICI-4998, CCAL FB VNT EXH

06/24/2009

3648653

2-RE-6297, ICI-4961 Channel Calibration

09/30/2010

391556

1-RE-6295 ICI-4961, CCAL

03/16/2009

4373552

1-RE-6295 ICI-4961, CCAL

04/12/2016

4374577

2-RE-6297 ICI-4961, CCAL

05/10/2017

4426655

X-RE-5700 ICI-4998, CCAL FB VNT EXH

01/22/2015

4520934

1-RE-6256 ICI-4959 CCAL HRAM

06/09/2015

5371788

X-RE-5701 INC-4915X, CCAL AB VNT GPRM

07/18/2019

5522342

1-RE-6290A INC-7079, CCAL CNTMT HRRM

05/16/2019

5522458

1-RE-6290B INC-7079, CCAL CNTMT HRRM

05/02/2019

5526341

1-RUK-2326A/2328A INC-4916 CCAL

07/17/2019

ASCAN

WBC System Calibration Data Package

11/20/2019

FSCAN

WBC System Calibration Data Package

09/12/2019

HP-0058

Argos/Sirius Calibration Data Sheet

11/10/2019

HP-0063

NE Technology SAM Calibration Data Sheet

10/22/2018

HP-0075

GEM-5 Calibration Data Sheet

02/04/2019

18

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

HP-1206

Ludlum Model 177 Frisker Calibration Data Sheet

01/27/2020

HP-2166

AMS-4 Calibration Data Sheet

10/04/2019

HP-4124

Thermo RO-20AA Calibration Data Sheet

01/29/2020

HP-5002

Low Volume Air Sampler Calibration Data Sheet

10/12/2018

HP-711812

RDS-31 Calibration Data Sheet

10/07/2019

Corrective Action

Documents

CR-YYYY-NNNN

2011-006222, 2016-001350, 2018-003694, 2018-006522,

2018-006631, 2018-007217, 2019-000184, 2019-001550,

2019-004125, 2019-004570, 2019-005318, 2019-007716,

2019-008045, 2019-008114, 2019-008129

TR-YYYY-NNNN

2018-006999, 2018-007197, 2018-007846, 2019-001511,

2019-003201, 2019-003405, 2019-003992, 2019-004146,

2019-004149, 2019-004221, 2019-005656, 2020-000063

Corrective Action

Documents

Resulting from

Inspection

CR-YYYY-NNNN

2020-000750, 2020-000783, 2020-000814

Miscellaneous

1-RE-6290A

Last Detector Primary Calibration

05/15/2019 19-001 through 19-007

Calibration Well Source Charts

08/08/2019

2Qtr FY19

CPNPP System Status: Radiation Monitoring

T190990

RadCal 2026C and 1800cc, 180cc, and 6cc detectors

05/29/2019

Procedures

CLI-782

APEX Gamma Spectroscopy Counting System

2

ICI-4959

Channel Calibration - High Range Area Radiation Monitors

4

ICI-4961

Channel Calibration - Digital High Range Area Monitors

4

ICI-4998

Channel Calibration - Gas Process Radiation Monitor

4

INC-7079

Channel Calibration -

Containment High Range Radiation Monitor Channels

1-RE-6290A/B and 2-RE-6290A/B

6

RPI-301

Portable Survey Instruments

13

RPI-800

Control of Radiation Protection Equipment

17

RPI-802

Performance of Source Checks

28

RPI-862

Calibration of the Argos/Sirius Personnel Contamination

Monitor and Gem-5 Gamma Exit Monitor

14

STA-619

Administrative Control of Digital Radiation Monitoring System

7

19

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

STA-650

General Health Physics Plan

8

STA-658

Radiation Protection Equipment Calibration Program

12

STA-677

Preventative Maintenance Program

13

STA-700

Surveillance Frequency Control Program

1

STI-677.01

PM Change Processing

2

Self-Assessments EVAL-2018-006

Work Management/Radiation Protection Audit

08/02/2018

EVAL-2019-007

Chemistry Control and Chemistry Measurement & Analysis

11/21/2019

71124.06

Calibration

Records

WO 5360001

X-RE-5567A, South Plant Vent Stack Radiation Monitor

Calibration

07/30/2018

WO 5421935

1-RE-4269, Unit 1 Station Service Water Train A to

Discharge Canal Radiation Monitor Calibration

10/24/2018

WO 5447947

X-FT-5288, LWPS LHMT X-01/X-02 Discharge to VD System

Flow Transmitter Calibration

09/27/2018

WO 5556086

2-RE-5100, Turbine Sump 2-04 Radiation Monitor Calibration 06/12/2019

WO 5576336

2-RE-4269, Unit 2 Station Service Water Train A to

Discharge Canal Radiation Monitor Calibration

09/25/2019

WO 5585319

X-RE-5253, Liquid Waste Processing Discharge Radiation

Monitor Calibration

10/28/2019

WO 5590739

X-RE-5570B, North Plant Vent Stack WRGM Radiation

Monitor Calibration

10/01/2019

WO 5631300

1-RE-4270, Unit 1 Station Service Water Train B to

Discharge Canal Radiation Monitor

01/14/2020

Corrective Action

Documents

CR-YYYY-NNNN

2019-008687, 2019-008794

TR-YYYY-NNNN

2017-000757, 2018-003362, 2019-001642, 2019-005866,

2019-006713, 2019-008605

Corrective Action

Documents

Resulting from

Inspection

TR-YYYY-NNNN

2020-000766, 2020-000815, 2020-000817

TR-YYYY-NNNN

2020-000766, 2020-000815, 2020-000817

Miscellaneous

CPSES Offsite Dose Calculation Manual, Unit 1 and Unit 2

34

2017 Annual Radioactive Effluent Release Report

03/12/2018

2018 Annual Radioactive Effluent Release Report

04/20/2019

G2018-034

Gaseous Discharge Permit - Unit 1 Containment Vent

02/27/2018

G2018-208

Gaseous Discharge Permit - Plant Vent Stack B

12/09/2018

20

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

G2018-210

Gaseous Discharge Permit - Non-Routine Gas Normal

12/10/2018

G2019-046

Gaseous Discharge Permit - Plant Vent Stack B

03/12/2019

G2019-193

Gaseous Discharge Permit - Unit 2 Containment Vent

11/24/2019

G2019-216

Gaseous Discharge Permit - Plant Vent Stack A

12/31/2019

L2018-023

Liquid Discharge Permit - Plant Effluent Tank 1

07/05/2018

L2018-040

Liquid Discharge Permit - Plant Effluent Tank 2

10/24/2018

L2018-051

Liquid Discharge Permit - Low Volume Waste Pond (LVWP)

12/01/2018

L2019-016

Liquid Discharge Permit - Plant Effluent Tank 1

02/14/2019

L2019-055

Liquid Discharge Permit - Squaw Creek Reservoir

08/01/2019

L2019-072

Liquid Discharge Permit - Plant Effluent Tank 2

12/12/2019

Procedures

CHM-170

Liquid and Gaseous Effluent Program

4

CHM-230

Guidelines for Sample Collection

3

CLI-744

Radioactive Effluent Pre-Release Permit Processing

2

CLI-745

Radioactive Effluent Post-Release Permit Processing and

Surveillance Tracking

3

STA-603

Control of Station Radioactive Effluents

21

STA-619

Administrative Control of the Digital Radiation Monitoring

System

7

STA-677

Preventive Maintenance Program

13

Self-Assessments EVAL-2019-007

Radioactive Waste, Effluents, Environmental, and Chemistry

Programs

11/21/2019

Work Orders

WO 5319196

Primary Plant Ventilation Exhaust Filter Unit X-16

01/31/2018

WO 5377734

Primary Plant Ventilation Exhaust Filter Unit X-01

10/03/2018

WO 5431297

Primary Plant Ventilation Exhaust Filter Unit X-02

11/17/2018

WO 5558463

Primary Plant Ventilation Exhaust Filter Unit X-02

09/18/2019

71124.07

Corrective Action

Documents

CR-YYYY-NNNN

2018-001574, 2018-001611, 2018-001760, 2018-004523,

2019-002077

TR-YYYY-NNNN

2018-001867, 2018-004228, 2019-001642, 2019-007287

2019-008284, 2019-009052, 2019-009165

Corrective Action

Documents

Resulting from

Inspection

CR-YYYY-NNNN

2020-000748

21

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

Miscellaneous

2017 Annual Radiological Environmental Operating Report

04/30/2018

2018 Annual Radiological Environmental Operating Report

04/01/2019

NUPIC Audit

23724

GEL Laboratories (JQA-14-097)

05/29/2014

NUPIC Audit

24747

(NOV2019-069)

GEL Laboratories (NOD-19-018)

08/29/2019

ODCM

Comanche Peak Steam Electric Station Offsite Dose

Calculation Manual Unit 1 and Unit 2

34

RPI-714-1-

20180715

2018 Land Use Census

07/31/2018

RPI-714-1-

20190620

2019 Land Use Census

07/25/2019

Procedures

RPI-538

Process Environmental Badges

9

RPI-710

Radiological Environmental Monitoring, Sampling, and

Analysis Program

22

RPI-713

Collection, Preparation, and Shipment of Radiological

Environmental Samples

19

RPI-714

Land Use Census

6

RPI-888

Calibration of Portable Air Sample Equipment

5

STA-653

Contamination Control Program

20

STA-654

Groundwater Protection Program

9

Self-Assessments EVAL-2019-007

Radioactive Waste, Effluents, Environmental, amd Chemistry

PRgrams

11/21/2019

Work Orders

WO- 4938991, 4965490, 5052258, 5080201, 5490927,

5651858, 5654059, 5654081, 5654093, 5654106,

5654119, 5654136, 5659602, 5659645, 5667801,

5736155, 5736168, 5736197, 5736232, 5736248,

5736282, 5736299, 5741625, 5747140