I 3.21 ALTERNATE SHUTDOWN SYSTEMS

Applicability:

]

Applies.to the operating status of the Alternate Shutdown System (ASDS). ]

Objective:.

~]

To define the operating status of the installed Alternate

]

Shutdown System..

]

Specification:-

]

'A.

The Alternate Shutdown System (ASDS), condisting of the following.

]

~

components, shall be. capable of performing its intended function

]

any time the plant is'in the Power Operation Condition.-

]

(Condition 7)

]

Alternate diesel generator (DG-2)

]

Turbine driven auxiliary feed water pump.(P-258)

]

Auxiliary charging pump (P-7)

]

.The alternate shutdown system supporting controls and

]

components which are necessary for the system to perform

]

its. intended function

]

B.

The alternate diesel generator shall have 100 gallons of

]

f fuel in its day tank and the ability to transfer additional

]

fuel from the. fuel oil storage tanks to the alternate diesel

))

generator day tank =in order to be considered capable of

]

performing its. intended function.-

]-

' Remedial' Actions:

]

A.

With the. Alternate Shutdown System (ASDS) not capable of performing ]

'its intended function, within seven days from the time of discovery, ]

either:

]

restore the required capability, or

~]

provide' substitute components with adequate capability to

]

i a

perform its intended function,'or

]

]

establish a roving fire watch for the following areas:.

.]

the cable tray rooms, the turbine building, the circulating water pumphouse, the switchgear room, and the cable vault.

]

The fire watch shall tour each of the above areas at least

]

once each hour.

.]

- B. : With the' Alternate Shutdown. System incapable of performing its

]

intended function for a period of thirty days, submit a report

]

to the NRC describing plans to restore the system capability

]

'[

to perform its intended function.

Submittal of a Licensee

]

j' Event Report.(LER) satisfies this requirement..

']