~ MAINE YANKEE ATOMIC POWER COMPANY-I
- ..u.
r
[
)..
I 3.21 ALTERNATE SHUTDOWN SYSTEMS
- Applicability:
]
Applies.to the operating status of the Alternate Shutdown System (ASDS). ]
Objective:.
~]
To define the operating status of the installed Alternate
]
Shutdown System..
]
Specification:-
]
'A.
The Alternate Shutdown System (ASDS), condisting of the following.
]
~
components, shall be. capable of performing its intended function
]
any time the plant is'in the Power Operation Condition.-
]
(Condition 7)
]
Alternate diesel generator (DG-2)
]
Turbine driven auxiliary feed water pump.(P-258)
]
Auxiliary charging pump (P-7)
]
.The alternate shutdown system supporting controls and
]
components which are necessary for the system to perform
]
its. intended function
]
B.
The alternate diesel generator shall have 100 gallons of
]
f fuel in its day tank and the ability to transfer additional
]
fuel from the. fuel oil storage tanks to the alternate diesel
))
generator day tank =in order to be considered capable of
]
performing its. intended function.-
]-
' Remedial' Actions:
]
A.
With the. Alternate Shutdown System (ASDS) not capable of performing ]
'its intended function, within seven days from the time of discovery, ]
either:
]
restore the required capability, or
~]
provide' substitute components with adequate capability to
]
i a
perform its intended function,'or
]
]
establish a roving fire watch for the following areas:.
.]
the cable tray rooms, the turbine building, the circulating water pumphouse, the switchgear room, and the cable vault.
]
The fire watch shall tour each of the above areas at least
]
once each hour.
.]
- B. : With the' Alternate Shutdown. System incapable of performing its
]
intended function for a period of thirty days, submit a report
]
to the NRC describing plans to restore the system capability
]
'[
to perform its intended function.
Submittal of a Licensee
]
j' Event Report.(LER) satisfies this requirement..
']
8505290142 850521 PDR ADOCK 05000309 P
PDR I'
3.21-1 05/21/85 l
^5413L-SEN I-a