ELECTRICAL POWER SYSTEMS 3/4.8.4 IILCIRICAL EQUIPMLN1 PROTECTIVE DEVICES CONIAINMENI PENLTRAll0N CONDUCTOR OVERCURRENT PR01EC11VE DEVIC _E_S LIMITING CONDITION FOR OPERATION 3.8.4.1 All containment penetration conductor overcurrent protective devices whose, circuit

'
' ' 9 h 2.0 i shall be OPERABLE.

timWin3 ault c.orreu.t eweeds h peectraticw raWMODES 1, 2, 3, and 4.S f

APPLICABILITY:

ACTION:

With one or more of the above required containment penetration conductor overcurrent protective device (s) inoperable:

Restore the protective device (s) to OPERABLE status or deenergize a.

the circuit (s) by tripping the associated backup circuit breaker, or racking out or removing the inoperable circuit breaker within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />, declare the affected system or component inoperable, and verify the backup circuit breaker to be tripped or the inoperable circuit breaker racked out, or removed, at least once per 7 days thereafter; the provisions of Specification 3.0.4 are not applicable to overcurrent devices in circuits which have their backup circuit breakers tripped, their inoperable circuit breakers racked out, or removed, or b.

Be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> a'nd in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

SURVEILLANCE REQUIREMENTS 4.8.4.1 All containment penetration conductor overcurrent protective devices whcse, circuit

/ ;;r '

T.t'_ 2.0 1 shall be demonstrated OPERABLE:

limilsv3 fault c.urred enree& tb pene.trate rating a.

At least once per 18 months:

4 1)

By verifying ~that the 13.8 kV circuit breakers are OPERABLE by selecting, on a rotating basis, at least 10% of the circuit breakers, and performing the following:

a)

A CHANNEL CALIBRATION of the associated protective relays, b)

An integrated system functional test which includes simulated automatic actuation of the system and verifying that each relay and associated circuit breakers and control circuits function as designed,xf x :;xi f

!_th 2.0 1, and h..

4.-

CALLAWAY - UNIT 1 3/4 8-16

~ _,m. -.,:. ;,g ~~'~

~~

~' "~ -

~

"~

4 9

E_LE,CJRICAL POWER SYSTEMS SURVElttANCE REQUIREMENTS (Continued)

For each circuit breaker found inoperable during these c) functional tests, an additional representative sample of at least 10% of all the circuit breakers of the inoperable type shall also be functionally tested until no more failures are found or all circuit' breakers of that type have been functionally tested.

By selecting and functionally testing a representative sample 2) of'at least 10% of each type of lower voltage circuit breakers.

Circuit breakers selected for functional testing shall be selected on a rotating basis. Testing of these circuit breakers shall consist of injecting a current in excess of the breakers nominal Setpoint and measuring the response time. The measured response time will be compared to the manufacturer's data to ensure that it is less than or equal to a value specified by Circuit breakers found inoperable during func-the manufacturer.

tional. testing shall be restored to OPERABLE status prior to resuming operation.

For each circuit breaker found inoperable during these functional tests, an additional representative sample of at least 10% of all the circuit breakers of the inoperable type shall also be functionally tested until no more failures are.found or all circuit breakers of that type have been functionally tested M,

By selecting and functionally testing a representative sam each type of fuse on a rotating basis.

Each repre ative fuses shall include at least 10% of al ses of that samp type. The etional test shall consist of ondestructive resistance measu nt test which dem rates that the fuse meets its manufacture design eria.

Fuses found inoper-able during these function ests shall be replaced with OPERABLE fuses prior "

esumin eration.

For each fuse found inoperabl ing these functio tests, an adaitional represent sample of at least 10% of a uses of that type shal functionally tested until no more fai are found all fuses of that type have been functionally te d.

At least once per 60 months by subjecting each circuit breaker to an b.

inspection and preventive maintenance in accordance with procedures prepared in conjunction with its manufacturer's recommendations.

CALLAWAY - UNil 1 3/4 8-17

1 i.]

t ji..g o

tt

[

1.

ELECTRICAL' POWER SYSTEMS-BASES

~

3/4.8.4 ELECTRICAL EQUIPMENT PROTECTIVE DEVICES Containment electrical penetrations and penetration conductors are protected by either deenergizing circuits not required during reactor operation or by demonstrating'the OPERABILITY of primary and backup overcurrent protection circuit breakers during periodic surveillance.

The-Surveillance Requirements applicable to lower voltage circuit breakers

d f ::: provide assurance of breaker : d in:: reliability by testing at least one representative sample of each manufacturer's brand of circuit breaker : d/ r 4eee:

Each manufacturer's molded case and metal case circuit breakers : d/:r 4meee are grouped into representative samples which are then tested on a' rotating

. basis to ensure that all breakers d/:r f ::: are tested.

If a wide variety

- exists within any manufacturer's brand of circuit breakers andk r f :::, it is necessary to divide that manufacturer's breakers : d/:r ft::: into groups and treat each group as a separate type ofl breaker :r f :: for surveillance p,urposes.

i k bst of cont.mmeu}, pemk.ra(tow ccmdudar overcurred. protec. hoe,

' devices u.>bcse, circtut I.iwEk$w3 f au.tl. tured ev.ceects lku peue,hraftow-raht$, t,$tk/ h$cemakh oS \\.ocahsN M Site. 'aucl Egt[tpvw,1, powered % tko proteded decd.st, shall' be availabte, at h plad

- dhc. th, accordauct, tdttk/ Sac,4to w, So. t:( c,) of 10 CFR. Put 50. Tise,

'Bddkhtow Or deleltklu; of 34A3 Cowktowd W ra.ttow toMr b

i overcurreul protecksue de.dtc.c. skan km. waAe. i. acc.ordaxe. ulih L

s.chw so.ss of to eso. %4 so.

4 9

l l-

!~

u l-

- CALLAWAY - UNIT 1 8 3/4 8-3

TABLE 3.8-1 CONTAINMENT PENETRATION CON 00CTOR M

OVERCURRENT PROTECTIVE DEVICES

~

POWEREO PROTECTIVE DEVICE EQUIPMENT NUMBER AND LOCATION 13.8-kV'Switchgear-Reactor Coolant Pump P-252PA010/-

OPBB01A B-252PA0Il0/252PA0101-Reactor Coolant Pump

P-252PA0108

-B-252PA0110/252PA0101 OPBB01B Reactor Coolant Pump P-252PA0205 OPBB01C

.8-252PA0211/252PA0202

.P-252PA0204

~

Reactor Coolant Pump B-252PA0211/252PA0202 DPBB010 480-V Load Center Hydrogen Recombiner

-P-125A. Fuse SGS01A B-52NG0304 Hydrogen Recombiner

'P-125A fuse

-SG501B B-52NG0404 Pressurizer Backup P-b?PG2102 Heaters through 52PG2111 B-250 A fuse Pressurizer Backup JP-52PG2202 Heaters lhrough 52PG2211 B-250 A fuse

-Containment Cooler l'-52NG01T AF 1 DSGN01A li-b?NG0108 Containment Cooler P-5/NG031AF1 OSGN01C li-S/NGU305 Containment Cooler P-S/NGU/lAIl 0SGN018 11-5?NGU708 Containment Cooler

' I'- S/NG041 Al I 0SGN010

'H-5?NGo405 PG20P MCC P-S?PG?ou/

11-S7PG200 l J

JCAllAWAY - UNII 1 3/4 8-18

\\&c.

p 1

TABLE 3.8-1 (Continued)

CONTAINMENT PENETRATION CON 00CTOR OVERCURRENT' PROTECTIVE DEVICES POWEREO PROTECTIVE'0EVICE EQUIPMENT NUMBER AND LOCATION 460-V Load Center (Continued)

Pressurizer Heater

- P-52PG2402 B-500A Fuse Pressurizer Heater P-52PG2403 B-500A Fuse Pressurizer Heater P-52PG2404 B-500A Fuse Pressurizer Heater

~

P-52PG2405

~B-500A Fuse Pressurizer Heater P-52PG2406

' B-500A Fuse Pressurizer Heater P-52PG2407 H-500A Fuse

.480-V Motor Control Ce'nter-RHR-Loop Inlet Iso P-52NG0180F 3 Viv EJHV8701B B-40A Fuse ESW from Ctmt-Air P-52NGO'2BHR2 Coolers Iso Viv EFHV46 B-lbA fuse CCF to Ctmt Iso'Viv l'-52NG02BDf 2 ECHV60 ll-10A Fuse CCW Centainment Isolation Valve

'P-S?NG01BHF1 EGHV132.

B-40A F uso.

PRT to Containment Valve P-52NG0100F1-BBHV8037A 0-15A l ose Pressurizer Relief Valve P-52NG01BBR3 BBHV8000A B-30A F use Reactor Coolant Orain Tank Pump P-52PG19NEF5 DPHB02A

.B-100A Fuse Lighting Transformer l'-52PG l9NCR 3 XQA26 ll-150A luse 3/4 8-19 x

CA1LAWAY - IINil L h

k.

TABLE 3.8-1-(Continued)

CONTAINMENT PENETRATION CONDUCTOR

--~7 OVERCURRENT PROTECTIVE DEVICES-PROTECTIVE DEVICE POWERED NUMBER AND LOCATION EQUIPMENT 480-V Motor Control Center (Continued)

P-52PG19NCR5 Machine Rm Exhaust Fan B-15A Fuse ~

DCGN04 P-5A Fuse Flux Mapping Motor Starters B-52PG19GDF3 SR06A P-5A Fuse Flux Mapping Motor Starters

- B-52PG19G0F6 SR068 P-52NG03CLF2

'RCP thermal barrier B-15A Fuse return italation Viv BBHV16 P-52NG01BHF4 CCW Containment Isolation Valve B-40A Fuse EGHV130 P-52NG02BBF4 Hydrogen Mixing Fan B-250A Fuse.

DCGN03B P-5?NG02BCF3 Hydrogen Mixing Fan B-250A Fuse DCGN030

. P-52NG01BBF 4 Hydrogen Mixing Fan B-250A Fuse DCCN03A P-52NG018CF3 Hydrogen Mixing Fan B-250A Fuse DCGNO3C P-52hG02BJF5 CROM Cooling Fan B-150A fuse DCGN01B P-52PG2VGAR2 CROM Cooling Fan B-150A Fuse OCGN01A

.P-52PG20NFR3 Pressurizer Cooling Fan B-15A Fuse DCGN05 P-52PG20Nff5 Reactor Coolant B-100A Fiae Drain Tank Pump DPHB028 P-52PC/0NEF1 Lighting Transformer B-150A Fuse XQA28

%./

r cal l AWAY - IINi l - 1 3/4 8-20 s

g

TABLE 3.8-1 (Continued)

CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE'OEVICES POWERED PROIECTIVE DEVICE-EQUIPMENT NUMBER AND LOCATION 480-V Motor Control Center (Continued)

Standby Lighting P-52NG02BJF1 B-40A Fuse Standby Lighting P-52NG02BJF2 B-40A Fuse PRT to' Containment Viv P-52NG02BHR3 BBHV8037B B-15A Fuse Pressurizer Relief Valve P-52NG0280F1 BBHV80008 B-30A Fuse CRDM Cooling Fan P-52NG01BJF5 OCGN010 B-150A Fuse CRDM Cooling Fan P-52PG19GBR2 DCGN01C B-150A Fuse Ctmt Iso Viv Ret from

-P-52NG0280F3 Thrm Barrier Cooling

'B-15A Fuse Coil EGHV62 P-52NG02BEF2 Sump to RHR Pump Viv EJHV88118 B-60A Fuse Ctmt Recirc Sump P-52NG02BEF3 Iso Viv ENHV7

-B-ISA Fuse Accumulator Iso Viv P-52NG02BGi3

_EPHV8808B B-60A fuse Accumulator Iso Viv P-52NGU2BHF2 EPHV88080 B-60A Fuse H Control System P-52NG02BFF3 2

Make-up Air Viv KAHV30 B-ISA Fuse P-52NG01BBF3 RC Pump Seal Water Iso Viv BGHV8112 B-ISA Fuse P-52NG018FF3 Sump to RHR Pump Vlv EJHV8811A B-60A Fuse 66 CALLAWAY - UNil 1 3/4 8-21 8./ h

TABLE 3.8-1 (Continued)

. CONTAINMENT' PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES M

POWERED-PROILCIIVE DEVICE EQUIPMENT NUMBER AND LOCATION 480-V Motor Control Center (Continued)

Ctmt Recirc Sump

'P-52NG01BEF3-Iso Viv ENHV1 B-15A Fuse-Accumulator Iso Viv P-52NG01BGF3 EPHV8808A B-60A Fuse Accumulator Iso Viv P-52NG01BGF2-EPHV8808C B-60A Fuse Ctmt Air to Aux Bldg P-52NG018FF2 ESF Filter Iso Viv GSHV20 B-ISA Fuse React Bldg Discharge P-52NG0188R2 Iso Viv LFFV95

~B-ISA Fuse RHR Loop Inlet P-52NG02BBF3 Iso Viv BBPV8702B B-40A Fuse RHR Loop Inlet P-52NG02BCF2-Iso Viv BBPV8702A 8-40A Fuse ESW to Ctmt Air P-52NG02BHF3.

Coolers Iso Viv EFHV34 B-ISA Fuse ESW to Ctmt Air P-52NG018CF 2 Coolers Iso Viv EFHV33 B-15A Fuse ESW from Ctmt Air P-52NG01BDF2-Coolers Iso Viv EFHV45 B-15A Fuse RHR Loop _ Inlet Iso Viv P-! /NG01DF l 2 EJHV8701A

(!-40A luse RCP Thermal Barrier P-57NG01CDF4 CCW Iso Valve BBHV13 11-ISA i use RCP Thermal Barrier P-52NG03CHF1 CCW Iso Viv BBHV14 R-15A Fuse Reactor Cavity Cooling P-521'Gl9NAF 4 '

Fan DCGN02A B-100A fuse Ctmt Atmospheric _ Control P-52PGl9NCF3-System Fan DCGR01A 11-60A f use 3/4 8-22 CALiAWAY - UNII 1 h, hb

~

( T, TABLE 3.8-1 (Continued)

CONT AINMENT PENETRATION CONDUCIOR OVERCURRENT PROTECTIVE DEVICES POWERED

' PROTECTIVE DEVICE-EQUIPMENT NUM8ER-AND LOCATION

-480-V Motor Control Center (Continued)

RCP A Space Heater

'P-52PG19NGF2 B-40 Fuse

.RCP'B 5 pace Heater

-P-52PG19NGF3-B-40 Fuse RCP A Oil Lift Pump

'P-52PG19NEF1 B-40A Fuse-RCP B Oil Lift Pump P-52PG19NGR3 H-40A Fuse Ctmt Normal Sump P-52PG19NFF1 Pump OPLF05A 8-15A Fuse Ctmt Normal Sump

P-52PG19NFF2 Pump OPLF05C 8-15A Fuse-unstrument-Tunnel

-P-52PG19NAF2 Sump Pump DPLF07A B-25A Fuse-RCP Thermal Barrier CCW P-52NG03CBF4 Iso V1v BBHV15 B-ISA Fuse RCP Thermal Barrier P-52NG03CLF2 CCW iso Viv BBHV16 8-15A Fuse Reactor Cavity Cooling

=P-52PGPUN8FS Fan DCGN028 B-100A F use -

Ctmt Atmospheric, Control P '2PG20NFF4 System Fan DCGR01B B-fiOA Fuse RCP C Space Heater

.P-52PG20NBFl.

H-40A Fuse RCP D Space Heater.

P-52PG20NCF1 JB-40A Fuse:

RCP C Oil Lift Pump P-52PG20NFF3 B-40A Fuse-Accumulator Tank A Isol Viv IEPR08C P-3A Fuse EPHV8808A RP139-B-3A Fuse 3/4 8-23 CALLAWAY - UNIT 1 s

6 eTC

e TABLE 3.8-1 (Continued)

CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES 9

POWERED PROTECTIVE DEVICE EQUIPMENT NUMBER AND LOCATION 480-V Motor Control Center (Continued)

Accumulator Tank C Isol Viv 1EPR080 P-3ALFuse EPHV8808C RP139 B-3A Fuse Accumulator Tank 8 Isol Viv.

4EPR08A P-3A Fuse EPHV88088 RP140 B-3A Fuse Accumulator Tank 0 Isol Viv 4EPR088 P-3A Fuse EPHV88080 RP140 B-3A Fuse Accumulator Tank'8 Vent Viv LEPK098 P-3A Fuse EPHV89508

'RL018 B-3A Fuse Accumulator Tank C Vent Viv IEPK090 P-3A Fuse EPHV89500 RL018 B-3A Fuse Accumulator Tank 0 Vent Viv 1EPK09F P-3A Fuse EPHV8950F RL018 B-3A fuse Accumulator Tank A Vent Vlv 4EPK09A P-3A Fuse EPHV8950A RLO1B' B-3A Fuse Accumulator Tank 8 Vent Viv 4EPK09C P-3A' Fuse EPHV8950C RLO18 B-3A Fuse Accumulator Tank C Vent V1v 4EPK09E P-3A Fuse EPHV8950E RL018 B-3A Fuse Cont. Mini, Purge Isol Viv

-4GTK038 P-3A Fuse GTHZ11 RLU20 8-3A Fuse Cont. Purge Isol Viv 4GIK030 P-3A fuse-GTHZ8 Hl.070 ll.lA Fuse RCP Breaker 5BBA01A P-15A fuse Control PA010/ B-15A Fuse RCP Breaker 5BBA01B P-LSA Fuse Control

.PA0108 B-ISA Fuse RCP Breaker 6BBA01C P-15A Fuse Control PA0205 8-15A Fuse RCP Breaker 6BBA010 P-15A Fuse Control PA0204 8-15A Fuse cal l AWAY - UNIT 1 -

3/4 6-24 r

b b

~

o TABLE 3.8-1 (Continued)

CONTAINMENT PENETRATION CON 00CTOR OVERCURRENT PROTECTIVE DEVICES POWERED PROTECTIVE-DEVICE NUMBER AND LOCATION EQUIPMENT 480-V Motor Control Center (Continued)

RCP Oil Lift SBBG02A P-2A Fuse PG19NEF1 B-1A Fuse Pump Control RCP D Oil Lift Pump P-52PG20NFF2-B-40A Fuse Ctmt Normal Sump P-52PG20NER2 B-15A Fuse Pump DPLF058 P-52PG20NGF4 Ctmt Normal Sump

.B-15A Fuse Pump DPLF05D Instrument Tunnel P-52PG20NDR2 8-25A Fuse Sump Pump OPLF07B Polar Crane P-52PG1904 HKE13 B-600A Fuse CRDM Control Rod Drive Power Gripper Coils (106 fused P-10A Fuse circuits) 8-30A Fuse Lift Coils (52 fused P-50A Fuse B-150A Fuse circuits)

Low Voltage Power and Control RCDT Heat Exchanger return to RCOT V1v 6HBK04B P-3A Fuse

-HB115 B-3A Fuse H8HV7144 6HBK05A P-3A Fuse RCDT Discharge Viv HB115 B-3A Fuse HBHV7143 Containment Isolation Viv IHBKl9A P-3A Fuse RLO21 B-3A Fuse HBHV7176 4KAG04A P-2A Fuse Hydrogen Purge Makeup Air NG02RFF3 B-1A Fuse Supply Viv KAHV33 Fire Protection Discharge Viv SKCQl55 P-3A Fuse KCXV261 KC2/4A B-3A Fuse CALLAWAY - UNIT 1 3/4 8-25

oet

c s.

TABLE 3.8.-1 (Continued)

CONTAINMENT PENETRATION CONDUCIOR 0VERCURRENT PROTECTIVE DEVICES POWERED PROTECTIVE DEVICE EQUIPMENT NUMBER AND LOCATION Low Voltage Power and Control (Continued)

Fire Protection Discharge Viv OKCQ155'P-3A Fuse KCXV262 KC2/4A 8-3A Fuse Fire Protection Detector SKCQ19X P-3A F use KCHPS261-C02

.KC2/4A -B-3A Fuse Fire Protection Detector

-SKCQ19Y P-3A Fuse KCHPS262-002 KC2/4A B-3A Fuse Fuel Transfer Panel

-6KE501A P-5A Fuse KE124 KE124 B-15A Fuse Fuel Transfer Panel 6KE501A P-5A Fuse KE125 KE125 B-15A Fuse ~

Containment Normal Sump Pump A SliGubA P-2A fuse DPLF05A PGl9Nf f I fl-1A fuse Containment Normal Sump Pump C SLIG06C P-2A luse DPLF05C PGl9NFf2 H-IA fuse Containment Normal Sump Pump B

' 6LFG06B P-2A Fuse DPLF058 PG20NER2 B-1A Fuse Containment Normal Sump Pump D 6LFG06D'P-2A Fuse DPLF050.

PG20NGF4.B-1A Fuse CRDM Cooling Fan D Discharge

~

SGNG03A P-5A Fuse Isolation Damper NG01BJF5 B-3A Fuse GNHZ44 CRDM Cooling Fan C SGNG03C P-5A Fuse Discharge Isolation Damper PGl9GBR2 0-3A Fuse GNHZ43 SIS Test Line Viv IIMK0411 P-IA fuse EMHV8824 R101/

Il.lA F use SIS Test Line Viv

-llMA04l1 P.tA fuse EMHV8881 R101/

11-IA Fuse BIT Test Line Viv

~4EMK04C P-3A Fuse EMHV8843 H101/

li-1A-luse 3/4 8-26 CALLAWAY - UNIT 1 bi a

y TABLE 3.8-1 (Continu:d)

CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES POWERED PROTECTIVE DEVICE EQUIPMENT NUMBER AND LOCATION Low Voltage Power and Control (Continued)

SI Test Line Viv 4EMK04E P-3A Fuse EMHV8871 RL017 8-3A Fuse SI Test Line Viv

~SEMK05A P-3A Fuse RL017 B-3A Fu'se EMHV8889A SI Test Line Viv SEMK05C P-3A Fuse-EMHV8889C RL017 B-3A Fuse.

BIT Test Line Viv f

SEMKOSE P-3A Fuse EMHV8882 RLO18 8-3A Fuse SI Test Line Viv 6EMK05B P-3A Fuse

'EMHV88890 RLO17 B-3A Fuse SI Test Line Viv 6 EMF 05D P-3A Fuse EMHV88898 RLO17 B-3A Fuse Containment Spray Sump Isol Viv IENG02A P-2A Fuse ENHV1 NG018EF3 B-1A Fuse Containment Spray Sump Isol Viv 4ENG02B P-2A Fuse ENHV7' NG028EF3 B-1A Fuse Accumulator Tank Isolation Valve IEPG02A P-2A Fuse EPHV8808A NG01BGF3 8-1A Fuse.

Accumulator Tank Isolation Valve 1EPG028 P-2A Fuse EPHV8808C NG018GF2 8-1A Fuse Accumulator Tank Isolation Valve IEPK02C P-3A Fuse EPHV88088 Indication RL018 8-3A Fuse SI Test Line Viv IEMK04A P-3A Fuse ENHV8823 RL017 B-3A Fuse RHR to charging /SI pump suctions 4EJG048 P-2A Fuse EJHV88048

'NG02AFR3 8-1A Fuse RHR Shutdown Suction Line Isol 1EJG05A P-2A fuse Valve NG01BEF2 8-1A Fuse EJHV8701A 3/4 8-27

'CALLAWAY - UNIT 1 s

k j

TABLE 3.8-1 (Continuea)

CONTAINMENT PENETRATION CCNDUCTOR

~

OVERCURRENT PROTdCTIVE DEVICES PROTECilVE DEVICE POWERED NUMBER AND LOCATION-EQUIPMENT

, Low Voltage Pover and Control (Continued)

RHR Shutdown Suction Line Isolation IEJGOSB P-21, Fuse Valve NG01BDF3 B-1A Fuse EJHV87018 Cont Recirc Sump Isolation Valve JEJG06A P-2A Fuse NG01BFF3 B-1A Fuse EJHV8811A Cont Recirc Sump Isolation Valve

4EJG06B P-2A Fuse NG02BEF2 B-1A Fuse-EJHV8811B Test Line Isol Viv Hot Leg Inj IEJK07A P-3A Fuse Line Solenoid RLO17 B-3A Fuse EJHCV8825 RHR Test Line Viv 1EJK07C P-3A Fuse RL017 B-3A Fuse EJHCV8890A

' 4EJK07B P-3A F use.

RHR Test Line Viv RL01l. B-3A Fuse EJHCV88908 Ctmt Sump Sample Isolation Viv P-lFJY13A'3A Fuse EJHV21 R1011 H-1RLY0lG 15A Breaker NG01ACR119 Ctmt Sump Sample Isolation Viv

'P-4LJYl3B 3A Fuse EJHV22 RLoll-P-4RLYO1G 15A Breaker NG02ACR140 S.G.C Cnt to Nuc Sample Sys Viv P-4BMY010.3A Fuse BMHV22 RLU24 B-4RLYO1H ISA Breaker NG02ACR127 S.G.A Tube Sheet Sample Viv P-4BMYO2A 3A Fuse BMHV35 RLO24 B-4RIY0lH ISA Breaker NG02ACRl2/

S.G.B Tube Sheet Sample Viv P-4HMYO2B 3A Iuse BMHV36 RLO24 H-4RLY0lH ibA Breaker NG02ACR127

.CALLAWAY -'UNii 1 3/4 8-28

)

s h

(

TABLE 3.8-1 (Continued)

CONIAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES POWERED PROTECTIVE DEVICE EQUIPMENT NUMBER AND LOCATION Low Voltage Power and Control (Continued)

S.G.C Tube Sheet Sample Viv P-4BMY02C 3A Fuse BMHV37-RLO24 B-4RLYO1H 15A Breaker NG02ACR127 S.G.D Tube Sheet Sample Viv P-4BMY020 3A Fuse 8MHV38 RLO24 B-4RLY01H ISA Breaker NG02ACR127 RHR Pump RWST Suction Valve IBNG03A-_P-2A Fuse BNHV8812A NG01ACR2 B-1A Fuse RHR Pump RWST Suction valve 4BNG038 ~ P-2A Fuse BNHV8812B NG02AFF4 B-1A Fuse Cont Cooler Isolation Valve IEFG09A P-2A Fuse EFHV33 NG01GCF2 B-1A Fuse 1EFG09C P-2A Fuse -

Cont Cooler Isolation Valve EFHV45 NG01BDF2 B-1A Fuse Cont Cooler Isolation Valve

-4EFG09B P-2A Fuse

-EFHV34 NG028HF3 B-1A Fuse Cont Cooler Isolation Valve 4EFG090 P-2A Fuse EFHV46 NG02BHR2 B-1A Fuse RC Pump CCW Return Cont Isol Viv 4 EGG 06A P-2A Fuse EGHV60 NG02BDF2 B-1A Fuse Cont 1501 Viv CCW Return from 1 EGG 10A P-2A fuse RC pump Ther Barr Viv NG02BDF 3 H-1A Fuse EGHV62 EGHV-60 Bypass Valve Cont Isol Viv lEGG)/A P-2A fu.e

.EGHV130 NGolHill4 B-1A Iuse EGHV-62 Bypass Valve Cont-Isol Viv 1 EGG 17B P-2A Fuse EGHV132 NGOIBHF3 B-LA fuse RHR to Charging /SI Pump Suction Viv IEJG04A P-2A Fuse EJHV8804A

~NG03CHF4 B-1A Fuse 3/4 8-29 CALLAWAY - UNIT 1 i

J TABLE 3.8-1 (Continued) i- ' '

~

CONTAINMENT PENETRATION CON 00CTOR 0VERCURRENT PROTECTIVE DEVICES

---g I

POWERED PROTECTIVE DEVICE 4

EQUIPMENT

'NUPEER AND LOCATION Low Voltage Power and Control (Continued)

Excess Letdown Path to PRT Isol Viv IBBK35A P-3A Fuse BBHV8157A-Rt.001 3A Fuse Excess Letdown Path to PRT Isol Viv 488K358 P-3A Fuse BBHV81578 RL001 6-3A Fuse Pressurizer Safety Viv IBBK37A P-3A Fuse BBHV8010A RLO21 8-3A Fuse Pressurizer Safety Viv 1BBK378 P-3A' Fuse BBHV8010B

.RLO21 B-3A Fuse Pressurizer Safety Viv 4BBK37C P-3A Fuse BBHV8010C RLO21 8-3A Fuse Pressurizer PORV Isolation Valve IBBG39A P-2A Fuse BBHV8000A NG01BBR3 B-1A Fuse a

Filtration Unit Damper 5GRK07A P-3A Fuse GRP0Z5 RtU20-0-1A Iuse Filtration Unit Damper

(>GRK020 P-1A Fuse GRP0Z15 RLO20 8-3A Fuse Ctmt Minipurge Isol Valve lGTK03A P-3A Fuse GTHZ5 RLO20 8-3A Fuse Hydrogen Analyzer Ctmt Isol Viv P-1G5YO10 3A Fuse.

GSHV13 Ridll 8-IRLYO1G 15A breaker NG01ACR119 Hydrogen Analyzer Ctmt Isol Viv l'-lG5Y0lt 3A Fuse GSHV14 Rl011 Il-lRLYO1G 15A Breaker NG01ACR11S Ctat Atmosphere Monitor Isol Viv

P-lG5Y10A 3A Fuse

'GSHV31 RLO20 Il-IRLYOIA 15A Breaker NGUIACR123 s_-

CALLAWAY - UNil 1-3/4 8-30

\\

\\

TABLE 3.8-1 (Continu:d)

CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES POWERED PROTECTIVE DEVICE EQUIPMENTS NUMBER AND LOCATION Low Voltage Power and Control (Continued)

Containment Atm Monitor Isol Viv P-1GSY108 3A Fuse GSHV34 RLO20 B-1RLY01A 15A Breaker NG01ACR123 Loose Parts Simulator P-65QYO2B 15A Breaker PG20GBR238 B-65QY02B 30A Fuse PG20GBR1 Reactor Coolant Sys Level Alarm P-6BBY16A 15A Breaker PG20GBR239 B-6BBY16A 30A Fuse

=PG20GBR1 CRDM Cooling Fan Space Heater P-6GNYO9F 15A Breaker PG20NBR225' B-6GNYO9F 30A Fuse PG20NBR1' CRDM Cooling Fan Space Heater P-6GNYO9H ISA Breaker PG20NBR2?6 B-6GNYO9ii 30A Fuse PG20NBR1 Reactor Cavity Cooling Fan P-6GNYO9K ISA Breaker Space Heater PG20NBR223 B-6GNYO9K 30A Fuse PG20NBR1 Accumulator Isolation Valve P-4EPY02C 15A Breaker Space Heater

-NG02BAR114-B-4EPYO2C 30A Fuse NG02BGR4 Accumulator Isolation Valve P-4EPY020 15A Breaker Space Heater NG028AR115

.B-4EPY020 30A Fuse

~NG02HGR4 Containment Cooler Fan Space P-4GNYHHI ISA Breaker Heater NG02BAR110 B-4GNYO98 30A Fuse NG02BGR4 3/4 8-31 CALLAWAY - UNIT 1

~

Pv 5

TABLE 3.8-1 (Continued)

CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES

-- g PROTECIIVE DEVICE POWERED NUMBER AND LOCATION EQUIPMENT Iow Voltage Power and Control (Continued).

P-4GNYO90 15A Breaker Containment Cooler Fan Space NG028AR111 Heater B-4GNYO90 30A-Fuse NG028GR4 P-4GNY09M 15A Breaker Hydrogen Mixing Fan Space Heater NG02BAR120 B-4GNYO9M 30A Fuse NG02BGR4 P-4GNY09P 15A Breaker Hydrogen Mixing Fan Space NG02BAR121 Heater H-4GNY09P 30A Fuse NG028GR4 P-1GNYO9A 15A Breaker Containment Cooler Fan Space HG01BAR119 Heater

.d LCNYO9A 30A Fuse u

NG01BER3 P-1GNYO9C 15A Breaker Containment Cooler Fan Space NG01BAR120 Heater B-1GNY0SC 30A-Fuse NG016ER3 P-1GNY09L 15A Breaker Hydrogen Mixing Fan Space NG018AR122 Heater B-lGNYO9L 30A Fuse NG018ER3 P-lGNYO9N 15A Breaker Hydrogen Mixing Fan Space NG0lilARl23 Heater ll-lGNYO9N 30A F use NG010ER3 P-5GNYU9E 15A Breaker CRDM Cooling Fan Space Heater PGl9NHf228 B-5GNYO9E 30A Fuse PGl9NHit P-1EPY02A 15A Breaker Accumulator Iso

-NG01BAR116 Valve Space Heater B-1EPYO2A 30A fuse

.NG018ER3 CALLAWAY - UNIT 1 3/4 8-32 c.

m TABLE 3.8-1 (Centinu:d)

CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES

, POWERED PROTECTIVE DEVICE EQUIPMENT

-NUMBER AND~ LOCATION Low Voltage Power and Control (Continued)

Accumulator ISO P-1EPY028 15A Breaker Valve.5 pace Heater NG0]BAR117 B-1EPY028 30A Fuse-NG01BER3 Ctmt Atm Monitor Isol Viv P-4G5Y10C 3A Fuse G5HV36 RLO20 -.

B-4RLY01A 15A Breaker NG02ACR130 Ctmt Atm Monitor-Isol Viv P-4G5Y100 3A Fuse G5HV39 RLO20 S-4RLY01A 15A Breaker NG02ACR130 CROM Cooling Fan Space Heater P-5GNY09G 15A Breaker PGl9NHF229

-B-5GNYO9G-30A Fuse PG19NHF1 Reactor Cavity Cooling Fan Space P-5GNYO9J 15A Breaker-Heater

'PG19NHF225 B-5GNYO9J 30A Fuse PG19NHF1-Rod Position Panel SF109A S$FY11AA P-30A f use PN0711 8-60A Fuse Rod Position Panel SF1098 55FY11A8 P-30A Fuse PN0/10 B-60A Fuse Normal sump Ctmt Isol Viv ILFG08A P-2A Fuse LFFV95 NG01BBR2 B-1A Fuse Instrument Tunnel Sump Pump 5LFG15A P-2A Fuse

'OPLF07A PG19NAF2 B-1A Fuse Instrument Tunnel Sump Pump

-6LFG158 P-2A Fuse DPLF07B PG20NDR2 B-1A Fuse Hydrogen Purge Ctmt Isolation Viv 1GSG03A P-2A ruse G5HV20 NG0tBFF7 B-1A fuse Pressurizer PORV Isol Viv 411HG3911 P-7A F use

-BBHV80008 NGU/IIDI I B-I A F use Call AWAY - IlNil 1 3/4 8-33 si L

o

~

TABLE 3.8-1 (Continued)

CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES POWERED PROILCIIVL'OEVICE.

EQUIPMENT NUMBER AND LOCATION Low Voltage Power and Control (Continued)

IBBK40A P-30A Fuse PZR PORV NK5108 B-3CA Fuse BBPCV455A 4BBK04B P-30A Fuse PZR PORV

.NK4421 8-30A Fuse BBPCV456A 5BGK048.P-3A Fuse Alternate Charging-Path Isol Valv RL001 B-3A Fuse BGHV8147 26BGK04A P-3A Fuse Normal Charging Path Isol Valv

_RLOOL B-3A Fuse BGHV8146 P-5LFY10A 3A Fuse Containment Cooler Drain Valve RLO23 LFLV97 B-5RLY0lH 15A Breaker PGl9GCR21/-

l*-5LI Y10C 3A F use Containment Cooler Drain Valve R1023 LFLV99 B-bRLY0lH'lbA Breaker PGl9GCR21/

l-6LFY10B 3A Fuse Containment Cooler Drain Valve RLO23 LFLV98 B-6RLYO1G 15A Breaker PG20GBR217 P-6LFY10D 3A Fuse

' Containment Cooler Drain Valve RLO23 LFLV100 0-6RLYO1G 15A Breaker PG20GBR217 P-6LFYl/A 3A Fuse Refueling Pool Stand Pipe RLO23 Discharge Valve B-6RLY0lG 15A Breaker LFLV122 l'G20GBR217

-Instrument Tunnel Sump 'Hoisture l'-SilY20A 15A Breaker Sensor

., - l'G l9 Nill /24 Il-5tFY20A.lHA Fu,e TLVF01 I'Gl9NilF I v

CALLAWAY - UNIT 1 3/4 8-34 f

?

661 t

TABLE 3,8-1 (Continu'd)

CONTAINMENT PENETRATION CONOUCTOR OVERCURRENT PROTECTIVE DEVICES POWERED PROIECIIVE DEVICL EQUIPMENT NUMBEF AND LOCATION.

Low Voltage Power and Control (Continued)

Instrument Tunnel Sump Moisture P-6LFY20B 15A Breaker' Sensor PG20NBR216.

TVLF02 B-6LFY208-30A Fuse PG20NBR1 Local Radiation Monitor Power P-550YO6C:15A Breaker Supplies PG19NHF215 SPRIA39-42

-B-550YO6C 30A' Fuse PG19NHF1 Press. Ctmt Isol Viv P-1SJYO10 3A Fuse SJHV128 RLO11 B-IRLYO1G 15A Breaker NG01ACR119 Press. Liq /HL 1&3 Sample Clr Viv

'P-4SJY01A 3A Fuse SJHV5 RLO11 B-4RLY01G 15A Breaker NG02ACR140' Ctmt Purge Isol Viv 1GTK03C P-3A Fuse GTHZ7 RLO20 B-3A Fuse Hydrogen Analyzer Ctmt Sample Viv P-1GSY01E 3A Fuse GSHV14 RLO11 B-1RLY01G 15A Breaker NG01ACR119 Hydrogen Anal Samp Return to Ctmt Viv P-lGSYO1F 3A Fuse GSHV18 RLO11 B-IRLYO1G 15A Breaker NGULACR119 Hydrogen Anal Ctmt Sample Viv P-4GSY01A 3A Fuse GSHV4 RLO11 B-4RLYO1G NG02ACR140 15A Breaker Hydrogen Anal Ctmt Sample Viv P-4GSY01B 3A Fuse GSHV5

-Rioll B-4RtYoLG ISA Breaker NGUIACR140 3/4 8-35 CALLAWAY - UNIT 1 b,b

TABLE 3.8-1 (Continued)

CONTAINMENT PENETRATION CONOUCTOR OVERCURRENT PROTECTIVE DEVICES

--~I PROTECTIVE DEVICE POWERED i

NUMBER AND LOCATION EQUIPMENT Low Voltage Power and Coutrol (Continued)

P-4GSY01C 3A Fuse Hydrogen and Samp Return to Ctmt Viv RL0ll GSHV9 B-4RLY0iG 15A Breaker NG02ACR140 SBBG02B-P-2A Fuse

.RCP 0il Lift PGl9NGR3 B-1A Fuse

' Pump Control

'6BBG02C P-2A Fuse RCP Oil Lift PG20NFF3 B-1A Fuse Pump Control 6BBG020 P-2A Fuse ~

RCP Oil Lift PG20NFF2 B-1A Fuse Pump Control IBBG03A P-2A. Fuse RCP Thermal Barrier Cooler Isol Viv -

NG03CDF4 8 1A Fuse BBHV13 IBBG03B P-2A Fuse RCP Thermal Barrier Cooler Isol Vlv NG03CHF1 B-1A Fuse BBHV14 IBBG03C P-2A Fuse RCP Thermal Barrier Cooler Isol Viv NG03CBF4 B-1A Fuse BBHV15

'1BBG03D P-2A' Fuse RCP Thermal Barrier Cooler Isol Viv NG03CLF2 B-1A Fuse BBHV16 bdBK05A-P-3A Fuse RCP Seal Water Return V1v RL001 B-3A Fuse BBHV8141A

'3BilkO58 P-3A F use RCP Seal Water. Return Viv RLOGI B-3A Iuse BBHV8141B 6lltlKOSC P.lA Fuse ~

R^P Seal Water Return Viv R1091 8-3A luse BBHV8141C 6BBK05D P-3A Fuse RCP Seal Water Return Viv R1001 B-3A Fuse BBHV81410 6BBK0/A P-3A fuse PRT Discharge to RCDT Viv RLu21 B-3A iuse BBHV8031 6BBK0/8 P-3A F use Reactor Makeup Water to PRT Viv RLO21 B-3A fuse BBHV8045

= cal.LAWAY'- UNil 1 3/4 8-36

TABLE 3.8-1 (Continued)

CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES PROTECTIVE'0EVICE POWERED 1

NUMBER AND LOCATION EQUIPMENT Low Voltage Power and Control (Continued) 6BBK08A P-3A Fuse RCOT Ht. Exch. to PRT Viv HB115 B-3A Fuse BBHV7141

'6BBK09A P-3A Fuse RV Flange Leakoff Line to RCOT Viv RLO21 B-3A Fuse BBHV8032 1BBK30C P-3A-Fuse Reactor Vessel Head Vent Viv RLO21 B-3A Fuse BBHV8002A 4BBK300 P-3A Fuse Rx Vessel Head Ve. Viv RLO21 B-3A Fuse BBHV80028 1BBG31A P-2A Fuse PRT Emergency Orain Line Viv NG0180F1 8-1A Fuse BBHV8037A 4BBG31B P-2A Fuse PRT Emergency Drain Line Viv NG02BHR3 8-1A Fuse BBHV80378 1EPK020 P-3A Fuse Accumulator Tank 0 Isol Viv RL018 B-3A Fuse EPHV88080 Indication IEPK02E P-3A Fuse Accumulator Tank A Isol Viv RL018 B-3A Fuse EPHV8808A Indication 1EPK02F P-3A Fuse Accumulator Tank C Isol Viv RL018 B-3A Fuse EPHV8808C Indication 4EPG02C P-2A Fuse Accumulator Tank B Isol Viv NG02BGF3 8-1A Fuse EPNV8808B Indication 4EPG020 P-2A Fuse Accumulator Tank 0 Isol Viv NG02BHF2 B-1A Fuse EPHV88080 Indication.

4EPK02A P-3A Fuse Accumulator Tank A Isol Vlv RL018 B-3A Fuse EPHV8808A Indication 4EPK02B P-3A Fuse Accumulator Tank C Isol Vlv RL018 B-3A Fuse EPHV8808C Indication 4EPK02G P-3A Fuse Accumulator Tank 8 Isol Viv RL018 B-3A Fuse EPHV88088 Indication 4LPK02H P-3A Fuse Accumulator Tank 0 Isol Viv RL018 B-3A Fuse EPHV88080 Indication CALLAWAY - UNIT 1 3/4 8-37 b [I

y

, TABLE 3.8-1 (Continued)

CONTAINMENT PENETRATION CON 00CTOR OVERCURRENT PROTECTIVE DEVICES g

POWEREO'-

PROTECTIVE DEVICE NUMBER AND LOCATION EQUIPMENT Low Voltage Power and' Control (Continued) x

?

3 SEPK03A P-3A Fuse' Accumulator' Nitrogen Supply Viv' EPHV8875A

~

RL018 B-3A Fuse

'~

Accumulator Nitrogen Supply Viv SEPK03B P-3A Fuse.

EPHV8875C RL018.8-3A Fuse SEPK03C P-3A Fuse t.

Accumulator Test Line Viv

.RL018 8-3A Fuse EPHV8877A t

.~

Reactor' Vessel Head Vent Viv 4BBK308 P-3A Fuse RLO21 B-3A Fuse BBHV8001B SEPK030 P-3A Fuse Accumulatcr Test line Viv RL018 B-3A Fuse EPHV8877C~~

SEPK03E P-3A Fuse-Accumulator Water Fill Line Viv RL018 B-3A Fuse EPHV8878A Accumulator Water Fill Line Viv 5EPK04A P-3A Fuse RL018 6-3A Fuse EPHV8878C Accumulator Test Line Viv

-5EPK04B P-3A Fuse RL018 B-3A Fuse EPHV8879A SEPK04C P-3A Fuse Accumulator Test Line Viv I

RL018 8-3A Fuse EPHV8879C v

Accumulator Test Line Viv 6EPK040 P-3A Fuse

~ y EPHV88798 RL018 B-3A Fuse Accumulator Test Line Viv 6EPK04E P-3A Fuse RL018 B-34 Fuse EPHV88790 i

Accumulator Nitrogen Supply Viv GEPK05A P-3A Fuse RL018 B-3A Fuse EPHV88758 Accumulator Nitrogen Supply Viv 6EPK058 P-3A Fuse RL018 8-3A Fuse EPHV88750 Accumulator Test Line Viv 6EPK05C P-3A Fuse EPHV88778 RLO18 B-3A Fuse Accumulator Test Line Viv 6EPK050 P-3A Fuse EPHV88770 RL018 B-3A Fuse CALLAWAY - UNIT 1 3/4 8-38 s

I

& CL t

4

. TABLE 3.8-1-(Continued)

CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES

. POWERED PROIECTIVE DEVICE-NUMBER AND LOCATION _

EQUIPMENT Low Voltaae' Power and Control (Continued)

' Accumulator Water Fill Viv 6EPK05E P-3A Fuse EPHV88788

-RL019 8-3A Fuse-Accumulator Water Fill Viv 6EPK05F.P-3A Fuse.

EPHV88780 LRL018 8-3A Fuse P-4SJY01B 3A Fuse.

Press. Vapor. Cont. Iso. Space.Viv.

SJHV12 RL011

.B-4RLY01G 15A Breaker NG02ACR140 P-4SJY01C'1A Fuse-Accums Sample Cont Iso! Viv

$JHV18-RL0l l' 6-4RLYO1G 15A Breaker NG02ACR140 Accumulator Sample Line'Viv P-SSJY038 3A Fuse.

SJHV16 RP211 B-SRPYO90 15A Breaker LPG 19NHF236 Accumulator Sample Line Viv P-5SJYO3C 3A Fuse SJHV17' RP211 8-5RPY090 ISA Breaker PG19NHF236' Accumulator Sample Line V1v P-5SJYO4B 3A Fuse SJHV14 RP211 6-5RPYO90 15A Breaker PGl9NHf236 Accumulator Sample Line Viv P-bSJ0Y4C.3A Fuse SJHV15 Rp21l B-bRPYU'JD ISA Breaker PGI9NHF236' HL Sample 3 V1v P-ISJYO6B 3A Fuse SJHV4 RP332_'

. B-IRPYO9F 15A Breaker 74G01BAR140 HL Sample 1 V1v P-4SJYO6A-3A Fuse SJHV3

.RP333 B-4RPYO9F 15A Breaker NG020AR140' CALLAWAY - UN!r 1 3/4 8-39 c

h P

h

m TABLE 3.8-1 (Centinund)

CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES POWERED q

PROIECTIVE DEVICE.

EQUIPMENT NUMBER AND LOCATION Low Voltage Power and Control (Continued)

Press Liquid Space Samp Isol V1v P-SSJYO6C 3A Fuse SJHV20 RP211.

B-5RPYO90 ISA Breaker PG19NHF236.

S.G. A Out to Nuc Sample Sys Viv P-4BMY01A 3A fuse BMHV19 RLO24 B-4RLY01H 15A Breaker NG02ACR121 S.G. B Out to Nuc Sample Sys Viv P-4BMY018 3A Fuse BMHV20 RLO24.

B-4RLYO1H 15A Ereaker NG2ACR127 S.G. C Out to Nuc Sample Sys Viv P-4BMY01C 3A Fuse BMHV21 RLO24 8-4RLYO1H 15A Breaker

.s NG02ACR127 CRDM Cooling Discharge Damper P-5GNY08A 3A Fuse GNHZ71 RLO20' B-5RLY01L-15A Breaker PGl9GCR230 CRDM Cooling Discharge Damper P-5GNY08C 3A Fuse GNHZ73 RLO20 8-5RLY01L'15A Breaker

G190CR230 CRDM Cooling Discharge Damper P-6GNYO8A-3A Fuse GNHZ72 RLO20 B-6RLY01J ISA Breaker PG20GBR222 CRDM Cooling Discharge Damper P-6GNYO8C 3A Fuse GNHZ74 RLO20 B-6RLY01J ISA Breaker PG20GBR222 Normal Letdown Isolation V1v 5BGK10A P-3A Fuse BGLCV459 RL001 B-3A Fuse

~-

CAllAWAY - UNil 1 3/4 8-40 I

(

I ABLE' 3.8-1_(Coginued)

CONTAINMENT PFNETRAIION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES POWERED PRolECTIVE' DEVICE EQUIPMENT NUMBERfAND' LOCATION-Low Voltage Power and Control (Continued)

Normal Letdown Isolation V1v 5BGK10B P-3A Fuse 8GLCV460 RLO0l'B-3A Fuse Pressuri'zer Spray Viv SBGK19A P-3A Fuse BGHV8145 Rtn01 8-3A Fuse Excess Letdown Line Isolation Viv 6BGK20A P-3A Fuse BGHV8143 RL001 B-3A Fuse Letdown Orifice Isolation Viv 58GK35A P-3A Fuse

-8GHV8149A RL001 B-3A Fuse Letdown Orifice Isolation Viv 58GK358 P-3A Fuse BGHV81498 RL001 B-3A Fuse Letdown Orifice Isolation Viv 5BGK35C P-3A Fuse BGHV8149C R1001 B-3A Fuse Letdown Containment Isolation V1v IBGK36A P-3A Fuse RLOOl B-3A Fuse 8GHV8160 Seal Water Ctmt Isolation V1v IBGG38A P-2A Fuse NG018BF3 B-1A Fuse 8GHV8112' Excess Letdown /RCS Isolation Viv 18GK48C P-3A Fuse RL001 8-3A Fuse 3GHV8153A Excess Letdown /RCS Isolation Viv 18GK48D P-3A Fuse RL001 B-3A Fuse BGHV8154A Excess Letdown /RCS Isolation Viv 48GK48A P-3A Fuse BGHV81538

.Rt001 8-3A Fuse Excess Letdown /RCS Isolation Viv 48GK488-P-3A Fuse BGHV81548 R1001 B-3A Fuse 488Gl?'A P-2A fuse RHR Pump Suction Isolation Valve' 88PV8702A NG02BCF2 B-1 A f use RHR Loop 2 Inlet 4BBG12B P-2A Fuse Isolation Valve 88PV87028 NG02BBF3 8-1A Fuse Ctmt Isol Nitrogen Supply to FCT Viv 188K13A P-3A Fuse 88HV8026 RLO21 B-3A' Fuse CALLAWAY - UNIT 1 3/4 8-41 e -,

m s

2-6.

9 TABLE 3.8-1'(Continued)

CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROFECTIVE DEVICES POWERED PROTECTIVE DEVICE NUMBER AND-LOCATION EQUIPMENT Low Voltage Power and Control (Continued) 1588K14C P-3A Fuse.

RCP Standpipe Makeup Viv RK021 3-3A fuse 88LCV180 5BBKL40 P-3A Fuse

-RCP Standpipe Makeup Viv sRK021.d-3A luse 88LCV181 6BBK14A P-3A Fuse RCP Standpipe Makeup Viv RLO21 B-3A Fuse-88LCV178 6BBK14B P-3A Fuse RCP Standpipe Makeup Viv

-RLO21 B-3A fuse 88LCV179 5BBK158 P-3A Fuse Reactor Coolant Loops RLO21 B-3A-Fuse-Instrumentation 5BBK15C P-3A Fuse Reactor Coolant Loops RLO21 B-3A Fuse Instrumentation Reactor Coolant Loops 6BBK150 f-3A F use.

RLO21 0-3A luse Instrumentation

-688K15E P-3A Fuse Reactor Coolant Loops Instrumentation RL021 H-3A Fuse Pressurizer Spray Valve 588K19A P-3A fuse 88PCV4558

'RLOO2 B-3A Fuse Pressurizer Spray Valve 588K198 P-3A Fuse 88PCV455C RLOO2 B-3A Fuse Reactor Vessel Head Vent Viv 188K30A P-3A Fuse 88HV8001A RLO21 8-3A fuse CRDM Cooling Fan 8 bGNGO:lB P-5A Fuse Discharge Isolation Damper NG02BJF5 B-3A Fuse GNHZ42 CROM Cooling Fan A 6GNG01D P-SA fuse Discharge Isolation Damper l'GPOGAR2 0 IA fuse GNHZal Cavity Cooling Fan Discharge Damper

$GNG04A P 6A fuse GNHZ47 PG19NAF4 6-4A Fuse v

CALLAWAY - UNIT 1 3/4 8-42 k

(.

.o

-I ABL E 3. 8-1,(Cuntinued]

CONIAINMENI PtNEIRAi10N CONUUC10R OVERCURRENT PROTECTIVL DEVICES POWERED PROTECTIVE DEVICE ~

EQUIPMENT

- NUMBER AND LOCATION

-Low Voltage Power and Control (Continued)

Cavity Cooling Fan Discharge Damper 6GNG048 P-6A Fuse GNHZ48 PG20N8FS,0-4A Fuse RCDT Vapor Space CTMT Isol Viv lHBK03A P-3A Fuse HBHV7126 RLO21 B-3A fuse RCOT Vapor Space CTMT Isol Viv 6HBK04A P-3A Fuse HBHV7127 HB115 B-3A Fuse

~

Accumulator Tank Discharge

- SEPYO78 P-3A F use.

Valve Position Switch RPO43 B-15A CB EPHV8808DA EPHV8808BA Accumulator Tank Discharge 6EPYO/A P-3A Fuse Valve Position Switch RPO4410-15A CB-1 EPHV8808AA EPHV8808CA CTMT Minipurge Exhaust 6GTY12A P-LSA. Breaker Isolation Damper PG20GBR134 8-20A Fuse GTHZ41 CTMT Minipurge Exhaust 6GTY12A P-15A Breaker Isolation Dampe.-

PG20GBR134 B-20A Fuse GTHZ42 in-Core Neutron Monitoring-Drive P-55RYO9A SA Fuse Unit Heater SR051 SR01A. 8 B-55RYO9A 20A Breaker PGi9GEf6 In-Core Neutron Monitoring Drive P-%RYO9A SA~ Fuse Unit Heater SR057-SR01C, D B-55RYO9A 20A Breaker PGt9Gil6 p

3/4 8-43 (CALLAWAY - UNIT 1 k