ML20116E362

From kanterella
Jump to navigation Jump to search
Proposed Tech Specs Re Engineered Safety Features Actuation Sys Instrumentation & 3/4.8.1,ac Sources
ML20116E362
Person / Time
Site: Callaway 
Issue date: 11/03/1992
From:
UNION ELECTRIC CO.
To:
Shared Package
ML20116E351 List:
References
NUDOCS 9211090140
Download: ML20116E362 (26)


Text

{{#Wiki_filter:, '. ~ ..[.' TABLE 3.3-3 (Continued) ENGINEERED SAFETY FEATURES ACTUATION SYSTEM INSTRUMENTATION n '154 .E MINIMUM .N-E TOTAL NO. CilANNELS CHANNELS APPLICABLE 5. h FUNCTIONAL UNIT OF CllANNELS TO TRIP OPERABLE MODES ACTION >.o 8. Loss of Power' .q a. 4;kV' Bus Undervoltage 4/ Bus 2/ Bus 3/ Bus 1,2,3,4/[6 19* 70 ' Loss of Voltage oo h - b. 4'kV Bus Undervoltage'- 4/ Bus 2/ Bus 3/ Bus 1,2,3,4/[' g -Grid Degraded Voltage mmu 9. Control' Room Isolation a. Manual Initiation 2 1 2 All 26**** b. Automatic Actuation 2 1 2 1,2,3,4 26-M Logic and Actuation '[ Relays (SSPS) i 'l-c. Automatic Actuation Logic 2 1 2-All 26**** and' Actuation Relays (BOP)ESFAS) d. Phase "A" Isolation See Item 3.a above for all Phase'"A" Isolation initiating functions i tog Agg,,. g-i,.fug and requirements. Load Sep,,eed Sevencer ce,- gy_ ~. ' 2-1/ Train 1/ Train 2-1/ Train 1, 2, 3, 4,S[d25 l 10. Selid-St m L aa 11. Engineered Safety Features 'g R-Actuation System Interlocks l a" a. Pressurizer Pressure, 3 2 2 1,2,3 20 i-y- P-11 g. b. Reactor Trip, P-4' 4-2/ Train 2/ Train 2/ Train 1, 2, 3 22 i I e . u.. . ~..,d

D TABLE 3.3-3 (Continued) c TABLE NOTATION

  1. Trip function may be blocked in this MODE below the P-11 (Pressurizer Pressure Interlock) Setpoint.

t

    1. Trip function automatically blocked above P-11 and may be blocked below P-11 when Safety injection on low steam line pressure is not blocked.

H# Trip function may be blocked just before shutdown of the last operating - main feedwater pump and restored just after the first main feedwater pump is pu't into service (following its startup trip test).

  • The provisions of Specification 3.0.4 are not applicable.

"One in Separation Group 1 and one in Separation Group 4.

      • The de-energization of one train of BOP-ESFAS actuation logic and actua-tion relays renders two of the four channels inoperable. Action Statement 21 applies to both Functional Units 6.c and 6 9 in this case.
        • The p>rovisions of Specification 3.0.4 are not applicable in MODES S and 6.

l [MSERT ACTIC-STATEMENTS ACTION 14 - With the number of OPERABLE channels one less than the Minimum Channels OPERABLE requirement, be in at least HOT STANDBY within 12 hours and in-COLD SHUTDOWN within the following 30 hours; however, one channel may be bypassed for up to 4 -hours for surveil-lance testing per Specification 4.3.2.1, provided the other channel is OPERABLE. ACTION 15 - With the number of OPERABLE channels one less than the Total Number --) of Channels, operation may proceed until performance of the next required ANALOG CHANNEL OPERATIONAL TEST provided the inoperable channel is placed in the tripped condition within-l hour. ACTION 16 - With the number of OPERMLE channels one less than the Total Number of Channels, operation may proceed provided the inoperable channel is placed in the bypass condition and the Minimum Channels OPERABLE requirement is met. One additional channel may be bypassed for up to 4 hours for surveillance testing per Specification 4.3.2.1. ACTION 17 - With less than the Minimum Channels OPERABLE requirement, operation may continue provided i.he containment purge supply and exhaust valves are maintained closed. ACTION 18 - With the number of OPERABLE channels one less than the Minimum Channels OPERABLE requirement, restore the inoperable channel to OPERABLE status within 48 hours or be in at least HOT STANDBY within the next-6 hours and in COLD SHUTDOWN within' the following 30 hours. ACTION 19 - With the nt.mber of OPERABLE channels one less than the Total Number of Channels STARTUP and/or POWER OPERATION may proceed provided the following conditions are satisfied; The inoperable channel is placed in the tripped condition a. within 1 hour, and 1.) CALLA'nAY - UNIT I 3/4 3-20 Amendment No. 26,U,69 Corrected I

_...._. _._ -.....~.

.=

OL-1130 i INSERT +0nly the shutdown portion of one sequencer is required to be OPERABLE in Modes 5 and 6 which corresponds to tho' OPERABLE Emergency Diesel Generator. t ++ Operability is only required for associated OPERABLE bus in Modes 5 and 6. k i l l.- h>pg -e-g, w r aqpsi.t, .m 9 e a w y p mw

~~ N g:P

} --- 4 g q TABLE 3.3-3,(Continued) Q / AC110H STATEMENTS (Continued) b. The Minimum Channels OPERABLE recuirement is met: however, the inoperable channel may be bypassed f or up to 2 hours for surveillance testing of other channels per Specification 4.3.2.1. ACTION 20 - With less than the Minimum Channels OPERABLE, within i hour determine by observation of the associated permissive annunciator window (s) that the interlock is in its required state for the existing plant condition, or apply Specification 3.0.3. ACTION 21 - With the number of OPERABLE channels one less than the Minimum Channels OPERABLE requirement, be in at least HOT STANDBY within 6 hours and in at least HOT SHUTOOWN within the following 6 hours; however, one channel may be bypassed for up to 2 hours for surveillance testing per Specification 4.3.2.1 provided the other channel is OPERABLE. ACTION 22 - With the number of OPERABLE channels one less than the Total Number of Channels, restore the inoperable channel to OPERABLE status within 48 hours or be in at least HOT STSDBY within the next 6 hours and in at least HOT SHUT 00WN within the following 6 hours. ACTION 23 - With the number of OPERABLE channels one less than the Total Number of Channels, restore the inoperable channel to OPERABLE status within 48 hours or declare the associated valve inoperable and take the ACTIGH required by Specification 3.7.1.5. ACTION 24 - With the number of OPERABLE channels one less than the Minimum Channels OPERABLE recuirement, declare the affected auxiliary feedwater pump inoperable and take the ACTION required by Specification 3.7.1.2. ACTION 25 - With the number of OPERABLE channels one less than the Minimum Channels OPERABLE requirement, declare the,affec-ted dieseA generator and off-site power sourceAnoperaDie and take the ACTION required by Specification 3('8.1.13 o r 3. 9.1. 2. Y ACTION 26 - With the number of OPERABLE channels one less thin'the Minimum Channels OPERABLE requirement, restore the inoperable channel to OPERABLE status within 48 hours or initiate and maintain opera-tion of the Control Room Emergency ventilation System. ACi!ON 27 - With the number of OPERABLE channels one less than the Minimum Channels OPERABLE requirement, be in at least HOT STANOBY within 12 hours; however, one channel may be bypassed for uo to 4 hours for surveillance testing per Specification 4.3.2.1 provided the other channel is OPERABLE. ACTION STATE. ENTS 28 THROUGH 31 ARE LOCATED ON OTHER TABLES.) M (NOTE: CALLAWAY - UNIT 1 3/4 3-21 Amendment No. 64

w .~- .) "l TABLE 3.3-4 (Continued) E ENGINEERED SAFETY FEATURES ACTUATION SYSTEM INSTRUMENTATION TRIP SETPOINTS l E"-< i TOTAL SENSOR TRIP Alt 0WABLE FUNCTIONAL UNIT ALLOWANCE (TA) Z. ERROR (5) SETP0lNT VALUE g Z 8. Loss of Power (Continued) W f b. 4 kV Undervoltage -Grid Degraded Voltage N.A. H.A. H.A. 104.5V 104.5+2.6,-0V (120V Bus) (120V Bus) w/119s delay w/119 1 11.6s delay 9. Control Room Isolation a. Manual Initiation N.A. N.A. H.A. N.A. N.A. U b. Automatic Actuation N.A. N.A. N.A. N.A. H.A. T Logic and Actuation O Relays (55PS) l c. Automatic Actuation Logic and Actuation Relays (00P ESTA5) H.A. N.A. N.A. N. A. H.A. i i d. Phase "A" Isolation See Item 3.a. above for all~ Phase "A"' Isolation Trip Setpoirits and A110wable ~ Values. W

10. Sulid Stoic Leed Seque;.cer NJ.

N.A. H. A.' N.A. H.A. /ca d SAadolce Emee,eng* ra ss Joynee,.

ty
11. Engineered Safety features Actuation

,,g - 3 TPr l System Interloc a. Pressurizer Pressure, j!d P-11 H.A. HA H.A. $ 1970 psig i 1981 psig

g i

b. Reactor Trip, P-4 H.A. M. A. H.A. N.A. ,H.A. ]

O ?" TjABLE 4.3-2 (Continued) p,r ENGINEERED SAFETY FEATURES ACTUATI0rt SYSTEM IflSTRUMENTAT10f4 SURVEILLANCE REQUIREMENTS 2 U TRIP ANALOG AClUATING MODES CllAtlNEL DEVICE MASTER SLAVE FOR W!lli11 i CitANNEL CilANNEL OPERATIONAL OPERATIONAL ACTUAll0N RLLAY RELAY SURVEILLANCE FUNCTIONAL UNIT CilECK CAllDRATI0tt TEST TEST LOGIC TEST TEST TEST 15 Rtqu_ IRED 6. Auxiliary feedwater (Continued) f. Loss-of-Of fsite Power N.A. R fl. A. M ti. A. ft. A. N.A.

1. 7. 3 9

Trip of All Main N.A. N.A. N.A. R N.A. fl. A. N.A. l.2 feedwater Pumps, M Y Pump Suction Pressure-R H fl. A. N.A. ft. A. fl. A. 1, 7, 3 h. Auxiliary feedwater S y Low 7. Automatic Switchover to Contairinent Sump a. Automatic Actuation N.A. N.A. N.A. N.A. It( 1) it(1) Q(3)

1. ?, 3, 4 Logic and Actuation Relays (SSPS) 7-M b.

RWST Level - Low-Low S R Q N.A. ft. A. fl. A. ft. A. I, 2, 3 -4 j R Coincident With M Safety injection See item 1 above for all Safety injection Surveillance Requirenents. ?. 8. Loss of Power 2 1,2,3.4,[G o a. 4 kV Undervoltage-N.A. R fl. A. M ll. A. N.A. N.A. b ' Loss of Voltage p a b. 4 kV Undervoltage-Grid Degraded Voltage ll. A. R ti. A. M ti. A. fl. A. N.A.

1. 7, 3, 4[6

1ADLE 4.3-2 (Continued) 9 [NGIN[ERED SAr[TY TEATURES ACTUATION SYST[M INSTRUMINTATION SURVEILLANCE R[QUIRIMENis E TRIP ANALOG ACIUAllNG MOD [5 CllANNI L DEVICE MA51( R St AV[ f O R M ilfit O CilANNE L CllANNTL OPIRATIONAL DP[RATIGNAL ACit!Afl0N RtiAY RIiAY StfRVL 111 ANCE gfUNCTIONAL UNIT CHECK CALIBRAil0N 1EST TE ST LOGIC T[5T if 5T IIst 15 RIQtilRID 9. Control Room isolation a. Manual Infllation M.A. H.A. N.A. R N.A. N.A. N.A. All b. Automatic Actuation N.A. N.A. N.A. H.A. H(1) H(1) Q(3) 1, 2, 3, 4 Logic and Actuation Relays (55PS) c. Automatic Actuation R Logic and Actuation Relays (BOP ESTAS) N.A. N.A. N.A. N.A. M(1)(2) N.A. N.A. All

  • 1' d.

Pha "A" Isolation See item 3.a. above for all Phase "A" Isolation Surveillance Requirements. 10. 61 l ' "' - te Le ed 'e encer M.A. M.. N.A. N.A. N(1)(2) N.A. N. A.' 1, 2, 3, 4, f (,, v 11. Ie Net [aNe7 /""" Actuation System _Interloc h a. Pressurizer Pressure, N.A. R fl N.A. N.A. N.A. N.A. 1, 2, 3 l P-11. b. Reactor Trip, P-4 H.A. M.A. N.A. R N.A. H.A. N.A. 1, 2,. 3 TABLE NOTAT103 R S (1) E*ach train shall be tested at least every 62 days on a STAGCCRID TEST BASIS. (2) Continuity check may be excluded from the ACTUATION LOGIC Il5T. e P (3) Except Relays K602 K620, K622, K624. K630 K140, and K741, which shall be tested at least once per 18 montte y during refueling and during each COLD $ltVIDOWN exceeding 24 hours unless they have been tested within the ~ previous 90 days, lhe specified 18 month frequency may be waived for. Cycle I provided the surveillance is performed prior to : g restart following the first refueling outage or June 1,:198f,, whichever occurs first. Ihe provisions of Specification 4.0.2 are resst'frem performance of this surveillance. TA13252T -*9 e T. w t-h:- L.--.

OL-1130 INSERT +0nly the shutdown portion of one sequencer is required to bc OPERABLE in Modes 5 and 6 which corresponds to the OPERABLE Emergency Diesel Generator. ++ Operability is only required for associated OPERABLE bus in Modes 5 and 6. w ^ --~-

~ ~. REVIS ay l Ek.ECTRICALPOWERSYSTEMS C. SOURCES 4 i L!MITING CONDITION FOR OPERATION 3.8.1.2 As a minimura, the following A.C. electrical power sources shall be OPERA 8LE: a One circuit between the offsite transmission network and the Onsite Class 1E Distribution System, and .i D. One diesel generator with: 1) A day tank containing a minimum volume of 390 gallons of fuel, 2) A fuel storagt system containing a minimum volume of 85,300 gallons of fuel, and 3) A fuel transfer pump. APPLICA8ILITY: MODES 5 and 6. ACTION: With less than the above minimum required A.C. electrical power sources )' OPERA 8LE, inneciately suspend all operations involving CORE ALTERATIONS, positive r$ activity changes, movement of irradiated fuel, or crane operation l with loads over the spent fuel pool. In aedition, Ghen in MODE 5 with the reactor coolant loops not filled, or in H00E 6 with the water level less than l 23 feet above the reactor vessel flange, immediately initiate corrective action i to restore the required sources to OPERA 8LE status as soon as possible. SURVE!LLANCE REOUIREMENTS 4.8.1.2 The above required A.C. electrical power sources shall be demonstrated OPERABLE by the performance of each of the requirements of Specifications

4. 8.1.1.1. 4. 8.1.1. 2 (except for Speci ficatbj4.8.1.1.2a.5)), and 4.8.1.1.3.

m ~v f '%f*' " #fBj, 6), to) _a 12) w me. Loca qu.meev ,y 4 0. u. 25. 5 .p w& l m 1 I-CALLAWAY - UNIT 1 3/4 8-8

9 Re-tvoed Technical Specification Paces. Page 3/4 3-19 Page 3/4 3-20 Page 3/4 3-21 Page 3/4 3-27 Page 3/4 3-36(a) Page 3/4 '3-37 Page 3/4-8-8 d I I L. j -. l^ 9 i

)

m i. TABLE 3.3-3 (CO!TTIITJED) ENGINEERED SAFETY FEATUPES ACTUATION SYSTEM INSTFUMENTATION MINIMOM TOTAL NO. CHANNELS CHANNELS APPLICABLE , FUNCTIONAL Ut_HT OF' CHANNELS TO TRIP OPERABLE MODES ACTION B. Loss of Power a. 4 kV Bus Undervoltage 4/ Bus 2/ Bus 3/ Bus 1, 2, 3, 4, 5++, 6++ 19* -Loss of Voltage b. 4 Kv Bus:Undervoltage 4/ Bus 2/ Bus 3/ Bus 1, 2, - 3, 4, 5++, 6++ 19* -Grid Degraded Voltage 9. Control Room Isolation .a. Manual Initiation 2 1 2 All. 26**** 'b. Automatic Actuation '2 1 2 1, 2, 3, 4 26 Logic.and Actuation Relays' (SSPS) c. Automatic Actuation Logic 2 1 2 All 26**** and Actuation Relays (BOP ESFAS) d. Phase."A" Isolation-See Item-3.a above for all Phase "A" Isolation initiating functions and . requirements. 10. Load Shedder '2-1/ Train 1/ Train 2-1/ Train 1, 2, 3, 4, 5+, 6+ 25 Emergency-' Load Sequencer 11. Engineered' Safety. Features Actuation System Interlocks a. Pressurizer Pressure, 3 2-2 1, 2, 3 20 P-11 b. Reactor Trip, P-4 4-2/ Train 2/Trau 2/ Train 1, 2, 3 22 -1 s 6 r d, m-m..~1

IAB.LE_3J-3 (Continued) 1 A EJ1Q_TAflON Trip function may be blocked in this MODE below the P-11 (Pressurizer Pressure Interlock) Setpoint. Trip function automatically blocked above P-11 and may be blocked below P-11 when Safety injection on low steam line pressure is not blocked. Trip function may be blocked just before shutdown of the last operating main feedwater pump and restored just after the first main feedwater pump is put into service (following its startup trip test). The provisions of Specification 3.0.4 are not applicable. One in Separation Group 1 and one in Separation Group 4. The de-energization of one train oi BOP ESFAS actuation logic and actuation relays renders two of the four channels inoperable. Action Statement 21 applies to both Functional Units 6.c and 6.g in this case. The provisions of Specification 3.0.4 are not applicable in Modes 5 and 6. + Only the shutdown portion of one sequencer is required to be OPERABLE in Modes 5 and 6 which corresponds to the OPERABLE Emergency Diesel Generator. ++ Operability is only required for associated OPERABLE bus in Modes 5 and 6. ACTION STATEMENTS 3 ACTION 14 - With the number of OPERABLE channels on less than the Minimum Channels OPERABLE requirement, be in at least HOT STANDBY within 12 hours and in COLD SHUTDOWN within the following 30 hours; however, one channel may be bypassed for up to 4 hours for surveillance testing per Specification 4.3.2.1, provided the other channelis OPERABLE. ACTION 15 - With the number of OPERABLE channels one less than the Total Number of Channels. operation may proceed until performance of the next required ANANLOG CHANNEL OPERATIONAL TEST provided the inoperable channel is placed in the tripped condition within 1 hour. ACTION 16 - With the number of OPERABLE channels one less than the Total Number of Channels, operation my proceed provided the inoperable channel is placed in the bypass condition and the Minimum Channels OPERABLE requirement is met. One additional channel may be bypassed for up to 4 hours for surveillance testing per Specification 4.3.2.1 ACTION 17 - With less than the Minimum Channels OPERABLE requirement, operation may continue provided the containment purge supply and exhaust valves are maintained closed. CALLAWAY - UNIT 1 3/4 3-20 Amendment No. 26,64,69 Corrected

-IABLE 3.3 3 (continued) _ ACTION STATEMENTS (continued) ACTION 18 - With the number of OPERABLE channels one less than the Minimum Channels OPERABLE requirement, restore the inoperable channel to OPERABLE status within 48 hours or be in at least HOT STANDBY within the next 6 hours and in COLD SHUTDOWN within the following 30 hours. ACTION 19 - With the number of OPERABLE channels one less than the Total Number of Channels, STARTUP and/or POWER OPERATION may proceed providr>d the following conditions are satisfied; a. The inoperable channelis placed in the tripped condition within 1 hour, and b. The Minimum Channels OPERABLE requirement is met; however, the inoperable channel may be bypassed for up to 2 hours for surveillance testing of other channels per Specification 4.3.2.1. ACTION 20 - With less than the Minimum Channels OPERABLE, within 1 hour determine by observation of the awociated permissivo annunciator window (s) that the interlock is in its required state for the existin0 plant condition, or apply Specification 3.0.3. ACTION 21 - With the number of OPERABLE channels one less than the Minimum Channels OPERABLE requirement, be in at least HOT STANDBY within 6 hours and in at least HOT SHUTDOWN within the following 6 hours; however, one channel may be bypassed for up'to 2 hours for surveillance testing per Specification 4.3.2.1 provided the other channelis OPERABLE, ACTION 22 - With the number of OPERABLE channels one less than the Total Number of Channels, restore the inoperable channel to OPERABLE status within 48 hours or be in at least HOT STANDBY within the next 6 hours and in at least HOT SHUTDOWN within the following. 6 hours. l ACTION 23 - With the number of OPERABLE channels one less than the Total u Number of Channels, restore the inoperable channel to OPERABLE status within 48 hours or declare the associated valve'inoperables and take the ACTION required by Specification 3.7.1.5. ACTION 24 - With the number of OPERABLE channels one less than the Minimum Channels OPERABLE requirement, declare the affected auxiliary feedwater pum[ noperable and take the ACTION required by -l Specification 3.. 1.2. j l -CALLAWAY.- UNIT 1 3/4 3-20a Amendment No. 64 -)

4. 4 .4 4 TABLE 3,3 3 bontinued) ACTION STATEMENTS (continued) ACTION 25 - With the number of OPERABLE channels one less than the Minimum Channels OPERABLE requirement, declare the affected diesel generator and off-site power source inoperable and take the ACTION required by Specification 3.8.1.1 or 3.8.1.2. ACTION 26 - With the number of OPERABLE channels one less than the Minimum Channels OPERABLE requirement, restore the inoperable channel to OPERABLE status within 48 hours or initiate and maintain operation of the Control Room Emergency Ventilation System. ACTION 27 - With the number of OPERABLE channels one less than the Minimum Channels OPERABLE requirement, be in at least HOT STANDBY within 12 hours; however, one channel may be bypassed for up to 4 hours for surveillance testing per Specification 4.3.2.1 provided the other channelis OPERABLE. (NOTE: ACTION STATEMENTS 28 THROUGH 31 ARE LOCATED ON OTHER ' TABLES.) l t l-I l l ' l 1: CALLAWAY - UNIT 1 3/4 3-21 Amendment No. 64

'V ? TABLE 3.3-4 (CO!FINUED) ENGINEERED SAFETY FEATURES ACTUATION SYSTEM INSTRUMENTATION TRIP SETPOI!TTS TOTAL SENSOR ' TRIP ALLO *dABLE ? FUNCTIONAL UNIT ' ALLO

  • DANCE (TA)

Z ERROR ( S_J_ SETPOINT VALUE ~8. Loss'of Power (Continued) b. 4 kV Undervoltage -' Grid Degraded Voltage' N.A. N.A. N.A. 104.5V 104.5+2.6, (120V Eus) (120V Bus) w/119s delay w/119111.6s delay. 9. Control Room Isolation- 'a. Manual Initiation N1 N.A. N.A. N.A. N.A. b. Automatic Actuation N.A. N.A. N.A. N.A. N.A. Logic and' Actuation' Relays (SSPS) c.

Automatic ~ Actuation' N.A.

N.A. N.A. N.A. N.A. Logic:and Actuation Relays. (BOP ESFAS)' d. PhaseA". Isolation .See. Item 3.a. above for all Phase "A" Isolation Trip Setpoints and Allowable ~. Values.

10.. Load' Shedder-Emergency N ; A.'

N.A, N.A. N.A. N.A. Load Sequencer-11. Engineered; Safety ' Features Actuation System' Interlocks. 'T. Pressurizer-Preisure, N.Al N.A. N.A. 5 1970 psig $_1981 psig-t ~ -P-11 (' i h-b. ' Reactor Trip, P-4 N.A; N.A. .N.A. N.A. .N.A i s-L o ,-c, .,+ w.-

e,. '.+. . :4 o -TABLE 4.3-2 (Continued). 4 ENGINEERED ' SAFETY FEATURES ACTUATION SYSTEM INSTRUMEITTATIOh SURVEILLANCE REOUIREMEITTS TRIP ICDES-ANALOG ACTUATING FOR WHICH c CHANNEL DEVICE MASTER- -SLAVE SURVEILLANCE l CHANNEL CHANNEL ' OPERATIONAL OPERATIONAL ACTUATION' REIAY REIAY ' IS FUNCTIONAL UNIT CHECK CALIBRATION TEST TEST LOGIC TEST TEST' TEST REOUIRED-6. Auxiliary Feedwater (Continued) f. Loss-of-Offsite Power N.A. R N.A. M N.A. N.A. N.A. 1, 2,'3" j. 'g. Trip'of All Main N.A. N. A. N.A. R N.A. N.A. N. 7.. 1, 2 Feedwater Pumps. .h. Auxiliary Feedwater S-R .M N.A. N.A. N.A. N.A. 1,'2, 3.- Pump Suction Pressure-Low l7. Aut'm tic Switchover to Cc .nment Sump-a. utomatic Actuation N.A. N.A. N.A. N.A. M(1) M(1) - Qt3) . 1, 2,.3, 4 i Logic and Actuation Relays ;-(SSPS) -b. RWST Level - Low-Low S R-Q '_ N. A. N.A. N.A. N.A. -1, 2,.3, 4: l' Coincident With i Safety Injection .See ' Item 1 above for all Safety Injection Surveillance Requirements. I" 8. ! Loss of Power l a. 4--kV Undervoltage- 'N.A. R N.A. M N.A. .N.A. .N.A. 1,.2,- 3, Loss of Voltage 4, 5++, 6++ b .4~kV Undervoltagee .N.A. R N.A. M' N.A. N.A. .N.A. 1, 2, 3, 9. Grid Degraded Voltage. 4, 5++, 6++ 1 M 2.u u . 1 W vr+-.- 'y"'+ eU-a-Nw t evv+- -ry.+

,e-TABLE 4.3-2 (Continuedj ENGINEERED SAFETY-FEATURES ACTUATION SYSTEM INSTRUIE3TATION SURVEILLANCE REOUIREtCITS j.. TRIP MODES-ANALOG ACTUATING FOR WHICH CHANNEL DEVICE MASTER SLAVE SURVEILLANCE.. CHANNEL CHANNEL OPERATIONAL OPERATIONAL ACTUATION RELAY RELAY. IS ~ FUNCTIONAL UNIT CHECK' CALIBRATION TEST TEST LOGIC TEST TEST TEST REOUIRED I 9. Control Room. Isolation a. Manual Initiation-N.A. N.A. N.A. R N A. N.A. N.A. All b. Automatic Actuation N.A. N.A. N.A. N.A. M(1) M(1) 'QI3) 1, 2, 3, 4- [ Logic and I-~.uation Relays- (SSI 6) j c. Automatic' Actuation N.A. N.A. N.A. N.A. M (1) (2) N.A. N.A. All Logic and Actuation . Relays (BOP ESFAS) -d. Phase "A" Isolation See Item 3.a. above for all Phase "A" Isolation Surveillance Requirements. 10. Load' Shedder Emergenct NIA. N.A. N.A. N.A. M (1) (2) N.A. N.A. 1,. 2, 3, Load Sequencer 4, 5+, 6+ 11. Engineered Safety Features- ~ Actuation' System Interlocks' .a # ' Pressurizer Pressure,

N.A.

R-Q N.A. ~ N.A. N.A. N.A.. 1,. 2,.3 P - 11.' b '. Reactor Trip,-P-4 N.A. N.A. N.A. R N.A. N.A. N. A'. 1, ; 2, ' 3 4 L. 4 ,I I -..-g ,_4 . ~ _,...

~ ' N ? y t 4 f : - -{ ~ TABLE 4.3-2 ' (Continued) EIGINEERED SAFETY FEATURES ACTUATION SYSTEM INSTRUMENTATION SURVEILIANCE REOUIREMENTS TABLE NOTATIONS I r (1) Each train shall be' tested at least'every'62 days on a STAGGERED TEST BASIS. ~ (2) Continuity check..may be excluded from the ACTUATION LOGIC TEST. (3)- Except Relays K602, K620, K622, K624, K630, K740, and K741, which shall be tested at least once per l'8 months' during refueling and2during each COI.D SHUTDOWN Exceeding 24 hours'unless they have.been tested within ttle previous 90 days. The'specified.18 month. frequency may be waived for Cycle 1 provided the surveillance is pe_lormed prior.to' restart ~ ~ following the firstfrefueling outage or June'1, 1986, whichever occurs first.. The previsions of Specification 4.0.2'are-reset..from performance of this surveillance. ~ -Only the shutdown ~ portion of.one sequencer is required to.be OPERABLE in Modes 5 and 6 which corresponds to.the '+ OPERABLE Emergency Diesel Generator. w. ' Operability'is only. required for associated OPERA 3LE bus in Modes 5 and 6. ++ 4 I 4 s 'y',-N gje - --pp e

i. d p'

is' '( wg-- p-- y ,1 4 y N-y = g.= g g y9 gj y g y a 3 7 g g-.g 4,sp q -y4 g .g .q-g.. ,44-

ELECTRICAL POWER SYSTEMS - A.C. SOURCES SHUTDOWN LIMITING CONDITION FOR OPERATION 3.8.1.2 As a minimum, the following A.C. electrical power sources shall be OPERABLE: a. One circuit between the offsite transmission network and the Onsite q Clrss 1E Distribution Syste,n, and l b. One diesel generator with. 1) A day tank containing a minimum volume'of 390 gallons of fuel, 2) A fuel storage system containing a minimum volume of 85,300 1 gallons of fuel, and 3) A fuel transfer pump. APPLICABILITY: Modes 5 and 6. q ACTION. l-With less than the above minimum required A.C. electrical power sources l-OPERAE'LE, immediately suspend all optrations involving CORE ALTERATIONS, positive reactivity changes, movement of irradiated _ fuel, or crane operation with loads over the spent fuel pool. In addition, when in Modt,5 with the reactor coolan' i loops not filled, or in Mode 6 with the water levelless than 23 feet above the reactor vessel flange, immediately initiate corrective action to restore the required sources to OPERABLE status as soon as possible. SURVEILLANCE REQUIREMENTS 4.8.1.2 The above required A.C. electrical power sources shall be demonstrated. OPERABLE by the performance of each of the requirements of Specifications 4.8.1.1.1, 4.8.1.1.2 (except 'or Specifications 4.8.1.1.2a.5), and 4.8.1.1.2f.5), 6),

10) and.12) for the LOCA esquencer portion of LSELS only), and 4.8.1.1.3.

CALLAWAY - UNIT 1 3/4 8-8

~ )_ ~ M 4 . a -i . ] t ' ) .4 ...i 9 - l . 't c' _a . e s Nuclear Safety Evaluation i 1 1 I .-. J e s- \\ -.r c 1 4 . W I ~ ( ,.',-4 + .,,4., .,.a -~ r ) + w -. 'w',' +

~' Page 1 of 3 i SAFETY EVALUATION This amendment application requests a revision to Technical Specifications (T/S) 3/4.3.2 and Surveillance Requirement 4.8.1.2. These specifications are revised to require the emergency diesel generator (EDG) solid-state load shedder emergency load sequel'cers (LSELS) and 4KV bus undervoltage (UV) devices be operable in plant modes 5 and 6. Proposed Change This amendment application revises T/S 3/4.3.2, Tables 3.3-3, 3.3 1, and 4.3-2 Functional Urits (8) " Loss of Power 4KV Bus" and (10) " Solid State Load Sequencer" by: 1) changing " Solid-State Load Sequencer" to " Load Shedder Emergency Load Sequencer" in Tables 3.3-3, 3.3-4, and 4.3-2, Functional Unit (10); 2) adding Mode 5 and 6 applicability for the LSELS and its supplying 4KV bus UV circuit to Tables 3.3-3 and 4.3-2, Functional Units (8) and (10); 3) adding notes to Tables 3.3-3 and 4.3-2 which explains the operability requirements of the LSELS and corresponding 4KV bus UV devices in Modes 5 & 6, and; 4) revising Table 3.3-3, Action Statement 25, which corresponds to Functional Unit (10), by adding a reference to Specification 3.8.1.2. 2 Surveillance Requirement 4.8.1.2 is revised by exempting the LOCA sequencer from the portions of Specification 4.8.1.1 which are not applicable (e.g., the LOCA sequencer is not required in Modes 5 and 6). Background and Safety Analysis The EDG solid-stated LSELS perform two basic functions, load shedding and load sequencing. The load shedding function removes selected loads from the Class 1E buses under degraded bus voltage conditions or upon the presence of a safety injection signal and scnds a starting signal to the EDG. The sequencing function actuates equipment fed from the Class 1E buses in a predetermined sequence following degraded bus voltage conditions or in the event of a loss-of-coolant accident. This ensures that the voltage and frequency of the Class 1E buses are not degraded below design parameters due to the he,vy starting currents of the actuated equipment. An inconsistency exists in T/S for the EDG solid-state LSELS which could lead to a T/S compliance problem. T/S Surveillance

H .Page12 of13-4.8;1.2, states:that the emergency diesel-generators:shall be ~ demonstratedioperable, in Modes 5 & 6, by the performance;of-Surveillance.RequirementL4.8.1.1.2.f. _This: surveillance requirement discusses the use of the shutdown /LOCAjsequencers,- which implies that the sequencers.are operable. However', T/S 1 3.3.2'(10) only requires the. load sequencersLto be operablefin-Modes 1 through'4. With the load sequencers de-energized'and_ j -inoperable in Modes 5 & 6 they are not required to be surveyed' per T/S 4.0.3 and they are'not. required-to be operable by the T/S 3.3.2 mode applicability. Per T/S 4.0.1, surveillances shall be! met in the modes specified in the LCO. Without the. load sequencers operable, surveillance 4.8.1.1.2.f cannot be met., This T/S amendment rectifies the above compliance _ concern by-imposing Mode 5 & 6 applicability for the LSELS. Requiring the LSELS to be operable in Modes 5 & 6 enhances plant operability in j the. shutdown modes and does not cause a safety concern. Previously T/S did not require the LOCA sequencer to be operable-since LOCA is not analyzed in Modes 5 & 6. The shutdown sequencers were not. required to be operable because plant operators were relied upon'to take manual action to recover from D a loss of offsite power. In addition, the Standardized Technical Specifications developed-by MERITS-(Methodically Engineered, Restructured and Improved Technical Specifications and associated Bases) support a. requirement for OPERABILITY of the sequencers in shutdown-modes. The requirements for sequencer OPERABILITY for thel OPERABLE AC source were originally stated in the draft for AC Sources-Shutdown, Modes 5 and 6.(LCO 3.8.2,_page 3.8-28). The review of. + the draft-suggested removing this section on the~ basis that " load-sequencers are integral to the diesel generator OPERABILITY, and do Iat require unique mention in the LCO". Evaluation The proposed change _to Technical Specifications does not involve an unreviewed safety question because-operation oftthe'Callaway-Plant with this change would not: 1. Increase the probability-of occurrence or the-consequences: of an accident or malfunction of equipment.important 'tua safety previously evaluated in the safetp analysis l report. There is no increase in the probability of occurrence,or the consequences of an accident. This change enhances plant-operation in shutdown modes, which adds a eafety benefit. 2. Create a possibility for an accident or malfunction ofEal different type than any previously. evaluated in.the safety analysis report. There is no new type of accident or malfunction created and the method and manner of plant operation will only change by adding OPERABILITY-requirements for LSELS.in MODES 5 & 6, which enhances 1 plant safety in! shutdown modes.

s - Attachment 3 Page_-3 of 3- ~ 1 -3. Reduce the margin c safety as defined in the basis for any. technical ~sp(cifac.ation. This is based on the fact that no-plant design ch. aces are involved and the method and manner y of plant operation remains the same, except - that-the LSSLS-willJbe required-to'oe operable.in. Modes 5 & 6. ~ Given'the above discussions as well as'those presented in.the Significant Hazards Evaluation, the proposed change does no_t-adversely affect or endanger the_ health or safety of the-general public or involve a significant safety hazard. I J i l + 1 .. = 3-y .+r,,.r $ _ q. riu. .e.-,w-. y-y,

j J' *,... .. ~...... .,~.~. _. _.. _._.-. "4'

  • d.9:

.t.,..

p,
' T

- { 4' 4, 34 4 e4 T',,'-

  1. ' f.-

g - s 3 -1

a. g..

? o, 4 .4, .f i r d )

  • )

s, .t J Attachment i l I Significant Hazards Evaluation 3 i- } '. 4 + 4 ~. 4 I rc P s ) 's u P i a . r.

k 4

h E 9., f h-49 l1 m M h y,p L 4 N~*I'*"' 99 V t'Fe t 4 1 we*w. e r%,- yev -2,s v. g .,,,%.r. ,,s, 3. ,,,..y,,

E ) e ) Page 1 of 1 ) SIGNIFICANT HAZARDS EVALUATION i This amendment applicatica requests a revision to Technical Specification 3/4.3.2 and Surveillance Requirement 4.8.1.2. These specifications are r6v:1 sed to require the solid-state load shedder emergency load sequencers (LSELS) and 4KV bus. undervoltage devices be operable in plant modes 5 and 6. The proposed change does not involve a significant hazards consideration because operation of Callaway Plant with this change would not: 1. Involve a Jignificant increase in the probability or y consequences of an accident previc:mly evaluated. The ~ Callaway-Safety Analysis Report has been reviewed,and been found to be unaffected by this proposed change. This change will not increase the probability or corsequences of any accident or malfunction of equipment because the LSELS will be required to be operable in modes 5 and 6 which enhances. plant operability. 2. Create-the possibility of a new or different kinu of accident from any previously evaluated. ' This change increases the operability requirement for th? L3ELS. .There is no new type of accident or malfunction created and the-method and manner of plant operation will only change by adding OPERABILITYfrequirements fnr LSELS in MODES 5 & 6, which enhances plant safety in shutdown-modes. 3. Involve a significant reduction in a margin of safety. The margin of safety remains unaffected since no design change is made and plant operation remains the-same. As discussed above, the: proposed change does not involve.a-significant increase in the probability or consequences of an j accident previously evaluated or create the' possibility.of a new or different kind of accident from any previous 2/ evaluated. This change does not result in a significant' reduction-in a margin of safety. Therefore,. it has been determined that the' proposed change-does not-involve a significant hazards consideration. + -.4 f l .,h n..,,oh.--,,c..,. +., ,w. ...re.- ,,e e m. a.w q,,,, i, y,,, - 2,.w. 3 m-- ,,+# y

-t s i t 6 i i t 1 3 J 1

t I

t !J l. Attachment.5 .l l' i Environmental Consideration -.j - Ia l .4 t 9 .-f p t i + l ' .Y -a 5 t I L

r t

g r .f. h s, e '6 .h .+ h i 1 t '.'k .. h ), : I 1 .a u . ( g-1_..__;.__..._..__m_.__ ,_-_.___=________._.1.1

i i -I . + Page 1 of 1 i i l ENVIRONMENTAL CONSIDERATION .j This amendment application requests a revision'to' Technical Specification 3/4.3.2 and Surveillance Requirement 4.8.1.2. These specifications are revised to require the solid-state load = shedders emergency load sequencers (LSELS) and 4KV bus r undervo3 tage devices be operable in plant modes 5 and 6. I The proposed amendment involves changes with respect to the use -- t of facility components located within the restricted area as defined in 10 CFR Part 20, and changes a surveillance requirement. Union Electric has determined that the proposed amendment involves no significant. increase in the amounts, and no significant change in the types, of any effluents that may be released offsite and that there is no significant increase in individual or cumulative occupational radiation exposure. l Accordingly, the proposed amendment meets the eligibility cri'eria.for categorical exclusion set forth in.10 CFR 51.22 (c) ? (9i. Pursuant to 10 CFR 51.22 (b) no environmental impact ^ statement or environmental assessment need be prepared in-connection with the issuance of this amendment. I a - t l ~ + (' ye,r N to-me-ww s ~ -q -q, p. y em}}