1 ATTACHMENT 3 to TXX 96393 AFFECTED TECHNICAL SPECIFICATION PAGES 9607120214 960709ADOCK 05000445 POR PDR P

_ ~ _

... to TXX-96393

~

Page 1 of 2

~

TABLE 3.3-3 ENGINEERED SAFETY FEATURES ACTUATION SYSTEM INSTRUMENTATION TRIP SETPOINTS FUNCTIONAL UNIT TRIP SETPOINT ALLOWABLE VALUE 1.

Safety Injection (ECCS Reactor Trip.

Feedwater Isolation. Control Room Emergency Recirculation.

Emergency Diesel Generator Operation. Containment Vent Isolation. Station Service Water.

Phase A Isolation. Auxiliary Feedwater-Motor Driven Pump. Turbine Trip, Component Cooling Water.

Essential Ventilation Systems, and Containment Spray Pump).

[

a.

Manual Initiation N.A.

N.A.

b.

Automatic Actuation Logic N.A.

N.A.

and Actuation Relays c.

Containment Pressure--High 1 13.2 psig 53.8 psig d.

Pressurizer Pressure--Low 11820 psig 11803.6 psig e.

Steam Line Pressure--Low

=

1) Unit 1 1605 psig*

tlhha-5594:0)psig*

I

2) Unit 2 1605 psig*

1 578.4 psig*

2.

Containment Spray a.

Manual Initiation N.A.

N.A.

b.

Automatic Actuation Logic N.A.

N.A.

and Actuation Relays c.

Containment Pressure--High-3 518.2 psig s18.8 psig COMANCHE PEAK - UNITS 1 AND 2 3/4 3-25 Unit 1 - Amendment No. 41 Unit 2 - Amendment No. 27

= -

, to TXX-96393

~

-i Page 2 of 2 TABLE 3.3-3(Continued)

ENGINEERED SAFETY FEATURES ACTUATION SYSTEM INSTRUMENTATION' TRIP SETPOINTS i

FUNCTIONAL UNIT TRIP SETPOINT ALLOWABLE VALUE 4.

Steam Line Isolatior, i

a.

Manual Initiati 1 N.A.

N.A.

i b.

Automatic Actuation Logic N.A.

N.A.

and Actuation Relays c.

Containment Pressure--High-2 5 6.2 psig 5 6.8 psig i

d.

Steam Line Pressure--Low 1

1) Unit 1 2 605 psig*

2[593-5 594';0)psig*

i

2) Unit 2 1 605 psig*

1 578.4 psig*

e.

Steam Line Pressure-Negative Rate--High 5 100 psi **

5178.7 psi **

i

+

e i

COMANCHE PEAK - UNITS 1 AND 2 3/4 3-27 Unit 1 - Amendment No. 41 i

Unit 2 - Amendment No. 27 t

m m

.