ML20106C805
| ML20106C805 | |
| Person / Time | |
|---|---|
| Site: | FitzPatrick |
| Issue date: | 09/25/1992 |
| From: | POWER AUTHORITY OF THE STATE OF NEW YORK (NEW YORK |
| To: | |
| Shared Package | |
| ML20106C798 | List: |
| References | |
| NUDOCS 9210060358 | |
| Download: ML20106C805 (13) | |
Text
..
ATTACHMENT I to JPN 92 057 PROPOSED TECHNICAL SPECIFl7ATION CHANGES IQ.RELECT A FIRE _ERQT,1CllON MODIFICATION (JPTS 91-020) 1 t
New York Power Authority JAMES A. FITZPATRICK NUCLEAR POWER PLANT-Docket No. 50-333 DPR 59 -
9210060358 920925 DR ADOCK 05000333 PDR
JAFNPP TABLE 3.12.1 i
i WATER SPRAY / SPRINKLER PROTECTED AREAS f'
AREA FIRE DETECTION TYPE PROTECTION (3)
TYPE INITIATION i
i 1)
West Cable Tunnel lonization and Electric Heat Water Spray Automatic / Manual Activated Device l
2)
East Cable Tunnel lonization and Electric Heat Water Spray Automatic / Manual Activated Device 3)
Recirculation MG Room Electric Heat Activated Device Fusible Link Sprinklers Automatic / Manual 9
4)
Emergency Diesels (1)
Electric Heat Activated Device Fusible Link Sprinklers Automatic / Manual 5)
HPCI E:ectric Heat Activated Device Water Spray Manual 6)
RCIC Electric Heat Activated Device Water Spray Manual i
i 7)
Standby Gas Treatment Trains (2)
Electric Heat Activated Device Water Spray Manual 8)
West Diesel Fire Pump Room Sprinkler Flow Alarm Fusible Link Sprinklers Automatic E
r 9)
Battery Room Corridor Ionization and Sprinkler Fusible Link Sprinklers Automatic t
Flow Alarm j
r Notes for Table 3.12.1 i
1.
Each of two (2) Emergency Diesel Generator Systems is a separate protected area. c9ch system coniains two (2) se. carate rooms.
2.
Each of two (2) Standby Gas Treatment trains is a separate area.
j 3.
All areas are also protected by fire hoses and portable dry chemical and/or CO fire extinguishers.
2 Arr endment No. [,1[,
244j
JAFNPP f
TABLE 4.12.1 WATER SPRAY / SPRINKLER SYSTEM TESTS CYCLING SPRAY NCZZLE HEADER INTEGRITY NOZZLE AIR AREA EACH VALVE INSPECT:ON INSPECTION FLOW TEST 1)
West Cable Tsinnel Once/6 Months Once/1.5 Years Once/1.5 Ye us Once/3 Years
't 2)
East Cable Tunnel Once/6 Months Once/1.5 Years Once/1.5 Years Once!3 Years t
3)
Recirculation MG Room Once/6 L'onths N/A Once/1.5 Years N/A i
4)
Emergency Diesel Rooms Once/6 Months N/A Once/1.5 Years N 'A l
{
5)
HPCI Once/6 Months Once/1.5 Years Once/1.5 Years Once/3 Years 6)
RCIC Once/6 Months Once/1.5 Years Once/1.5 Years Once/3 Years I
7)
Standby Gas Treatment Trains Once/6 Months Once/1.5 Years Once/1.5 Years Once/3 Years i
8)
West Diesel Fire Pump Room None(1)
N/A Once/1.5 Years N/A l
9)
Battery Room Corridor None(1)
N/A Once/1.5 Years N/A i
Notes for Table 4.12.1 l
i 1.
Wet pipo sprinkler system.
i E
Amendment No.
2444
_ ~.. -
Attachment il to JPN 92 057 L
i SAFETY EVALUATION FOR PROPOSED TECHNICAL SPECIFICATION CHANIIES TO REFLECT A FIRE PROTfCTION MODIFICATION (JPTS-91-01Q) 1.
RESCRIPTION_OF THE PROPOSED CHANGEJ i
This application for an amendment to the James A. FitzPatrick Technical Specifications adds operability and surveillance requirements to Tables 3.12.1 and 4.12.1 to reflect a plant modification that willimprove fire protection at the i
Authority's FitzPatrick nuclear power plant. The modification installs an autornatic fire suppression system n the battery room corridor. The changes to the Technical Specifications are addressed below.
Minor ctuinges in format. such as type font, margins or hyphenation, are not described in this submittal. The a changes are typographical in nature and do not affect the content of the Technical Specifications.
Plne 2441. Table 3.12.1 Insert item 9 with the following information:
Area:
Battery Room Corridor Fire Detection:
lonization and Sprinkler Flow Alarm Type Protection: Fusible Link Sprinklers Type Initiation:
Automatic Pano 244a. Table 4l2d insert item 9 with the following information:
Area:
Battery Room Ccaidor Cycling Each Valve:
None(1)
Spray Nozzle Inspection:
N/A Header Integrity inspection: Once/1.5 Years Nozzle Air Flow Test:
N/A 11.
PURPOSE OF THE P,ROPOSEDJHANGES The purpose of the proposed changes to the Technical Specifications is to add operability and surveillance requirements to Tables 3.12.1 and 4.12.1 to reflect a plant modification that willimprove fire protection at the Authority's FitzPatrick nuclear power plant.
On August 2,1991 Authonty personnel met with the NRC staff to discuss James A.
FitzPatrick Nuclear Power Plant fire protection. At this meeting the Authoritv committed to install a fire suppression system in the Battery Room Corridor prior to l
restart from the 1992 refueling outage. The Authority subsequently confirmed this commitment in Reference 1.
l
' 1 to JPN 92 057 SAFETY EVALUAT:ON Page 2 of G The NRC staff granted the Authority an exemption from the requirements of 10 CFR 50, Appendix R, Section Ill.G.3.b which allowed continued plant cperation until a fixed fFe suppression system is installed in this area (Reference 2). When this suppression system is ;nstalled, the battery room corridor (Fire Zone BR-5) will be in compliance with the requirements of 10 CFR 50, Appendix R, Section lil.G.3 and the exemption will no longer be requiied.
A description of fire Zone BR 5 was included in the attachment to Reference 3. As an interim compensatory measure a continuous fire watch has been posted in this area.
The modification will not change the existing fire detection capability in the battery room corridor which consists of ionization smoke detectors. These detectors will continue to alarm in the control room. in addition, a system pressure switch, installed with the new cuppression system, will indicate actuation by alarming in the contr01 room.
The new suppression system is a wet pipe design with fusible link sprinklers that are heat actuated to allow for sectionalized fire suppression capability. The system is automatically initiated when the nearby temperature reaches the melting point of the fusible Ill.
SAEETY IMPLlCATIONS OF THE PROPOS.f_Q CHANGES The proposed changes to the Technical Specifications have no adverse safety implications. The addition of a new suppresr. ion system for the Battery Room Corridor improvas the ability of the plant fire protection system to supprer.s fires.
The system was designed and analyzed in accordance with James A. FitzPatrick Fire Protection Program requirements (Reference 4). The operability and sur>eillance requirements added to reflect this modification are consistent with operability and surveillance requirements for similar fire protection systems. These requirements are also consistent with industry practice as contained in the Standard Technical Specifications (Reference 5). The changes do not alter the conclusions of the Fit 2 Patrick accident analyses as documented in the FSAR or tha NRC staff's SER.
Design and Analysis The modified fire suppression system was designed, analyzed, and installed in accordance with the FitzPatrick Fire Protection Program requirements. Specific design and analysis information related to the conclusions in the modification safety evaluation include the following:
- 1. Seismic interactions between the new fire suppression system and safety related equipment are prevented. The new fire suppression system is a Class M System that will be Seismic Class 11 supported. Supports are spaced to prevent the creation of missiles and to preclude pipe rupture (except for line cracks associated g
l' with moderate energy piping) with attendant flooding (Reference 6).
i g-..,-,
--,,,e,
,,,n
,e e
a e
.- - -- -~
l Attachment il to JPN-92 057 SAFETY EVALUATION Pap 3 of 6
- 2. Adequato drainage is provided by fivo floor drains in thu battery room area (i.e.,
the battery room corridor and the two adjoining battery rooms) to accommodate fo;l system actuation. System operation, full flow through all sprinklers, exceeds the flooding associated with a moderate energy oipe crack (Reference 7). Water on the battery area floor will not damago safaty related equiprnent. The operation of tho batturieu is not af fected since the batteries are raised o the floor.
- 3. Water damage due to events such as inadvertent actuation or pipe crack from the fire suppression system will not affect the ability of the plant in achieving and maintaining safe shutdown from the control rooin. Because the affects of the postulated fire in the Battery Room Corridor (i.e., loss of shutdown capability from the control room) are more savoro than those from water damage, the addition of sprinklers provides a not safety benefit slnce the response time to such a fire is reduced with a corresponding reduction in potential fire damage.
Water spray in the battery room corridor will not af fect the cables located in the battery room corridor since all such cables are fully insulated and are impervious to the water spray. Operation of the circuits associated with those cables will remain unaffocted by the operation of the fire suppression system, including those cables required for RCIC operation. Establishing and inaintaining the reactor in a cold shutdown condition can, therefore, be achieved without resorting to remoto/ alternate shutdown (i.e., t. ig ADS /LPC0 from outside of the control rooma Watar damage to the distribution transformers (71PT-71ESSB1 and 71PT-71 ACB2) in the battery room corridor may cause the loss of "B" t* i control room indication. This will not prevent the operators from determining plant statua and achieving reactor shutdowr from the control room since the "A" train instruments remain available. Water damage to the equipment panels (71ESSB1 and 71 ACB2) resulting in the loss of vontilation for the battery rooms and battery room corridor will be mitigated by establishing temporary ventilation as required by Abnormal Operating Procedure AOP-58 (Roference 8).
Limiting Conditions for Operation The systern added to Table 3.12.1 is subject to the same limiting conditions for operation as those which are in Specification 3.12,B. This consistency with established operating restrictions and reporting requirements ensures that the plant modification will provide an equivalent level of protection and margin of safety as that provided by other fire protection systems.
Surveillance Hequirements An entry of "NONE" is proposed for the cyc!ing of valves in the new system. The now cuppression system is automatica'..y actuated by local heat levels requiring no detactor/ actuation circuitry and has only onb normally open testable valve. This valvo is an outside stem and yoke (OS&Y) valve which is manually operated for maintenance purposes an.1 system shutoff sihile the survoillance requirement is intended to allow operator determination of system operability. A surveillanc6
l l
Attachtnent il to JpN-92-057 SAFETY EVALUATION Page 4 of 6 frequency of "NONE" is consistent with existing Technical Specification requitunents and current NRC requirements for wet pipe fire protection systems provided in Section 4.7.7.2 of tne Standard Technical Specifications.
Tho surveillance requirements to perform a spra" nozzle inspection and a nozzle air flow test are specified as " Nut Appbcable" in trus proposed Technical Specification amendment. IJFPA 15 (Ref erence 91 specifies that "All spray nozzles shall be inspected f or proper positioning, extemal loading, and corrosion, and cleaned if necessary at intervals of not more than twelve months
." The new suppression systun is a wet pipe system with closed sprinklers. The surveillance requirement of
'Not Applicable" is consistent with existing Technical Specification requireme:'ts and current NRC requirements for wet pipe fire protection systems provided in Section 4.7.7.2 of the Standard Technical Specifications.
A survei' lance requirement to inspect ihe f.eader integrity once per 1.5 vears is proposed for the battery toom corridor system. This is consistent with surveillance requirements for other similar fire protection systems in the Technical Specifications.
The frequency interva' is longer than NFPA 15 which requires annual inspection but is consistent with NRC Ouidance provided by Section 3/4.7.7.1 of the Standard Technical Specifications.
IV.
EV A U) AILQ_N_Q F_SlG ME!C A NT H A Z A R D S C O N SI D E R AT I Q N Operation of the FitzPatrick plant in accordance with the proposed Amendment would not involve a significant hazards consideration as defined in 10 CFR 50.92, since it would not:
- 1. mvolva a significant increase in the probability or consequences of an accident graviously evaluated.
The prooosed changes revise the Technica! Specifications to reflect a plant modification to the F;te Protection System. These changas willincrease the abihty to suppress fires. The modification to the fire protection system will not adversely affect the ability of plant personnel and fire protection equipment to detect and extinguish a fire. The proposed revis.on to Tables 3.12.1 and 4.12.1 of the Te^hnical Specifications will provide hmitin0 conditions of operation and surveillance requirements for the modification consistent with the limiting conditions of operation and surveillance requirements of other similar fire protection systems. These changes to the Technical Specifications assure that the new system is operable by periodic surveillance and that required e.ctions are taken if it is not available.
- 2. create the possibility e' a new or dif ferent kind of accident from any accident previously evaluated.
The modification does not create the possibility.f a new or dif ferent kind of accident. The modification to the fire protectico system provides additional protection against the possibihty of fire in the battery room corridor. The
' 1 to JPN 92-05!
SAFETY EVALUATION Page 5 of G proposed changes to the Technical Specifications uv not alter plant operations or operating procedures. The provision of a wet pipe sprinkler system can result in water sprays but the shutdown requirements due to previously analyzed fire effects bound the effects of water spray. The effects of inadvertent actuation have been evaluated and do not initiate a dif forent kind of accident. Althou0h it may cause the foss of certain equipment, it is less limiting than other analyzed events including a fire in this area.
? involve a significant reduction in a margin of safety.
The proposed revision to the Technical Specificadons to reflect the installation of a fire suppression system in the battery room corridor will not adversely af fect the marg' l dafety for equipment and personnel in thet area. These changes improve the plant's capability to suppress fires and limit fire dama00. The potential for flor n.g or water damage has been evaluated and is bounded by fire ef fects. This chan0e, therefore, results in a net improvement in plant safety.
V.
[N EIEMENTATION Of TH':_EROPQSED_Cif ANG ES These proposed changes wili not affect the ALARA Pro 0 ram at the FitzPatrick plant, nor will they impact no environment. The surveillance requirements will not add inspections to hi h radiation areas. The construction work to implement the 0
modification will be insido existin0 structures so there will be no environmental discharges. The construction work w ll not be in ;adiation areas. When completed, testin0 of the modification will be in compliance with current practices and will not impact the environment in a manner different than cutrent practice. These practices do not have unacceptable consequences. The modification supported by these technical specification changes willimprove the plant's Fire Protection Program capability in miti atin0 fires.
0 VI. QQNQWS10h The changes, as propot,ed, do not constitute an unreviewed safety question as defined in 10 CFR 50.59. That is, they:
1, will not chan0c the probability nor the consequences of an accident or malfunction of equipment important to safety as previously evaluated in the Safety Analysis Report;
- 2. will not increase the possibility of an accident o malfunc: an of a type different from any previously evaluated in the Safety Analysis Report;
- 3. will not reduce the margin of safety as defined in the basis for any technical specification; and i
- 4. involve no significant hazards consideration, as defined in 10 CFR 50.92.
~
^
Attachment il to JPN-92-057 SAFETY EVALUATION Pogo 6 of 0 Vil, MEEEENCES 1.
NYPA letter, R.E. Beodio to U.S. NRC, dated August 16,1991. (JPN 51-043),
rogarding schedule for short term fire protection ections.
2.
NRC lotter, R.A. Capra to R.E. Boedio, dated Scptember 18,1991, (JAF 91294), "Issut nce of a Technict.; Exemption from a Requiremont of 10 CFR part 50, Appendix R, for the James A. FitzPatrick Nuclear Power Plant (TAC NO. 81184)."
3.
NYPA letter, R.J. Converse to U.S. NRC, dated July 31,1991, (JAFP 91-0454),
" Exemption Roquest for Area Wide Supprossion in the Ba'tery Room Corridor."
4 James A. FitzPatrick Nuclear Power Plant Safety Evaluation for Fire Protection -
Dattery Room Corridor (BR5) Modification, JAF SE-91-086, Revision 1, dated August 19,1992.
5.
NUREG-0122, " Standard Technical Specifications for General Electric BoilinD Water Reactors (BWR/5)", Revision 3, dated Fall 1980.
6.-
James A. FitzPatrick Nuclear Power Plant Pipo Stress Calculation, JAF-CALC-FPS-00609. Revision 0, dated July 23,1992.
7.
James A. FitzPatrick Nuclear Power Plant Battery Room Corridor Flooding Analysis, JAF-CALC-FPS-00558, Revision 0, dated June 16,1992.
8.
James A. FitzPatrick Nuclear Power Plant Abnormal Operating Proceduto, l
AOP-58, "Stetion Battery Room Emergency Ventilation," Revision 1, dated tu0ust 15,1991.
'1 National Firo Protection Association Document 15 (NFPA 15), " Water Spray Fixed Systems for Firo Protection," datad $ 990.
- 10. James A. FitzPatrick Nuclear Power Plant Updated Final Safety Arialysis Report, Section./ 8 "Firo Protection System," through Revision 5, dated January 1992.
- 11. James A. FitzPatrick Nuclear Power Plant Safety Evaluation Report (SER), dated November 20,1972 and supplements.
l l
__..,_,.a.
..m
ATTACHMENT lli to JPN 92 057 PROPOSED TECHNICAL SPECIFICATION CHANGES TO HEFLECT A FIRE PROTECTION MODIFICATION Mell&UP OF TECMitCAL SPECIFICATIOfL[%QES (JPTS 91020) t
+
1 0
New York Power Authority JAMES.A. FITZPATRICK NUCLEAR POWER PLANT Docket No. 50-333 l
DPR 59 L
L r-
.e
..e.
'. APT.E 3.I1.I WATE:: SPRAY / SPRINKLER'PROTFrTrn ADCAS e-as
-m=
~m~.-4.. _ -. ~.,
AREA FIRE DETECTION TYPE PFOTECTION (3)
TYPP INITTAT1ong 1) west Cable Ionizati.on and Electric w ter Spray Automatic Mai.ual a
e Tunnel Heat Activated IVvice j
)
East Cable Ionization and Electric water Sprey Automatic / Manual Tunnel Heat Activated Devire 3)
Recirculation Electric Heat Fusible Link Automatic /Manuel l.
MC Foom Activated Device Sprinklers 4)
Emergency' Electric Heat Fusible Link A u t o*=a t i c/ Ma n u a l Diescis (1)
Activated Device Sprinklers 5)
HPCI Electric Heat Nater Spray Manual i
Activated Device j
6)
PCIC-Electric Heat water Spray Manual l
Activated Device 4
l
?)
Standtsy Cas-Electric P*st w ter Spraf Manus' a
Trentwent Trains (2)
Activated Device B) west Diesel Fire Sprinkler Flow Fusible Link Automat *c l
Pump Room Ala rse Sprinklers (M
i i
Notes for Tabis 3.12.1 l -+_
L 1.
Each of two f2) Esmergency Diesel Generator Systems is a separate protected area. each system contains g_;
l yT two (2) separate rooms.
A.t 2.
Each of two (2) Standby Ces Treatment trains is a separate area.
flee entinguishers.
3 All r.reas are also protected by fire..oses and portable dry cheemical and/or CO2 Ar=-ndw nt No. }(. I s .
214j s
4 Tant.E 4.12.1 WATEk SPR A? SPR INRLER SYSTEM TESTS CYCLI.G SPRAY POZZI.E HEADER INTEGw!TY Nozzrz arp AREA EACH VALVE INSPECTION INSPECTION FtJws TrsT
' ' ~ ~
~
-. - _. ~. _
1)
West Cable Once/6 Months Once/1.5 Tears 07ce/1.5 Years Once/3 Yemes Tunnel 2)
East Cabl*
Once/6 Months once/1.5 Yents Once/1.5 Yeers Once/3 Years Tunnel l
3)
Recirculation Once/6 Months N/A O-ce/1.5 Years N/A MG Poom 4)
Emergency Once/S Months N/A Once/1.5 Years N/A Diesel Poems l
5)
HPCI Occe/6 Months Once/1.5 Years onee/1.' Years Onc e 'l Years 6)
DFIC 09ce/6 Months Orce/1.5 Years Once/1.5 Years Once/3 Years 1
7)
Standby Gas Once/6 Months Once/1.5 Years Onca/1.5 Y-ars Onta/3 Yests Treatw nt Train?
l 8)
Mest Diese! Fire None (1)
N/A Once/1.5 Years M/A l
Pep Room
+
Notes for Table 4.12.1 L-v'
% {, 1.
Met pipe sprinkler Oystem Ec H
Amen +*nt no, y(, 142 2449 i
b
INSERT "A" Battery lonization and Sprinkler Fusible Link Automatic Room Corridct flow Alarin Sprinklers INSERT
- B*
Battery Nonf' N/A Once/1.5 Years N/A Room Corridor e
I
-