Amend 79 to License NPF-3,changing Tech Spec Table 3.6-2 Re Containment Isolation Valve to Allow for Modified Steam Generator Blowdown & Drain Sys
ML20101N428
Person / Time
Site: Davis Besse 
(NPF-003)
Issue date: 12/11/1984
From: Stolz J
Office of Nuclear Reactor Regulation
To:
Toledo Edison Co, Cleveland Electric Illuminating Co
Shared Package
ML20101N432 List:
References
TAC 66415, NPF-03-A-079 NUDOCS 8501040023
Download: ML20101N428 (7)


Text

E[

o UNITED STATES g

N AR REGULATORY COMMISSION o

h CASHINGTON. D. C. 20555

,o*

+..**

TOLEDO EDISON COMPANY AND THE CLEVELAND ELECTRIC ILLUMINATING COMPANY DOCKET NO. 50-346 DAVIS-BESSE NUCLEAR POWER STATION, UNIT NO. 1 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 79 License No. NPF-3 1.

The Nuclear Regulatory Comission (the Comission) has found that:

A.

The application for amendment by the Toledo Edison Company and The Cleveland Electric Illuminating Company (the licensees) dated September 25, 1981, as supplemented September 26, 1983, and of the Atomic Energy Act of 1954, as amended (the Act)quirements September 11, 1984, complies with the standards and re and the Comission's rules and regulations set forth in 10 CFR Chapter I; B.

The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Comission; C.

There is reasonable assurance (1) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Comission's regulations; D.

The issuance of this amendment will not be inimical to the comon-defense and security or to the health and safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Comission's regulations and all applicable requirements have been satisfied.

2.

Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment, and paragraph 2.C.(2) of Facility Operating License No. NPF-3 is hereby amended to read as follows:

8501040023 841212 PDR ADOCK 05000346 l

Y PDR l

. _ _ - ~ -

Technical Specifications The Technical Specifications contained in Appendices A and B, as revised through Amendment No. 79', are hereby incorporated in the license. The Toledo Edison Company shall operate the facility in accordance with the Technical Specifications.

3.

This license amendment is effective as of its date of issuance.

FOR THE NUCLEAR REGU ATORY COMMISSION oh

. Stolz, Chief 0 rating Reactors Braho6 #4 ivision of Licensing

Attachment:

Changes to the Technical Specifications Date of Issuance: December 11, 1984 4

l I

i

\\

ATTACHMENT TO LICENSE AMENDMENT NO. 79 FACILITY OPERATING LICENSE NO. NPF-3 DOCKET NO. 50-346 Replace the following pages of the Appendix "A" Technical Specifications with the enclosed pages. The revised pages are identified by Amendment number and contain vertical lines indicating the area of change. The corresponding overleaf pages are also provided to maintain document completeness. -

Page 3/4 6-18 3/4 6-22 O

a O

,m.

y,_ _ - __ __ _

.-r

TABLE 3.6-2 CONTAIlmENfI50LATIONVALYE5(Continued)

PENETRATION VALVE ISOLATION NUMBER NUMBER FUNCTION TIME (seconos) 16 RC1719A Containment Vessel' Vent Header 10.

16 RC17198 Containment Vessel Vent Header 10 18 i 55598 Steam Generator Secondary Water Sagle Line 10 19 MU33 Normal RCS Makeup Line 10 19 i HP2A Nigh Pressure Injection Line 15 20 i HP28 High Pressure Iidection Line 15 21 DW6831A Domineralized Water Supply Line 10 21 DW68318 Domineralized Water Supply Line 10 22 i HP2D High Pressure Injection Line 15 25 C51531 Containment Spray Line 35 25 C51530 Containment Spray Line 35 30 f. DH9A Containment Sump Emergency Recire 71 Line

]'

31 i DH98 Containment Sug Emergency Recire Line 71 32 MC1773A RC5 Drain to RC Drain Tank 10 32 RC17738 RC5 Drain to RC Drain Tank 10

)

37 i FW601 Main Feedwater Line 15 38 i FW612 Main Feedwater Line 15 l

" 39 i M5100 Main Staan Line 5

l i

" 40 i M5101 Main Staam Line 5

l

40 i M5101-1 Main Steam Line 10 t

l DAVIS-BESSE. UNIT 1 3/4 6-17 Amendment No./, /2 S

9 e

TABLE 3.6-2 CONTAlletENT ISCLATION VALVES (Continued)

PENETRATION VALVE ISOLATION NUMBER NUMBER FUNCTION TIME (seconos) 41 RC232 Press'urizer Quench Tank Circulating Inlet Line 10 42A SA2010 Service Air Supply Line 10 425 CV5010E containment Vessel Air Sample Return 15 43A IA2011 Instruent Air supply Line 10 438 CV5011E Containment Vessel Air Sample Return 15 44A CF1541 Core Flood Tank, Fill and N2 Supply Line 10 448 NN236 Pressurizer Quench Tank M2 Supply Line 10 47A CV1545 Core Flood Tank Sample Line 10 4 78 CV1542 Core Flood Tank Vent Line 10 48 RC229A Pressurizer Quench Tank Circulating Outlet Line 10 48 RC2298 Pressurizer Quench Tank Circulating 10 Outlet Line 50 i HP2C High Pressure Injection Line 15 51 CV5037 Hydrogen Purge System Exhaust Line 60 51 CV5038 Hydrogen Purge System Exhaust Line 60 52 MU66A Reactor Coolant P e p Seal Supply 12 53 MU668 Reactor Coolant Pump Seal Supply 12 54 MU66C Reactor Coolant Pump Seal Supply 12 55 MU66D Reactor Coolant Pump Seal Supply 12 56 Mu38 Reactor Coolant Pump Seal Return 12 i

56 MU59A Reactor Coolant Pump Seal Return 30 I

$6 MU598 Reactor Coolant Pop Seal Return 30 f

56 MU59C Reactor Coolant Pump Seal Return 30 56 MU59D Reactor Coolant Pump Seal Return 30

{

57 MS603 Steam Generator Blowdown Line 80 l

60 HS611 Steam Generator Dlowdown Line 80 i

DAVIS-BESSE, UNIT 1 3/4 6-18 Amendment No. 79

[

(_

..m.-

n we--

s' n

  • rer

TABLE 3.6-2 CONTAINMENT ISOLATION VALVES (Continued)

PENETRATION VALVE ISOLATION NUMBER NUMBER FUNCTION, TIME

  • 29 f DH11 Decay Heat Pump Su: tion Line N/A
  • 29 DH23 Decay Heat Pump Suction Line N/A 29 f PSV4849 Decay Heat Pump Su: tion Line N/A 35 i AF599 Au'xiliary Feedwater Line N/A 36 i AF608 Auxiliary Feedwater Line N/A

+39 # MS107 Main Steam Line N/A

+39 i MS107A Main Steam Line N/A a40 i M5106 Main Steam Line N/A 4

e40 i MS106A Main Steam Line N/A 41 RC113 Pressurizer Quen:h Tank Inlet Line N/A 42A SA502 Service Air Supply Line N/A 428 CY124 Containment Vessel Air Sample Return N/A 43A IA501 Service Air Supply Line N/A 438 CV125 Containment Vessel Air Sar@le Return N/A 44A CF15 Core Flood Tank Fill and Nitrogen Supply Line N/A 44S NN58 Pressurizer Quench Tank Inlet Line N/A

'47A CF2A Core Flood Tank Sample Line N/A

'47A CF2B Core Flood Tank Sample Line N/A

'478 CF5A Core Flood Tank Vent Line N/A

'47B CF5B Core Flood Tank Vent Line N/A 49 DH87 Refueling Canal Fill Line N/A 49 DH88 Refueling Canal Fill Line N/A DAVIS-BESSE UNIT 1 3/4 6-21 Amendment No..'

4 O

. m.

6 CONTAINMENT ISCLATION VALVES (Centinued)

PENETRATION VALVE ISOLATION NUMBER NUMBER FUNCTION TIME 49

'DH87 Refueling Canal Fill Line N/A 49 DH88 Refueling Canal Fill Line N/A 50 i HP48 High Pressure Injection N/A 52 MU242 RCP Seal Water Supply N/A 53 MU243 RCP Seal Water Supply N/A 54 MU244 RCP Seal Water Supply N/A 55 MU245 RCP Seal Water. Supply N/A Deleted Deleted Deleted Deleted 59 Flange Secendary Side Cleaning (Inside Containment)

N/A 59 Flange Secondary Side Cleaning (Outside Contairinent)

N/A 67 CV209 Hydrogen Dilution System Supply N/A 69 CY210 Hydrogen Dilution System Supply N/A 71A # CV20003 Contairynent Pressure Sensor N/A 71C CF16 Core Flood Tank Nitrogen Fill Line h/A 72A f CV2001B Containment Pressure Sensor N/A 72C f CV624B Containment Pressure Differential Transmitter N/A 73A # CV20028 Containment Pressure Sensor N/A 73C f CV6458 Containment Pressure Differential Transmitter N/A 74A f CV20038 Containment Pressure Sensor N/A

+74C DH2735 Pressurizer Auxiliary Spray N/A

  • 74C DH2736 Pressurizer Auxiliary Spray N/A

%y be opened on an intermittent basis under administrative control.

fNot subject to Type C leakage tests. '

" Surveillance testing not reguired prior to entering MODE 4 but shall be performed prior to entering Mode 3.

ffProvisions of Specification 3.0.4 are not applicable provided the valve is in the closed positions and deactivated.

DAVIS-BESSE, UNIT 1 3/4 6-22 Amendment No. J. g,79 e