_. _ _ _ _ _ _.... _ _ _ _ _ _ _. _ _ _ _.. _ _
l i
TABLE 3.3-4 g
I
-49 ENGINEERED SAFETY FEATURES ACTUATION SYSTEN INSTRUNENTATION TRIP VALUES
'o B
ALLOWA8LE i
FUNCTIONAL UNIT TRIP SETPOINT VALUES e
1.
SAFETY IKJECTION (SIAS) a.
Manual (Trip Buttons)
Not. Applicable Not Applicable t
u i
b.
Containment Pressure - High 5 17.1 psia
$ 17.3 psia III c.
Pressurizer Pressure - Low 1 1684 psla(1) 1644 psia l
d.
Automatic Actuation Logic Not Applicable Not Applicable 2.
CONTAI N NT SPRAY (CSAS) a.
Manual (Trip Buttons)
Not Applicable Not Applicable R
t b.
Containment Pressure -- High-High i 17.7 psia i 18.0 psia j
w h
c.
Automatic Actuation Logic Not Applicable Not Applicable j
i 3.
CONTAllelENT ISOLATION (CIAS) a.
Manuel CIAS (Trip Buttons)
Not Applicable Not Applicable j
b.
Containment Pressure - High 1 17.1 psia 5 17.3 psia j
II)
III c.
Pressurizer Pressure - Low 1 1684 psia 1 1644 psia d.
Automatic Actuation Logic Not Applicable Not Appilcable 4.
NAIN STEAN LINE ISOLATION j
a.
Manual (Trip Buttons)
Not Applicable Not Appilcable I2) b.
Steam Generator Pressure - Low 3 764 psia (2) 748 psia c.
Containment Pressure - High 1 17.1 psia
$ 17.3 psia j
d.
Automatic Actuation Logic Not Applicable Not Applicable 9602080220 960206 l
PDR ADOCK 05000382 P
TABLE 3.3-4 (Continued)
ENGINEERED SAFETY FEATURES ACTUATION SYSTEM INSTRUMENTATION TRIP VALUES ALLOWABLE FUNCTIONAL UNIT TRIP VALUE VALUES 5.
SAFETY INJECTION SYSTEM SUMP RECIRCULATION (RAS) a.
Manual RAS (Trip Buttons)
Not Applicable Not Applicable b.
Refueling Water Storage Pool - Low 10.0% (57,967 gallons) 9.08% (52,634 gallons) l c.
Automatic Actuation Logic Not Applicable Not Applicable 6.
LOSS OF POWER 4.16 kV Emergency Bus Undervoltage 1 3245 volts 1 3245 volts a.
(Loss of Voltage) b.
480 V Emergency Bus Undervoltage 1 372 volts 1 354 volts 4.16 kV Emergency Bus Undervoltage c.
(Degraded Voltage) 2 3875 volts 1 3860 volts 7.
Manual (Trip Buttons)
Not Applicable Not Applicable b.
Steam Generator (l&2) level - Low 1 2 7. 4 %"
1 26. 7%"*'
Steam Generator AP - High (SG-1 > SG-2) s 123 psid s 134 psid c.
d.
Steam Generator AP - High (SG-2 > SG-1) s 123 psid s 134 psid e.
Steam Generator (l&2) Pressure - Low 2 764 psia
1 748 psla
f.
Automatic Actuation Logic Not Applicable Not Applicable g.
Control Valve Logic (Wide Range SG Level - Low) 1 36. 3%"
1 3 5. 3%"
WATERFORD - UNIT 3 3/4 3-20 Amendment No. 447 4,113 7
l h
SPECIAL TEST EXCEPTIONS 3/4.10.2 MODERATOR TEMPERATURE COEFFICIENT, GROUP HEIGHT, INSERTION, AND POWER DISTRIBUTION LIMITS LIMITING CONDITION FOR OPERATION 3.10.2 The moderator temperature coefficient, group height, insertion, and power distribution limits of Specifications 3.1.1.3, 3.1.3.1, 3.1.3.5, 3.1.3.6, 3.1.3.7, 3.2.2, 3.2.3, 3.2.7, and the Minimum Channels OPERABLE requirement of Functional Unit 15 of Table 3.3-1 may be suspended during the performance of PHYSICS TESTS provided:
The THERMAL POWER is restricted to the test power plateau a.
which shall not exceed 85% of RATED THERMAL POWER, and b.
The limits of Specification 3.2.1 are maintained and determined as specified in Specification 4.10.2.2 below.
APPLICABILITY:
MODES 1 and 2.
ACTION:
With any of the limits of Specification 3.2.1 being exceeded while the require-ments of Specifications 3.1.1.3, 3.1.3.1, 3.1.3.5, 3.1.3.6, 3.1.3.7, 3.2.2, 3.2.3, 3.2.7, and the Minimum Channels OPERABLE requirement of Functional Unit 15 of Table 3.3-1 are suspended, either:
Reduce THERMAL POWER sufficiently to satisfy the requirements of a.
Specification 3.2.1, or~
b.
Be in HOT STANDBY within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.
SURVEILLANCE REQUIREMENTS 4.10.2.1 The THERMAL POWER shall be determined at least once per hour during PHYSICS TESTS in which the requirements of Specifications 3.1.1.3, 3.1.3.1, 3.1.3.5, 3.1.3.6, 3.1.3.7, 3.2.2, 3.2.3, 3.2.7, or the Minimum Channels OPERABLE requirement of Functional Unit 15 of Table 3.3-1 are suspended and shall be verified to be within the test power plateau.
I 4.10.2.2 The linear heat rate shall be determined to be within the limits of Specification 3.2.1 by monitoring it continuously with the Incore Detector Monitoring Systes pursuant to the requirements of Specifications 4.2.1.2 and 3.3.3.2 during PHYSICS TESTS above 5% of RATED THERMAL POWER in which the requirements of Specifications 3.1.1. 3, 3.1. 3.1, 3.1. 3. 5, 3.1. 3. 6, 3.1. 3. 7. 3. 2. 2, 3.2.3, 3.2.7, or the Minimum Channels OPERABLE requirement of Functional Unit 15 of Table 3.3-1 are suspended.
WATERFORD - UNIT 3 3/4 10-2 AMENDMENT N0. 13
SPECIAL TEST EXCEPTIONS 3/4.10.4 CENTER CEA MISALIGNMENT LIMITING CONDITION FOR OPERATION 3.10.4 The requirements of Specifications 3.1.3.1 and 3.1.3.6 may be suspended during the performance of PHYSICS TESTS to determine the isothermal temperature coefficient, moderator temperature coefficient, and power coefficient provided:
a.
Only the center CEA (CEA #1) is misaligned, and b.
The limits of Specification 3.2.1 are maintained and determined as specified in Specification 4.10.4.2 below.
APPLICABILITY:
MODES 1 and 2.
ACTION:
i With any of the limits of Specification 3.2.1 being exceeded while the j
requirements of Specifications 3.1.3.1 and 3.1.3.6 are suspended, either:
a.
Reduce THERMAL POWER sufficiently to satisfy the requirements of Specification 3.2.1, or b.
Be in HOT STANDBY within'6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.
SURVEILLANCE REQUIREMENTS 4.10.4.1 The THERMAL POWER shall be determined at least once per hour during PHYSICS TESTS in which the requirements of Specifications 3.1.3.1 and/or 3.1.3.6 are suspended and shall be verified to be within the test power plateau.
4.10.4.2 The linear heat rate shall be determined to be within the limits of Specification 3.2.1 by monitoring it continuously with the Incore Detector Monitoring System pursuant to the requirements of Specifications 4.2.1.2 and 3.3.3.2 during PHYSICS TESTS above 5% of RATED THERMAL POWER in which the requirements of Specifications 3.1.3.1 and/or 3.1.3.6 are suspended.
WATERFORD - UNIT 3 3/4 10-4
gt TABLE 4.3-2 (Continued) a 92 ENGINEERED SAFETY FEATURES ACTUATION SYSTEN INSTRUNENTATION SURVEILLANCE REQUIRENENTS B
CHANNEL N00ES FOR WHICH CHANNEL CHANNEL FUNCTIONAL SURVEILLANCE l
c=
FUNCTIONAL UNIT CHECK CALIBRATION TEST IS REQUIRED 5
5.
SAFETY INJECTION SYSTEN i
RECIRCULATION (RAS) a.
Manual RAS (Trip Buttons)
N.A.
N.A.
R 1,2,3,4 l
b.
Refueling Water Storage Pool - Low S
R Q
1, 2, 3, 4 c.
Automatic Actuation Logic (except subgroup relays)
N.A.
N.A.
Q(2) 1, 2, 3 Actuation Subgroup Relays N.A.
N.A.
N(1) (3) 1, 2, 3 6.
LOSS OF POWER (LOV) w a.
4.16 kV Emergency Bus 3:
Undervoltage (Loss of Voltage)
N.A.
R D(4) 1, 2, 3 o,
4 b.
480 V Emergency Bus cn Undervoltage (Loss of i
Voltage)
N.A.
R D(4) 1, 2, 3 c.
4.16 kV Emergency Bus Undervoltage (Degraded Voltage)
N.A.
R D(4) 1, 2, 3 i
. e.
2m
!h as
.R
- + -
4
.e m
4 m
n--
M
-m-
.a u
-w.m m
-m---
4 4
NPF-38-176 ATTACHMENT B
l l
1ABLE 3.3-4 l
ENGINEERED SAFETY FEATURES ACTUATION SYSTEM INSTRUMENTATION TRIP VALUES ALLOWABLE' FUNCTIONAL UNITS TRIP SETPOINT VALUES 1.
SAFETY INJECTION (SIAS) a.
Manual (Trip Buttons)
Not Applicable Not Applicable b.
Containment Pressure - High s 17.1 psia s 17.4 psia 1684 psia (1) 2 1649.7 psia (1) c.
Pressurizer Pressure - Low 2
d.
Automatic Actuation Logic Not Applicable Not Applicable 2.
CONTAINMENT SPRAY (CSAS) a.
Manual (Trip Buttons)
Not Applicable Not Applicable t
b.
Containment Pressure -- High-High s 17.7 psia s 18.0 psia t
c.
Automatic Actuation Logic Not Applicable Not Applicable 3.
CONTAINMENT ISOLATION (CIAS) a.
Manual CIAS (Trip Buttons)
Not Applicable Not Applicable i.
f b.
Containment Pressure - High s 17.1 psia s 17.4 psia 1684 psia (1) 2 1649.7 psia (1)-
t c.
Pressurizer Pressure - Low 2
d.
Automatic Actuation Logic Not Applicable Not Applicable 4.
MAIN STEAM LINE ISOLATION a.
Manual (Trip Buttons)
Not Applicable Not Applicable 2 749.9 psia (2) b.
Steam Generator Pressure - Low 2 764 psia (2) f c.
Containment Pressure - High s 17.1 psia s 17.4 psia r
d.
Automatic Actuation Logic Not Applicable Not Applicable f
WAlERFORD - UNIT 3 3/4 3-19 l
.m a
e
-i TABLE 3.3-4 (Continued)
ENGINEERED SAFETY FEATURES ACTUATION SYSTEN INSTRUNENTATION TRIP VALUES ALLOWABLE
~
FUNCTIONAL UNIT TRIP VALUE VALUES 5.
SAFETY INJECTION SYSTEM SUNP RECIRCULATION (RAS) a.
Manual RAS (Trip Buttons)
Not Applicable Not Applicable b.
Refueling Water Storage Pool - Low 10.0% (57. % 7 gallons) 9.08% (52.634 gallons) c.
Automatic Actuation Logic Not Applicable Not Applicable 6.
LOSS OF POWER a.
4.16 kV Emergency Bus Undervoltage 2 3245 volts 2 3245 volts (Loss of Voltage) b.
480 V Emergency Bus Undervoltage 2 372 volts 2 354 volts c.
4.16 kV Emergency Bus Undervoltage (Degraded Voltage) 2 3875 volts 2 3860 volts 7.
Manual (Trip Buttons)
Not Applicable Not Applicable b.
Steam Generator (1&2) Level - Low 2 27.4g(3) (4) 2 26.48t(3) (4) c.
Steam Generator AP - High (SG-1 > SG-2) s 123 psid s 134 psid d.
Steam Generator AP - High (SG-2 > SG-1) s 123 psid s 134 psid e.
Steam Generator (1&2) Pressure - Low 2 764 psia (2) 2 749.9 psia (2) f.
Automatic Actuation Logic Not Applicable Not Applicable g.
Control Valve Logic (Wide Range 2 36.3t(3) (5) 2 35.3t(3) (5)
SG Level - Low)
WATERFORD - UNIT 3 3/4 3-20 AMENDNENT NO. 113
_ _. ~..
SPECIAL' TEST EXCEPTIONS 3/4.10.2 MODERATOR TEMPERATURE COEFFICIENT. GROUP HEIGHT, INSERTION. AND POWER DISTRIBUTION LIMITS LIMITING CONDITION FOR OPERATION 3.10.2 The moderator temperature coefficient, group height, insertion, and power distribution limits of Specifications 3.1.1.3, 3.1 3.1, 3.1.3.5, 3.1.3.6, 3.1.3.7, 3.2.2, t
3.2.3, 3.2 7, and the Minimum Channels OPEPABLE requirement of Functional Unit 15 of Table 3.3-1 may be suspended during the performance of PHYSICS TESTS provided:
a.
The THERMAL POWER is restricted to the test power plateau which shall not exceed 85% of RATED THERMAL POWER, and b.
The limits of Specification 3.2.1 are maintained and determined as specified in Specification 4.10.2.2 below.
APPLICABILITY: MODES 1 and 2.
ACTION:
With any of the limits of Specification 3.2.1 being exceeded while the requirements of Specifications 3.1.1.3, 3.1.3.1, 3.1.3.5, 3.1.3.6, 3.1.3.7, 3.2.2, 3.2.3, 3.2.7, and the Minimum Channels OPERABLE requirement of Functional Unit 15 of Table 3.3-1 are suspended, either:
a.
Reduce THERMAL POWER sufficiently to satisfy the requirements of Specification 3.2.1, or b.
Be in HOT STANDBY within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.
SURVEILLANCE REQUIREMENTS 4.10.2.1 The THERMAL POWER shall be determined at least once per hour during PHYSICS TESTS in which the requirements of Specifications 3.1.1.3. 3.1.3.1, 3.1.3.5. 3.1.3.6, 3.1.3.7, 3.2.2, 3.2.3, 3.2.7, or the Minimum Channels OPERABLE requirement of Functional Unit 15 of Table 3.3-1 are suspended and shall be verified to be within the test power plateau.
4.10.2.2 The linear heat rate shall be determined to be within the limits of Specification 3.2.1 by monitoring it continuously with the Incore Detectiony Monitoring System pursuant to the requirements of Specifications 4.2.1.2 and 3.3.3.2 during PHYSICS TESTS above 5% of RATED THERMAL POWER in which the requirements of Specifications 3.1.1.3, 3.1.3.1, 3.1.3.5. 3.1.3.6, 3.1.3.7. 3.2.2. 3.2.3. 3.2.7, or the Minimum Channels OPERABLE requirement of Functional Unit 15 of Table 3.3-1 are suspended.
WATERFORD - UNIT 3 3/4 10-2 AMENDMENT 13
i SPECIAL TEST EXCEPTIONS 3/4.10.4 CENTER CEA MISALIGNMENT LIMITING CONDITION FOR OPERATION 3.10.4 The requirements of Specifications 3.1.3.1 and 3.1.3.6 may be suspended during the performance of PHYSICS TESTS to determine the isothermal temperature coefficient, moderator temperature coefficient, and' power coefficient provided:
L a.
Only the center CEA (CEA #1) is misaligned, and -
b.
The limits of Specification 3.2.1 are maintained and determined as specified in Specification 4.10.4.2 below.
I APPLICABILITY: MODES 1 and 2.
ACTION:
With any of the limits of Specification 3.2.1 being exceeded while the requirements of Specifications 3.1.3.1 and 3.1.3.6 are suspended, either:
a.
Reduce THERMAL POWER sufficiently to satisfy the requirements of specification 3.2.1, or b.
Be in HOT STANDBY within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.
SURVEILLANCE REQUIREMENTS 4.10.4.1 The THERMAL POWER shall be determined at least once per hour during PHYSICS TESTS in which the requirements of Specifications 3.1.3.1 and/or 3.1.3.6 are suspended and shall be verified to oe within the test power plateau.
4.10.4.2 The linear heat rate shall be determined to be within the limits of Specification 3.2.1 by monitoring it continuously with the Incore Detection _f Monitoring System pursuant to the requirements of Specifications 4.2.1.2 and 3.3.3.2 during PHYSICS TESTS above 5% of RATED THERMAL POWER in which the requirements of Specifications 3.1.3.1 and/or 3.1.3.6 are suspended.
WATERFORD - UNIT 3 3/4 10-4
I l
l l
TABLE 4.3-2 (Continued) l l
ENGINEERED SAFETY FEATURES ACTUATION SYSTEM INSTRUMENTATION SURVEILLANCE REQUIREMENTS 1
CHANNEL MODES FOR WICH CHANNEL CHANNEL FUNCTIONAL SURVEILLANCE FUNCTIONAL UNIT CHECK CALIBRATIONS TEST IS REQUIRED 5.
SAFETY INJECTION SYSTEM RECIRCULATION (RAS) a.
Manual RAS (Trip Buttons)
N.A.
N.A.
R 1,2,3,4 b.
Refueling Water Storage l
Pool - Low 5
R Q
1,2,3,4 i
c.
Automatic Actuation Logic (except subgroup relays)
N.A.
N.A.
Q(2) 1, 2, 3, 4 Actuation Subgroup Relays N.A.
N.A.
M(1) (3) 1,2,3,4 6.
LOSS OF POWER (LOV) a.
4.16 kV Emergency Bus Undervoltage (Loss of Voltage)
N.A.
R D(4) 1, 2, 3 b.
480 V Emergency Bus Undervoltage (Loss of Voltage)
N.A.
R D(4) 1, 2, 3 c.
4.16 kV Emergency Bus Undervoltage (Degraded Voltage)
N.A.
R D(4) 1, 2, 3 I
WATERFORD - UNIT 3 3/4 3-26 AMENDMENT NO.,78
....m
.+..
- a
-