ML20100D190

From kanterella
Jump to navigation Jump to search
Interim Deficiency Rept 55(e)-84-44 Re Rosemount Model 1153B Transmitters.Initially Reported on 841012.Investigation of Corrective Action in Progress.Final Rept Expected by 850121
ML20100D190
Person / Time
Site: Nine Mile Point 
Issue date: 11/13/1984
From: Mangan C
NIAGARA MOHAWK POWER CORP.
To: Starostecki R
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
References
(NMP2L-0236), (NMP2L-236), 55(E)-84-44, NUDOCS 8412050712
Download: ML20100D190 (2)


Text

+b

'[& :s,

N3FKdBA MIAGARA MOHAWK POWER CORPORATION /300 ERIE BOULEVARD WEST. SYRACUSE, N Y.13202/ TELEPHONE (315) 4741511 1

November 13,1984 (NMP2L0236)

Mr. R. W. Starostecki, Director U.- S. Nuclear Regulatory Commission Region I-Division of Project and Resident Programs 631 Park Avenue

' King -of Prussia, PA 19406 Re: Nine Mile Point - Unit 2 Docket No. 50-410

Dear Mr. Starostecki:

Enclosed is an interim report, in accordance with 10CFR50.55(e), for the problem concerning_ Rosemount Model 1153B transmitters.-

This problem was reported via tel-con to T. Silko of your staff on October 12, 1984 Very truly yours, C. V. Mangen Vice President Nuclear Engineering and Licensing CVM/GG/dd Enclosure xc: Director of Inspection and Enforcement U. S. Nuclear Regulatory Commission Washington, DC ~20555 R. A. Graami, _ NRC Resident Inspector ProjectFile(2) 8412000712 1113

~

PDR-ADOCK 0 410 s

PDR

^

~

-/_

'.i. f */ -

s

gt #

a NIAGARA M0 HAWK POWER CORPORATION NINE MILE POINT - UNIT 2 00CKET NO.-50-410 Interim Report for a Problem Concerning Rosemount Model 1153B Transmitters (55(e)-84-44)

Description of the Problem The problem concerns Model 1153 Series B pressure transmitters manufactured by Rosemount Incorporated after January 10, 1984.

Rosemount has identified a potential leakage path in the seal of the threads between the sensor module and the electronic-housing.

According to Rosemount, there is a possibility that this leak path could allow moisture from. the ambient surrounding environment -to enter the electronics housing during abnormal operating conditions and cause the transmitter to stop functioning.

Transmitter Mark Nos. 2RSS*PT109 and 2IAS*PT230 through 236 are affected by this problem.

These transmitters have no direct control function.

Pressure transmitter Mark No. 2RSS*PT109 monitors the pressure of the automatic depressurization system Tank No. 33 and provides a pressure indication at the remote shutdown panel.

Pressure transmitter Mark Nos. 2IAS*PT230 through 236 monitor the pressure of the automatic depressurization system accumulator Tank Nos. 32 through 38 Rosemount Incorporated is still investigating the corrective action.

Therefore, a final report will be submitted by January 21, 1985, t