Resubmits 840928 Response to Generic Ltr 84-15, Proposed Staff Actions to Improve & Maintain Diesel Generator Reliability, to Include Oath & Affirmation
ML20100A646
Person / Time
Site: Summer 
Issue date: 11/29/1984
From: Dixon O
SOUTH CAROLINA ELECTRIC & GAS CO.
To: Harold Denton
Office of Nuclear Reactor Regulation
References
GL-84-15, NUDOCS 8412040026
Download: ML20100A646 (1)


Text

"

l SOUTH CAROLINA ELECTRIC & GAS COMPANY POST OFFIC 764 COLuwelA. south CAROLINA 29218 O. W. DIXON. Jn.

uvC$e'd'o',*.' [r$,..

November 29, 1984 Mr. Harold R. Denton, Director Office of Nuclear Reactor Regulation U.S. Nuclear Regulatory Commission Washington, D.C. 20555

Subject:

Virgil C. Summer Nuclear Station Docket No. 50/395 Operating. License No. NPF-12 Generic Letter 84-15 Diesel Generator Reliability

Dear Mr. Denton:

In a letter dated September 28, 1984, South Carolina Electric and Gas Company (SCE&G) provided a response to Generic Letter 84-15,

" Proposed Staff. Actions to Improve and Maintain Diesel Generator Reliability."

The Generic Letter requested that the submittal be made under oath or affirmation.

However, SCE&G did not include the oath or affirmation in the response.

Therefore, SCE&G is hereby retransmitting as Attachment A to this letter, the September 28, 1984 submittal.

The statements and matters set forth in this letter and its attachment are true and correct to the best of my knowledge, information and belief.

If you have any questions, please advise.

Very truly yours, l

V a

m O. W.

i Mn, Jr.

I AMM/OWD/gj

Attachment:

C. A. Price cc:

V. C.

Summer T.

C. Nichols, Jr./O. W. Dixon, Jr.

C.

L. Ligon (NSRC)

E.

H.

Crews, Jr.

K.

E. Nodland E.

C. Roberts R. A.

Stough W. A. Williams, Jr.

G.

Percival C. W. Hehl D. A.

Nauman J. P.

O'Reilly J.

B.

Knotts, Jr.

NPCF Group Managers

/g, U

O. S. Bradham File

$25tggohSeasgg gQ c

P

ATTACHMENT A

' ' SOUTH CAROLINA ELECTRIC & gas COMPANY post 088lC. 764 CotunaciA; SouTM CAmoWNA 29218 O. W. Omom.J..

mve$*.I.Y.Ir$.

September 28, 1984 Mr.. Harold R. Denton, Director Office of Nuclear Reactor Regulation U.S. Nuclearz Regulatory Commission Washington, D.C.

20555-

Subject:

Virgil C. Summer Nuclear Station Docket No. 50/395 Operating License No. NPF-12 Generic Letter 84-15 Diesel Generator Reliability

Dear Mr. Denton:

This letter is provided in response to Generic Letter 84-15,

" Proposed Staff Actions to Improve and Maintain Diesel Generator Re liab ility."

South Carolina Electric and Gas Company (SCEEG) maintains two (2) diesel generators at the Virgil C.

Summer.

Nuclear Station.

These diesel generators are 12 cylinder, V-configuration with a 4,250KW continuous rating.

They were manufactured by Fairbanks Morse and are equipped with prewarm systems designed to maintain lube oil. and jacket water cooling systems betweeen 100*F and 140*F.

The d'iesel generators are currently tested in accordance with the l

requirements of Regulatory. Guide 1.108, Revision 1, August 1977, and the Technical Specifications for the facility.

Fast starts f rom ambient normal standby conditions verify the capability of the diesel generators to:

Accelerate to rated speed, voltage, and frequency in 1.10 1)

(.

seconds.

2)

Synchronize and load to > 4,250 KW within i 60 seconds.

j Test starts with the prewarm systems as described above do not constitute " Cold Starts" per criteria established in Generic Letter 83-41, " Fast Cold Starts of Diesel Generators."

SCEEG considers the present testing and surveillance programs at l

the: Virgil C. Summer Nuclear Station sufficient to demonstrate the reliability of the diesel generators.

However, the proposed

[

Technical Specification changes outlined in Generic Letter 84-15 l

should help to further decrease engine wear and improve diesel l

engine reliability.

W2{# //2.-

i

(

O Mr. Harold.R. DGnton Generic' Letter 84-15

' Diesel Generator Reliability September-28, 1984 Page #2 Summer Nuclear Station maintains a record which The Virgil C.

itemizes the demands and failures experienced by each diesel generator in the manner outlined in Kegulatory Guide 1.108, Item C.3.a.

Additionally, a yearly data report is maintained for each diesel generator's reliability in accordance with NGREG 0737, Item II.K.3.17.

The number of valid tests and failures for the two (2) diesel generators for the Virgil C. Summer Nuclear Station is listed in Attachment I to this letter.

The Virgil C. Summer Nuclear Station does not have a formal diesel generator reliability program for attaining and 7

maintaining a reliability goal as addressed in Generic Letter 84-15.

However, the reliability of the diesel generators is maintained by the below actions and is considered to be adequate based on the test results documented in Attachment I.

1)

Surveillance Testing performed in accordance with the requirements of Technical Specification 3.8.1.1 and l

Regulatory Guide 1.108.

In accordance with NUREG-0737, Item II.K.3.17, a program has 2) been established using existing plant procedures for data collection including Emergency Core Cooling System (ECCS) outage times, duration and cause of the outage, components involved in the outage, and corrective action taken.

A j

l l

plant procedure for removal and restoration of station equipment provides measures for data collection.

The ECCS data taken by this procedure will be reviewed by appropriate plant personnel to determine if improvements to availability l

l of ECCS is needed.

J 3)

As. stated by the'NRC, upon completion of modifications addressed in the Safety Evaluation Report, Section 9.5.4 (by startup af ter the first refueling outage), the: design of the diesel generators and their auxiliary systems will be in conformance with the recommendations of NUREG/CR-0660.

Conformance with the recommendations provides reasonable assurance of continued diesel generator reliability.

SCE&G has, however, performed a review of the sample diesel generator Technical Specification changes found in the Attachment to Enclosure 1 and Appendix A of Generic Letter 84-15.

SC E&G' s position is that these proposed Technical Specification changes These do provide for increased diesel engine reliability.

changes are beneficial because they help to reduce the number of fast starts without prelube, thus decreasing possibility of additional engine wear.

These proposed Technical Specifications,

{

Mr. Harold R. Denton Generic Letter 84-15 Diesel Generator Reliability September 28, 1984 Page 63 if determined by the Staf f to be acceptable, would help to provide the Virgil C. Summer Nuclear Station with a formal reliability program for the diesel engines.

If you have any further questions, please advise.

Very truly yours, 7

I// t' p

~

0. W.

xo n, J r.

AMM/OWD/gj

Attachment:

C.

A.

Price cc:

V. C.

Summer T. C. Nichols, Jr./O. W. Dixon, Jr.

C.

L.

Ligon (NSRC)

K.

E. Nodland E.

H. Crews, Jr.

R. A.

Stough E.

C. Roberts G.

Percival W. A.

Williams, Jr.

C. W. Hehl D. A.

Nauman J.

B.

Knotts, Jr.

t i

J. P. O' Reilly NPCF Group Managers File l

0. S.

Bradham 1

l l.

4 ATTACHMENT I DIESEL GENERATOR A Last 100 Valid Demands

  • Failures Starts 0

36 Last 20 Valid Demands Failures Starts 0

20 DIESEL GENERATOR B Last 100 Valid Demands

  • Failures Starts 1**

41 Last 20 Valid Demands Failures Starts 0

20 Have not had 100 valid demands to date I

Failure occurred 12/18/82, 33 valid starts since that event