ML20096F455
| ML20096F455 | |
| Person / Time | |
|---|---|
| Site: | 05200004 |
| Issue date: | 12/12/1995 |
| From: | Wingate G GENERAL ELECTRIC CO. |
| To: | |
| Shared Package | |
| ML20096F375 | List: |
| References | |
| 25A5824, NUDOCS 9601230401 | |
| Download: ML20096F455 (26) | |
Text
yv;. -
,=v, GENuclearEnw
- 5^58 *
,, o REVISION STATUS SHEET DOCUMENT TITLE PANDA TEST PLAN -TEST M9 LEGEND OR DESCRIPTION OF CROUPS TYPE:
TEST SPECIFICATION FMF:
SBWR MPL NO:
T10-5010 THIS ITEM IS OR CONTAINS A SAFETY.RElATED ITEM YES @ NO O EQUIP CLASS CODE C REVISION l
C 0
RM-03285 2 1995 PRINTS TO MADE BY APPROVALS GENERAL ELECTRIC COMPANY G.A. WINCATE 12/4/95 J.E. TORBECK 12/11/95 175 CURTNER AVENUE SAN JOSE CALIFORNIA 95125 CHKD BY:
ISSUED R. AHMANN gEb l 21995 r-NA CONT ON SHEET 2 MS WORD (3/28/94) 9601230401 960117 PDR ADOCK 05200004 A
9
@MCNRSf' rey J 25A5824 SH No. 2 G
TABLE OF CONTENTS
- 1. SCOPE.....
..3
- 2. APPLICABLE DOCUMENTS............
. 3
- 4. TEST FACILITY CONFIGURATION...................
........................ 5
- 5. CONTROL SYSTEM DESCRIPTION.....
11
.11 5.1 RPV llEAER POWER CONTROL.,.
.. I 1 5.2 DRYWELIlWETWELL VACUUM BREAKER CONTROL..
- 6. REQUIRED MEASUREMENTS
............12
- 7. DATA RECORDING, PROCESSING AND ANALYSIS....
.........17
.17 7.1 DATA RECORDING....
7.4 DATA PROCESSING AND ANALYSIS..
. 17
- 8. S IIA KEDO WN TESTS...
........... 19
- 9. TEST MATRIX........
..... 20 9.1 TEST DESCRIPTION.,
. 20
. 25 9.2 TEST ACCErrANCE CRITERIA....
- 10. RE PO RTS.....................................
............. 26
- 11. TEST 110LD/ DECISION POINTS...............
.............. 26
r 25A5824 SH No 3 EDE iiry)/
arv. 0 m
- 1. SCOPE This test plan defines the detailed requirements, beyond those already identified in GE Spec 25A5587, for the PANDA transient integral system tests M9. This Test Plan specifically covers the test program objectives, the experimental facility configuration, the test facility control, the test instrumentation, the data acquisition, processing and analysis, the test initial and boundary conditions and the test reports for test M9.
This test plan is applicable to the SBWR Design Certification project only.
R. APPLICABLE DOCUMENTS
- a. PANDA Test Specification, GE Spec 25A5587.
This document provides the general specification of requirements for tests in the PANDA facility to support SBWR Design Certification.
- b. PANDA Steady State Tests--
PCC Performance Test Plan & Procedure, PSI Doc. TM-42-94-11/ ALPHA 410.
This document provides a general description of the PANDA test facility and the specific plan and procedure for steady state tests of the PCC condenser performance.
- c. PANDA PROJECT CONTROL PLAN, GE Doc.
PPCP-QA-01.
This document describes the organization, quality related activities, events and procedures necessary to ensure and verify that the PANDA project at PSIis conducted under the provisions of the GE SBWR Quality Assurance Plan as described in NEDG-31831.
- d. PANDA Test Plan, GE Spec 25A5764 This test plan defines the detailed requirements, beyond those already identified in GE Spec 25A5587, for the PANDA transient integral system tests M3, MSA, MSB, M4 and M7.
t 9
EhM nsv. 0 25A5824 sH No.4
- 3. TEST OBJECTIVES The objectives of the PANDAintegral systems tests are to provide additional data to: (a) provide a sufficient database to confirm the capability of TRACG to predict SBWR containment system performance, including potential systems interaction effects. (Integral Systems Tests) and (b) Demonstrate startup and long-term operation of a passive containment cooling system.
(Concept Demonstration).
The specific objectives and approach for the tests covered by this test plan are given below:
The objective is to perform test M9 with conditions simulating the transition from the GDCS injection phase to the long-term PCC cooling phase of the post-LOCA transient.
The approach to meet these objectives will be to set the GDCS initial conditions (level and temperature) and RPV conditions (initial water level and power through the test) to obtain containment behaviors (e.g. drywell pressure change, vacuum breaker operation) which are representative of the SBWR during this transition period.
--,__a
25A5824 sH No. 5 EM REV. 0
- 4. TEST FACILTIY CONFIGURATION The PANDA test facilityis described in detailin Section 3 of PSI report ALPHA 410. For Test M9 the PANDA facility will be configured tc simulate the SBWR post-LOCA configuration as follows:
- 1) Table 4.1 identifies the key PANDA facility geometry and effective flow area ( A / /k )
characteristics. In Table 4.1, the r quired tolerance for the PANDA as-built value relative to the corresponding SBWR scaled value is tabulated for each of these key characteristics. In addition, the required accuracy for the as-built value for each of the key characteristics is tabulated in Table 4.1. The actual as-built accuracy should be approximately equal to or less than the required accuracy tabulated in Table 4.1. The actual as-built accuracies depend on the source of the as-built value. These sources can be measurements by PSI or Electrowatt (i.e.
line losses, line lengths, elevations), manufacturer's specifications or design standards (i.e.,
PCC/IC tubes), or calculations from as-built dimensions (i.e., vessel volumes, losses for lines without flow tests).
- 2) The RPV will supply steam to each drywell with two steam lines (one to each dqwell). These two steam lines will have the same pressure loss characteristics.
- 3) RPV heater power will be controlled as a function of time to create conditions similar to the early phase of the GDCS injection after which it will be ramped back to simulate the scaled decay heat and stored energy release.
- 5) All three PCC units will be lined-up to take feedflow from the drywells, to vent noncondensables and steam into the water volume of the suppression pool, and drain condensate to the GDCS volume.
- 6) The PCC pools will be filled and isolated from each other. During the test, no water will be added or drained.
- 7) The i ly direct lines of communication between the drywell and wetwell will be through the vacuum breakers (when the wetwell pressure exceeds dqwell pressure sufficiently to open the vacuum breaker) and the main vent lines (which will be submerged within the wetwells).
- 8) The GDCS pressure equalization lines to both drywells will be open.
- 9) The GDCS drain line with check valve will be lined up to return PCC condensate to the RPV l
as part of the test initiation sequence.
- 10) The Equalizing lines between the RPV and wetwells will be valved out of sersice.
I
1 O
Eh 25A5824 su No. 6 Table 4.1:
PANDA Transient Integral System Tests Key Facility Characterisdcs PARAMETER TOLERANCE FOR PANDA PANDA AS-BUILT ACCURACY AS-BUILTVALUE REI ATIVE TO SBWR SCALED VALUE FOR PANDA PCC Heat Ex. chancer Tubing
-Length i5%
i5mm
-Outside i5%
i 0.3 mm Diameter
-Thickness i 15 %
0.2 mm PCC Heat Exchancer Headers
-Outside i5%
i5mm diameter
-Length 15%
i5mm
-Steel thickness i5%
i 0.3 mm cylindiical SeCdOn
-Steel thickness i5%
i 0.3 mm end plates
-Distance i5%
i5mm between headers (drums)
gx_.
,=y 25A5824 SH No. 7 EhM arv. O Table 4.1:
PANDA Transient Integral System Tests Key Facility Characteristics (continued)
PARAMETER TOLERANCE FOR PANDA AS-PANDA AS-BUILT ACCURACY BUILT VALUE REI ATIVE TO SBWR SCATED VALUE FOR PANDA Vessel Volumes
-RPV i 10 %
i2%
-Dr>well 1 i 10 %
i2%
-Drywell 2 i 10 %
2%
-Wetwell 1 i 10 %
2%
-Wetwell 2 10 %
i2%
-GDCS (1) i2%
- PCC pools (2) 2%
(1)
GDCS pool volume is not scaled to SBWR (2)
PCC pool volumes are not scaled to SBWR
/
O MNuciaarEnergy wx 25A5824 sH NO. 8 c
Table 4.1:
PANDA Transient Integral System Tests Key Facility Characteristics (continued)
PARAMETEE TOLERANCE FOR PANDA AS-PANDA AS-BUILT BUILT VAIJJE RELATIVE TO ACCURACY SBWR SCALED VALUE FOR PANDA-Elevation Differences P1V-P2V-PSV 2cm i1cm discharges PIC inlet to outlet i 10 cm iIcm P2C inlet to outlet 10 cm iIcm PSC inlet to outlet i10 cm ilcm P1V,P2V,PSV 5cm i1cm discharges relative to normal suppression poollevel MV1 and MV2 i5cm ilcm discharges relative to normal suppression poollevel P1V,P2V,PSV i5cm i1cm l
discharges relative to MV1 and MV2 discharges P1F, P2F, PSF inlet
+ 200 cm/ - 0 1cm relative to MS1 and l
MS2 discharge
25A5824 SH No.9 Eh as v. O Table 4.1:
PANDA Transient Integral System Tests Key Facility Characteristics (continued)
PARAMETER TOLERANCE FOR PANDA AS.
PANDA AS-BUILT BUILT VALUE RET ATIVE TO ACCURACY SBWR SCAT FD VALUE FOR PANDA Elevations (relative to TAF/ Heaters)
P1F,P2F, PSF
+ 200 cm/ - 0 i5mm intet PlC,P2C,PSC i5 cm i5mm inlet P1V,P2V,PSV i 5 cm i5mm discharge GRT inlet 15cm 5mm GRT oudet i5cm i5mm MV1 oudet i5cm i5mm MV2 oudet i5cm i5mm MSL 1 oudet 15cm i5mm MSL 2 oudet 5cm 5mm Top of RPV 25 cm i 50 mm chimney
g%..
+y 1
9'
@hEf3ENg7 any. 0 25A5824 SH NO.10 1
1 Table 4.1:
PANDA Transient Integral System Tests Key Facility Characterisdcs (continued)
PARAMETER TOLERANCE FOR PANDA A& BUILT PANDA AS-BUILT VALUE RELATIVE TO SBWR ACCURACY SCAI ED VALUE FOR PANDA Connecting Line Flow Resistances RPV to DW1 1 20 %
i 10 %
i 10 %
DW 1 to PCC1 i 20 %
i 10 %
DW 2 to PCC2 i 20 %
10 %
DW 2 to PCCS 1 20 %
i 10 %
DW 1 to WW 1 (3) i 10 %
(LOCA vent)
DW 2 to WW 2 (3) 10 %
(LOCA vent)
PCC1 to GDCS i 20 %
i10%
PCC2 to GDCS 20 %
i 10 %
PCC3 to GDCS i 20 %
i10%
PCC1 to WW 1 i 20 %
i10%
PCC2 to WW 2 20 %
i 10 %
PCCS to WW 2 i 20 %
i 10 %
GDCS to RPV 1 20 %
i 10 %
WW 1 to DW 1 1 20 %
i 10 %
(bypass /vac. brkr)
(3) LOCA vents are not scaled to SBWR P
A 25A5824 sH No.1I E h N uiiv g /
nsv. 0 5.
CONTROL SYSTEM DESCRIITION In order to perform the transient integral system tests, several control systems are to be used to establish initial and boundary condidons for each test. These control systems will be used to manage and regulate the key test parameters prior to the test. Following test initiation, only the RPV heater power and the vacuum breaker controllers will be used. A main control system, which includes the electronic controllers, will be used to perform the operations.
5.1 RPV IIeater Power Control During the test initiadon the electrical power to the RPV beaters will be placed in automadc control to follow the curve specified in Section 9. This power together with the GDCS conditions will give representative RPV steam flow to the drywells during the GDCS injection phase of the LOCA after which it will match the scaled decay pc.
and RPV structural heat release of the base case test MS.
5.2 Drywell/Wetwell Vacuum Breaker Control The operation of the vacuum breaker valves will be controlled based on the measured pressure difference between the dqwell and wetwell. Drywell pressure is initially established at a value equal to or greater than the wetwell pressure to conform to the post-LOCA condition specified for the beginning of each individual test. During the course of a test if the drywell to wetwell pressure drops below a minimum value the vacuum breaker valve control will automatically open both valves between the dnwell and wetwell volumes. The wetwell-to-drywell differential pressure at which the vacuum breakers open will be set at 0.47 psi (3.24 kPa), and the differential pressure at which the vacuum breakers close will be set at 0.30 psi (2.06 kPa).
l
t 25A5824 sa no.12 9'
MMBCltRSr'Erungy ner. o 6.
REOUIRED MEASUREMENTS Table 6.1 gives the measurements required to meet the objectives for Test M9. With the -
exception of the temperature indication, no PANDA instrumentadon other than that in Table 6.1 is necessary for the performance of Test M9. The sensors idendfied in Table 6.1 must be operable prior to initiation of these tests. Itis acceptable if a sensor is not operable,if the backup identified in the second column is operable.
Temperature measurements in the PCCs and the various connected vessels are desirable, but not all of these temperature measurements are required for the performance of these tests as discussed below. The temperature measurements required for these tests with an accuracy of 1.5"C are as follows:
RPV steam dome (at least one).
PCC tubes; (It is required that 50% of the tube wall and fluid sensors be available. The available sensors must include at least 40% of the probes above and at least 40% of the probes below the horizontal mid-plane of the tube bundle.Within these constraints, the test engineer has responsibility and authority tojudge whether or not sufficient PCC temperature sensors are operable to initiate a test).
PCC pools: 30% of the liquid probes including one of the lowest three elevations.
DW: 50% of the fluid probes including either the lowest elevation or one thermocouple from the water-surface probe.
WW: 50% of the gas probes,50% of the liquid probes and two out of three of the floating probes.
GDCS pool: 50% of the fluid probes and one thermocouple from the floating probe.
Vessel walls: 20% of GDCS, DW, and WW.
System lines: 50% of the gas and liquid temperature probes in each system line used for the test (if number of sensors is odd, round to lower whole number, i.e. 3 sensors total in one line means one is required).
In Table 6.1 a subset of the required instruments are identified as " top priority measurements".
Time history plots of these top priority measurements are to be included in the Test File (see Section 7.3) and the Apparent Test Results (ATR) Report (see Section 10). In addition to the top priority measurements identified in Table 6.1, there are other top priority measurements. These are: 1) the total electrical power to the heaters in the RPV which is determined during post-test
o 25A5824 sH No.13 GENucienerEnnwgy nev. o
' data processing, and 2) some temperature measurements. The top priority temperature measurements are: RPV steam dome temperature measurement, highest and lowest temperature measurement location in each drywell, highest and lowest temperature measurement location in the gas space of each wetwell, highest liquid temperature measurement location in each wetwell, and one temperature measurement in the GDCS drain line and in each of the three PCC vent lines.
As noted in Section 7.4, the operator will perform checks as possible to confirm instrumentation performance. These checks will include comparison of redundant measurements.
s 824 snNo.14 g
Table 6.1:
INSTRUMENTATION REQUIRED
- FOR TEST M9 Processid **
Backup Accuracy Location CBNB1 +
N/A Valve position : Vacuum Breaker Line 1 (On/Of0 CB.VB2 +
N/A Valve position : Vacuum Breaker Line 2 (On/Of0 MD.MV1 MI.MV1 0.5 kPa pressure diff. meas. Main Vent line DWl->SCl MD.MV2 MI.MV2 0.5 kPa pressure diff. meas. Main Vent line DW2->SC2 MD.P1F MV.PlF 0.5 kPa pressure diff. meas. PCC1 Feed DWl->PCCl MD.PlV.2 MI.PlV.1 0.5 kPa pressure diff. meas. PCCl Vent PCCl-> SCI MD.P2F MV.P2F 0.5 kPa pressure diff. meas. PCC2 Feed DW2->PCC2 MD.P2V.2 MI.P2V.1 0.5 kPa pressure diff. meas. PCC2 Vent PCC2->SC2 MD. PSF MV.P3F 0.5 kPa pressure diff. meas. PCC3 Feed DW2->PCCS MD.PSV.2 MI.P3V.1 0.5 kPa pressure diff. meas. PCCS Vent PCCD->SC2 MD.VB1 MD.VB2 0.5 kPa pressure diff. meas. Vacuum Breaker SCl-DW1 MDNB2 MD.VB1 0.5 kPa pressure diff. meas. Vacuum Breaker SC2-DW2 MI.MV1 MD.MV1 N/A(on/ofl) phase indicator Main Vent line DW1->SCl MI.MV2 MD.MV2 N/A(on/of0 phase indicator Main Vent line DW2->SC2 MI.PlV.1 MD.PlV.2 N/A(on/of0 phase indicator PCCl Vent PCCl->SCl M1.P2V.1 MD.P2V.2 N/A(on/of0 phase indicator PCC2 Vent PCC2->SC2 MI.PSV.1 MD.PSV.2 N/A(on/of0 phase indicator PCC3 Vent PCC3->SC2 MP.D1 +
2.5 kPa absol. pressure meas. Drywell 1/ DW1 i
/
25A5824 snuo.15
@ h C g Y--
arv. O Table 6.1:
INSTRUMENTATION REQUIRED
- FOR TEST M9 Processid **
Backup Accuracy Location MP.RP.1 +
2.5 kPa absol. pressure meas. Reactor Pressure Vessel /
2.5 kPa absol, pressure meas. Suppression Chamber 1/
SCl ML.UI 0.2mt PCC 1 pool level ML.U2 0.2 mt PCC 2 poollevel ML.U3 0.2 mt PCC 3 poollevel ML.RP.1 0.2 m RPV level ML.Sl ML.S2 0.05 m Suppression poollevel ML.D1 ML.D2 0.05 m Drywell water level MPG.Dl 1(2) t 5.00 %
air partial pres. meas. Drywell 1(2) / DW1(2) o (highest probe in DW1(2))
MPG.Sl t
5.00 %
air partial pres. meas. Wetwell /WW1 MV.MS1 (1)
MV.MS2 N/A volume flow meas. Main Steam line RPV->DW1 MV.MS2 (1)
MV.MSI N/A volume flow meas. Main Steam line RPV->DW2 MV.PlF (1)(2) 3.00 %
volume flow meas. PCCI Feed DWl->PCCl MV.P2F (1)(2) 3.00 %
volume flow meas. PCC2 Feed DW2->PCC2 MV.P3F (1)(2) 3.00 %
volume flow meas. PCC3 Feed DW2->PCC3 MW.RP.1 3.00 %
electrical power meas Reactor Pressure Vessel /
j RPV l
i
9' ED arv. O 25A5824 sH NO.16 Table 6.1:
INSTRUMENTATION REQUIRED
- FOR TEST M9 Processid **
Backup Accuracy Location MW.RP.2 3.00 %
electrical power meas Reactor Pressure Vessel /
electrical power meas Reactor Pressure Vessel /
electrical power meas Reactor Pressure Vessel /
electrical power meas Reactor Pressure Vessel /
electrical power meas Reactor Pressure Vessel /
(+ ) Top Priority Measurements, additional high priority temperature measurements are defined in the text of this section.
(*)
It is required that temperature monitoring capabilitywith an accuracy of 1.5 C be available for these tests as described in the text of this section.
(**) PANDA instrumentation identification system is described in Section 5.2 of ALPHA 410
($) Differential accuracy over short time intervals is 10.02m (t) Any of the other instruments for determining or inferring air partial pressure in drywells/wetwells may backup these instruments.
(1) For volumetric flow rate measurements, all additional measurements (pressure and temperature) required to convert the volumetric flow rate to a mass flow rate are required.
(2) 2 of the 3 volumetric flowmeters for PCC feed lines are required.
(3) All instrumentation listed in this table is required to be operable only while the monitored process value is within the instruments operating range as defined in Table 5.3 of ALPHA-410.
1
o 25A5824 sH No.17 MhM nsv. 0 7.
DATA RECORDING. PROCESSING AND ANALYSIS 7.1 Data Recording During (approximately) the first two hours of the test (until the first drywell pressure peak is reached) the data for all channels will be recorded at 6 samples per minute. During the rest of the test (after the peak drywell pressure is reached) the data will be recorded at 1 sample per minute. It is necessary that the data sampling rate be sufficient to record opening and closing of the vacuum breakers between the drywells and wetwells.
7.2 Data Records The digitally acquired data will be recorded in real time for the entire duration of the test.
Immediately after the test, a copy of the data file will be created in order to have a backup record of the data file. Also to be recorded with this data file are all information required to perfonn subsequent processing of the data.
7.3 Data Sheets The following data sheets will be prepared for each test for inclusion in the PANDA Test File (PTF). The unique test number will be printed on each sheet.
- 1) print table containing the list of the measurements with their main characteristics (identification, span, calibration constants, associated error, location on the facility, i
measurement channel number and sampling frequency) j
- 2) graphs of top priority measurements identified in Section 6 as a function of time (time histories). Graphs may show groups of up to 8 test measurements.
- 3) print table showing the position (status) of all on-off valves,just after the beginning andjust before the end of the test and periodically throughout the duration of the test.
7.4 Data Processing and Analysis During the preconditioning of the test facility and during the running of the transient tests,the operators will monitor the required instrumentation identified for these tests in Table 6.1. The operators will check whether or not redundant measurements are consistent and perform other congruency checks including zero checks as possible to verify that the instrumentation and data i
acquisition system are working correctly.
i 9
@M REv. 0 25A5824 s!! No.18 1
1 Following compledon of the tests described in Section 9, data reducdon will be performed to support preparation of the Apparent Test Results Reports (ATR). This data reduction willinclude a representadve set of time history plots of system flows, differendal pressure, vessel pressures, air partial pressure (O sensor readout), and temperatures covering the full test duradon for top 2
priority measurements. These results will be reviewed and reported in the ATR (see Section 10).
The Data Transmittal Report (DTR) will transmit all the data for the transient integral system tests (see Secdon 10).
25A5824 SH No.19 g
8.
SHAKEDOWN TESTS No additional shakedown tests are planned.
n a
)
4 1
i
.i 1
'l 1
i J
1 l
i a
9 EM nsv. 0 25A5824 SH No. 20 9.
TEST MATRIX 9.1 Test Description A series of transient integral tests will be conducted using the PANDA facility configured as described in Section 4. The tests will be performed using detailed procedure (s). The following summarizes the approach to be followed by the test procedure (s).
The drywells, wetwells, GDCS tank and PCC pools will be pre-conditioned and brought separately to their required initial conditions (or slightly higher temperatures and/or pressures if heat loss or stabilization is expected to bring conditions within their required range).
Once the initial conditions of the various vessels are confinned to match the values specified in Table 9.1, the test is initiated as follows:
Start to open all valves which must be open in lines between vessels per the test configuradon in Section 4, except the valves in the RPV to drywell steamlines and GDCS drain line valve, within a period of approximatel 5 minutes.
f
- 1) place RPV heater controls in automatic operation to follow the time dependent heater power determined from the specification in Table 9.2.
- 2) after heater energization perform the following
- open the valves in both RPV to drywell steamlines
-open the GDCS drain line valve From this point on for test M9 there are no further operator actions, at the end of 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> data recording may be terminated and the test declared complete.
O i
25A5824 sH NO 21 EM nsv. 0 l
i Table 9.1: INITIAL CONDITIONS FOR PANDA TEST M9 RPV Drywell Wetwell GDCS PCC Pools Total Pressure (kPa) 319 318 301 318 100 Air Pressure (kPa) 0 0
256 302 N/A Vapor Temperature (K) 409 409 352 329 N/A Liquid Temperature (K) 409 409 352 329
-373 2.00 (2) 3.8 14.8 (3) 23.6 Collap-M Water Level (m) (1) I Notes:
(1) Water levels are specified relative to the top of the PANDA heater bundle.
(2) The nominal DW condition is no water. However, a small amount of spill from the RPV to the DW at the start of the test is acceptable.
(3) The GDCS level should be chosen such that the combination of GDCS injection and inidal level swell taises the RPV leveljust to the elevadon of the main steam lines.
O
\\
e MW W0 25A5824 SH NO. 22 Table 9.2a: POWER FOR PANDA TEST M9; Shutdown Power vs. Time TIME FROM SCRAM PANDA TIME DECAY HEAT (Fraction PANDA DECAY (sec)
(sec) of Full Power)
HEAT (MW) 1040 ' (Start M9) 0 0.0175 1.4 1583 543 0.0175 1.4 1600 560 0.0174 1.395 1650 610 0.0173 1.381 1700 660 0.0171 1.366 2000 960 0.0160 1.280 2500 1460 0.0150 1.200 2940' 1900 0.0141 1.130 3599' 2559 0.0141 1.130 3600 2560 0.0132 1.056 3650 2610 0.0131 1.048 4000 2960 0.0127 1.016 5000 3960 0.0119 0.952 6000 4960 0.0112 0.896 7000 5960 0.0107 0.856 7200 6160 0.0106 0.848 8000 6960 0.0103 0.824 9000 7960 0.0100 0.800 10000 8960 0.00972 0.778 14400 13360 0.00928 0.742 18000 16960 0.00881 0.705 20000 18960 0.00859 0.687 28800 27760 0.00788 0.630
Ihese entries mark discontinuties created by the intersection of the decay beat curve with constant power plateaus and as such the decay heat represented is an artifact of curve fitting.
e 25A5824 sHNo 23 NM REv. O Table 9.2a: POWER FOR PANDA TEST M9; Shutdown Power vs. Time TIME FROM SCRAM PANDA TIME DECAY HEAT (Fraction PANDA DECAY (sec)
(sec) of Full Power)
HEAT (MW) 30000 28960 0.00781 0.625 36000 34960 0.00748 0.598 40000 38960 0.00729 0.583 50000 48960 0.00689 0.551 60000 58960 0.00658 0.526 70000 68960 0.00631 0.505 80000 78960 0.00609 0.487
i 9'
@hSainrg arv. O 25A5824 SH NO. 24 Tabic 9.2b: POWER FOR PANDA TEST M9; (Total Power *)/(Decay Power) vs. Time TIME FROM SCRAM (sec)
TOTAL POWER */ DECAY POWER 1040 (Test Start) 1.000 3599 1.000 3600 1.070 5000 1.058 7500 1.038 10,000 1.025 12,500 1.019 15,000 1.016 20,000 1.010 25,000 1.008 30,000 1.007 72,000 1.000
- Total power includes contribution from reactor structure stored energy Note: Tolerance on PANDA power throughout transient is 25 kW or 0.025 MW.
a 25A5824 snNo.25
@hM REv. 0 9.2 Test Acceptance Criteria In order to assure the objectives of these tests are met, itis necessary that:
- 1) the values over the 1 minute period prior to the test for the following initial conditions must be within the specified ranges:
reference matrix value 4 kPa (all vessels except
- Total Pressure (kPa)
=
drywell)
- Drywell Air Partial Pressure (kPa)=
reference matrix value i 2 kPa reference matrix value 2 *K(all vessels
- Mean Vapor Temperature (K)
=
except GDCS/all tests) reference matrix value 4 *K(GDCS vessel)
- Mean Vapor Temperature (K)
=
mean value i 2 *K(all vessels
- Local Vapor Temperature (K)
=
except GDCS/all tests) mean value i 4 'K(GDCS vessel)
- Local Vapor Temperature (K)
=
reference matrix value 2 'K (except for
- Mean Liquid Temperature (K)
=
PCC pools)
)
Saturation temperature at actual emironmental
- Mean Liquid Temperature (K)
=
pressure +0/-4 *K (for PCC pools) mean value 2*K
- Local Liquid Temperature (K)
=
- Wetwell and GDCS Water Levels =
reference matrix value i 0.100 m
- RPV Water Level reference matrix value 10.200 m
=
\\
- PCC Pool Level reference matrix value 10.200 m
=
- 2) the required instrumentation defined in Section 6 and Table 6.1 be operational
- 3) at test initiation and throughout the transient (to be confirmed during post-test data analysis):
1
- RPV Power
= reference matrix value 25 kW or 0.025 MW
b
\\
I i
25A5624 SH No. 26 EMSne,yf asy. O FINAL 10.
REPORTS One brief Apparent Test Results (ATR) report will be prepared covering the results for each of the transient integral tests based on the data reduction described in Section 7. The ATR will summarize the apparent results. The format for this report will include: test number, test objective, test date, data recording period, names of data files, list of failed or unavailable instruments considered to be required for the test, list of pressure and differential pressure instruments with zero not in tolerance or over-range during test, deviations from test procedure, problems, table of actual initial conditions based on average and standard deviation over a one minute time periodjust before the start of the test of all parameters with a specified acceptance criteria in section 9.1 and time history plots of top priority measurements over the test duration.
The ATR report is a verified report, approved by the PSI PANDA Project Manager, and will be transmitted to the GE within approximately two weeks of the completion of each transient integral system test.
The Data Transmittal Report (DTR) containing all data for transient integral system test M9 will be issued approximately two months after the last test is performed. It will proside detailed information on the test facility configuration, test instrumentation, test conditions and the format for the data. In addition, samples of data will be presented in tables and plots. The DTR will be verified before it is issued, approved by the PSI PANDA Project Manager, and then be transmitted to GE.
11.
TEST HOLD / DECISION POINTS The Test Procedure (s) must have been reviewed and approved by GE's Project Manager, GE Site QA Representative and PSI's PANDA Project Manager before the transient testing described in Section 9 can be performed.
- -