ML20096F436
| ML20096F436 | |
| Person / Time | |
|---|---|
| Site: | 05200004 |
| Issue date: | 11/21/1995 |
| From: | Wingate G GENERAL ELECTRIC CO. |
| To: | |
| Shared Package | |
| ML20096F375 | List: |
| References | |
| 25A5785, NUDOCS 9601230390 | |
| Download: ML20096F436 (28) | |
Text
.
3 c' 9
bl61FM 25A5785 SH NO.1 REv. 0 EIS IDENT: SBWR PANDA REVISION STATUS SHEET DOCUMENT TITLE PANDA TEST PLAN-TESTS M2, M10A, M10B LEGEND OR DESCRFTION OF GROUPS TYPE:
SPECIFICATION FMF:
SBWR MPL NO:
T10-5010 l -DENOTE CHANGE THIS ITEM IS OR CONTAINS A SAFETY RELATED ITEM YES @ NO O EQUIP CLASS CODE
.C REVISION l
C 0
RM-03027 g g } jg%
i l
PRINTS TO MADEBY APPROVALS GENERAL ELECTRIC COMPANY G.A. WINGATE 11/16/95 J.E. TORBECK 175 CURTNER AVENUE SANJOSE CALIFORNIA 95125 CHKD BY:
ISSUED
'/
W gY 2 l 1995 A. FORTIN R. AHMANN CONT ON SHEET 2 MS WORD (3/28/94)
DISK =25A5785 9601230390 960117'~
PDR ADOCK 05200004 A
.o 2a. A a. So.
SH NO. 2 e
EM arv. 0 3
TABLE OF CONTENTS
- 1. SCOPE.............................................................................................................3-4
- 2. APPLICAB LE DO CUMENTS............................................................................. 3
- 4. TEST FACILITY CO NFIGURATION........................................................................... 5
- 5. CONTRO L SYSTEM DESCRIPTION................................................................~......... 12 5.1 RPV HEAHR POWER CONTROL...............................................................................12 5.2 DRYWELL/WETWELL VACUUM BREAKER CONTROL........................................................ 12
- 6. REQUIRED MEASUREMENTS.................................................................
.. 13
- 7. DATA RECORDING, PROCESSING AND ANALYSIS....................
19 7.1 D ATA RECORDING..................................
..........................................................19 7.4 DATA PROCESSING AND ANALYSIS................
.......................................................19 8. S HAKED O WN TESTS................................................................................................ 21 8.1 PU RPOSE.....................
.. 21 9.TESTMATRDC..............................................................................................................22 9.1 TEST DESCRIITON.................
.......... 22 9.2 TEST ACCEPTANCE CRITERIA.....
.27
- 10. REPORTS.........................................................................................................................28
- 11. TEST HO LD /D ECISION POINTS.................................................................................. 28
25A5785 sH.No. 3 EMMSJg asv. 0
- 1. SCOPE This test plan defines the detailed requirements, beyond those already identified in GE Spec 25A5587, for the PAN' A transient integral system tests M2, M10A & M10B. This Test Plan D
specifically covers the test program objectives, the experimental facility configuration, the test facility control, the test instrumentation, the data acquisition, processing and analysis, the test initial and boundary conditions and the test reports for tests M2, M10A & M10B.
This test plan is applicable to the SBWR Design Certification project only.
- 2. APPLICABLE DOCUMENTS
- a. PANDA Test Specification, GE Spec 25A5587.
4 This document provides the general specification of requirements for tests in the PANDA facility to support SBWR Design Certification.
- b. PANDA Steady State Tests--
PCC Perfonnance Test Plan & Procedure, PSI Doc. TM-42-9+11/ ALPHA 410.
This document provides a general description of the PANDA test facility and the specific plan and procedure for steady state tests of the PCC condenser perfonnance.
- c. PANDA PROJECT CONTROL PLAN, GE Doc.
PPCP-QA-01.
This document describes the organization, quality related activities, events and procedures necessary to ensure and verify that the PANDA project at PSIis conducted under the prodsions of the GE SBWR Quality Assurance Plan as described in NEDG-31831.
- d. PANDA Test Plan, GE Spec 25A5764 4
This test plan defines the detailed requirements, beyond those already identified in GE Spec 25A5587, for the PANDA transient integral system tests M3, MSA, M3B, M4 and M7. This Test Plan specifically covers the test program objectives, the experimental facility configumtion, the test facility control, the test instrumentation, the data acquisition, processing and analysis, the test initial and boundary conditions and the test reports for tests M3, M3A, M3B, M4, M7.
l
.o
\\
25A5785 saxoA Eh nzv. 0 1
- 3. TEST OBJECTIVES The obje :tives of the PANDA integal systems tests are to provide additional data to: (a) provide a sufficient database to confirm the capability of TRACC to predict SBWR containment system performance, including potential systems interaction effects. (IntegmlSystems Tests)and (b) Demonstrate startup and long-term operation of a passive conminment cooling system.
(Concept Demonstmtion).
The specific objectives and approach for the tests covered by this test plan are:
a) Perform Test M2 with nominal post-LOCA initial condi'. ions \\ith all steam flow directed through the steam line from the RPV to Dnwell 2 to create asymmetric distributions of steam and non<ondensable gas concentrations and demonstrate the PCCS/ containment performance under these conditions. Contingency testing is to be performed at the end of the 20 hour2.314815e-4 days <br />0.00556 hours <br />3.306878e-5 weeks <br />7.61e-6 months <br /> performance of M2 to demonstrate PCC restart in response to increased heat load demand.
b) Perform Test M10A with nominal post-LOCA initial conditions' with only the two PCC condensers connected to Drywell 2 operational and all steam flow directed through the steam line from the RPV to Dgwell 2 to create asymmetric distributions of steam and non-
. condensable gas concentrations and demonstrate the PCCS/ containment performance under these conditions, i.e. long term migration of non-condensible gas (air) from Drywell 1 to Dgwell 2.
c) Perform Test M10B with nominal post-LOCA initial conditions'with only the two PCC condensers connected to Drywell 2 operational and all steam flow directed through the steam line from the RPV to Drywell I to create asymmetric distributions of steam and non-condensable gas concentrations and demonstrate the PCCS/ containment performance under these conditions, i.e. maximum non-condensible gas volume purge rate through each PCC (total volume of DW1 and DW2 through two PCCs).
' Nominal post-LOCA initial conditions" are those used for test M3 which are derived from the SBWR main steam line break LOCA analysis at one hour after LOCA initiation.
O
25A5785 sa so.5 EM nev. 0
- 4. TEST FACILITY CONFIGURATION The PANDA test facility is described in detailin Section 3 of PSI report ALPHA 410. For Tests M2, M10A & M10B the PANDA facility will be configured to simulate the SBWR post-LOCA configuradon as follows:
- 1) Table 4.1 identifies the key PANDA facility geometry and effective flow area ( A /[i) characteristics. In Table 4.1, the required tolerance for the PANDA as-built value reladve to the corresponding'SBWRscaled value is tabulated for each of these key characteristics. In addidon, the required accuracy for the as-built value for each of the key characterisdcs is tabulated in Table 4.1. The actual as-built accuracy should be approximately equal to or less than the required accuracy tabulated in Table 4.1. The actual as-built accuracies depend on the source of the as-built value. These sources can be measurements by PSI or Electorwatt (i.e.
line losses, line lengths, elevations), manufacturer's specifications or design standards (i.e.,
PCC/IC tubes), or calculations from as built dimensions (i.e., vessel volumes, losses for lines without flow tests).
- 2) The RPV will supply steam to the dqwells as follows:
a) For test M2 & M10A the RPV will supply steam only to Dnwell 2 through its single connecting steam line.
l b) For test M10B the RPV will supply steam only to Drywell 1 through its single connecting steam line.
- 3) RPV heater power will be controlled as a function of time to simulate the scaled decay heat and stored energy release.
- 5) The PCC units will be lined up as follows:
a) For test M2 all three PCC units will be lined-up to take feedflow from the drywells, to vent noncondensables and steam into the water volume of the suppression pool, and drain condensate to the GDCS volume.
b) For tests M10A & M10B only the two PCC units connected to Drywell 2 will be lined-up to take feedflow from the drywell, to vent noncondensables and steam into the water volume of the suppression pool, and drain condensate to the GDCS volume.
S
25A5785 sH No. 6 EN asv. 0
- 6) The PCC pools will be configured as follows:
a) the PCC pools will be filled and isolated from each other.
b)During the test, no water will be added or drained from the PCC pools.
7)
The only direct lines of communication between the drywell and wetwell will be through the vacuum breakers (when the werwell pressure exceeds drywell pressure sufficiently to' open the vacuum breaker) and the main vent lines (which will be submerged within the wetwells).
- 8) The GDCS pressure eqi 21iradon lines to both drywells will be open.
- 9) The GDCS drain line with check valve will be lined up to return PCC condensate to the RPV.
- 10) The Equalizing lines between the RPV and wetwells will be valved out of service.
l l
I i
4 l
i (swrup) i saapeay usa.w2aq mmg;
% g; aaue2s!q-i sa2cid pua wtu g o ;
%g; ssstr'tattp !aals-i uopaas izappu!@a tum g o ;
%97 SS3 tnt 3?q21331S-mmg;
% g; tp2usI-Jalatuurp tutu g ;
%g; aplsino-s2apeaH la3ueyax3 2E3H Dl/DDd wtug07
% 91 ;
ssatnt3141-
.raisureja tum g 0 ;
%g; ap!sino-mmg;
%g; tpausg-au!qni aa3ueyax3
~
323H Dl/DDd YONVd mod - -
3EIVA ud1VDS &%8S 01 3AI1Y1,:18 3EIVAiTIGHSV ADVMf1DDVITIGH$V VGNVd VONVd M03 3DNVh5101 N
sapsuassemo 43rtm3 ag l
sasal massig [w22atuI zuaysu*21 VGNVd
- I*F *1981
%meyonN3D MA
=
CON HS 9849V96 I
9-25.-\\5785 s u o.8 EDULg asv. 0 Table 4.1:
PANDA Transient Integral System Tests Key Facility Charactedstics(condnued)
PARAMETER TOLERANCE FOR PANDA AS-PANDA AS-BUILT ACCURACY BUILT VALUE RFT ATIVE TO SBWR SCAT FD VALUE FOR PANDA Vessel Volumes
-RPV 10 %
2%
~
-Drywell 1 10 %
2%
-Drfwell 2 10 %
2%
-Wetwell 1 10 %
2%
-Wetwell 2 10 %
2%
-CDCS (1) 2%
-IC/PCC pools (2) 2%
(1)
GDCS pool volume is not scaled to SBhR (2)
IC/PCC pool volumes are not scaled to SBWR
25A5785 sH No. 9
@hb%g nev. O a
Table 4.1:
PANDA Transient Integral System Tests Key Facility Characteristics (continued)
PARAMETER TOLERANCE FOR PANDA PANTA AS-BUILT AS BUILT VALUE Rrf ATIVE ACCURACY TO SBWR SCALED VALUE FOR PANDA Elevation Differences PlV-P2V-PSV 2cm Icm discharges PLC inlet to outlet 10 cm 1cm P2Cinlet to outlet 10 cm 1cm P3C inlet to outlet 10 cm 1cm PlV, P2V, PSV 5cm 1cm discharges relative to normal suppression poollevel MV1 and MV2 5cm 1cm discharges relative to normal suppression poollevel P1V,P2V,PSV 5cm Icm discharges relative to MV1 and MV2 discharges PlF, P2F, P3F inlet
+ 200 cm/ - 0 1cm relative to MS1 and MS2 discharge
S' 25A5785 suso.10
@ Mar'IAar'C;f,.g)f azv. 0 Table 4.1:
PANDA Transient Integral System Tests Key Facility Characteristics (continued)
PARAMETER TOTTRANCE FOR PANDA AS. PANDA AS BUILT BUILTVALUE Rrr ATIVE TO ACCURACY SBWR SCATrn VALUE FOR PANDA I
Elevadons (relative to TAF/ Heaters)
P1F,P2F, PSF
+ 200 cm/ - 0 5mm inlet PIC,P2C,PSC 5cm i5mm inlet PlV,P2V,PSV 5cm 5mm discharge GRTintet 5cm 5mm GRT outlet 5cm 5mm MV1 outlet 5cm 5mm MV2 outlet 5cm 5mm MSL 1 outlet 5cm 5mm MSL 2 outlet 5cm 5mm Top of RPV 25 cm 50 mm chimney
25A5785 su so.11 EDbMM arv. O Table 4.1:
PANDA Transient Integral System Tests Key Facility Characteristics (continued)
PARAMETER TOIFRANCE FOR PANDA AS-BUILT PANDA AS-BUILT VALUE RELATTVE TO SBWR.
ACCURACY SCALED VALUE FOR PANDA Connecting Line Flow Resistances RPV to DW1 20 %
10 %
10 %
DW 1 to PCC1 20 %
10 %
DW 2 to PCC2 20 %
10 %
DW 2 to PCC3 20 %
10 %
DW I to WW 1 (3) 10 %
(LOCA vent)
DW 2 to WW 2 (3) 10 %,
(LOCA vent)
~
PCCI to GDCS 20%
10 %
PCC2 to GDCS 20%
10 %
~
PCC3 to GDCS 20 %
10 %
PCC1 to WW 1 20 %
10 %
PCC2 to WW 2 20 %
10 %
PCCS to WW 2 i 20 %
10 %
GDCS to RPV 20 %
10 %
WW 1 to DW 1 20%
10 %
(bypass /vac. brkr)
(3) LOCA vents are not scaled to SBWR
1 G
25A5785 su so.12 EM asv. 0 5.
CONTROL SYSTEM DESCRIPTION In order to perform the tmnsient integral system tests, several control systems are to be used to establish initial and boundary conditions for each test. These control systems will be used to manage and regulate the key test parameters prior to the test. Folkswing test inidadon, only the RPV heater power and the vacuum breaker controllers will be used. A main control system, which includes the electronic controllers, will be used to perform the operations.
5.1
. RPV Heater Power Control The electrical power to the heaters in the RPV will be controlled automatically following test initiation, to match the decay power and RPV structural heat release specified in Section 9.
5.2 Dnwell/Wetwell Vacuum Breaker Control The operation of the vacuum breaker valve will be controlled based on the measured pressure difference between the drywell and wetwell. Drywell pressure is initially established at a value equal to or greater than the wetwell pressure to conform to the post-LOCA condition specified for the beginning of each individual test. During the course of a test if the drywell to wetwell pressure drops below a minimum value the vacuum breaker valve control will automatically open the valve. The wetwell-tcxitywell differential pressure at which the vacuum breaker for Dnwell 1 opens will be set at 0.47 psi (3.24 kPa), and the differential pressure at which the vacuum breaker for Dnwell I closes will be set at 0.3 psi (2.06 kPa). The opening and closing differential pressure for the vacuum breaker in Dnwell 2 will be set 0.1 psi higher than the corresponding'setpoints for the Drywell I vacuum breaker, i.e. at 0.57 psi (3.9 kPa) and 0.4 psi (2.8 kPa), respectively.
a.
25A5785 ss so.13 gg 6.
REO_UIRED MEASUREMENTS
'able 6.1 gives the measurements required to meet the objectives for Tests M2, M10A & M10B.
dith the exception of the temperature indication, no PANDA instrumentadon other than that in i
Table 6.1 is necessay for the performance of Tests M2, M10A & M10B. The sensors identified in Table 6.1 must be operable prior to initiation of these tests. It is acceptable if'a sensoris not operable, if the backup identified in the second column is operable.
Temperature measurements in the PCCs and the various connected vessels are desirable, but not all of these tempemture measurements are required for the performance of these tests as discussed below. The temperature measurements required for these tests with an accuracy of 1.5'C are as follows:
RPV steam dome (at least one).
PCC tubes; (It is required that 50% of the tube wall and fluid sensors be available. The available sensors must include at least 40% of the probes above and at les.st 40% of the probes below the hodzontal mid-plane of the tube bundle. Within these constmints, the test engineer has responsibility and authority tojudge whether or not suficient PCC
{
temperature sensors are operable to initiate a test).
1 PCC pools: 30% of the liquid probes including one of the lowest three elevations.
DW: 50% of the fluid probes including either the lowest elemtion or one thermocouple from the water-surface probe.
WW: 50% of the gas probes,50% of the liquid probes and two out of three of the floating probes.
GDCS pool: 50% of the fluid probes and one thermocouple from the floating probe.
Vessel walls: 20% of GDCS, DW, and WW.
System lines: 50% of the gas and liquid temperature probes in each system line used for the test (if number of sensors is odd, round to lower whole number, i.e. 3 sensors total in one line means one is required).
In Table 6.1 a subset of the required instruments are identified as " top priority measurernents".
Time histon plots of these top priority measurements are to be included in the Test File (see Section 7.3) and the Apparent Test Results (ATR) Report (see Section 10). In addition to the top prionty measurements identified in Table 6.1, there are other top priority measurements. These are: 1) the total electrical power to the heaters in the RPV which is determined during post-test I
25A5785 sH so.14 ED arv. O data processing, and 2) some temperature measurements. The top priority temperature measurements are: RPV steam dome temperature measurement, highest and lowest temperature measurement location in each drywell, highest and lowest temperature measurement location in the gas space of each wetwell, highest liquid temperature measurement location in each wetwell, and one temperature measurement in the GDCS drain line and in each of the three PCC vent lines.
As noted.in Section 7.4, the operator will perform checks as possible to confirm instrumentation perforinance. These cheeks will include comparison of redundant measurements.
9 e
4 k
I
25A5785 su so 15
@DM arv. O Tabk 6.1:
INSTRUMENTATION REQUIRED
- FOR TEST M2, M10A & M10B 5
Proiessid
- Backup Accuracy Location CB5B1 +
N/A Valve position : Vacuum Breaker Line 1 (On/Off)
Uj.VB2+
N/A Valve position : Vacuum Breaker Line 2 (On/Off)
MD.MV1 MI.MV1 0.5 kPa pressure diff. meas. Main Vent line DWl->SC1 MD.MV2 MI.MV2 0.5 kPa pressure diff. meas. Main Vent line DW2->SC2 MD.PIF#
MV.PIF 0.5 kPa pressure diff. meas. PCCI Feed DW1->PCCl MD.PlV.2#
MI.PlV.1 0.5 kPa pressure diff. meas. PCCI Vent PCCI-> SCI MD.P2F MV.P2F 0.5 kPa pressure diff, meas. PCC2 Feed DW2->PCC2 MD.P2V.2 MI.P2V.1 0.5 kPa pressure diff. meas. PCC2 Vent PCC2->SC9 i
1 MD.P3F MV.P3F 0.5 kPa pressure diff. meas. PCC3 Feed DW2->PCC3 MD.PSV.2 MI.PSV.1 0.5 kPa pressure diff. meas. PCCS Vent PCC3->SC2 MD.VB1 MD.VB2 0.5 kPa pressure diff. meas. Vacuum Breaker SCl-DW1 MD.VB2 MD.VB1 0.5 kPa pressure diff. meas. Vacuum Breaker SC2-DW2 MI.MV1 MD.MV1 N/A(on/off) phase indicator Main Vent line DWl-> SCI MI.MV2 MD.MV2 N/A(on/off) phase indicator Main Vent line DW2->SC2 MI.PlV.1#
MD.PlV.2 N/A(on/off) phaseindicator PCCl Vent PCCI-> SCI MI.P2V.1 MD.P2V.2 N/A(on/off) phase indicator PCC2 Vent PCC2->SC2
I 3
S
25A5785 ssso.16 EhM nsv. O Table 6.1:
INSTRUMENTATION REQUIRED
- FOR TEST M2, M10A & M10B
\\
Processid **
Backup Accuracy Location MI.PSV.1 MD.PSV.2 N/A(on/of0 phase indicator PCC3 Vent PCC3->SC2 MP.D1 +
2.5 kPa absol. pressure meas. Dgwell 1/ DW1 MP.RP.1 +
2.5 kPa absol. pressure meas. Reactor Pressure Vessel / RPV M P.Sl +
2.5 kPa absol. pressure meas. Suppression Chamber 1/ SCI ML.Ul + #
0.2 mt PCC 1 poollevel ML.U2 +
0.2 mt PCC 2 poollevel ML.US +
0.2 mt PCC 3 poollevel ML.RP.1 0.2 m RPV level ML.Sl MLS2 0.05 m Suppression poollevel ML.D1 ML.D2 0.05 m D well water level 9
MPG.D l_1 +
MPG.D1_2 or 5.007c air panial pres. mea. Dnwell 1/ DW1 (highest MPG.Dl_3 probe in DWI)
MPG.D2_1 +
MPG.D2_2 or 5.007o air partial pres. meas. Drywell 2 / DW2 (highest MPG.D2_3 probe in DW2)
MPG.Dl_2 MPG.Dl_1 or 5.00 7o air partial pres. meas. Dnwell 1/ DW1 MPG.Dl_3 MPG.D2_2 MPG.D2 1 or 5.007o air partial pres. meas. Drywell 2 / DW2 MPG.D2_3
05A5785 sa.so.17 ED sv. O Table 6.1:
INSTRUMENTATION REQUIRED
- FOR TEST M2, M10A & M10B Processid **
Backup Accuracy Locadon MPG.Dl_3 MPG.Dl_1 or 5.00 %
air partial pres. meas. Drywell 1/ DW1 MPG.D1_2 MPG.D2_3 MPG.D2_1 or 5.00 %
air partial pres, meas. Drywell 2 / DW2 MPG.D2_2 MPG.Sl MPG.S2 5.00 %
air partial pres. meas. Wetwell /\\MV1 MPG.S2 MPG.S1 5.00 %
air partial pres. meas. Wetwell /WW2 MV.MSI N/A volume flow meas. Main Steam line RPV->DW1 (1)+
MV.MS2 N/A volume flow meas. Main Steam line RPV->DW2 (1)+
4 MV.PlF 3.00 %
volume flow meas. PCCI Feed DWl->PCCI (1)(2) #
MV.P2F 3.00 %
volume flow meas. PCC2 Feed DW2->PCC2 (1)(2)
MV. PSF 3.00 %
volume flow meas. PCC3 Feed DW2->PCC3 (1)(2)
electrical power meas Reactor Pressure Vessel / RPV 1
.\\BV.RP.2 3.00 %
electrical power meas Reactor Pressure Vessel / RPV MW.RP.3 3.00 %
electrical power meas Reactor Pressure Vessel / RPV MW.RP.4 3.00 %
electrical power meas Reactor Pressure Vessel / RPV MW.RP.5 3.00 %
electrical power meas Reactor Pressure Vessel / RPV i
i i
25A5785 ssNo.t8 ENrrf=r!~i:c.yy arv. O Table 6.1:
INSTRUMENTATION REQUIRED
- FOR TEST M2, M10A & M10B Processid **
Backup Accuracy Location MW.RP.6 3.00 %
electrical power meas Reactor Pressure Vessel / RPV
(+) Top Priority Measurements, additional high priority temperature measurements are defmed in the text of this section.
(*) It is required that temperature monitoring capability with an accumcy of 1.5'C be anilable for these tests as descdbed in the text of this section.
(**) PANDA instmmentation identification system is descdbed in Section 5.2 of ALPHA 410
($) Differential accuracy over short time intervals is 0.02m
(#) Not required for tests MIDA & M10B
(+) The instruments for the main steam line not being used for test performance are not required.
(1; For volumetric flow rate measurements, all additional measurements (pressure and temperature) required to comert the volumetric flow rate to a mass flow rate are required.
(2) 2 out of 3 for M2 and 1 out of 2 for M10A&M10B, respectively, volumetric flowmeters for PCC feed lines are required.
(3) Allinstrumentation listed in this table is required to be operable only while the monitored process value is within the instruments operating range as defined in Table 5.3 of ALPHA-410.
1 25A5785 sa so.19 ED asv. 0 7.
DATA RECORDING. PROCESSING AND ANALYSIS 7.1 Data Recording During (approximately) the first two hours of the test (until the first drywell pressure peak is reached) the data for all channels will be recorded at 6 samples per minute. During the rest of the test (after the peak drywell pressure is reached) the data will be recorded at 1 sample per minute. It is necessary that the data sampling rate be sufficient to record opening and closing of the vacuum breakers between the drywells and wetwells.
7.2 Data Records The digitally acquired data will be recorded in real time for the entire duration of the test.
Immediately after the test, a copy of the data file will be createrl in order to have a backup record of the data file. Also to be recorded with this data file are allinformation required to perform subsequent processing of the data.
7.3 Data Sheets The following data sheets will be prepared for each test for inclusion in the PANDA Test File (PTF). The unique test number will be printed on each sheet.
- 1) print table containing the list of the measurements with their main characteristics (identification, span, calibration constants, associated error, location on the facility, measurement channel number and sampling frequency)
- 2) graphs of top priority measurements identified in Section 6 as a function of time (time histories). Graphs may show groups of up to 8 test measurements.
- 3) print table showing the position (status) of all on-off valves,just after the beginning andjust before the end of the test and periodically throughout the duration of the test.
7.4 Data Processing and Analysis During the preconditioning of the test facility and during the running of the transient tests,the operators will monitor the required instrumentation identified for these tests in Table 6.1. The operators will check whether or not redundant measurements are consistent and perform other congruency checks including zero checks as possible to verify that the instrumentation and data acquisition system are working correctly.
i
4 9
25A5785 sH No.20 EMELy/
azv. O Following completion of the tests described in Section 9, data reduction will be performed to support preparation of the Apparent Test Results Reports (ATR). This data reduction will include a representative set of time history plots of system flows, differential pressure, essel pressures, air partial pressure (O sensor readout), and temperatures covering the full test duration for top 2
priority measurements. These results will be reviewed and reported in the ATR (see Section 10).
The Data Transmittal Report (DTR) will transmit all the data for the transient integral system tests (see Section 10).
4
25A5785 sH No.21
@hM arv. 0 8.
SHAKEDOWN TESTS 8.1 Purpose The purposes of the shakedown tests are to:
- confirm test facility ability to establish a quasi 4teady state set ofinitial conditions
- confinn adequacy of data acquisition system
- confinn ability to achieve a smooth but rapid transition L w-en the pre-test initial conditions line-up to the test line-up
- confirm the adequacy of the test procedures.
For tests (M2, M10A & M10B), no shakedown tests are planned.
I
S' 25A5785 sH No.22 Eh stsv. 0 9.
TEST MATRIX 9.1 Test Description A series of transient integral tests will be conducted using the PANDA facility configured as described in Section 4. The tests will be performed using detailed procedure (s). The following summarizes the approach to be followed by the test procedure (s).
' The drywells, wetwells, GDCS tank and PCC pools will be pre <onditioned and brought separately to their required initial conditions (or slightly higher temperatures and/or pressures if heat loss or stabilization is expected to bring conditions within their required range).
Once the initial conditions of the various vessels are confirmed to match the values specified in Table 9.1, the test is initiated as follows:
Start to open all valves which must be open in lines between vessels per the test configuration in Section 4, except the valves in the RPV to drywell steamlines, within a period of approximately 5 minutes.
Then, the following sequence should be performed as quickly as possible:
4
- 1) Establish steam flow as follows:
a) For test M2 & M10A open the valve in the steamline from the RPV to Drywell 2 b) For test M10B open the valve in the steamline from the RPV to Drywell 1 2)
Place RPV heater controls in automatic operation to follow the time dependent heater power determined from the specification in Table 9.2.
From this point on for tests M10A & M10B there are no futher operator actions For tests M10A & M10B after at least 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> of test operations and when the indications for both drywells show that non-condensible gas partial pressure is no longer changing, data recording may be terminated, and the test performance declared complete.
(continued on next page for test M2)
25A5785 5H No.23 E
nav. O Test M2 will continue for at least 20 hours2.314815e-4 days <br />0.00556 hours <br />3.306878e-5 weeks <br />7.61e-6 months <br />.
The following describes contingency testing to be done after 20 hours2.314815e-4 days <br />0.00556 hours <br />3.306878e-5 weeks <br />7.61e-6 months <br /> in test M2 as follows:
- a. at 20 hr, increase the power to 800 kw.
- b. after the system has reached a quasi-steady state condition, close the feedflow line to one of the PCCs. This PCC should be one which is removing the most heat as evidenced by the actual PCC pool level response.
- c. after the system has reached a quasi-steady state ' condition, data recording may be terminated, and the test performance declared complete.
i 4
m l
I i
1 i
S#
25A5785 sa so.24 EMO aav. 0 TaWe 9.1: INITIAL CONDITIONS INITIAL' CONDITIONS FOR PANDA TESTS M2, M10A & M10B RPV Drywell Wetwell GDCS PCC Pools Total Pressure (kPa) 295 294 285 294
=100 Air Pressure (kPa) 0 13 240 274 N/A Vapor Temperature (K) 406 404 352 333 N/A Liquid Temperature (K) 406 404 352 333
=373 Collapsed Water Level (m) 11.2 (2) 3.8 10.7 (3) 23.6 (1)
Notes:
-(1) Water levels are specified relative to the top of the PANDA heater bundle.
(2) The nominal DW condition is no water. However, a small amount of spill from the RPV to the DW at the start of the test is acceptable.
(3) The GDCS level should be positioned in hydrostatic equilibrium with the RPV level (including an appropriate adjustment for temperature difference).
[
25A5785 su so.25 E
nrv. O Table 9.2a: POWER FOR PANDA TESTS M2, M10A & M10B; Shutdown Power vs. Time TIME FROM SCRAM (sec)
DECAYHEAT (%)
PANDA DECAYHEAT (MW) 3600 (Test start) 0.0132 1.056 3650 0.0131 1.048 4000 0.0127 1.016 5000 0.0119 0.952 6000 0.0112 0.896 7000 0.0107 0.856 7200 0.0106 0.848 8000 0.0103 0.824 9000 0.0100 0.800 10000 0.00972 0.778 14400 0.00928 0.742 18000 0.00881 0.705 20000
_0.00859 0.687 j
28800
,0.00788 0.630 30000 0.00781 0.625 36000 0.00748 0.598 40000 0.00729 0.583
\\
50000 0.00689 0.551 i
60000 0.00658 0.526 70000 0.00631 0.505 80000 0.00609 0.487
S'
'25A5785 SH NO. 26 EM asv. O Table 9.2b:
POWER FOR PANDA TESTS M2, M10A & M10B;(Total Power *)/(Decay Power) vs. Time TIME FROM SCRAM (sec)
TOTAL POWER */ DECAY POWER 3600 (Test Start) 1.070 5000 1.058 7500 1.038 10,000 1.025 12,500 1.019 15,000 1.016 20,000 1.010 25,000 1.008 30,000 1.007 72,000 1.000
- Total power includes contribution from reactor structure stored energy Note: Tolerance on PANDA power throughout transient is 25 kW or 0.025 MW.
a, 25A5785 s u o.27 E
bN arv. 0 9.2 Test Acceptance Criteria In order to assure the objectives of these tests are met, it is necessary that:
- 1) the values over the 1 minute period prior to the test for the following initial conditions must be within the specified ranges:
- Total Pressure (kPa) reference matrix value 4 kPa (all vessels except
=
drywell)
- Drywell Air Parual Pressure (kPa)=
reference matrix nlue i 2 kPa
- Mean Vapor Temperature (K) reference matrix value 2 *K(all vesseis except
=
GDCS/all tests)
- Mean VaporTemperature (K) reference matrix value 4 *K(GDCS)
=
- LocalVaporTemperature (K) mean value 2 *K(all vessels except GDCS/all
=
tests)
- Local Vapor Temperature (K) mean value 4 *K(GDCS)
=
- Mean Liquid Temperature (K) =
reference matrix value 2 *K (except for PCC' pools)
- Mean Liquid Temperature (K)
Saturation tempemture at actual environmental
=
pressure +0/-4 'K (for PCC pools)
- Local Liquid Temperature (K) =
mean value 2 *K
- Wetwell and GDCS Water Levels =
reference matrix value 0.100 m
- RPV Water Level reference matrix value 0.200 m
=
- PCC Pool Level reference matrix nlue 0.200 m
=
- 2) the required instrumentation defined in Section 6 and Table 6.1 be operational
- 3) at tess initiation and throughout the transient, (to be confirmed during post-test data analysis):
RPV Power reference matrix nlue 25 kW or 0.025 MW
=
i S#
25A5785' sH No.28 EM E~ g -
nev. O FINAL 10.
REPORTS One brief Apparent Test Results (ATR) report will be prepared covering the results for each of the transient integral tests based on the data reduction described in Section 7. The ATR will summanze the apparent results. The format for this repon will include: test number, test objective, test date, data recording period, names of data files, list of failed or unavailable instnnnents considered to be required for the test, list of pressure and differential pressure instruments with zero not in tolerance or over-range during test, deviations from test procedure, problems, table of actual initial conditions based on average and standard deviation over a one minute time periodjust before the start of the test of all parameters with a specified acceptance criteria in section 9.1 and time history plots of top priority measuremenu over the test duration.
The ATR repon is a verified report, approved by the PSI PANDA Project Manager, and will be transmitted to the GE within approximately two weeks of the completion of each transient integral system test.
The Data Transmittal Report (DTR) containing all data for transient integral system tests M2, M10A &l0B will be issued approximately two months after the last test is performed. It will provide detailed information on the test facility configuration, test instrumentation, test conditions and the format for the data. In addition, samples of data will be presented in tables and plots. The DTR will be verified before it is issued, approved by the PSI PANDA Project Manager, and then be transmitted to GE.
11.
TEST HOLD / DECISION POlbES The Test Procedure (s) must have been reviewed and approved by GE's Project Manager, GE Site 1
QA Representative and PSI's PANDA Project Manager before the transient testing described in Section 9 can be performed.
.