ML20095K039

From kanterella
Jump to navigation Jump to search
Proposed TS 3/4.3.1 Re Reactor Protection Sys instrumentation,3/4.3.6 Re Control Rod Block Instrumentation & 3/4.3.7.6 Re Source Range Monitors
ML20095K039
Person / Time
Site: Grand Gulf 
Issue date: 04/30/1992
From:
ENTERGY OPERATIONS, INC.
To:
Shared Package
ML20095K032 List:
References
NUDOCS 9205040285
Download: ML20095K039 (17)


Text

- _ _ _ _ - - _ _ - - _

I

),

- to GNRO-92/00034

-GGNS PCOL-92/02 -- MARKED-UP TECHNICAL SPECIFICATION PARIES

..L 9205040285 920430 PDR ADOCK 05000416 P

PDR

Grand Gulf Nuclear Station Unit 1 Attachm:nt 3 to GNRO-92/00034

)

PCOL 92/02 Page 1 of 9 3/4.3 INSTRUMENTATION 3/4.3.1 REACTOR PROTECTION SYSTEM INSTRUMENTATION LIMITING CONDITION FOR OPERATION 3.3.1 As a minimum, the reactor protection system instrumentation channels shown in Table 3.3.1-1 shall be OPERABLE with the REACTOR PROTECTION SYSTEM RESPONSE TIME as shown in Table 3.3.1-2.

APPLICABILITY:

As shown in Table 3.3.1-1.

ACTION:

With the number of OPERABLE channels less than required by the Minimum a.

OPERABLE Channels per Trip System requirement for one trip system, place the inoperable channel and/or that trip system in the tripped condition

  • within twelve hours.

b.

With the number of OPERABLE channels less than required by the Minimum OPERABLE Channels per Trip System requirement for both trip systems, place at least one trip system ** in the tripped condition within one hour and take the ACTION required by Table 3.3.1-1.

SURVEILLANCE REQUIREMENTS 4.3.1.1 Eacn reactor protection system instrumentation channel shall be demonstrated OPERA 8LE by the performance of the CHANNEL CHECK, CHANNEL FUNCTIONAL TEST and CHANNEL CALIBRATION operations for the OPERATIONAL CONDITIONS and at the frequencies shown in Table 4.3.1.1-1.

4.3.1.2 LOGIC SYSTEM FUNCTIONAL TESTS and simulated automatic operation of all channels shall be perfo med at least once per 18 months.

4.3.1.3 The REACTOR PROTECTION SYSTEM RES60NSE TIME of each reactor trip functional unit shown in Table 3.3.1-2 shall be demonstrated to be within its limit at least once per 18 months.

Each tast shall include at least one chan-nel per trip system such that all channels are tested at least once every N times 18 months where N is the total number of redundant channels in a specific rea o i

system.

(.rAsee+

i

  • An inoperable channel need not to placed in the tripped condition where this would cause the Trip Function to occur.

In these cases, the inoperable channel shall be restored to OPERABLE status within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> or the ACTION required by Table 3.3.1-1 for that Trip Function shall be taken.

    • The' trip system need not be placed in the tripped condition if this woL1d cause the Trip Function to occur. When a trip system can be placed in the tripped condition without causing the Trip Function to e : cur, place the trip system with the most inoperable channels in the tripped condition; if both systems have the same number of inoperable channels, place either trip system in the tripped condition.

GRAND GULF-UNIT 1 3/4 3-1 Amendment No. 6 9,.__.

~'

Grand Gulf Nuclear Station Unit 1 to GNRO-92/00034 PCOL 92/02 Page 2 of 9 Insert for Paae 3/4 3-1 4.3.1.4 The provisions of Specification 4.0.4 are not applicable to the Channel functional Test surveillance for the Intermediate Range Monitors for entry into the applicable OPERATIONAL CONDITIONS (as specified in Table 4.3.1.1-1) from OPERATIONAL 70NDITION 1, provided the surveillances are performed within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after such

' ry.

l l

l 1

l l

l l

Gr'and Gulf Nuclear Station Unit 1 Attaci *innt 3 to GNRO-92/00034 '

PCOL 92/02 Page 3 of 9 INSTRUMENTATION l

3/4.3.6 CONTROL-ROD BLOCK INSTRUMENTATION LIMITING' CONDITION FOR OPERATION 3.3.6.

The control rod block instrumentation channels shown in Table 3.3.6-1 shall be OPERABLE with their trip setpoints set consistent with the values shown in the Irip Setpoint column of Table 3.3.6-2.

APPLICABILITY: As shown in Table 3.3.6-1.

ACTION:

a.

Witt a control rod block instrumentation channel trip setpoint less conservative than the value shcwn in the Allowable Values column of Table 3.3.6-2, declare the channel inoperable until the channel is restored to OPERABLE status with its trip setpoint adjusted consistent with the Trip Setpoint value.

b.

With the number of OPERABLE channels less than required by the Minimum OPERABLE Channels per Trip Function requirement, take the ACTION required by Table 3.3.6-1.

SURVEILLANCE REQUIREMENTS 4.-3Yhachoftheaboverequiredcontrolrodblocktripsystemsand l.

i s rumentation channels shall be demonstrated OPERABLE by the performance of the CHANNEL CHECK, CHANNEL FUNCTIONAL TEST and CHANNEL CALIBRATION operations 9

WME#

)

~

y.s.c.2 TLe provinoas oS syeamccedio,

u. a. q ac, no 4 a.p p itec h te l o JLe % nel Fusehaa l les4 soueil\\a>xc.es G +Le D4eree hade % ge in6 M acs ud

&vcce R% e no ^%s kc en4ry (rlo %kw aff cdle OPERMtoNM COM0!M^G h

(as speeiDeA &t TA le '/. 34' D fro-Omma'M Y

SU"0 !#

  1. rC k N D I 7~/ O^l 1, ;DTO V E eC socLed -

pck d Au 12 Loucs ake<

y GRAND GULF-UNIT 1 3/4 3-52

TABLE-3.3.6-1 3-n

^

CONTROL ROD BLOCK INSTRUMENTATION

'O 4

' MINIMUM-APPLICABLE 5

OPERABLE. CHANNELS OPERATIONAL

[

'; ~

TRIP FUNCTION PER TRIP FUNCTION CONDITIONS ACTION g*

1.

ROD PATTERN CONTROL SYSTEM b.

a,

' Low Power Setpoint 2

1,.: 2

'60 E

b.

High Power Setpoint--

2 1#.

'60-3 g

'2.

APRM of a..

Flow' Biased Neutron Flux-3

Upscale..

6 1

61 b.

.. Inoperative

'6 1, 2, 5 61.

5 c.

Downscale 6

1 61-

-d.

' Neutron' Flux - Upscale, Startup 6-

'2, 5

.61 3.

SOURCE' RANGE MON 2T01S_

g)

.g#

w a.

Det'ctor-not fuk1 in 4

2 61 a

2**

5 j

62 Upscale (b)'

W-b.

4 2

61 2**

5 62 Inoperative ( )

4 2

61 c.

f, 2**

5 62 d.

-Jownscale(c) 1

t -

4 2

j 61 8

2**

5

/

62 7-3 4.

INTERMEDIATE RANGE MONITORS' R

j a.

Detector not full in 6

2, 5 61 I

b.

Upscale.

6 2, 5 61 c.

Inopeatig) 6 2'5 61 j

d.

Downscale 6

2, 5 61

'D g

- yO 5.

SCRAM DISCHARGE VOLUME

. aa $.

.. ater Level-High 2

1, 2, 5"'

62

~ *N W

a.

3 o

6.

REACTOR COOLANT SYSTEM RECIRCULATION FLOW l

a.

.. Upscale 3

1 62

' gg

~

7.

REACTOR MODE SWITCH SHUTDOWN POSITION 2

3, 4 63 s.

4

~

se

l.

Gfand Gulf Nuclear Station Unit 1 Attachmtnt 3 to GNRO-92/00034 PCOL 92/02 Page 5 of 9 IN$7RUMENTATION B BLE 3.3.6-1 (Continued)

CONTROL ROD BLOCK INSTRUMENTATION ACTION ACTION 60 Declare the RPCS inoperable and take the ACTION required by Specification 3.1.4.2.

ACTION 61 With the number of OPERABLE Channels:

One less than required by the Minimum OPERABLE Channels per a.

Trip Function requiretrent, restore the inoperable channel to OPERABLE status within 7 dsys or place the inoperable channel in the tripped condition within the next hour, b.

Two or more less than required by the Minimum OPERABLE Channels per Trip Function requirement, place at least one inoperable channel in the tripped condition within one hour.

ACTION 62 With the number of OPERABLE channels less than required by the Minimum OPERABLE Channels per Trip Function requirement, place the inoperable channel in the tripped condition within one hour, ACTION 63 With the number of OPERABLE channels less than required by the Minimum OPERABLE Channels per Trip Function requiremant, initiate a rod block.

NOTES With more than one control rod withdrawn.

Not applicable to control rods removed per Specification 3.9.10.1 or 3.9.10.2.

OPERABLE channels must be associated with SRMs required OPERABLE per Specification 3.9.2.

With THERMAL POWER greater than the Low Power Setpoint.

(a) This function shall be automatically bypassed if detector count rate is

> 100 cps or the IRM channels are on range 3 or higher.

(b) This function shall be automatically bypassed when the associated IRM channels are on range 8 or higher.

(c) This function shall be automatically bypassed when the IRM channels are on range 3 or higher.

(d)

This function s

  1. S r,h p )

p p @ g g annels are j

M

'3 5'

bW b

.;;b$* /uhnet!e r llE reh& h^C vgd ;~ a4e 3 6) A 4 (c. ). r]/s' r'

g GRAND GULF-UNIT 1 Amendment No.69, -

)

i -,..

t

-bci h

TABLE 4.3.6-1 Oy' r ct z

CONTROL ROD BLOCK INSTRUMENTATION SU.VEILLANCE REQUIREMENTS gp o =c

=

CHANNEL OPERATIONAL Nz m

E:

CHANNEL FUNCTIONAL CHANNEL CONDITIONS FOR WHICH S

5 TRIP FUNCTION CHECK TEST CALIBRATION (a)

SURVEILLANCE REQUIRED F

N 1.

ROD PATTERN CONTROL SYSTEM

~

a.

Low Power Setpoint NA S/U(b),M Q

1, 2 ET -

b.

Hiph Power Setpoint NA S/U(b),g q

ya,

{-

2.

APRM g

2:

a.

Flow Biased Neutron Flux-m II)(9), SA 1

Upscale NA V

W N

1,2,5 b.

Inoperative NA S/U,W Wg) c.

Downscale NA W

' SA 1

d.

Neutron Flux - Upscale, Startup NA S/U(b) g q

2, 5 w

3.

SOURCE RANGE MONITORS g

E a.

Detector not full in NA S/U,W NA 2,

b.

Upscale NA S/U,W Q

2,.

c.

Inoperative NA S/U,W NA d.

Downscale NA S/U,W Q

2b h

4.

INTERMEDIATE RANGE MONITORS a.

Detector not. full.in NA S/0,W NA 2, 5 9

b.

Upscale NA S/U,W Q

2, 5 3

c.

Inoperative NA S/U,W NA 2, 5 8

d.

Downscale NA S/U,W Q

2, 5 g

g 5.

SCRAM DISCHARGE VOLUME 6

a.

Water Level-High NA M

R 1, 2, 5*

[zy 6.

WEACTOR COOLANT SYSTEM RECIRCULATION FLOW o

({

[

a.

Upscale NA M

Q 1

[h 7.

REACTOR MODE SWITCH SHUTDOWN F551IION NA R

NA 3, 4 gg L

Gr'and Gulf Nucl:ar Station Unit 1 to GNRO-92/00034 PCOL 92/02 Page 7 of 9 l

?-

' INSTRUMENTATION TABLE 4.3.6-1 (Continued)

CONTROL R00 BLOCK INSTRUMENTATION SURVEILLANCE RE0VIREMENTS NOTES:

a.

Neutron detectors may be excluded from CHANNEL CALIBRATION.

b.

Within 7 days prior to startup.

c.

[ Deleted) d.

[ Deleted) e.

[ Deleted) f.

This calibration shall consist of the adjustment of the APRM channel to conform to the power values calculated by a heat balance during OPERATIONAL CONDITION 1 when THERMAL POWER is greater than or equal to 25% of RATED THERMAL POWER.

Adjust the APRM channel if the absolute difference is greater than 2% of RATED THERMAL POWER.

g.

This calibration shall consist of the adjustment of the APPJi flow biased channel to conform to a calibrated flow signal.

h.

This calibration shall consist of verifying the trip setpoint only.

With any control rod withdrawn.

Not applicable to control rods removed per Specification 3.9.10.1 or 3.9.10.2.

With THERMAL POWER greater than the Low Power Setpoint.

^~

ro ypv rv~

g s

W k)henevec Ye re Y 50^c-lon L5 nCb bg ASSC x

as $ad&J W %6 /e 3M 0 / no b 60 & # 6).!!

\\

J

'w

~~-

l GRAND GULF-UNIT 1 3/4 3-57 Amendment No.16, 49 __

l l

J

4 Gr'and Gulf Nucl:ar Station Unit 1 to GNRC 92/00034 PCOL 92/02 Page 8 of 9 INSTRUMENTATION SOURCE RANGE MONITORS LIMITING CONDITION FOR OPERATION 3.3.7.6 At least the following source range monitor channels shall be OPERABLE.

a.

In OPERATIONAL CONDITION 2*,

four, b.

In OPERATIONAL CONDITION 3 or 4, two.

APPLICABILITY:

OPERATIONAL CONDITIONS 2*, 3 and 4 ACTION:

a.

I*, OPERATIONAL CONDITION 2* with one of the above required source range monitor channels inoperable, restore at least 4 source range monitor channals to OPERABLE statur within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> or be in at least HOT SHUTOOWN ithin the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.

b.

In OPERATIONAL CONDITION 3 or 4 with one or more of the above required source-range monitor channels inoperable, verify all insertable con-trol rods to be fully inserted in the core and lock tne reactor mode switch in the Shutdown position within one hour.

SURVEILLANCE REQUIREMENTS 4.3.7.6 Each of the above required source range monitor channels shall be demonstrated OPERABLE by:

a.

Performance of a:

1.

CHANNEL CHECK at least once per:

a) 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> in CONDITION 2*,

a PER ATION A L Y

b) 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> in CONDITION 3 or 2.

CHANNEL CALIBRATION ** at least once per 18 months.

b.

Performance a CHANNEL FUNCTIONAL TEST:

1.

Within ours prior to moving the reactor mode switch from the Shutdown position, 4f-not-peformed-witMn-the-prev 40us-

?-dayrr,- and 2.

At least once per 31 day c.

Verifying, prior to withdrawal of control rods, that the SRM count rate is at least 0.7 cps with the detector fully inserted.

(

  • With IRM's on range 2 or below.

l

    • extr detectors may be excluded from CHANNEL CALIBRATION.

.# ree.r+

fffRINRTE -UNIT 1 3/4 3-77 g

4 1

Gr'and Gulf Nuclear Station Unit 1 to GNRO-92/00034 PCOL 92/02 Paga 9 of 9 Insert for Pace 3/4 3-77 The provisions of Specification 4.0.4 are not applicable to the Source Range Monitor Channel functional test-surveillances for entry into OPERATIONAL CONDITIONS 2*,

3 or 4 from OPERATIONAL CONDITION 1,

provided the

-surveillances are performed within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> after such entry.

,'I

,=-2--

. Attachment 4 to GNRO-92/00034 k

PCOL-92/02-PROPOSED TECHNICAL SPECIFICATIONS CHANGES

B91E. Proposed changes are denoted as shaded areas.

+-

=,n..

e

^

3/4.3 INSTRUMENTATION 67MAC42/0CW X - ': 3/4.3.1 REACTOR PROTECTION SYSTEM INSTRUMEN MTION P c< g e / o f 7 LIMITING CONDITION FOR OPERATION 3.3.1 As a minimum, the reactor protection system instrumentation channels shown in Table 3.3.1-1 thall be OPERABLE with the REACTOR PROTECTION SYSTEM RESPONSE TIME as hown in Table 3.3.1-2.

APPLICABILITY: As shown in Table 3.3.1-1.

ACJ1QH:

a.

With the number of OPERABLE channels less than required by the Minimum OPERABLE Channels per Trip System requirement for one trio system, place the inoperable channel and/or that trip system in the tri'pped condition

  • within twelve hours.

b.

With the number of OPERABLE channels less than required by the Hinimum OPERABLE Channels per Trip System requirement for both trip systems, place at least one trip system ** in the tripped condition within one hour and take the ACTION required by Table 3.3.1-1.

SURVEILLANCE REQUIREMENTS i

4.3.1.1 Each reactor protection system instrumentation channel shall be demonstrated OPERABLE by the performance of the CHANNEL CHECK, CHANNEL FUNCTIONAL TEST and CHANNEL CALIBRATION operations for the OPERATIONAL CONDITIONS and at the frequencies shown in Table 4.3.1.1-1.

4.3.1.2 LOGIC SYSTEM FUNCTIONAL TESTS and simulated automatic operation of all channels shall be performed at least once per 18 months.

4.3.1.3 The REACTOR PROTECTION SYSTEM RESPONSL TIME of eacn reactor trip functional unit shown in Table S.3.1-2 shall be demonstrated to be within its limit at least once-per 18 months.

Each test shall include at least one chan-nel per trip system such that all channels are tested at least once every N times 18 months where N is the total number of redundant channels in a specific reactor _trir system.

413!Q EThip roVi sibiidf } Speb) fi hit i 6M410 f 4 ? are fn6FAppli ca bl e stithe ChannelifunctionahTestisurveillance?fo6the?Intesmediate RangecMonitorsif6r

~

bnt rys ihtosthef app 1 t cabl s10PERAT10NAld CONDITIONSf(asi speci fied firi

~ "

Tabl e (4b37111il )[S from30PERAT 10 NAE C0hJI TI0N il [ p ro videdit h s n u rv perfohnedgi. thin 121hou.rMa't)ffsuc.hfentry]

" " ~ ~

~

~ '"~

An inoperable channel need not be placed in the tripped condition where this would:cause the Trip Function to occur.

In these cases, the inoperable channel shall be restored to OPERABLE status within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> or the ACTION required by Table 3.3.1-1 for that Trip Function shall be-taken.

The trip system need not be placed in the tripped condition if this.would cause the Trip Function to occur.

When a trip system can be placed in the tripped condition without causing the Trip Function to occur, place the trip -ystem with the most inoperable channels in the tripped condition; if s

both systems have the same number of inoperable channels, place either trip system in the tripped condition.

GRAND GULF-UNIT 1 3/4 3-1 AmendmentNo.69(

J

l

'f0Q L 92/0 L khadMd Y N JNSTRUMENTATJ0ff t3p/go-92 ocs39 3/4.3.6 CONTROL ROL BLOCK INSTRUMENTATION

[

g g of 7 LIMITING CONDITION FOR OPERATION 3.3.6.

The control rod block instrumentation channels shown in Table 3.3.6-1 shall-be OPERABLE with their trip setpoi'its set consistent with tne values shown in the Trip Setpoint column of Table 3.3.6-2.

APPLICABIllTY: As shown in Table 3.3.6-1.

ACTION:

a.

With a control rod block instrumentation channel trip setpoint less conservative than the value shown in the Allowable Values column of Table 3.3.b-2, declare the thannel inoperable until the channel is restored to OPERABLE status with 4. trip setpoint adjusted consistant with the Trip Setpoint value, b.

With the number of OPERABLE channels less than required by the Minimum CPERABLE Channels per Trip Function requirement, take the ACTION required by Table 3.3.6-1.

SURVEILLANCE REQUIREMENTS 4.3.611 Each of the above required control rod block trip systems and instru-mentation channels shall be deronstrated OPERABLE by the performance of the CHANNEL CHECK, CHANNEL FUNCTIONAL TEST and CHANNEL CAllBRATION operations for the OPERATIONAL CONDITIONS and at the frequencies shown in Table 4.3.6-1.

41326.!27The proiisionslof/Speel fication*4:0.'4 L are riotiapplica'bl'el. to t the

~

Channel ; Functi onal.1 Test; forc the:L in termedi ate.:. Range Monitors rand Source Range Monitors 1for'entryLfnt0 their applicabl.c.OPERATIONAlcCONDITIONS.(asrspecified in-Table 4.-3.6-1); from-0PERATIONAL CONDITION ll, provided the surveilla.ncesiare performed.pi.thiaT121hourstafter such ontry.-

i l

GRAND GULF-UNIT 1 3/4 3-52 Amendment? No.:

f e

e.

6 TABLE 3.3.6-1 CONTROL R00 BLOCK INSTRUMENTATIOJi MINIMUM APPLICABLE OPERABLE CHANNELS OPERATIONAL l

E!P FUNCTION P[R TRIP FUNCTION CONDITIONS ACT!0N o

'O 1.

ROD PATTERN CONTROL SYSTEM a.

Low Power Setpoint 2

1, 2 60 r

2 1#

60

b. High Power Setpoint N

N'-

2..APRM O

a.

Flow Biased Neutron Flux-6 1

61 N-Upscale 6

1, 2, 5 61 b.

Inoperative c.

Downscale 6

1 61 d.

Heutron Flux - Upscale, Startup 6

2, 5 61 3.

SOURCE RANGE MONITORS 61 i }

4 2

a.

Detector not full in 2**

5" 62 b.

Upscale (b) 4 2

61 2**

5..

62 Inoperative (b) 4 2"

61 c.

2**

5 6T d.

DownscaleN}

4 2

6:

2**

5 62 4.

INTERMEDIATE RANGE MONITORS a.

Detector not full in 6

2, 5 61 6

2, 5 61 b.

Upscale 6

2, 5 61 Inoperatig}

6 2, 5 61 h

c.

Downscale d.

bN k

5.

SCRAM DISCHARGE VOLUME a.

Water Level-High 2

1, 2, 5*

62 j

(Ik 6.

REACTOR COOLANT SYSTEM RECIRCULATION FLOW 3

1 62 o

+t a.

Upscale

-h N yN 7.

REACTOR MODE SWITCH SHUTDOWN POSITION 2

3, 4 63 8

bu GRAND GULF-UNIT 1 3/4 3-;3 AmendmentNo.69h Ts

-* P'C C L 92 /02 bN"*NeY Y b*

[7//20 42/ coo 3Y OC Y#

JNSTRUMENTATION p

TABLE 3.3.6-1 (Continued)

CONTROL R0D BLOCK INSTRUMENTATION ACTION ACTION 60 - Declare the RPCS inoperable and take the ACTION required by Specification 3.1.4.2.

With the number of OPf RABLE Channels:

ACTION 61 a.

One less than required by the Minimum OPERABLE Channels per Trip Function requirement, restore the inoperable channel to OPERABLE status within 7 days or place the inoperable channel in the tripped condition within tha next hour.

b Two or more less than required by the Minimum OPERABLE Channels per Trip Function requirement, place at least one inoperable channel in the tripped condition within one hour.

ACTION 62 - With the number of-OPERABLE channels less than required by the Minimum OPERABLE Channels per Trip Function requirement, place the inoperable channel in the tripped condition within one hour, ACTION 63 - With the number of OPERABLE channels less than required by the Minimum OPERABLE Channeis per Trip Function requitement, initiate a rod block.

NOTES With more than one control rod withdrawn. Not applicable to control rod removed per Specification 3.9.10.1 or 3.9.10.2.

OPERABLE channels must be associated with SRMs required OPERABLE per Specification 3.9.2.

With THERMAL POWER greater than the Low Power Setpoint.

    1. y (Whe65Vsh the 7 1 at~edf fdnd t'i ond M not[ tippas sed ? a'sTs peci fi edMnotes7 (s )

thfough (c))

f (a) This function shall be automatically bypassed if detector count rate is

> 100 cps or'the IRM channels are on range 3 or higher.

(b) This function shall be automatically byparsed when the associated IRM channels are on range 8 or higher.

(c).-This function shall be automatically bypassed when the IRM channels are on range 3 or higher.

(d) This function shall be automatically bypassed when the IRM channels are on range 1.

GRAND GULF-UNIT 13/4 3-54 Amendment No. 69b ~

-t-TABLE 4.3.6-1 CONTROL-R00 BLOCK INSTRUMENTATION SURVEILLANCL REOUIREMENTS CHANNEL OPERATIONAL CHANNEL' FUNCTIONAL CHANNEL y

CALIBRATION (8) COND11 IONS FOR W SURVEILLANCE REQUIRED h'

TRIP FUNCTION.

. _C'EC K TEST g

1.

R0D PATTERN CONTROL SYSTEM a.

Low Power Setpoint NA S/U(b),M Q

1, 2-4

- N b.

High Power Setpoint NA S/U(b) g 9

3.

2.

APRM D

a.

Flow Biased Neutron Flux-Upscale NA

'W WW IS), SA 1

b.

Inoperative.

NA S/U,W N

1, 2, 5 c.

Downscale NA W

WC}, SA 1

d.

Neutron Flux - Upscale, Startup NA S/U(b) g n

75 3.

SOURCE RANGE MONITORS 2E#

a.

Detector not full in NA S/U,W NA 28, 5 b.

Upscale NA S/U.W Q

- 2Y, 5 c.

Inoperative NA S/U,W NA 5

d.

Downscale NA S/U,W Q

2 5

4.

INTERMEDIATE RANGE MONIl0RS a.

Detector not full in NA S/U,W NA 2, 5 b.

Upscale NA S/U,W Q

2, 5 c.

Inoperative NA S/U,W

'NA 2, 5 d.

Downscale NA S/U,W Q

2, 5 5.

SCRAM DISCHARGE VOLUME g

a.

Water Level-High NA M

R 1, 2, 5*

5 1

i N

O M

6.

RtACTOR COOLANT SYSTEM RECIRCULATION FLOW hE a.

Upscale NA M

Q l

N

7.. REACTOR MODE SWITCH SHUTDOWN POSITION NA R

NA 3, 4 GRAND GULF-UNIT 1 3/4 3-56 Amendment No. 49R ~ "

pgjog Y sc L d Y /c

-l Jgot 6M/Zm 92/C0039' MkTEPGA11.0B p

g o/,7 lADM LLi1 (Continued)

[.0ff]MLROD BLOCK IN.STRUMENTAT10N SURyflLL ANCE R_E0VIREMENTS E01ES:

a.

Neutron detectors may be excluded from CHANNEL CAllBRATION.

b.

Within 7 days prior to startup.

c.

[ Deleted) d, (Deleted) e.

[ Deleted) f.

This calibration shall consist of the adjustment of the APRM channel to conform to the power values calculated by a heat balence during OPERATIONAL CONDITION 1 when THERMAL POWER is greate-than or equal to 25% of RATED THERMAL POWER. Adjust the APRM channel if the absolute-difference is greater than 2% of RATED THERMAL POWER.

g.

This calibration shall consist of the adjustment of the APRM flow biased -

I channel to conform to a calibrated flow signal.

h.

This calibration shall consist of verifying the trip setpoint only.

With 4 ontrol rod withdrawn.

Not applicable to control rods removed 1

per S?

ication 3.9.10.1 or 3.9.10.2, With THEhMAL POWER greater than the Low Power Setpoint.

!U'lWhenever thsTrelat'ed function is not' bypassSi.as specifiedsinLTable -

~

3.4.6Fll, notes (a)'throughf(c).

4 i

f v

GRAND GULF-UNil 13/4 3-57 AmendmentNa.49[

b

  • ).

}llgg./m./ f./n

,- INSTRUMENTATION h/Vf@-92lCCC.5Y

'*o.

SOURCE RANGE MONITORS

,qq 7 of 7 LIMITING CONDITION FOR OPERAT!DN 3.3.7.6 At least the following source range monitor channels shall be OPERABLE.

a.

in OPERATIONAL CONDil10N 2*,

four, b.

Ir OPERATirNAL CONDITION 3 or 4, two.

APPLICABILITY: OPERATIONAL CONDITIONS 2*, 3 and 4.

eLTl0!i:

a.

In OPERATIONAL CONDITION 2* with one of the above required source range monitor channels innperable, restore at least 4 source range monitor channels to OPERABLE status w10in 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.

b.

In OPERATIONAL CONDITION 3 or 4 with one or more of the above f

required source range tronitor channels inoperable, verify all insertable control rods to be fully inserted in the core and lock the reactor mode switch in the Shutdown oosition within one hour.

SURVEILLANCE REQUJREMENTS 4.3.7.6 Each of the above required source range monitor channels shall be demonstrated OPERABLE by:

a.

Performance of a:

1.

CHANNEL CHECK at least once per:

a) 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> in OPERATION _Al. CONDITION 2*,

and b) 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> in OPERATIONAL CONDITION 3 or 4.

2.

CHANNEL CAllBRATION** at least once per 18 months, b.

Performance of a CHANNEL FUNCTIONAL TEST:

l 1.

Within;!Edays. prior to moving the reactor mode switch from the Shutdoin positionpand

2. -

At lea!t once per 31 days",

c.

Verifying, prior to withdrawal of control rods, that the SRM count rate is at least 0.7 cps with the detector fully inserted.

  • With IRH's on range 2 or below.

~

    • Neutron detectors may.be excluded from CHANNEL CAllBRATION.

)iThe 'prodstopidf!Spect ficationl4.0.4 are not' applicable Lto"the: So0rce Rarige Monitor Channel Functional: test ~ surveillancos for entryxintc! OPERATIONAL ~

CONDlT10NSL?.* M o #4jfrom 0PERATIONAL CONDITION-l' provided the

l surveillances are. performed,withirr12choursiafter such entryl c

l GRAND GULF-UNIT 1 3/4 3-77 Amendment?Not

-. -.