Proposed Tech Specs,Allowing One Time Extension of AOT Specified in TS 3/4.5.2 for Each RHR Train from 72 H to 7 Days
ML20094N888
Person / Time
Site: Summer South Carolina Electric & Gas Company icon.png
Issue date: 11/21/1995
From:
SOUTH CAROLINA ELECTRIC & GAS CO.
To:
Shared Package
ML20094N887 List:
References
NUDOCS 9511280216
Download: ML20094N888 (6)


Text

.

EMERGENCY CORE COOLING SYSTEMS-2 3/.5.2' ECCS SUBSYSTEMS - T,y 2 350*F LIMITING CONDITION FOR OPERATION 3.5.2 Two independent Emergency Core Cooling System (ECCS) subsystems #shall be OPERABLE with each subsystem comprised of:

a.

One OPERABLE centrifugal charging pump, b.

One OPERABLE residual heat removal heat exchanger, c.

One OPERABLE residual heat removal pump, and d.

An OPERABLE flow path capable of taking suction from the refueling water storage tank on a safety injection signal and automatically transferring suction to the residual heat removal sump during the recirculation' phase of operation.

APPLICABILITY: MODES 1, 2 and 3.

ACTION:

a.

With one ECCS subsystem inoperable, restore the inoperable subsystem to OPERABLE status within 72 hourfor be in at least HOT STANDBY vithin the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in HOT SHUTDOWN within the following 6 i

hours, l

2.

b.

In the event the ECCS is actuated and injects water into the Reactor Coolant System, a Special Report shall be prepared and submitted to

(

the Commission pursuant to Specification 6.9.2 within 90 days describ-ing the circumstances of the actuation and the total accumulated actuation cycles to date. The current value of the usage factor for each affected safety injection nozzle shall be provided in this Special Report whenever its value exceeds 0.70.

b 4 Th4, a DoWOlc. od age. +ime for e,ach R H E -f ra an maye evi4eded do 7 dq s for the pur pe w of m ainten u c.

d mod S caton. This e+ce pton maq onl3 be wee d one -hme pc g.ga., t rain u d is ncrt va t e d a&r Dece.mber 31,1997.

SlM4ER - UNIT 1 3/4 5-3 9511280216 951121

~

PDR ADOCK 05000395 R-.

_._ _.__ RDR_,..

e EMERGENCY CORE COOLING SYSTEMS 3/4.5.2 -ECCS SUBSYSTEMS-T2vg 2350*F LIMITING CONDITION FOR OPERATION 3.5.2 Two independent Emergency Core Cooling System (ECCS) subsystems

  • shall be l

OPERABLE with each subsystem comprised of:

?

a.

One OPERABLE centrifugal charging pump, b.

One OPERABLE residual heat removal heat exchanger, j

c.

One OPERABLE residual heat removal pump, and

.[

-d.

An OPERABLE flow path capable of taking suction from the refueling water storage tank on a safety, dual heat removal sump during the injection signal and automatically transferring suction to the resi recirculation phase of operation.

APPLICABILITY: MODES 1,2 and 3.

ACTION:

l a.

With one ECCS subsystem inoperable, restore the inoperable subsystem to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />

  • or be in atleast HOT STANDBY l

within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in HOT SHUTDOWN within the following 6

hours, b.

In the event the ECCS is actuated and injects water into the Reactor.

Coolant System, a Special Report shall be prepared and submitted to

'1 the Commission pursuant to Specification 6.9.2 within 90 days describ-ing the circumstances of the actuation and the total accumulated actuation cycles to date. The current value of the usage factor for each affected safety injection nozzle shall be provided in this 4

l Special Report whenever its value exceeds 0.70.

i I

l

  • ' The allowable outage time for each RHR train may be extended to 7 days for the purpose of maintenance and modification. This exception may only be used one time per RHR train and is not valid after December 31,1997.

1 SUMMER'- UNIT 1 3/45-3 Amendment.

4-c

Docum:nt Control Desk I

Attachm:ntII

~

TSP 950010 RC-95-0283 Page l'of 2.

i SAFETY EVALUATION l

FOR REVISING THE SPECIFICATION FOR ECCS SUBSYSTEMS-Tavg 2 350 DEGREES FAHRENHEIT IN THE VIRGIL C. SUMMER NUCLEAR STATION TECHNICAL SPECIFICATIONS i

Description of Amendment Reauest South Carolina Electric & Gas Company (SCE&G) proposes to revise the Virgil C.

Summer Nuclear Station (VCSNS) Technical Specifications (TS) 3/4.5.2, ECCS SUBSYSTEMS - Tavg 2:350*F to add the following footnote:

"The allowable outage time for each RHR train may be extended to 7 days for the purpose of maintenance and modification. This exception may only be used one time per RHR train and is not valid after December 31,1997."

The proposed TS change request (TSCR) will allow a one time extension of the current TS 3.5.2 ACTION statement, item (a.) outage time from 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> to 7 days.-

This will permit maintenance to the residual heat removal (RHR) heat exchangers and modification of the RHR pump suction header valves to be performed at power when radiation levels associated with the components are at their lowest, thus resulting in reduced personnel exposure.

VCSNS Health Physics (HP) has performed a radiological assessment of the required RHR heat exchanger maintenance and valve modification. The assessment resulted in an estimated collective dose of approximately 20 person-REM to perform the maintenance and modification on both trains of RHR while at power. Based on the previous three refueling outages at VCSNS, radiation exposures could be 2 to 3 times higher if these activities were to be performed during a plant shutdown.

. The requested time of 7 days is based on experience gained from previous repair evolutions on the components.

i

)

1

Document Control Desk AttachmentII i

TSP 950010-RC-95-0283

~ '

,Page 2 of 2 k

Safety Evaluation The large break loss of coolant (LBLOCA) is a design basis accident that is not considered to occur during the lifetime of plant operation. It is used as a design basis to assure conservatism. The safety function of the RHR system is to provide a low pressure, high volume water source for reflooding the core following a large break that results in a rapid depressurization. Following a small break LOCA, the RHR pumps may be required to provide suction pressure to the safsty injection system during sump recirculation and for long term decay heat removal. The loss of coolant j

accident analyses only take credit for one train of RHR. TS requires that both trains of RHR be operable in Mode 1. One train is allowed to be inoperable for a period of 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />. The proposed TSCR will provide for a one time extension of the allowable l

outage time from 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> to 7 days to allow maintenance and a modification to be performed at power. The alternative is to perform the maintenance and modification l

during plant shutdown; however, that is during the time of peak radiation level in the RHR system due to its use during plant cooldown. A dose savings between 20 to

[

40 person-REM is expected by performing the maintenance and modification at jl power rather than after a plant shutdown.

During the outage time, the redundant train will remain operable and be available to perform the safety function assumed by the safety analysis. The effect of having one RHR train out of service for 7 days was evaluated. The evaluation used the core 4

damage frequency (CDF) from the PRA model based on the VCSNS IPE model with equipment history updates and incorporation of plant modifications performed l

through Cycle 7. The CDF calculated by the PRA model is 1.006E-4 per reactor year.

i Use of the current allowable outage time of 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> for each RHR train results in a CDF of1.024E-4 per reactor year. Use of a 7 day allowable outage time raises the CDF to 1.050E-4 per reactor year. The change results in a one time totalincrease in i

CDF of 2.6E-6.

The 2.6E-6 increase in CDF is considered small when compared to the 20 to 40 person-REM savings in exposure; therefore, SCE&G has determined that the i

reduction in exposure justifies the increase in CDF by performing these activities during Mode 1 operation.

Pursuant to the above information, the proposed TSCR does not involve a significant reduction in the margin ofsafety.

1

- Docum:nt Control Desk AttechmentIII TSP 950010 -

RC-95 0283 '

- Page 1 of 2 NO SIGNIFICANT HAZARDS DETERMINATION FOR REVISING THE SPECIFICATION FOR ECCS SUBSYSTEMS-Tavg 2: 350 DEGREES FAHRENHEIT IN THE VIRGIL C. SUMMER NUCLEAR STATION TECHNICAL SPECIFICATIONS

)

)

Description of Amendment Request South Carolina Electric & Gas Company (SCE&G) proposes to revise the Virgil C.

Summer Nuclear Station (VCSNS) Technical Specifications (TS) 3/4.5.2, ECCS SUBSYSTEMS - Tavg 2350 F to add the following footnote:

"The allowable outage time for each RHR train may lie extended to 7 days 1

for the purpose of maintenance and modification. This exception may only be used one time per RHR train and is not valid after December 31,1997."

i The proposed TS change request (TSCR) will allow a one time extension of the current TS 3.5.2 ACTION statement, item (a.) outage time from 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> to 7 days.

This will permit maintenance to the residual heat removal (RHR) heat exchangers and modification of the RHR pump suction header valves to be performed at power when radiation levels associated with the components are at their lowest, thus resulting in reduced personnel exposure.

j VCSNS Health Physics (HP) has performed a radiological assessment of the required i

RHR heat exchanger maintenance and valve modification. The assessment resulted in an estimated collective dose of approximately 20 person-REM to perform the maintenance and modification on both trains of RHR while at power. Based on the j

previous three refueling outages at VCSNS, radiation exposures could be 2 to 3 times

. higher if these activities were to be performed during a plant shutdown.

The requested time of 7 days is based on experience gained from previous repair evolutions on the components.

2 4

A

Document Control D:sk Attachm:ntIII

. TSP 950010 RC-95-0283 -

- Page 20f 2 Basis for No Significant Hazards Consideration Determination SCE&G has evaluated the proposed change to the VCSNS TS described above i

against the Significant Hazards Criteria of10 CFR 50.92 and determined that the change does not involve any significant hazard for the following reasons:

1.

The probability or consequences of an accident previously evaluated is not significantly increased.

The probability of an accident previously evaluated in the FSAR does not change. A one time extension to increase the allowed outage time for each train of RHR from 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> to 7 days affects only RHR train availability which does not contribute to the probability of a LOCA. The proposed change to TS 3/4.5.2 l

has been shown to have only a small increase in Core Damage Frequency. The consequences of a LOCA does not change from those currently resulting from a LOCA initiated while in TS 3.5.2 ACTION statement (a.), thus, there is no change in consequences of an accident previously evaluated in the FSAR.

2.

The possibility of an accident or a malfunction of a different type than any previously evaluated is not created.

i The proposed TSCR only results in a one time increase in the allowable outage time for each train of RHR.It does not result in an operational condition different from that which has already been considered by TS. Therefore, the change does not create the possibility of a new or different kind of accident or malfunction.

3.

The margin of safety has not been significantly reduced.

The effects ofincreasing the allowed outage time on the calculated core damage J

frequency has been evaluated and determined to be small.

1

[

- Pursuant to 10CFR50.91, the preceding analysis provides a determination that the proposed TSCR poses no significant hazard as delineated by 10CFR50.92.

t 4

.